rapid 600c continuous mixing plant user...

91
Issue 1.3 1 Rapid 600C Continuous Mixing Plant User Manual Pneutrol International Limited, 5 Caulside Drive, Antrim, Co. Antrim, N. Ireland. TEL: +44 (0) 28 9448 1800 FAX: +44 (0) 28 9448 1801 03/11/2015

Upload: ngonhi

Post on 04-May-2018

244 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 1

Rapid 600C Continuous Mixing Plant

User Manual

Pneutrol International Limited,

5 Caulside Drive,

Antrim, Co. Antrim, N. Ireland.

TEL: +44 (0) 28 9448 1800

FAX: +44 (0) 28 9448 1801

03/11/2015

Page 2: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 2

Contents

1: GENERAL INFORMATION .......................................................................................................... 4

1.1: System Hardware ...................................................................................................................... 4 1.2: System Software Standard Features.......................................................................................... 5

2: SYSTEM SET-UP ........................................................................................................................... 6 2.1: Standard Navigation bar: .......................................................................................................... 7

3: RUNNING INFORMATION: ......................................................................................................... 8 3.1 Running Screen – Manual Controls: ........................................................................................ 10

4: STATISTICS: ................................................................................................................................ 14

4.1: Production Summary: ............................................................................................................. 15 4.2: Stock: ...................................................................................................................................... 17 4.3: Trucks: .................................................................................................................................... 18 4.4: Drivers: ................................................................................................................................... 19 4.5: Delivery Supplier: ................................................................................................................... 20

5: RECIPE SCREEN: ........................................................................................................................ 21 5.1: View/Edit Recipes: ................................................................................................................. 22

5.1.1: Calibrate Recipes: ............................................................................................................ 23 5.2: Recipe Groups:........................................................................................................................ 28

6: CUSTOMERS: .............................................................................................................................. 29 7: SETUP: .......................................................................................................................................... 30

7.1: Plant Setup: ............................................................................................................................. 31 7.1.1: General Variables: ........................................................................................................... 32 7.1.2: Drives: .............................................................................................................................. 33

7.1.3: Times: .............................................................................................................................. 34 7.1.4: Drain Times: .................................................................................................................... 35

7.1.5: Alarm Times: ................................................................................................................... 36 7.1.6: Tolerances: ....................................................................................................................... 37 7.1.7: Rates:................................................................................................................................ 38

7.1.8: Drive Comms Control: ..................................................................................................... 39 7.1.9: Cement Calibration .......................................................................................................... 40

7.2: Material Setup: ........................................................................................................................ 44 7.3: Supplier Setup: ........................................................................................................................ 45

7.4: Moisture Setup: ....................................................................................................................... 46 7.5: Printer Setup: .......................................................................................................................... 48

7.6: IO Status: ................................................................................................................................ 50 7.7: Users: ...................................................................................................................................... 51

8: CHARTS: ....................................................................................................................................... 52

8.1: Historical Chart: ...................................................................................................................... 53 8.2: Real Time Flows Chart: .......................................................................................................... 55

9: MANUALS: ................................................................................................................................... 57 10: BACKUP DATABASE: .............................................................................................................. 58 11: REMOTE LAPTOP ..................................................................................................................... 59

11.1: Remote Viewing on Laptop: ................................................................................................. 60

11.2: Laptop Assuming Main Control of Plant: ............................................................................. 61 12: DIAGNOSTICS/ALARMS: ........................................................................................................ 64

12.1: Alarms Screen: ...................................................................................................................... 64

13: REMOTE ACCESS: .................................................................................................................... 65 13.1: Modifying Network Providers’ APN Settings: ..................................................................... 67

14: SHUTDOWN SYSTEM: ............................................................................................................. 69 15: USEFUL INFORMATION: ........................................................................................................ 69

15.1: Pausing The System: ............................................................................................................. 69 15.2: Emergency Stop: ................................................................................................................... 70 15.3: Safety Pull Switches ............................................................................................................. 71

Page 3: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 3

15.4: Mixer Castell Interlocking System ....................................................................................... 73

15.5: How To Reset VSD’s ............................................................................................................ 75 15.6: Compressor ........................................................................................................................... 76

