Item No. Item Description Quantity Unit of Measurement (UOM) Rate AMOUNT HALDIA INSTALLATION SAFETY PLC : 1 Supply of -Dual Redundant Safety Programmable Logic Controller (SIL2 Certified) with Licensed Software (Engg./ Loader software) including marshalling cabinet/s [for ESD System] IO Count :: DI : 551, DO : 205, AI 2 wire TX : 58, AI 3 wire TX HART : 10 , Pulse Input Card : 0, Serial RS 485 : 5 1 Set 2 Supply of -Power Distribution cabinet with MCBs for individual isolation for distribution of 230VAC, Single Phase UPS/Non-UPS Supply to field and control room instrumentation. 1 Nos. 3 Supply of Engg Cum Operator Station with 21" LCD Monitor. Operating System Windows 2008 Server 1 Nos. 4 Supply of - Operator Station with 21" LCD Monitor. Operating System Windows 7 2 Nos. 5 Supply of -Laser Jet Printer A4 size color 1 Nos. 6 Supply of -Networking Hardware comprising of : Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT 6 structured cables, associated hardware and cables (power / signal / control) required for interpanel connectivity of centralised instrumentation. 1 Lump Sum 7 Supply of -System cabinets to house Ethernet Switch, Networking Hardware as per tender specification. TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be provided by BPCL shall also be housed in the System Cabinet. 1 Nos. 8 Supply of -Open Table type console centers for mounting the servers / workstations in control room (i.e. Engg Cum Operator Station, Operator Station) 1 Set 9 Supply of -Un-Interrupted Power Supply of Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni- Cd batteries. Note: Incase if actual calculated system load exceeds 10KVA then UPS rating shall be 120% of the actual calculated load. 1 Set 10 Supply of -Explosion Proof / Weather proof ESD Push Button Station 15 Nos. 11 Supply of -Flameproof / Weatherproof Hooter 2 Nos. 12 Supply of -Weatherproof Hooter 2 Nos. 13 Supply of -Level Switch SIL 2 Certified 14 Nos. 14 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands, thimbles, ferrules, connectors etc. complete) and other installation material as per tender specification. No. of Cable Entries - Multi Core : 2 Nos (bottom entry) - Branch Cables : 12 Nos (side entry) Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables. 1 Nos. 15 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands, thimbles, ferrules, connectors etc. complete) and other installation material as per tender specification. No. of Cable Entries - Multi Core : 2 Nos (bottom entry) - Branch Cables : 6 Nos (side entry) Cable Size for Power JB - Multi Core : 24C x 1.5 mm2 - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables. 6 Nos. 16 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands, thimbles, ferrules, connectors etc. complete) and other installation material as per tender specification. No. of Cable Entries - Multi Core : 2 Nos (bottom entry) - Branch Cables : 12 Nos (side entry) Cable Size for Power JB - Multi Core : 24C x 1.5 mm2 - Branch Cable : 2C x 1.5 mm2 Note: These are copper cables. 24 Nos. 17 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands, thimbles, ferrules, connectors etc. complete) and other installation material as per tender specification. No. of Cable Entries - Multi Core : 2 Nos (bottom entry) - Branch Cables : 6 Nos (side entry) Cable Size for Control JB - Multi Core : 12C x 1.5 mm2 - Branch Cable : 2C x 1.5 mm2 Note: These are copper cables. 22 Nos. 18 Supply of -FLP/WP Signal Junction Box-Triad, (including FLP/WP SS cable glands, thimbles, ferrules, connectors etc. complete) and other installation material as per tender specification. No. of Cable Entries - Multi Core : 2 Nos (from bottom only) - Branch Cables : 8 Nos (from sides) Cable Size for Signal JB - Multi Core : 8 Triad x 1.5 mm2 - Branch Cable: 1 Triad x1.5 mm2 (for HC Detectors / Transmitters) Note: These are copper cables. 2 Nos. 19 Supply of -FLP/WP Signal Junction Box, (including FLP/WP SS cable glands, thimbles, ferrules, connectors etc. complete) and other installation material as per tender specification. No. of Cable Entries - Multi core : 2 Nos (from bottom only) - Branch Cables : 12 Nos (from sides) Cable Size for Signal JB - Multi Core : 12 P x 1.5 mm2 - Branch Cable: 1 P x1.5 mm2 Note: These are copper cables. 6 Nos. Supplying of perforated AL cable trays along with accessories (e.g coupler plate , aluminium saddles, screws, nuts, washers ) of following sizes: a) 50 mm 785 RMT b) 100 mm 50 RMT c) 150 mm 310 RMT d) 200 mm 100 RMT e) 300 mm 1000 RMT 20 SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION, PATNA TOP & RAJBANDH TOP

Upload: others

Post on 06-Aug-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

HALDIA INSTALLATION SAFETY PLC :

1 Supply of -Dual Redundant Safety Programmable Logic Controller (SIL2

Certified) with Licensed Software (Engg./ Loader software) including

marshalling cabinet/s [for ESD System] IO Count :: DI : 551, DO : 205, AI 2

wire TX : 58, AI 3 wire TX HART : 10 , Pulse Input Card : 0, Serial RS 485 :

5

1

Set

2 Supply of -Power Distribution cabinet with MCBs for individual isolation for

distribution of 230VAC, Single Phase UPS/Non-UPS Supply to field and control

room instrumentation.

1

Nos.

3 Supply of Engg Cum Operator Station with 21" LCD Monitor.

Operating System Windows 2008 Server 1

Nos.

4 Supply of - Operator Station with 21" LCD Monitor.

Operating System Windows 72

Nos.

5 Supply of -Laser Jet Printer A4 size color 1 Nos.

6 Supply of -Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.

1

Lump Sum

7 Supply of -System cabinets to house Ethernet Switch, Networking Hardware as

per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

8 Supply of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg Cum Operator Station, Operator

Station)

1

Set

9 Supply of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Set

10 Supply of -Explosion Proof / Weather proof ESD Push Button Station15

Nos.

11 Supply of -Flameproof / Weatherproof Hooter 2

Nos.

12 Supply of -Weatherproof Hooter 2

Nos.

