raychem high voltage outdoor termination up to … · raychem high voltage outdoor termination up...

4
Raychem High Voltage Outdoor Termination up to 245 kV Powering the UK Cable Services Limited

Upload: doankien

Post on 18-Aug-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Raychem High Voltage Outdoor Termination up to … · Raychem High Voltage Outdoor Termination up to 245 kV Model variations System add ons. ... Basic impulse level kV 325 550 650

Raychem High Voltage Outdoor Terminationup to 245 kV

Powering the UKCable Services Limited

Page 2: Raychem High Voltage Outdoor Termination up to … · Raychem High Voltage Outdoor Termination up to 245 kV Model variations System add ons. ... Basic impulse level kV 325 550 650

The Raychem OHVT SystemThe high voltage outdoor termination(OHVT) is designed for voltage up to245 kV and to operate under severeenvironmental conditions.Polymeric insulated cables of variousdesigns can be adopted with respect toshielding and metal sheath. Compositeor porcelain housings with differentcreepage lengths are available coveringthe most common and also extremepollution levels. The installation of thetermination can be done by trainedinstaller equiped with conventional tools.

The termination is designed accordingto following standards: IEC-60840,IEC-60815, IEEE-48; IEEE-1313

CreepageVariations according to individualrequirements- pollution class- normal sheds- alternating sheds

Cable lugDifferent types of cable lugs available- mechanical with defined torque- crimp octant or hexagonal

InsulatorVariations of insulator materials- composite- porcelain

AdapterVariations to customize thetermination contact bolt

Fibre optic kitFor special application with fibreoptic wire equipped cables

Arcing hornTo adjust the arcingdistance

Raychem High Voltage Outdoor Termination up to 245 kV

Model variations

System add ons

Page 3: Raychem High Voltage Outdoor Termination up to … · Raychem High Voltage Outdoor Termination up to 245 kV Model variations System add ons. ... Basic impulse level kV 325 550 650

Cable lugThe cable lug is suitable for all commoncondutors made of aluminium orcopper.

Sealing systemThe flexible double sealing system isinstaller-friendly and ensures permanentprotection against environmentalinfluences of the top assembly.Heat-shrinkable polymeric tubecontaining oil-resistant sealantencapsulates the connector barreland the polymeric insulation transition.

Insulator housing and oil-fillingThe pressure-tight composite housingis made of a glass fibre reinforced (GFR)resin tube with silicone rubber shedsmoulded to the tube.The interface between stress cone, cable insulation and inner housing will be filled from the top with silicone oil. No prior heating of silicone oil required.

Stress coneThe silicone rubber stress cone providesthe electrical field control function andcan easily be applied without tools. Theapplication range is taken by differentsizes of stress cones.

Base plate and support insulators4 support insulators can be used on thebase plate to mount the terminationinsulated. The termination can bemounted direct on the supportstructure as well. All metallic fittingsare made of corrosion resistant Al alloy.

Gland and sealThe cable gland outer serving isadapted through different gland sizes,which can serve the individual shieldingand armouring of the cable.The heat-shrinkable tube provides theouter protection and sealing for thecable gland area.

Raychem High Voltage Outdoor Termination up to 245 kV

Top end sealing system

Cable lug

Insulator housingand oil-filling

Stress cone

Cable gland andbottom end sealing

Base plate

Page 4: Raychem High Voltage Outdoor Termination up to … · Raychem High Voltage Outdoor Termination up to 245 kV Model variations System add ons. ... Basic impulse level kV 325 550 650

Cable stripper Gas torch Straightening slide rails Tool box Heating blanket

Technical data: 72 kV 123 kV 145 kV 170 kV 245 kV

Rated voltage U0/U (Um) kV 36/69(72.5) 64/115(123) 76/132(145) 87/161(170) 127/220(245)

Basic impulse level kV 325 550 650 750 1050

Max. continuous operating temperature °C 90 90 90 90 90

Max. conductor emergency temperature °C 150 150 150 150 150

Conductor short circuit temperature °C 250 250 250 250 250

Short circuit current (sheath) kA / 1sec 40 40 40 40 40

Creepage (Pollution class IEC 60815) a – e a – e a – e a – e a – e

Withstand voltage support insulators (AC/DC) kV 10/20 10/20 10/20 10/20 10/20

Application Range:

Conductor mm2 2000 2000 2000 2500 2500

Diameter over Insulation (Composite) mm 34 – 97 34 – 97 34 – 97 34 – 108 71 - 119

(Porcelain) mm 34 – 74 34 – 74 34 – 74 -- 71 - 119

Diameter over sheath mm 110 110 110 119 160

Tools

Tools required for cable preparation can also be purchased or rented from Cable Services.

All listed dimensions are standard size to serve the common application of these terminations.

For special applications and bigger cable sizes please contact your local Cable Services representative.

Raychem High Voltage Outdoor Termination up to 245 kV

Whilst Cable Services Limited has made every reasonable effort to ensure the accuracy of the information contained in this brochure, Cable Services Limited cannot assure that this information is error free. For this reason, Cable Services Limited does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Cable Services Limited reserves the right to make any adjustments to the information at any time. Cable Services Limited expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Cable Services Limited’s only obligations are those stated in Cable Services Limited’s Standard Terms and Conditions of Sale. Cable Services Limited will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgment to evaluate the suitability of a product for a certain purpose and test each product for its intended application. In case of any potential ambiguities or questions, please don’t hesitate to contact us for clarification.

Cable Services - WrexhamRhosddu Industrial Estate, Rhosrobin, Wrexham LL11 4YZ.Tel: 01978 340450Fax: 01978 311315Email: [email protected]

Cable Services - StoneUnit 2 Douglas Park, Opal Way,Stone Business Park, Stone, Staffordshire ST15 0YJTel: 01785 825970Fax: 01785 825977Email: [email protected]

Smith Electrical - GlasgowUnit 14, Block 8,Thornliebank Industrial Estate, Glasgow G46 8JH.Tel: 0141 621 2060Fax: 0141 638 9996Email: [email protected]

Cable Services - Liverpool43 St. Johns Road, Liverpool L20 8AZ.Tel: 0151 9339022Fax: 0151 9339765Email: [email protected]

To place an order or for more information please contact your Cable Services sales team.

www.cableservices.co.uk

RS 21752

Issue

4 03

/12

Powering the UKCable Services Limited