15.7: Pneumatic Valve Box Lubricators/Air Pressure Setup ......................................................... 78 15.8: HMI ....................................................................................................................................... 79 15.9: How to Calibrate Moisture Probes ........................................................................................ 80 15.10: Admix Dispenser ................................................................................................................ 82 15.11: Hydraulic Controls .............................................................................................................. 83

15.12: What to Do If You Have a Problem? .................................................................................. 84 16: APPENDIX 1 – Best Practice/Regular Checks ........................................................................... 85 17: APPENDIX 2 – Full Alarm List .................................................................................................. 86 18: APPENDIX 3 – Troubleshooting Guide...................................................................................... 90

Page 4: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 4

1: GENERAL INFORMATION The Control System and Software have been designed and developed specifically for the control of

Concrete Batching Plants. The Hardware that is housed inside our Control Panel has been chosen

for its reliability in operation and for flexibility in different applications.

The software is 'Customised' for each plant and is therefore suitable for all types of plants and

plant layouts.

1.1: System Hardware

CONTROLLER: - ALLEN BRADLEY Micrologix Processor.

- Uses Industry Standard Ladder Logic Programs.

- CSA Certification to Class 1 Division 2.

- Battery-backed up memory for protection of program and data.

- Can be expanded to take in 256 additional discrete I/O - Built-in LCD with backlight allows you to view controller and I/O status

TERMINAL: - Exor eTOP 15” touch screen operator interface

- 16.2M colours, providing XGA 1024x768resolution display

- Energy efficient LED display - Displays all plant data.

- Displays plant operation on screen.

PRINTER: - Able Systems Ltd Ap1400V Thermal Panel Printer

- Robust design with added protection for harsh environments

- Mechanism life of 13 million print lines - Print speed of 80mm/sec

- Flexible connectivity

Dennis Bauer
Cross-Out
Dennis Bauer
Inserted Text
Mixing
Page 5: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 5

1.2: System Software Standard Features

1. STORAGE OF RECIPES: Each recipe will contain the details regarding a specific blend of

materials, which is the amount of each of the aggregates, cement, water and additives if required.

There is no limit to the number of recipes the system can store.

2. PASSWORD PROTECTION: Information in the memory of the computer can be protected by a

password code to prevent any unauthorised person deleting, changing or resetting stored data.

3. STOCK CONTROL: Materials in stock and material usage are stored in memory on the HMI.

These may be displayed as required to give daily or monthly totals for each material used in the

plant and stock levels remaining.

4. NO FEED: Should a bin be empty or material be bridged in the bin then an alarm message will

be given.

5. PRINTER: The system printer is used to print a ticket on demand or automatically given the parameters input for print detail.

6. PLANT ALARMS: An alarm message will be placed in an alarm log and displayed on the

monitor. A printout will be given of any/all alarm faults together with a date and time.

Alarm messages are given for specific faults e.g.

‘Mixer not running’

The operator may therefore rectify the problem quickly and so save on plant 'Down Time'.

An audible and/or visual alarm is also available where the operator may be a considerable

distance from the Control Panel.

Once the alarm has been initiated the operator may push the alarm accept button at the control

panel once to cancel the audible/visual alarm. He must then push the alarm accept button again

to continue batching once the fault has been rectified. Also the operator may rectify an alarm when in the alarm screen using option "F1: ACCEPT ALARMS".

7. MONITOR:

Displays Selection Menus. Displays recipes

Displays mix tolerances

Displays alarms

Displays plant Inputs and Outputs.

Displays running screen.

Displays a variety of stock and production reports Displays customer information

Page 6: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 6

2: SYSTEM SET-UP

When the generator is started, the UPS and HMI will automatically be turned on. During the course of normal use, if the HMI is not being used, it will automatically go into sleep mode. There

is a small LED in the top right hand side of the HMI which alerts the user to the following:

Red – Power is on, but the HMI is turned off

Amber – Power is on, but the HMI is in sleep mode

Green – Power is on and the HMI is on

When the HMI is powered on, the following Log On screen will appear:

Enter user name and password to log onto the system. This will launch the running screen of the

continuous mixing plant and highlight the following as sown below in the figure:

Conveyor status

Mixer status

Drive speed

Material loads across the system

Tons per hour target

Page 7: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 7

2.1: Standard Navigation bar:

The navigation bar (shown above) appears at the top of all screens in the system except for the reports screens.

View Alarms. In order to view alarms, hold down the ‘alt’ key and press 1.