13 Supply of -Level Switch SIL 2 Certified 14

Nos.

14 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable)

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

15 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

6

Nos.

16 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

24

Nos.

17 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Control JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

22

Nos.

18 Supply of -FLP/WP Signal Junction Box-Triad, (including FLP/WP SS cable

glands, thimbles, ferrules, connectors etc. complete) and other installation

material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

Note: These are copper cables.

2

Nos.

19 Supply of -FLP/WP Signal Junction Box, (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

6

Nos.

Supplying of perforated AL cable trays along with accessories (e.g coupler

plate , aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 785 RMT

b) 100 mm 50 RMT

c) 150 mm 310 RMT

d) 200 mm 100 RMT

e) 300 mm 1000 RMT

20

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

Page 2: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

Fixing of perforated AL cable trays along with accessories (e.g coupler plate ,

aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 785 RMT

b) 100 mm 50 RMT

c) 150 mm 310 RMT

d) 200 mm 100 RMT

e) 300 mm 1000 RMT

Supply & laying of Hume pipes (NP2) across Road crossing including road

cutting & remaking of WBM roads of following sizes ( if required as per site

condition)

a) 6 inch dia Hume pipe 30 RMT

b) 8 inch dia Hume pipe 40 RMT

c) 10 inch dia Hume pipe 50 RMT

23 Modification at MCC Panels including Supply of relays / contactors, PVC wires,

lugs, ferrules, erection hardware (as required) to provide potential free contacts

to be connected to the PLCs (Safety) for status (Motor Running / Trip) &

command (Start / Stop / ESD command) from PLCs.

Note : applicable for existing MCCs of TLF/ TWF/ TWD / FW Pumps (as

applicable)

23

Nos.

24 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends

Cable size - 1 pair x 1.5 mm2

12238

Meter

25 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 1Triad x 1.5 mm2

1927

Meter

26 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 12pair x 1.5 mm2

1102

Meter

27 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 8Triad x 1.5 mm2

585

Meter

28 Laying of Power Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 3C x 1.5 mm2

5159

Meter

29 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

1105

Meter

30 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 36C x 1.5 mm2 OR 36C x 2.5 mm2

50

Meter

31 Laying of Control Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 2C x 1.5 mm2

42594

Meter

32 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

5143

Meter

33 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 12C x 1.5 mm2

4634

Meter

34 Excavation & backfilling of cable trenches

Staking out, marking the outline for excavation, excavation in any type of soil,

PCC or hard rock for general site grading by machinery or manually up to 750

mm below NGL, 400 mm wide for all depths as given below including removal

of stumps and roots to full extent removal of all vegetation including bushes

and grass, dewatering & leveling., dressing and backfilling after cable is laid

etc; complete as per specifications and instructions of Engineer In-Charge

(EIC).

Scope of work shall also include Supply/filling of sand & supply /placing of

Class B bricks in for excavated trenches subsequent to laying of cables. 2000

RMT

35 Erection, Testing & Commissioning of -Dual Redundant Safety Programmable

Logic Controller (SIL2 Certified) with Licensed Software (Engg./ Loader

software) including marshalling cabinet/s

[for ESD System]IO Count :: DI : 551, DO : 205, AI 2 wire TX : 58, AI 3 wire

TX HART : 10 , Pulse Input Card : 0, Serial RS 485 : 5

1

Set

36 Erection, Testing & Commissioning of -Power Distribution cabinet for

distribution of 230 VAC Single Phase UPS/Non-UPS supply to equipments /

instruments in control Room & field.

1

Nos.

37 Erection, Testing & Commissioning of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Nos.

38 Erection, Testing & Commissioning of -Engg cum Operator Station with 21"

LCD Monitor.

Operating System Windows 2008 Server

1

Nos.

39 Erection, Testing & Commissioning of -Workstation (OIC) with 21" LCD

Monitor.

Operating System Windows 7

2

Nos.

40 Erection, Testing & Commissioning of -Laser Jet Printer A4 size color 1 Nos.

41 Erection, Testing & Commissioning of - Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.

1

Lump Sum

42 Erection of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg. Cum Operator Station, Operator

Station)

1

Set

43 Erection of -System cabinets to house Ethernet Switch, Networking Hardware

as per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

44 Installation Testing & Commissioning of -Explosion Proof / Weather proof ESD

Push Button Station15

Nos.

22

21

Page 3: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

45 Installation Testing & Commissioning of -Flameproof / Weatherproof Hooter 2

Nos.

46 Installation Testing & Commissioning of -Weatherproof Hooter 2 Nos.

47 Installation Testing & Commissioning of -Level Switch SIL 2 Certified 14

Nos.

48 Installation Testing & Commissioning of FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

49 Installation Testing & Commissioning of -FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

6

Nos.

50 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

24

Nos.

51 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

22

Nos.

52 Installation Testing & Commissioning of - FLP/WP Signal Junction Box-Triad,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

2

Nos.

53 Installation Testing & Commissioning of - FLP/WP Signal Junction Box,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

6

Nos.

54 Testing & Commissioning of MCC Panels (subsequent to modifications carried

out by vendor)1

Lump Sum

Powering ON and functional checking of following field instrumentation at

Safety PLC and Engg cum Operator Station as per Functional Design

Specification.

Lump Sum

a) Hi-Hi Level Switch 14Nos

b) Level Tx. - Radar Type 14Nos

c) Level Tx. - Servo Type 14Nos

d) Pneumatic ROSOV 28Nos

e) DBB Valve (Electric Actuator) 6Nos

f) HC Detector - Point Type 2Nos

g) HC Detector - Open Path Type 6Nos

h) ESD Push Button Station 15Nos

i) FLP / WP Hooter 2Nos

j) WP Hooter 2Nos

k) Modified MCC Panel 23Nos

l) Existing MOVs (ESD Ports) 67Nos

m) Existing Batch Controller (ESD Ports) 20Nos

n) Existing Main Power Distribution system (Non-Critical Loads) ESD Port 10

Nos

o) Rim Seal Protection System (PLC)3

Nos

p) HVLR System (PLC)8

Nos

55

Page 4: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

56 Development of software Drivers (Engg cum Operator Station Resident) to

serially interface follwoing field instrumentation / sub-systems with safety PLC.

