Building Management SystemMaster-Controller RCO 700D-M/W
Data sheet
RCO 700D-MRCO 700D-W
Application Controlesta RCO 700D-.. are free programmable Master Controllers. The devices are suitablefor the operation within a network. The Master Controllers Controlesta RCO 700D-.. can beused for the automatic control, monitoring and optimisation within the building automation.The Master Controllers can be connected together via Ethernet to a Multi-Master-Network(peer-to-peer Communication). The implemented interfaces and protocols offer a variety ofcommunication and integration abilities. As a native BACnet Controller the Master Controllersupports on demand the BACnet protocol according to the ANSI/ASHRAE Standard 135-2004(ISO16484-5). Options for the Data Link Layer of the BACnet Building Controller (B-BC):BACnet/Ethernet, BACnet/IP, BACnet/MSTP und BACnet/PTP. Router functionality according toClause 6. BBMD (BACnet/IP Broadcast Management Device) function can be activated if re-
quired. The controller RCO 700D-W includes additionally an integrated Web server for thevisualization and operation of plant data and alarms via Intranet or Internet with a standardweb browser. The HTML pages are designed comfortably and efficiently with the RCO-tool.
Features 32 Bit-Micro processor with real time operation system 8 MB SD-RAM 4 MB Flash Memory 1 slot for SD-Memory Card as internal and external data and program memory. 2 x RS232 Interface: Used for the connection to bms, pc, analogue/gms-messenger, modem
and printer as well as for the connection of the already implemented protocols. 2 x RS485 Interface: For the connection of the already implemented protocols as well as for
the communication to the Controlesta RCO C Master network. 2 x Ethernet Interfaces (In/Out with integrated Hub-Functionality) for the peer-to-peer com- munication based on Ethernet for the connection of Master Controller within the Multi- Master-Network and the connection to the BMS-Software.
1 x L-Bus 1-connection with selectable speed (default: 100 Kbps) for the connection of upto 32 Slave-Modules RCO C
1 x L-Bus 2-connection with selectable speed (default: 100 Kbps) for the connection of upto 32 I/O-Modules RCO D
The already implemented protocols like ASCII, Modbus RTU Master/Slave, M-Bus, Wilo,Grundfos, RCO C, Energesta REN and BACnet can be combined with the integrated Inter-
faces (Ethernet, RS232, RS485). The operator panel RCO 640D-S can be connected via the L-Bus Standardised algorithms for PID regulation Integrated alarm and modem handling The free programming of all functions of the plant software is done by the engeneering
software Controlesta RCO-tool Battery back up for the real time clock Approved to European EMC standards CENELEC EN 50 082-1 and EN 55 011
CE-Approval
Environmental Conditions Ambient temperature 0 ... 50 CStorage temperature -20 ... 60 CAmbient humidity 0 ... 90 % rh., non condensingProtection Class III
-
8/13/2019 RCO700-4-10 en
2/4
2
Execution Housing plastic, for DIN-rail mountingProduction According to ROHSDimensions w x h x d, 160 x 136 x 35 mmWeight 270 g
Electrical Data Power supply 24 VAC/DC +/- 10 %, Class II
Output voltage 8 modules can be supplied over T-BusConnectors with 24 VDC via L- Bus 2. If more than 8 modules are connected to the bus, a power
module has to be used.Power consumption 5 W without Slaves (max. 8 modules can be supplied)Wire capacity 14 ... 24 AWG (0,25 ... 2,5 mm2)Main tightening torque 4 In-lb (0,45 Nm)Protection acc. to EN60529 IP 20
Communication Interfaces
Functional data Memory 8 MB SD-RAM4 MB Flash memory for the operating system
1 slot for SD-Memory Card as data and program memory
Power failure safety Data and programs are secured on the SD-Memory Card
Real time clock In case of a power cut battery backup is providedBatterie: CR2032, 210mAh
Building Management SystemMaster-Controller RCO 700D-M/W
Interface
Com 1 (RS232)Com 2 (RS232)
RS485_1RS485_2
L-Bus 1
L-Bus 2
Ethernet In/out
Protocols / Functions
ASCII ProtokollModbus RTU Master/SlaveM-Bus
WiloGrundfosEnergesta RENRCO-netBACnet Point to Point, EIA232BACnet Point to Point, ModemConnection to- BMS (operation, visualisation)- PC (programming),- Modem (analogue, gsm)- Printer- Messenger (SMS to mobil provi-
der, Fax, e-Mail)
Modbus RTU Master/SlaveWilo
GrundfosRCO CEnergesta RENBACnet/MSTP MasterBACnet/MSTP Slave
L-Bus-protocol for the field buscommunication with up to 32RCO C slave-modules.Operator panels RCO 640D-S canbe connected
L-Bus-protocol for the field buscommunication with up to 32
RCO D I/O-modules.Operator panels RCO 640D-S canbe connected
Ethernet protocol for the cross- linking of Master Controllers
- BACnet/IP- BACnet/IP, Foreign Device- BACnet/Ethernet, ISO 8802-3
Connection
RJ45Length: 15m
Two wire connection(Twisted Pair, shielded)
up to max. 1200 m
Four wire bus (TwistedPair, shielded) incl.