View Running Screen. In order to view the running screen, hold down the ‘alt’ key and press 2.

View Silo Screen. In order to view the silo control, hold down the ‘alt’ key and press 3.

View Recipes. In order to view the recipes, hold down the ‘alt’ key and press 4.

View Plant Setup. In order to view system setup, hold down the ‘alt’ key and press 5.

You also can enter any of the navigation bars by just touching them on touch screen or by left clicking the mouse over them.

Page 8: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 8

3: RUNNING INFORMATION:

After the HMI is powered up, the running screen is the default, home screen, which allows the operator to oversee the entire continuous mixing process.

The Auto/Manual selector switch in the top right of the screen, lets the user know which control

mode the plant is currently in.

A graphical representation of the plant is shown in the running screen. The running screen has

weight indicator boxes around the weigh hoppers which show the actual weight in each hopper. The current live drive speeds are also shown.

In the top left hand corner of the running screen the following information is displayed:

Load Qty (Tns) – actual batched quantity versus the target Agg/Cem Qty Rate (Tns/Hour) – actual quantity rate in tons per hour versus the target rate

Target % - Percentage of each material being used in the current recipe. Calculated from the load

quantity and target tons per hour rate.

Actual % - Percentage of each material being used in the current recipe, calculated from the

amount of material leaving the hoppers and feeders (continuously updated.) Actual Kgs or Lbs/s – Displays the actual flow rate per second of each material

Batched (Tns) – Displays how many ton of material have been utilized

Water Adjust % – this allows the user to change the water target percentage in real time.

To the bottom left of the Running Screen the Start, Abort, Hold and Shutdown buttons are

displayed.

When the Start button is pressed, a dialogue box as shown below pops up on screen:

Page 9: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 9

A close up of this dialogue box is shown below:

The user can select the recipe, customer, site and truck using the drop down menus. After selecting these 4 options the user enters the quantity to be batched and the batching rate (in tons

per hour). We will look at how recipes, customer information, site details and truck information

are entered later in this manual. After a load has been completed, the same details will

automatically appear in the start dialogue box. Al the user will need to do is press “Start”.

Page 10: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 10

The second button along the bottom of the screen is the Abort button. When this button is pressed, the system immediately stops what it is doing and resets its automatic program – any

material already weighed up will have to be discharged from the system manually by the operator.

This buttons function is primarily used to reset the program, but in case of emergency if the

wrong mix has been setup or started, this button can be used to minimise the amount of material

produced in error.

Beside Abort is the Hold button, this button does exactly what it says, when this button is pressed the entire plant will pause what it is doing and wait until its pressed again to taken off

hold. The mixer and outloading conveyor will continue to run, but the aggregate belts feeding the

mixer and also the cement filling/emptying process will pause. A large, red ‘HOLD’ warning

appears below auto/manual toggle switch on the running screen.

The last button in this row is the Shutdown button, this button is used to shutdown the plant when in the middle of a production run. For example, if the user has started the plant off making

25 tons of material, the shutdown button can be pressed at anytime, this will ensure the plant

stops producing any further material and shuts the system down in an orderly fashion as it would

do if it had reached its 25 ton target, ensuring the outfeed belt and mixer are totally drained out

and empty of material.

3.1 Running Screen – Manual Controls: At any point the user can chose to turn the plant into manual control as shown below by selecting

the auto/manual switch in the top right corner:

Page 11: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 11

When in manual mode, as you can see from the screenshot above, manual control buttons appear beside every device that can be controlled. These manual controls are very user friendly and very

intuitive. Each belt can be started and stopped using the green pushbuttons, there are

pushbuttons to fill and run the cement weigh hoppers and to open and close doors. The second

type fo buttons used are 2 position selector switches – these can be toggled from left to right and

are generally used for switching processes on and off. As the screenshot above demonstrates - additives, water, cement, aggregates and the gob hopper control can be turned off and on.

The Gob Hopper has its own unique auto/manual control sequence. In the bottom left of the

mimic screen, there is a Gob Hopper Auto On. When this button is turned onto the ‘On’ position,

the gob hopper door will operate as per the times configued in the plant setup (where there are

gob hopper open and gob hopper closed times). At the end of an automatic batch, the gob hopper doors will always remain open. When the Gob Hopper auto/manual selector switch is turned to

manual, 2 new push buttons will appear, one for open gob hopper, one for close gob hopper –

these buttons allow the operator to control the gob hopper door completely manually.