1) HART Protocol based Field Instrumentation [eg. (Pr / Temp / Flow) Tx. /

Mass FLow Meters / Hydrocarbon Detectors

2) MODBUS RTU Protocol based PLCs pertaining to (a) Rim Seal Protection

system; (b) Fire Fighting Control system ; (c) Master control station of MOVs;

(d) Electric / Pneumatic Fail safe Remote operated shut-off valves (e)

Communication Interface Unit of TFMS System (f) HVLR system (g) VFDs

3) TCP/IP Protocol between TAS and TFMS system and safety PLC system

NOTE :

(1) The scope of work under this item include Data base generation, Graphic

configuration, PLC loader software modification & any other requirement at

Engg / Operator Station.

(2) Development of software drivers for all the instruments / systems to be

supplied by vendor will not be considered under this item.;

(3) Vendors have to develop dynamic graphics of all the facilities at an

Installation.

1

Nos.

57 Supply, fabrication, welding, erection and painting of structural steel confirming

to IS 2062 latest edition, consisting of channels, beams, angles, flats, tubular

sections, etc; fabrication of steel structures, structural frame for Junction Boxes,

cable trays, field instruments [ under vendor' scope of supply & only HC

Detectors free issue item from BPCL). This includes supply of bolts, nuts

washers, shims, packs, putty, gas, welding electrodes, and all other

consumables as required, cleaning and surface preparation of all steel surfaces

with emry paper/wire brush, supply and application of 2 coats of red oxide zinc

phosphate primer of 30 to 35 microns dft each, supply and application of 2

coats of synthetic enamel paint of 30 to 35 microns dft of approved shade. Rate

to include excavating pit for grouting the member, grouting the structural steel

member in PCC M15, shuttering, ramming, finishing the same with cement

slurry etc; complete at all depths and as per approved drawing or instruction of

EIC. The height of frame shall be 1.3m from the FGL and 0.45m inside earth

for grouting purpose. The buried portion shall be coated with bitumen on all

sides before grouting the same in PCC. PCC shall be minimum 350mm x

350mm x 450mm for each leg of the frame / member.

The exposed portion of the PCC surface shall be whitewashed.

15000

Kilograms

58 Making of Electrical Earthing Pits - Complete electrical earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.

30

Nos.

59 Making of Instrument Earthing Pits -Complete instrument earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.30

Nos.

60 System Design & Engineering 1 Lump Sum

61 Factory Acceptance Test 1 Lump Sum

62 Training (at Factory) 1 Lump Sum

63 Training (at Site)

1

Lump Sum

64 Site Acceptance Test 1 Lump Sum

65 Documentations including as built drawings (6 Sets). 1 Lump Sum

66 CMC (Comprehensive Maintenance Charges) for 5 years (Post Warranty

Period)1

Lump Sum

PARADEEP INSTALLATION SAFETY PLC :

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

1 Supply of -Dual Redundant Safety Programmable Logic Controller (SIL2

Certified) with Licensed Software (Engg./ Loader software) including

marshalling cabinet/s

[for ESD System] IO Count :: DI : 467, DO: 191,AI 2 WIRE TX : 50, AI 3

WIRE TX HART : 6, SERIAL RS 485 : 5

1

Set

2 Supply of -Power Distribution cabinet with MCBs for individual isolation for

distribution of 230VAC, Single Phase UPS/Non-UPS Supply to field and control

room instrumentation.

1

Nos.

3 Supply of Engg Cum Operator Station with 21" LCD Monitor.

Operating System Windows 2008 Server 1

Nos.

4 Supply of - Operator Station with 21" LCD Monitor.

Operating System Windows 72

Nos.

5 Supply of -Laser Jet Printer A4 size color 1 Nos.

6 Supply of -Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.

1

Lump Sum

7 Supply of -System cabinets to house Ethernet Switch, Networking Hardware as

per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

8 Supply of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg Cum Operator Station, Operator

Station)

1

Set

9 Supply of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Set

10 Supply of -Explosion Proof / Weather proof ESD Push Button Station15

Nos.

11 Supply of -Flameproof / Weatherproof Hooter 2

Nos.

12 Supply of -Weatherproof Hooter 2

Nos.

13 Supply of -Level Switch SIL 2 Certified 11

Nos.

Page 5: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

14 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

15 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

2

Nos.

16 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

15

Nos.

17 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

24

Nos.

18 Supply of -FLP/WP Signal Junction Box-Triad, (including FLP/WP SS cable

glands, thimbles, ferrules, connectors etc. complete) and other installation

material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

Note: These are copper cables.

1

Nos.

19 Supply of -FLP/WP Signal Junction Box, (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

6

Nos.

20 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 4Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

4

Nos

Supplying of perforated AL cable trays along with accessories (e.g coupler

plate , aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 2500

RMT

b) 100 mm 200

RMT

c) 150 mm300

RMT

d) 200 mm1200

RMT

e) 300 mm1500

RMT

Fixing of perforated AL cable trays along with accessories (e.g coupler plate ,

aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 2500

RMT

b) 100 mm 200

RMT

c) 150 mm300

RMT

d) 200 mm1200

RMT

e) 300 mm1500

RMT

Supply & laying of Hume pipes (NP2) across Road crossing including road

cutting & remaking of WBM roads of following sizes ( if required as per site

condition)

a) 6 inch dia Hume pipe 30 RMT

b) 8 inch dia Hume pipe 40 RMT

c) 10 inch dia Hume pipe 50 RMT

24 Modification at MCC Panels including Supply of relays / contactors, PVC wires,

lugs, ferrules, erection hardware (as required) to provide potential free contacts

to be connected to the PLCs (Safety) for status (Motor Running / Trip) &

command (Start / Stop / ESD command) from PLCs.

Note : applicable for existing MCCs of TLF/ TWF/ TWD / FW Pumps (as

applicable)

15

Nos.

