re: sunshine gardens – lighting study

4
February 20, 2020 City of Encinitas Planning Department 505 S. Vulcan Avenue Encinitas, California 92024 RE: Sunshine Gardens – Lighting Study To Whom It May Concern, Schmidt Design Group has prepared a lighting plan for submittal with the Sunshine Gardens application for City review. The lighting plan includes proposed street light designs and locations, as shown on Sheet L- 1.6 of the plan set. All lights in the project would comply with the City of Encinitas’ Residential Lighting Standards under Section 30.40.010(I) of the Encinitas Municipal Code, which require: I. Performance Standards—Residential Lighting Standards. The following standards shall apply to all residential and commercial zones: 1. All light sources shall be shielded in such a manner that the light is directed away from streets or adjoining properties. 2. All residential zones and commercial uses adjoining residential zones shall not have a measured sustained light standard in excess of one-half foot-candle at the property line. Outdoor lighting fixtures shall be fully shielded so as to cause all emitted sustained light to be projected below an imaginary horizontal plane passing through the lowest point of the luminary, lamp or light source used in the fixture. The luminary, lamp, or light source shall not be directly visible from any adjoining residential property. The shielding requirement shall not apply to decorative landscape lighting fixtures of 50 watts or less, holiday lighting, fossil fuel lighting, or lighting within front yard areas intended to illuminate pedestrian and vehicular entries, landscaping/architectural accents, and the like. Skylights, greenhouses, and agricultural production activities are exempt. Public recreational facilities are not subject to the performance standards, but shall be reviewed through the use permit process for minimizing lighting impacts to surrounding properties, and may be subject to restrictions on operating hours and/or the number and type of lighting fixtures. 3. All interior commercial lots shall not have a measured sustained light standard in excess of one foot-candle at the property line. Outdoor lighting fixtures shall be fully shielded so as to cause all emitted sustained light to be projected below an imaginary horizontal plane passing through the lowest point of the luminary, lamp or light source used in the fixture. Skylights, greenhouses, and agricultural production activities are exempt. Permitted lighting structures and fixtures in place as of December 31, 2004 associated with commercial uses shall be considered legal nonconforming pursuant to Chapter 30.76 of the Municipal Code, and as such may remain in place as long as they are not altered in any manner increasing light trespass onto adjoining properties. 4. Street lighting is not subject to the performance standards, but shall be evaluated

Upload: others

Post on 01-Oct-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RE: Sunshine Gardens – Lighting Study

February 20, 2020 City of Encinitas Planning Department 505 S. Vulcan Avenue Encinitas, California 92024 RE: Sunshine Gardens – Lighting Study To Whom It May Concern, Schmidt Design Group has prepared a lighting plan for submittal with the Sunshine Gardens application for City review. The lighting plan includes proposed street light designs and locations, as shown on Sheet L-1.6 of the plan set. All lights in the project would comply with the City of Encinitas’ Residential Lighting Standards under Section 30.40.010(I) of the Encinitas Municipal Code, which require:

I. Performance Standards—Residential Lighting Standards. The following standards shall apply to all residential and commercial zones: 1. All light sources shall be shielded in such a manner that the light is directed away from

streets or adjoining properties.

2. All residential zones and commercial uses adjoining residential zones shall not have a measured sustained light standard in excess of one-half foot-candle at the property line. Outdoor lighting fixtures shall be fully shielded so as to cause all emitted sustained light to be projected below an imaginary horizontal plane passing through the lowest point of the luminary, lamp or light source used in the fixture. The luminary, lamp, or light source shall not be directly visible from any adjoining residential property. The shielding requirement shall not apply to decorative landscape lighting fixtures of 50 watts or less, holiday lighting, fossil fuel lighting, or lighting within front yard areas intended to illuminate pedestrian and vehicular entries, landscaping/architectural accents, and the like. Skylights, greenhouses, and agricultural production activities are exempt. Public recreational facilities are not subject to the performance standards, but shall be reviewed through the use permit process for minimizing lighting impacts to surrounding properties, and may be subject to restrictions on operating hours and/or the number and type of lighting fixtures.

3. All interior commercial lots shall not have a measured sustained light standard in excess of one foot-candle at the property line. Outdoor lighting fixtures shall be fully shielded so as to cause all emitted sustained light to be projected below an imaginary horizontal plane passing through the lowest point of the luminary, lamp or light source used in the fixture. Skylights, greenhouses, and agricultural production activities are exempt. Permitted lighting structures and fixtures in place as of December 31, 2004 associated with commercial uses shall be considered legal nonconforming pursuant to Chapter 30.76 of the Municipal Code, and as such may remain in place as long as they are not altered in any manner increasing light trespass onto adjoining properties.

4. Street lighting is not subject to the performance standards, but shall be evaluated

Page 2: RE: Sunshine Gardens – Lighting Study

through proposed subdivision/projects and street design projects consistent with the modification process to street standards in order to preserve dark sky character of the community, while still maintaining the necessary lighting for safety purposes.

Nolen Communities, acting as Entitlement Manager for Sunshine Encinitas, LLC (applicant), will engage a lighting consultant to complete a Photometric Lighting Study, which will be provided with the second submittal after the City has reviewed the lighting plan. If you have any questions, please contact me at your convenience at [email protected]. Sincerely, Brian Grover Managing Partner Nolen Communities, LLC

Page 3: RE: Sunshine Gardens – Lighting Study

WERMERS COMPANIES5120 SHOREHAM PLACE, #150, SAN DIEGO, CA.(858) 535-1475

SUNSHINE GARDEN APARTMENTS ENCINITAS, CA.05-28-2020

JOB NO.: 20233

0 15 30 60

1" = 30'-0"SCALE :

Designed By:

ER/RL

Drawn By:

ER

Checked By:

RL

Plot Date:

5.28.2020

Plans Prepared Under Supervision of:

ROY L. LOPEZELECTRICAL ENGINEER

DATE: 5.28.2020LIC. NO. 13442 (949) 753-1553 Fax (949) 753-1992

8825 Research Drive

OMB ELECTRICAL ENGINEERS, INC.