There is also the ability to adjust the speed in Hertz of the water VSD from the manual control screen. The yellow box can be clicked on and the desired new sped in Hertz can be typed in.

There is an additional button at the top called Silo Screen, pressing this button reveals the screen

shown below:

The silo controls screen provides the user with buttons to control silo filling operations. Indicators and input buttons are provided to test the silo controls and to start the silo filter as

shown above. There are various indicator boxes around the silo which can give the user its

status, such as fill pipe valve closed or fill pipe valve open, silo low level, silo pressure switch

fault, silo PRV fault, silo filter islolator on and silo high level and tacho feedback (if applicable). If

any component is green, it indicates that item is healthy, however, if something is red, it

highlights there is a fault with this piece of equipment.

Page 12: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 12

Silo Operating Procedure

1) To activate the system, the operator must press the lamp test button, which will activate

the system fault neon’s and the beacon / klaxon. When the operator has checked the fault

lights and beacon / klaxon are operating correctly he/she can press the filter start button.

If the filter start button is not pressed within 15 minutes of the lamp test button being

pressed the system will reset and the lamp test will have to be pressed before the filter can be started.

2) When the filter start button is pressed the Safe-silo system checks all of the safety sensor

inputs to ensure everything is healthy before opening the fill pipe valve and starting the

silo filter. When the system is operating, the filter start pushbutton will be change to ‘Filter Stop’

3) If a high level is reached, the warning beacon / klaxon will energise to alert the truck

driver to stop filling, the indicator neon on the mimic will illuminate red and the fill pipe

valve will close after 45 seconds. When the fill pipe closes after a high level it will not open

again until the high level signal has been removed. The red neon will remain illuminated until the high level signal has been removed. The alarm beacon / klaxon can be cancelled

at any time by pressing the alarm cancel button.

If any of the following faults occur the fill pipe valve will close immediately and the alarm

beacon / klaxon will energise:

If the High Level fail safe signal is lost (also known as the Tacho signal)

If the Pressure Switch sensor activates

If any faults occur the status neon will illuminate red and remain energised until the

alarm cancel button is pressed.

If a high level fail safe fault has been installed and a fault occurs, the tacho neon will flash

red for 45 seconds unless the alarm cancel is pressed. Then once the lamp test button is pressed the alarm light will re-energize.

4) When the truck driver has finished discharging into the silo he should press the ‘Filter

Stop’ button which will close the silo fill pipe valve and allow the filter to remain cleaning

for 10 minutes. If the stop button is not pressed the system will automatically shut down

after 45 minutes.

Page 13: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 13

Immediate System Shutdown

The rotating paddle high level probes have a motor driven paddle extended into the silo. The

paddle shaft is fitted with a motion detector.

When the paddle comes into contact with the cement and stops turning, the motor tries to turn

against the paddle, activating a clutch fitted with monitoring switches to give a high level alarm

signal.

If the rotating paddle high level has a fail safe indicator fitted, when the coupling from the motor

to the paddle shaft becomes disengaged the motion detector will indicate that the motor is turning and the paddle is not. The high level fail safe alarm will come on immediately and the system will

shut down.

If the filter is blocked, the silo will over pressurize and the pressure switch will activate causing

the system to immediately shut down.

Page 14: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 14

4: STATISTICS:

From the main menu, move the mouse over ‘Statistics’ to see the plant statistics menu. The system has reporting mechanisms for information relevant to the plant, such as the daily

production screen, a full stock inventory, a record of stock accuracy and docket printing. The

operator can choose what data is required to be reported.

From here, we are given options to view the following plant statistics:

Production Summary

Stock

Trucks

Drivers

Delivery Suppliers

Page 15: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 15

4.1: Production Summary:

From the statistics menu, select ‘Production Summary’ to view the batching history. From here

the operator can view all load details between the dates selected at the top of the screen. Press the

‘tab’ key to highlight the start date. Then use the up, down, left and right arrow keys to change

the date. Press the tab key again to move to the end date and repeat the process. Pressing the ‘tab’ key again will highlight the production list. Then Use the up and down arrows to select the

different drops within the list.