25 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends

Cable size - 1 pair x 1.5 mm2

6980

Meter

21

23

22

Page 6: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

26 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 1Triad x 1.5 mm2

600

Meter

27 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 12pair x 1.5 mm2

1710

Meter

28 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 8Triad x 1.5 mm2 OR 8Triad x 2.5 mm2

207

Meter

29 Laying of Power Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 3C x 1.5 mm2

3699

Meter

30 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

677

Meter

31 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 36C x 1.5 mm2

50

Meter

32 Laying of Control Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 2C x 1.5 mm2

18740

Meter

33 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

5274

Meter

34 Laying of Multicore Control & Power Cables (Copper Conductor, FRLS PVC

Armoured) in under ground cable trenches or in above ground cable trays

including Glanding / Termination / Loop checking at both ends

Cable Size - 12C x 1.5 mm2

6243

Meter

35 Excavation & backfilling of cable trenches

Staking out, marking the outline for excavation, excavation in any type of soil,

PCC or hard rock for general site grading by machinery or manually up to 750

mm below NGL and 400 mm width for all depths as given below including

removal of stumps and roots to full extent removal of all vegetation including

bushes and grass, dewatering & leveling., dressing and backfilling after cable

is laid etc; complete as per specifications and instructions of Engineer In-

Charge (EIC).

Scope of work shall also include Supply/filling of sand & supply /placing of

Class B bricks in for excavated trenches subsequent to laying of cables.

2000 RMT

36 Erection, Testing & Commissioning of -Dual Redundant Safety Programmable

Logic Controller (SIL2 Certified) with Licensed Software (Engg./ Loader

software) including marshalling cabinet/s

[for ESD System] IO Count :: IO Count :: DI : 467, DO: 191,AI 2 WIRE TX :

50, AI 3 WIRE TX HART : 6, SERIAL RS 485 : 5

1

Set

37 Erection, Testing & Commissioning of -Power Distribution cabinet for

distribution of 230 VAC Single Phase UPS/Non-UPS supply to equipments /

instruments in control Room & field.

1

Nos.

38 Erection, Testing & Commissioning of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Nos.

39 Erection, Testing & Commissioning of -Engg cum Operator Station with 21"

LCD Monitor.

Operating System Windows 2008 Server

1

Nos.

40 Erection, Testing & Commissioning of -Workstation (OIC) with 21" LCD

Monitor.

Operating System Windows 7

2

Nos.

41 Erection, Testing & Commissioning of -Laser Jet Printer A4 size color 1 Nos.

42 Erection, Testing & Commissioning of - Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.1

Lump Sum

43 Erection of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg. Cum Operator Station, Operator

Station)

1

Set

44 Erection of -System cabinets to house Ethernet Switch, Networking Hardware

as per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

45 Installation Testing & Commissioning of -Explosion Proof / Weather proof ESD

Push Button Station15

Nos.

46 Installation Testing & Commissioning of -Flameproof / Weatherproof Hooter 2

Nos.

47 Installation Testing & Commissioning of -Weatherproof Hooter 2 Nos.

48 Installation Testing & Commissioning of -Level Switch SIL 2 Certified 11

Nos.

49 Installation Testing & Commissioning of FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

Page 7: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

50 Installation Testing & Commissioning of -FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

2

Nos.

51 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

15

Nos.

52 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

24

Nos.

53 Installation Testing & Commissioning of - FLP/WP Signal Junction Box-Triad,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

1

Nos.

54 Installation Testing & Commissioning of - FLP/WP Signal Junction Box,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

6

Nos.

55 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables :4 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

4

Nos

56 Testing & Commissioning of MCC Panels (subsequent to modifications carried

out by vendor)1

Lump Sum

Powering ON and functional checking of following field instrumentation at

Safety PLC and Engg cum Operator Station as per Functional Design

Specification.

Lump Sum

a) Hi-Hi Level Switch 11Nos

b) Level Tx. - Radar Type 11Nos

c) Level Tx. - Servo Type 11Nos

d) Pneumatic ROSOV 22Nos

e) DBB Valve (Electric Actuator) 6Nos

f) HC Detector - Point Type 2Nos

g) HC Detector - Open Path Type 3Nos

h) ESD Push Button Station 15Nos

i) FLP / WP Hooter 2Nos

j) WP Hooter 2Nos

k) Modified MCC Panel 15Nos

l) Existing MOVs (ESD Ports) 64Nos

m) Existing Batch Controller (ESD Ports) 20Nos

n) Existing Main Power Distribution system (Non-Critical Loads) ESD Port 8

Nos

o) Rim Seal Protection System (PLC)4

Nos

p) HVLR System (PLC)4

Nos

58 Development of software Drivers (Engg cum Operator Station Resident) to

serially interface follwoing field instrumentation / sub-systems with safety PLC.

1) HART Protocol based Field Instrumentation [eg. (Pr / Temp / Flow) Tx. /

Mass FLow Meters / Hydrocarbon Detectors

2) MODBUS RTU Protocol based PLCs pertaining to (a) Rim Seal Protection

system; (b) Fire Fighting Control system ; (c) Master control station of MOVs;

(d) Electric/ Pneumatic Fail safe Remote operated shut-off valves (e)

Communication Interface Unit of TFMS System (f) HVLR system (g) VFDs

3) TCP/IP Protocol between TAS and TFMS system and safety PLC system

NOTE :

(1) The scope of work under this item include Data base generation, Graphic

configuration, PLC loader software modification & any other requirement at

Engg / Operator Station.

(2) Development of software drivers for all the instruments / systems to be

supplied by vendor will not be considered under this item.;

(3) Vendors have to develop dynamic graphics of all the facilities at an

Installation.

1

Nos.

57

Page 8: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

59 Supply, fabrication, welding, erection and painting of structural steel confirming

to IS 2062 latest edition, consisting of channels, beams, angles, flats, tubular

sections, etc; fabrication of steel structures, structural frame for Junction Boxes,

cable trays, field instruments [ under vendor' scope of supply & only HC

Detectors free issue item from BPCL). This includes supply of bolts, nuts

washers, shims, packs, putty, gas, welding electrodes, and all other

consumables as required, cleaning and surface preparation of all steel surfaces

with emry paper/wire brush, supply and application of 2 coats of red oxide zinc

phosphate primer of 30 to 35 microns dft each, supply and application of 2

coats of synthetic enamel paint of 30 to 35 microns dft of approved shade. Rate

to include excavating pit for grouting the member, grouting the structural steel

member in PCC M15, shuttering, ramming, finishing the same with cement

slurry etc; complete at all depths and as per approved drawing or instruction of

EIC. The height of frame shall be 1.3m from the FGL and 0.45m inside earth

for grouting purpose. The buried portion shall be coated with bitumen on all

sides before grouting the same in PCC. PCC shall be minimum 350mm x

350mm x 450mm for each leg of the frame / member.