Irvine, CA 92618

E-Mail: [email protected]

StatisticsDescription Symbol Avg Max Min Max/Min Avg/Min Avg/MaxCalc Zone #1 2.3 fc 30.1 fc 0.1 fc 301.0:1 23.0:1 0.1:1

Calc Zone #2 3.1 fc 7.4 fc 1.0 fc 7.4:1 3.1:1 0.4:1

Calc Zone #3 1.9 fc 7.6 fc 0.3 fc 25.3:1 6.3:1 0.3:1

Calc Zone #4 3.3 fc 7.0 fc 0.6 fc 11.7:1 5.5:1 0.5:1

Calc Zone #6 2.6 fc 34.2 fc 0.1 fc 342.0:1 26.0:1 0.1:1

Calc Zone #6 1.4 fc 6.7 fc 0.3 fc 22.3:1 4.7:1 0.2:1

Luminaire Schedule

Symbol Label Quantity Manufacturer Catalog Number Description Lamp NumberLamps Filename Lumens Per Lamp Light Loss Factor Wattage

S1

12 COOPER LIGHTINGSOLUTIONS - INVUE(FORMERLY EATON)

LXS-B2-LED-D1-T3-S 1 4346.726 0.71 48

S2

45 COOPER LIGHTINGSOLUTIONS - LUMIERE(FORMERLY EATON)

1 618.3757 0.71 8.3

S3

3 FOCUS INDUSTRIES FL-LED-OMNI3 3/4"DIA X 1-3/4"H. LED LUMINAIRE 1 165.1009 0.71 2.62

S46 Lithonia Lighting 1 3131.765 0.71 22.55

S5

15 Fc Lighting 1 344.7034 0.71 15.697

S6

15 B-K LIGHTING, INC. NS-LED-e66-MFL-13 3 -0.3333333 0.71 6.95

4000K CCT, 80 CRILEDS Industrial,Landscape, Parks,Pathway, Pedestrian,Residential, Sidewalk,Walkway, Accent, Bollard

THREE WHITE LIGHTEMITTING DIODES(LEDS), AIMED AT THEHORIZON.

MACHINED CYLINDRICALMETAL HOUSING, 1 BLACKCIRCUIT BOARD WITH 3 LEDS

WDGE2 LED WITH P3 -PERFORMANCE PACKAGE, 4000K,80CRI, VISUAL COMFORT FORWARDOPTIC

LUXESCAPE OUTDOORARCHITECTURAL LUMINAIRE 70CRI, 4000K LEDS AND TYPE IIIOPTIC, GRAPHITE METALLICPAINTED FINISH, SPIDER MOUNTRetail, Roadway, Sidewalk, Site,Street, Substation, Security,Corrosion Resistant, VandalResistant, Wet Location

LUMIERE EON LED LUMINAIREBOLLARD, SINGLE HEAD, ONELIGHTBAR, TYPE 2

LXS-B2-LED-D1-T3-S.ies

LED-OMNI-3_0.ies

WDGE2_LED_P3_40K_80CR I_VF.ies

FCSL203-120V-4K-340LM-BK.IES

LED-e66-MFL-13-ITL85924.IES

303-B1-LEDB1-4000-UNV-T2-DIM10-CS.ies

FCSL203-120V-4K-BKETL FIXTURE

WDGE2 LED P3 40K80CRI VF

303-B1-LEDB1-4000-UNV-T2-DIM10-CS

SITE LIGHTING PHOTOMETRIC PLAN

E-1.0

Page 4: RE: Sunshine Gardens – Lighting Study

CANOPY PENDANT MOUNTED LIGHTFIXTURE - TYPE "S3" MOUNTING +10'-0"

POST TOP PEDESTRIAN FIXTURE - TYPE "S1"MOUNTING AT +14'-0"

RECESSED WALL MOUNTED FIXTURE - TYPE "S5"MOUNTING AT +2'-0"

DECORATIVE WALL MOUNTED LIGHT FIXTURE - TYPE "S4" MOUNTING +9'-0"

PALM TREE RING MOUNTED LIGHT FIXTURE - TYPE "S6" MOUNTING +10'-0"

WERMERS COMPANIES5120 SHOREHAM PLACE, #150, SAN DIEGO, CA.(858) 535-1475

SUNSHINE GARDEN APARTMENTS ENCINITAS, CA.05-28-2020

JOB NO.: 20233Designed By:

ER/RL

Drawn By:

ER

Checked By:

RL

Plot Date:

5.28.2020

Plans Prepared Under Supervision of:

ROY L. LOPEZELECTRICAL ENGINEER

DATE: 5.28.2020LIC. NO. 13442 (949) 753-1553 Fax (949) 753-1992

8825 Research Drive

OMB ELECTRICAL ENGINEERS, INC.

Irvine, CA 92618

E-Mail: [email protected]

PEDESTRIAN WALKWAYS BOLLARDFIXTURE - TYPE "S2" MOUNTING AT +42"

LIGHTING FIXTURE SPEFICIATIONS

E-2.0