The operator can then view information about each load by selecting it in the list. He/she will

have the option of Viewing a summary of that load (F1), or viewing a drop report for that load (F2). Pressing ‘F3’ automatically sets the dates to show only today’s production. Pressing ‘F4’ sets the

dates to show production since the beginning of the week (Sunday). Pressing ‘F5’ sets the dates to

show production since the beginning of the month. The operator can also print a docket for that

load if necessary (F6). A production report can be printed by pressing ‘F7’. Pressing ‘F8’ will show

a bar graph for the production. Pressing ‘F9’ will prompt you to select the dates which you want to view any manual batches recorded. The operator also has an (F12) option which allows the user

to look back at historical charts and trending for loads previously completed. When this button is

selected, the following dialogue box appears:

Page 16: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 16

The user is provided with the option to select the particular weighers or flow rates they require to

view on the chart. For more information on charts, please see section 8.

The operator can view all the loads completed for a certain customer or truck by pressing the tab

button to highlight the ‘Customer’ or ‘Truck’ and pressing the up and down arrow to select the

customer or truck number.

When options (F1) or (F2) are selected, the user will be asked whether or not they want to view

any events, drops or manual controls that occurred during that load in the report. This is selected

by default. The appropriate report will then be shown, along with the standard report options.

The appropriate production report will then be shown, along with the standard report options as shown below:

Page 17: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 17

4.2: Stock:

From the statistics menu, select ‘Stock Screen’ to view the stock screen. The stock screen allows

the operator to keep track of stock levels within the plant and modify if necessary. Use the arrow

keys to select the date for which you want to view stock. This will automatically open today’s date

by default.

For any given day, selected at the top of the screen, the operator can view the amount of each

material present in stock at the start of the day (‘Open’), any deliveries for that day (‘Delivered’),

stock usage for that day (‘Usage’), any stock adjustments made (‘Adjusted’) and the actual current stock quantity (‘Quantity’).

This screen gives the operator the options to:

Make a new delivery (F1)

Make a stock adjustment (F2)

Set low levels for each Bin [F3] – option at top of screen to set alarm when stock low levels reached.

View a report on the history of deliveries(F4)

View a report on the history of adjustments (F5)

View the stock report (F6)

View the material usage (F7)

Toggle Admixture Units between KG’s/Ltrs (F11)

By pressing ‘F1’ to make a new delivery, the ‘Delivery Details’ column will appear on the right

hand side of the screen. Use the up/down arrow keys to select a supplier, or just type in the name of a new supplier. Use the ‘tab’ key to move onto the delivery date and change if necessary (Using

arrow keys). Again use the ‘tab’ key to move onto the docket number field and type in a docket

number for the delivery. Then enter any notes deemed appropriate. Then use the ‘tab’ key to move

down through the material delivery units and adjust as appropriate. Press ‘F1’ to confirm the

delivery, or ‘F2’ to cancel and undo any changes.

Pressing ‘F2’ to adjust stock levels works similarly. Use the ‘tab’ key to move down through the

quantity units for each material and adjust as appropriate. Press ‘F1’ to confirm the adjustment,

or ‘F2’ to cancel and undo any changes.

Page 18: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 18

4.3: Trucks:

From the statistics menu, press ‘F5’ to view truck statistics. This screen allows the operator to set

up the plants fleet.

Use the up/down arrow keys to move through the list of existing trucks. Use the ‘tab’ key to move

through the truck details for any particular truck. Any changes which are made, pressing ‘F1’ will

save these changes. ‘F2’ will undo the changes.

The operator can add a new truck by pressing the ‘F1’ key. If this is selected, use the tab key to

move to each of the ‘Code’, ‘Registration’ ,‘Truck Capacity’ and ‘Drivers’ fields and enter

appropriate details. The changes can then be saved (F1) or undo (F2).

To delete a truck, select one in the list and press ‘F2’.

Press ‘F9’ to view any changes made to the truck details between the two selected dates. Any

changes which have been made can be Printed (F1) or Saved to a file.

Page 19: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 19

4.4: Drivers: From the statistics menu, select ‘Drivers’ to view details of all drivers.

The operator can add a new truck by pressing the ‘F1’ key. If this is selected, use the tab key to

move the ‘Driver Code’ and ‘Name’ fields and enter appropriate details. The changes can then be saved (F1) or undo (F2).

To delete a driver, select one in the list and press ‘F2’.

Again by pressing ‘F9’ to view any changes made to the driver details between the two selected

dates. Any changes which have been made can be Printed (F1) or Saved to a file.