The exposed portion of the PCC surface shall be whitewashed.

15000

Kilograms

60 Making of Electrical Earthing Pits - Complete electrical earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.

30

Nos.

61 Making of Instrument Earthing Pits -Complete instrument earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.30

Nos.

62 System Design & Engineering 1 Lump Sum

63 Factory Acceptance Test 1 Lump Sum

64 Training (at Factory) 1 Lump Sum

65 Training (at Site) 1 Lump Sum

66 Site Acceptance Test 1 Lump Sum

67 Documentations including as built drawings (6 Sets). 1 Lump Sum

68 CMC (Comprehensive Maintenance Charges) for 5 years (Post Warranty

Period)1

Lump Sum

TOTAL

RAJBANDH TOP SAFETY PLC :

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

1 Supply of -Dual Redundant Safety Programmable Logic Controller (SIL2

Certified) with Licensed Software (Engg./ Loader software) including

marshalling cabinet/s

[for ESD System] IO Count :: DI : 325, DO: 134,AI 2 WIRE TX : 55, AI 3

WIRE TX HART : 4, SERIAL RS 485 : 5

1

Set

2 Supply of -Power Distribution cabinet with MCBs for individual isolation for

distribution of 230VAC, Single Phase UPS/Non-UPS Supply to field and control

room instrumentation.

1

Nos.

3 Supply of Engg Cum Operator Station with 21" LCD Monitor.

Operating System Windows 2008 Server 1

Nos.

4 Supply of - Operator Station with 21" LCD Monitor.

Operating System Windows 72

Nos.

5 Supply of -Laser Jet Printer A4 size color 1 Nos.

6 Supply of -Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.

1

Lump Sum

7 Supply of -System cabinets to house Ethernet Switch, Networking Hardware as

per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

8 Supply of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg Cum Operator Station, Operator

Station)

1

Set

9 Supply of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Set

10 Supply of -Explosion Proof / Weather proof ESD Push Button Station15

Nos.

11 Supply of -Flameproof / Weatherproof Hooter 2

Nos.

12 Supply of -Weatherproof Hooter 2

Nos.

13 Supply of -Level Switch SIL 2 Certified 7

Nos.

14 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

15 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

4

Nos.

16 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Control JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

12

Nos.

Page 9: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

17 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

12

Nos.

18 Supply of -FLP/WP Signal Junction Box-Triad, (including FLP/WP SS cable

glands, thimbles, ferrules, connectors etc. complete) and other installation

material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

Note: These are copper cables.

1

Nos.

19 Supply of -FLP/WP Signal Junction Box, (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

11

Nos.

Supplying of perforated GI cable trays along with accessories (e.g coupler

plate , aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 344

RMT

b) 100 mm 782

RMT

c) 150 mm394

RMT

d) 200 mm22

RMT

e) 300 mm1263

RMT

Fixing of perforated GI cable trays along with accessories (e.g coupler plate ,

aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 344

RMT

b) 100 mm 782

RMT

c) 150 mm394

RMT

d) 200 mm22

RMT

e) 300 mm1263

RMT

Supply & laying of Hume pipes (NP2) across Road crossing including road

cutting & remaking of WBM roads of following sizes ( if required as per site

condition)

a) 6 inch dia Hume pipe 20 RMT

b) 8 inch dia Hume pipe 30 RMT

c) 10 inch dia Hume pipe 40 RMT

23 Modification at MCC Panels including Supply of relays / contactors, PVC wires,

lugs, ferrules, erection hardware (as required) to provide potential free contacts

to be connected to the PLCs (Safety) for status (Motor Running / Trip) &

command (Start / Stop / ESD command) from PLCs.

Note : applicable for existing MCCs of TLF/ TWF/ TWD / FW Pumps (as

applicable)

15

Nos.

24 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends

Cable size - 1 pair x 1.5 mm2

2688

Meter

25 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 1Triad x 1.5 mm2

303

Meter

26 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 12pair x 1.5 mm2

2521

Meter

27 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 8Triad x 1.5 mm2

167

Meter

28 Laying of Power Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 3C x 1.5 mm2

553

Meter

29 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

899

Meter

30 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 36C x 1.5 mm2

50

Meter

31 Laying of Control Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 2C x 1.5 mm2

7858

Meter

32 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

2736

Meter

33 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 12C x 1.5 mm2

2032

Meter

21

22

20

Page 10: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

34 Excavation & backfilling of cable trenches

Staking out, marking the outline for excavation, excavation in any type of soil,

PCC or hard rock for general site grading by machinery or manually up to 750

mm below NGL and width 400mm for all depths as given below including

removal of stumps and roots to full extent removal of all vegetation including

bushes and grass, dewatering & leveling., dressing and backfilling after cable

is laid etc; complete as per specifications and instructions of Engineer In-

Charge (EIC).

Scope of work shall also include Supply/filling of sand & supply /placing of

Class B bricks in for excavated trenches subsequent to laying of cables.

1000 RMT

35 Erection, Testing & Commissioning of -Dual Redundant Safety Programmable

Logic Controller (SIL2 Certified) with Licensed Software (Engg./ Loader

software) including marshalling cabinet/s

[for ESD System] IO Count :: DI : 325, DO: 134,AI 2 WIRE TX : 55, AI 3 WIRE

TX HART : 4, SERIAL RS 485 : 5

1

Set

36 Erection, Testing & Commissioning of -Power Distribution cabinet for

distribution of 230 VAC Single Phase UPS/Non-UPS supply to equipments /

instruments in control Room & field.

1

Nos.