Power supply, lenght 40 600 m, dependend ofcable type and speed ofthe bus, can be extendedby use of a Power BridgeModule RCO 302D-P
Four wire bus (TwistedPair, shielded) incl.
Power supply, lenght 40 600 m, dependend ofcable type and speed ofthe bus, can be extendedby use of a Power BridgeModule RCO 302D-P
RJ45
Technical details
Transmision speed:57.600 bps (default) adjustableup to 115.200 bps
BACnet: 9.600 / 57.600 /115.200 bps
Transmision speed:Up to 57.600 bps.
Device address adjustable viaDIP-switches
BACnet: 9.600 / 19.200 /38.400 / 76.800 bps
Transmision speed:Standard: 100 Kbpsadjustable to 20 KbpsDevice address adjustable viaDIP-switches
Transmision speed:Standard: 100 Kbps
adjustable to 20 / 100 / 500 /1000 KbpsDevice address adjustable viaDIP-switches
10/100 Base-T
-
8/13/2019 RCO700-4-10 en
3/4
3
Programming Each Controller RCO 700D-M or RCO 700D-W has to be programmed individually. The freeprogrammability of all functions is done with the Engineering Software RCO-tool. The toolsupports text programming as well as graphical programming.
Software The RCO 700D-M or RCO 700D-W firmware provides a variety of helpful HVAC functions (PID- loop, Enthalpy) mathematical and logical operations. Time schedules, Alarms or Data logs can
be set up easily.
Operation The RCO 700D-M or RCO 700D-W can be accessed by PC, laptop or the operator panel (L-Bus).If a modem is connected, remote access or alarm monitoring by PC is possible. Local orremote access can be password protected.
Point schematic
1. DIP-Switch for the addessing of the RCO-bus ID2. RS485_13. RS485_24. Ethernet5. Ethernet6. DIP-switch for the termination resistor L-Bus1 (T)7. COM1 (RS232)8. COM2 (RS232)9. L-Bus 110. L-Bus 211. Power
DIP-switch settings
DIP-switch 1-6: Address 0-63 adjustable
The termination resistor for L-Bus 1 must be activated for the first and the last device (ON)
L-Bus 1 not active L-Bus 1 active L-Bus 1 active L-Bus 1 active
The terminator resistor for the L-Bus 2 is allready activated internally
Building Management SystemMaster-Controller RCO 700D-M/W
1 2
ON
OFF1 2
ON
OFF1 2
ON
OFF1 2
ON
OFF
1
32
7
6
54
11109
8
A1 B1 G1A2 B2 G2 A3 B3 P3 G3 A4 B4 P4 G4 PE N L
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Address 0 Address 1 Address 2
Address 3 Address 4 Address 5
Address 6 Address 7 Address 63
-
8/13/2019 RCO700-4-10 en
4/4
4
Building Management SystemMaster-Controller RCO 700D-M/W
Dimension drawing
Delivery RCO 700D-MRCO 700D-W
160,00
156,00
88,
30
136,
00
30,00
25,00
Cutout dimension: 156 x 92 mm