Page 20: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 20

4.5: Delivery Supplier:

From the statistics menu, select ‘Delivery Supplier’ to view details of all suppliers.

The operator can add a new supplier by pressing the ‘F1’ key. If this is selected, use the tab key to

move to the ‘Name’ or ‘Short Name’ fields and enter appropriate details. The changes can then be

saved (F1) or discarded (F2).

To delete a supplier, select one in the list and press ‘F2’.

Again by pressing ‘F9’ to view any changes made to the Delivery Supplier details between the two

selected dates. Any changes which have been made can be Printed (F1) or Saved to a file.

Page 21: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 21

5: RECIPE SCREEN:

From the main menu, select Mix Design to view the recipe menu screen.

This gives us the following options:

View/Edit Recipes

Recipe Groups

Page 22: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 22

5.1: View/Edit Recipes:

From the recipes menu, select ‘View/Edit Recipes’. This screen allows the operator to configure

all recipes for the plant. Features include:

Virtually unlimited recipes.

Recipe configurable aggregate bin hole settings.

Recipe configurable cleanout belt setting. (when ticked this will run cleanout belt during

production)

Recipe usage report

Material usage report by recipe or selection of recipes

Ability to view change history

Down the left of the screen, there is a list of all existing recipes. These can be easily edited by selecting one using the up/down arrows as normal, then using the tab key to move through all

the properties which make up the recipe. Each can be edited, and if any changes are made, the

user will be presented with the options of saving (F1) or undoing the changes (F2).

If a new recipe is required, enter the screen and press ‘F1’ to Add New. Select the recipe section which the new recipe is to be created under and press ‘F1’. The ‘Name’ field will be highlighted.

Enter a name and use the ‘tab’ key to move on to the next field. Once all values have been

entered, press ‘F1’ to save, or ‘F2’ to undo the changes. Recipes can also be deleted, by selecting a

recipe from the existing list on the left of the screen and pressing ‘F2’.

Some recipe statistics are also available, such as a record of all changes made to a recipe (F9), a summary of recipe usage (F6) and a material usage report (F7), configurable by selecting one or

any number of recipes to be reported on. These reports will appear in the usual format.

Note: If these buttons are grayed out, the current user may not have the rights to access these

features.

Page 23: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 23

In addition, there are also built in checks to ensure mistakes are not made, for example, when entering in a recipe, the total aggregate and cement percentages must add up to 100%, otherwise

an error message will be displayed when the user has tried to save the recipe:

5.1.1: Calibrate Recipes: At the bottom of each recipe there is a calibration button, this allows the user to enter a new

calibration for the aggregate of that recipe. Before any new calibration is considered, the user

must physically check around any weight scales or belts. They must also be sure to charge the

mixer with an appropriate amount of material so that calibration material isn’t filling the mixer and throwing off calibration numbers! For more info see Appendix 3. When the calibration

button is selected, the following screen appears:

The user is asked to specify the aggregate low running speed. Normally this is set to 10 Hertz,

when ‘Next’ is clicked on, a dialogue box appears for setting the Low calibration time:

Page 24: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 24

The user is asked to specify the aggregate low calibration time. Normally this is set to 120

seconds, when ‘Next’ is clicked on, the mixer and belts will start, allowing the system to run

aggregate through the system on the appropriate gate setting for this period of time - it is important the user has a truck below the end of the belt, as the amount of material run through

the plant must be weighed after the low calibration has finished. As the low calibration time is

running, you will see the following dialogue box:

The countdown timer allows the user to clearly see how long is left to run on the low calibration time. After the low calibration time has completed, the following dialogue box will appear:

The system displays confirmation that the low aggregate calibration has been completed. After

the “Next” button is selected, the finish low calibration screen appears as below:

Page 25: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 25

The user must now enter the actual weight of material run through the plant during the low

calibration time. On this dialogue box you will notice the average weigh value appears – this is to

allow the user to compare the most recent low calibration with other calibrations – this is a quick

way to flag up a problem with the calibration just performed – if the reading was significantly

different to similar low calibrations, this would point to a blockage or other mechanical problem.

The user also has the ability to ‘Repeat LOW Calibration’ if required.

Next the user must specify the high aggregate calibration speed:

Usually this would be set for the maximum speed of the belt – in most cases this will be 60 Hertz.