37 Erection, Testing & Commissioning of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Nos.

38 Erection, Testing & Commissioning of -Engg cum Operator Station with 21"

LCD Monitor.

Operating System Windows 2008 Server

1

Nos.

39 Erection, Testing & Commissioning of -Workstation (OIC) with 21" LCD

Monitor.

Operating System Windows 7

2

Nos.

40 Erection, Testing & Commissioning of -Laser Jet Printer A4 size color 1 Nos.

41 Erection, Testing & Commissioning of - Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.

1

Lump Sum

42 Erection of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg. Cum Operator Station, Operator

Station)

1

Set

43 Erection of -System cabinets to house Ethernet Switch, Networking Hardware

as per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

44 Installation Testing & Commissioning of -Explosion Proof / Weather proof ESD

Push Button Station15

Nos.

45 Installation Testing & Commissioning of -Flameproof / Weatherproof Hooter 2

Nos.

46 Installation Testing & Commissioning of -Weatherproof Hooter 2 Nos.

47 Installation Testing & Commissioning of -Level Switch SIL 2 Certified 7

Nos.

48 Installation Testing & Commissioning of FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

49 Installation Testing & Commissioning of -FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

4

Nos.

50 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

12

Nos.

51 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

12

Nos.

52 Installation Testing & Commissioning of - FLP/WP Signal Junction Box-Triad,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

1

Nos.

53 Installation Testing & Commissioning of - FLP/WP Signal Junction Box,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

11

Nos.

Page 11: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

54 Testing & Commissioning of MCC Panels (subsequent to modifications carried

out by vendor)1

Lump Sum

Powering ON and functional checking of following field instrumentation at

Safety PLC and Engg cum Operator Station as per Functional Design

Specification.

Lump Sum

a) Hi-Hi Level Switch 7Nos

b) Level Tx. - Radar Type 7Nos

c) Level Tx. - Servo Type 7Nos

d) Electric Fail Safe ROSOV (Electric Actuator) 14Nos

e) DBB Valve (Electric Actuator) 6Nos

f) HC Detector - Point Type 1Nos

g) HC Detector - Open Path Type 2Nos

h) ESD Push Button Station 15Nos

i) FLP / WP Hooter 2Nos

j) WP Hooter 2Nos

k) Modified MCC Panel 10Nos

l) Existing MOVs (ESD Ports) 36Nos

m) Existing Batch Controller (ESD Ports) 12 Nos

n) Existing Main Power Distribution system (Non-Critical Loads) ESD Port 8

Nos

o) Rim Seal Protection System (PLC)3

Nos

p) HVLR System (PLC)4

Nos

56 Development of software Drivers (Engg cum Operator Station Resident) to

serially interface follwoing field instrumentation / sub-systems with safety PLC.

1) HART Protocol based Field Instrumentation [eg. (Pr / Temp / Flow) Tx. /

Mass FLow Meters / Hydrocarbon Detectors

2) MODBUS RTU Protocol based PLCs pertaining to (a) Rim Seal Protection

system; (b) Fire Fighting Control system ; (c) Master control station of MOVs;

(d) Electric / Pneumatic Fail safe Remote operated shut-off valves (e)

Communication Interface Unit of TFMS System (f) HVLR system (g) VFDs

3) TCP/IP Protocol between TAS and TFMS system and safety PLC system

NOTE :

(1) The scope of work under this item include Data base generation, Graphic

configuration, PLC loader software modification & any other requirement at

Engg / Operator Station.

(2) Development of software drivers for all the instruments / systems to be

supplied by vendor will not be considered under this item.;

(3) Vendors have to develop dynamic graphics of all the facilities at an

Installation.

1

Nos.

57 Supply, fabrication, welding, erection and painting of structural steel confirming

to IS 2062 latest edition, consisting of channels, beams, angles, flats, tubular

sections, etc; fabrication of steel structures, structural frame for Junction Boxes,

cable trays, field instruments [ under vendor' scope of supply & only HC

Detectors free issue item from BPCL). This includes supply of bolts, nuts

washers, shims, packs, putty, gas, welding electrodes, and all other

8000

Kilograms

58 Making of Electrical Earthing Pits - Complete electrical earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.

20

Nos.

59 Making of Instrument Earthing Pits -Complete instrument earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.20

Nos.

60 System Design & Engineering 1 Lump Sum

61 Factory Acceptance Test 1 Lump Sum

62 Training (at Factory) 1 Lump Sum

63 Training (at Site) 1 Lump Sum

64 Site Acceptance Test 1 Lump Sum

65 Documentations including as built drawings (6 Sets). 1 Lump Sum

66 CMC (Comprehensive Maintenance Charges) for 5 years (Post Warranty

Period)1

Lump Sum

PATNA TOP SAFETY PLC :

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

1 Supply of -Dual Redundant Safety Programmable Logic Controller (SIL2

Certified) with Licensed Software (Engg./ Loader software) including

marshalling cabinet/s

[for ESD System] :IO Count :: DI : 409, DO: 182,AI 2 WIRE TX : 65, AI 3

WIRE TX HART : 4, SERIAL RS 485 :4

1

Set

2 Supply of -Power Distribution cabinet with MCBs for individual isolation for

distribution of 230VAC, Single Phase UPS/Non-UPS Supply to field and control

room instrumentation.

1

Nos.

3 Supply of Engg Cum Operator Station with 21" LCD Monitor.

Operating System Windows 2008 Server 1

Nos.

4 Supply of - Operator Station with 21" LCD Monitor.

Operating System Windows 72

Nos.

5 Supply of -Laser Jet Printer A4 size color 1 Nos.

6 Supply of -Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.

1

Lump Sum

7 Supply of -System cabinets to house Ethernet Switch, Networking Hardware as

per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

8 Supply of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg Cum Operator Station, Operator

Station)

1

Set

9 Supply of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Set

10 Supply of -Explosion Proof / Weather proof ESD Push Button Station15

Nos.

55

Page 12: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

11 Supply of -Flameproof / Weatherproof Hooter 2

Nos.

12 Supply of -Weatherproof Hooter 2

Nos.

13 Supply of -Level Switch SIL 2 Certified 9

Nos.

14 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

15 Supply of -FLP/WP Power Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

4

Nos.

16 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

14

Nos.

17 Supply of -FLP/WP Control Junction Box (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Control JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

15

Nos.

18 Supply of -FLP/WP Signal Junction Box-Triad, (including FLP/WP SS cable

glands, thimbles, ferrules, connectors etc. complete) and other installation

material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

Note: These are copper cables.

1

Nos.

19 Supply of -FLP/WP Signal Junction Box, (including FLP/WP SS cable glands,

thimbles, ferrules, connectors etc. complete) and other installation material as

per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

13

Nos.

Supplying of perforated GI cable trays along with accessories (e.g coupler

plate , aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 2008 RMT

b) 100 mm 380 RMT

c) 150 mm 350 RMT

d) 200 mm 370 RMT

e) 300 mm 700 RMT

Fixing of perforated GI cable trays along with accessories (e.g coupler plate ,

aluminium saddles, screws, nuts, washers ) of following sizes:

a) 50 mm 2008 RMT

b) 100 mm 380 RMT

c) 150 mm 350 RMT

d) 200 mm 370 RMT

e) 300 mm 700 RMT

Supply & laying of Hume pipes (NP2) across Road crossing including road

cutting & remaking of WBM roads of following sizes ( if required as per site

condition)

a) 6 inch dia Hume pipe 40 RMT

b) 8 inch dia Hume pipe 50 RMT

c) 10 inch dia Hume pipe 60 RMT

23 Modification at MCC Panels including Supply of relays / contactors, PVC wires,

lugs, ferrules, erection hardware (as required) to provide potential free contacts

to be connected to the PLCs (Safety) for status (Motor Running / Trip) &

command (Start / Stop / ESD command) from PLCs.

Note : applicable for existing MCCs of TLF/ TWF/ TWD / FW Pumps (as

applicable)

12

Nos.

24 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends

Cable size - 1 pair x 1.5 mm2

4380

Meter

25 Laying of Signal Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 1Triad x 1.5 mm2

280

Meter

22

21

20

Page 13: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

26 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 12pair x 1.5 mm2

2037

Meter

27 Laying of Multicore Signal Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 8Triad x 1.5 mm2

100

Meter

28 Laying of Power Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 3C x 1.5 mm2

1763

Meter

29 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

630

Meter

30 Laying of Multicore Power Cables (Copper Conductor, FRLS PVC Armoured) in

under ground cable trenches or in above ground cable trays including Glanding

/ Termination / Loop checking at both ends

Cable Size - 36C x 1.5 mm2

50

Meter

31 Laying of Control Cables (Copper Conductor, FRLS PVC Armoured) in above

ground cable trays including Glanding / Termination / Loop checking at both

ends Laying / Glanding / Termination / Loop checking at both ends.

Cable Size - 2C x 1.5 mm2

8241

Meter

32 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 24C x 1.5 mm2

1904

Meter

33 Laying of Multicore Control Cables (Copper Conductor, FRLS PVC Armoured)

in under ground cable trenches or in above ground cable trays including

Glanding / Termination / Loop checking at both ends

Cable Size - 12C x 1.5 mm2

2003

Meter

34 Excavation & backfilling of cable trenches

Staking out, marking the outline for excavation, excavation in any type of soil,

PCC or hard rock for general site grading by machinery or manually up to 750

mm below and 400 mm width NGL for all depths as given below including

removal of stumps and roots to full extent removal of all vegetation including

bushes and grass, dewatering & leveling., dressing and backfilling after cable

is laid etc; complete as per specifications and instructions of Engineer In-

Charge (EIC).

Scope of work shall also include Supply/filling of sand & supply /placing of

Class B bricks in for excavated trenches subsequent to laying of cables.

1500 RMT

35 Erection, Testing & Commissioning of -Dual Redundant Safety Programmable

Logic Controller (SIL2 Certified) with Licensed Software (Engg./ Loader

software) including marshalling cabinet/s

[for ESD System] IO Count :: DI : 409, DO: 182,AI 2 WIRE TX : 65, AI 3

WIRE TX HART : 4, SERIAL RS 485 :4

1

Set

36 Erection, Testing & Commissioning of -Power Distribution cabinet for

distribution of 230 VAC Single Phase UPS/Non-UPS supply to equipments /

instruments in control Room & field.

1

Nos.

37 Erection, Testing & Commissioning of -Un-Interrupted Power Supply of

Parallel Redundant UPS System of a min 10KVA with 30 mins backup using Ni-

Cd batteries.

Note: Incase if actual calculated system load exceeds 10KVA then UPS rating

shall be 120% of the actual calculated load.

1

Nos.

38 Erection, Testing & Commissioning of -Engg cum Operator Station with 21"

LCD Monitor.

Operating System Windows 2008 Server

1

Nos.

39 Erection, Testing & Commissioning of -Workstation (OIC) with 21" LCD

Monitor.

Operating System Windows 7

2

Nos.

40 Erection, Testing & Commissioning of -Laser Jet Printer A4 size color 1 Nos.

41 Erection, Testing & Commissioning of - Networking Hardware comprising of :

Redundant Manageable Fast Ethernet Switches, including LAN Networking CAT

6 structured cables, associated hardware and cables (power / signal / control)

required for interpanel connectivity of centralised instrumentation.1

Lump Sum

42 Erection of -Open Table type console centers for mounting the servers /

workstations in control room (i.e. Engg. Cum Operator Station, Operator

Station)

1

Set

43 Erection of -System cabinets to house Ethernet Switch, Networking Hardware

as per tender specification.

TFMS System centralized hardware ( e.g CIUs , surge arrestors etc. ) to be

provided by BPCL shall also be housed in the System Cabinet.

1

Nos.

44 Installation Testing & Commissioning of -Explosion Proof / Weather proof ESD

Push Button Station15

Nos.

45 Installation Testing & Commissioning of -Flameproof / Weatherproof Hooter 2

Nos.

46 Installation Testing & Commissioning of -Weatherproof Hooter 2 Nos.

47 Installation Testing & Commissioning of -Level Switch SIL 2 Certified 9

Nos.

48 Installation Testing & Commissioning of FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 36C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

1

Nos.

49 Installation Testing & Commissioning of -FLP/WP Power Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 3C x 1.5 mm2

Note: These are copper cables.

4

Nos.

Page 14: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

50 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 12 Nos (side entry)

Cable Size for Power JB

- Multi Core : 24C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

14

Nos.

51 Installation Testing & Commissioning of -FLP/WP Control Junction Box

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (bottom entry)

- Branch Cables : 6 Nos (side entry)

Cable Size for Power JB

- Multi Core : 12C x 1.5 mm2

- Branch Cable : 2C x 1.5 mm2

Note: These are copper cables.

15

Nos.

52 Installation Testing & Commissioning of - FLP/WP Signal Junction Box-Triad,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi Core : 2 Nos (from bottom only)

- Branch Cables : 8 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 8 Triad x 1.5 mm2

- Branch Cable: 1 Triad x1.5 mm2

(for HC Detectors / Transmitters)

1

Nos.

53 Installation Testing & Commissioning of - FLP/WP Signal Junction Box,

(including FLP/WP SS cable glands, thimbles, ferrules, connectors etc.

complete) and other installation material as per tender specification.

No. of Cable Entries

- Multi core : 2 Nos (from bottom only)

- Branch Cables : 12 Nos (from sides)

Cable Size for Signal JB

- Multi Core : 12 P x 1.5 mm2

- Branch Cable: 1 P x1.5 mm2

Note: These are copper cables.

13

Nos.

54 Testing & Commissioning of MCC Panels (subsequent to modifications carried

out by vendor)1

Lump Sum

Powering ON and functional checking of following field instrumentation at

Safety PLC and Engg cum Operator Station as per Functional Design

Specification.

a) Hi-Hi Level Switch 9Nos

b) Level Tx. - Radar Type 9Nos

c) Level Tx. - Servo Type 9Nos

d) Electric Fail Safe ROSOV (Electric Actuator) 18Nos

e) DBB Valve (Electric Actuator) 9Nos

f) HC Detector - Point Type 1Nos

g) HC Detector - Open Path Type 2Nos

h) ESD Push Button Station 15Nos

i) FLP / WP Hooter 2Nos

j) WP Hooter 2Nos

k) Modified MCC Panel 12Nos

l) Existing MOVs (ESD Ports) 46Nos

m) Existing Batch Controller (ESD Ports) 20Nos

n) Existing Main Power Distribution system (Non-Critical Loads) ESD Port 9

Nos

o) Rim Seal Protection System (PLC)5

Nos

p) HVLR System (PLC)4

Nos

56 Development of software Drivers (Engg cum Operator Station Resident) to

serially interface follwoing field instrumentation / sub-systems with safety PLC.

1) HART Protocol based Field Instrumentation [eg. (Pr / Temp / Flow) Tx. /

Mass FLow Meters / Hydrocarbon Detectors

2) MODBUS RTU Protocol based PLCs pertaining to (a) Rim Seal Protection

system; (b) Fire Fighting Control system ; (c) Master control station of MOVs;

(d) Electric/ Pneumatic Fail safe Remote operated shut-off valves (e)

Communication Interface Unit of TFMS System (f) HVLR system (g) VFDs

3) TCP/IP Protocol between TAS and TFMS system and safety PLC system

NOTE :

(1) The scope of work under this item include Data base generation, Graphic

configuration, PLC loader software modification & any other requirement at

Engg / Operator Station.

(2) Development of software drivers for all the instruments / systems to be

supplied by vendor will not be considered under this item.;

(3) Vendors have to develop dynamic graphics of all the facilities at an

Installation.

1

Nos.

57 Supply, fabrication, welding, erection and painting of structural steel confirming

to IS 2062 latest edition, consisting of channels, beams, angles, flats, tubular

sections, etc; fabrication of steel structures, structural frame for Junction Boxes,

cable trays, field instruments [ under vendor' scope of supply & only HC

Detectors free issue item from BPCL). This includes supply of bolts, nuts

washers, shims, packs, putty, gas, welding electrodes, and all other

consumables as required, cleaning and surface preparation of all steel surfaces

with emry paper/wire brush, supply and application of 2 coats of red oxide zinc

phosphate primer of 30 to 35 microns dft each, supply and application of 2

coats of synthetic enamel paint of 30 to 35 microns dft of approved shade. Rate

to include excavating pit for grouting the member, grouting the structural steel

member in PCC M15, shuttering, ramming, finishing the same with cement

slurry etc; complete at all depths and as per approved drawing or instruction of

EIC. The height of frame shall be 1.3m from the FGL and 0.45m inside earth

for grouting purpose. The buried portion shall be coated with bitumen on all

sides before grouting the same in PCC. PCC shall be minimum 350mm x

350mm x 450mm for each leg of the frame / member.

The exposed portion of the PCC surface shall be whitewashed.

8000 Kilograms

58 Making of Electrical Earthing Pits - Complete electrical earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.

20

Nos.

55

Page 15: Rate AMOUNT - Bharat Petroleum · Cable Size for Power JB - Multi Core : 36C x 1.5 mm2 or 36C x 2.5 mm2 (as applicable) - Branch Cable : 3C x 1.5 mm2 Note: These are copper cables

Item No. Item Description Quantity Unit of

Measurement

(UOM)

Rate AMOUNT

SCHEDULE OF QUANTITIES/ RATES"; HALDIA COASTAL OIL INSTALLATION , PARADEEP INSTALLATION,

PATNA TOP & RAJBANDH TOP

59 Making of Instrument Earthing Pits -Complete instrument earthing for control

room equipments & field equipments. Designing, providing & constructing plate

electrode type earthing pits etc; as per tender specifications.20

Nos.

60 System Design & Engineering 1 Lump Sum

61 Factory Acceptance Test 1 Lump Sum

62 Training (at Factory) 1 Lump Sum

63 Training (at Site) 1 Lump Sum

64 Site Acceptance Test 1 Lump Sum

65 Documentations including as built drawings (6 Sets). 1 Lump Sum

66 CMC (Comprehensive Maintenance Charges) for 5 years (Post Warranty

Period)1

Lump Sum