The user must now click on the ‘Next’ button to set the duration for the high calibration as shown

below:

Page 26: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 26

Above, the user must set how long the full calibration is to run for. Normally this would be set for 120s. The plant will start-up and run for the pre-set time using the belt drive speeds set

previously. It is important the user has a truck below the end of the belt once again, as the

amount of material ran through the plant must be weighed after the full calibration time has

finished. Once again, the user will be able to view the full calibration countdown timer as shown

below:

After the full calibration timer has finished, the following dialogue box will appear:

The above dialogue box confirms the calibration has completed successfully. The user must now

click ‘Next’ again to be taken to the finish calibration dialogue box:

Page 27: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 27

The user must now enter the weight of material ran through the plant during the 60s high speed calibration time (after it has been weighed) into the first text box. Again the average weigh value

appears – this is to allow the user to compare the most recent high calibration with other

calibrations – as before this is a quick way to flag up a problem with the calibration just

performed – if the reading was significantly different to similar high calibrations, this would point

to a blockage or other mechanical problem. Again there is an option to ‘Repeat HIGH Calibration’ if required.

The recipe screen is now updated displaying the new results and time/date stamp as shown

below:

It is imperative the user clicks ‘Save’ in the bottom left hand side of the recipe screen to complete

final confirmation of calibration and save the new recipe details and calibration details.

Immediately after calibration the user must now run a given amount of the newly calibrated recipe (normally 10Tons) through the plant and weigh it to confirm accuracy of calibration.

Page 28: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 28

5.2: Recipe Groups: From the recipes menu, select ‘Recipe Groups’ to view. This feature allows the ability to add

different material sections to display in the recipes for editing.

A new recipe group section can be added by pressing the ‘tab’ key to highlight it and press the

‘spacebar’ key to select it and it will be added on the right. Press the ‘tab’ key to move over to the

right and select the different material sections to be shown on the recipe. Press ‘F1’ to save the

changes. The screen is typically only used by PIL or other authorised personnel.

Page 29: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 29

6: CUSTOMERS:

From the main menu, select ‘customers’ to view and edit the customers’ details.

If a new customer is required, enter the customer setup screen and press ‘F1’ to Add New. Enter a

customer’s name and use the ‘tab’ key to move on to the next field. Once all fields have been

entered, press ‘F1’ to save, or ‘F2’ to undo the changes. Customers can also be deleted, by

selecting a customer from the existing list on the left of the screen and pressing ‘F2’.

Each customer can have several sites which can be added by pressing ‘F5’ and entering in the details to the fields and pressing ‘F1’ to save. A site can be removed from a customer by selecting

the site and pressing ‘F6’ to delete.

Each customer can have certain recipes assigned to them therefore when adding a load for that

customer the recipes are narrowed down to only a few to choose from. It can be narrowed down

further by assigning certain recipes to customer’s sites. To assign a recipe to a customer, select the customer and press ‘F7’. All the recipes appear. Press

the ‘tab’ key to highlight the first recipe and use the up and down arrows move through them.

Press the ‘spacebar’ to select the recipe to be assigned to the customer. When the appropriate

recipes are selected press ‘F1’ to move back to the customer’s screen and press ‘F1’ again to save

changes or ‘F2’ to undo. To assign a recipe to a customer’s site, select the customer’s site and press ‘F8’. Follow the same process to assigning a recipe to a customer.

All changes made to customers are recorded and these reports will appear in the usual format by

pressing ‘F9’.

Page 30: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 30

7: SETUP:

From the main menu, select ‘Plant Configuration’ to view the configuration menu screen.

This gives us the following options:

Plant Setup

Materials

Supplier Setup

Moisture Setup

Printer Setup

IO Status

Users

Page 31: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 31

7.1: Plant Setup:

From the ‘Plant Configurations’ menu, select ‘Plant Setup’ to view the plant setup screen. This

screen allows the operator to accurately control how the plant runs, and in particular, the times

taken for various processes which occur during a load.

When the screen appears, there will be a list of categories down the left side of the screen. Select

the appropriate category using the up/down arrow keys. The categories available are:

General Variables

Drives

Times

Drain Times

Alarm Times

Tolerances

Rates

Drive Comms Control

Moving up and down through the list will display a number of properties for each category. Use

the ‘tab’ key to highlight the property/variable to be changed or select the desired box with the

touchscreen. Make the change. In the case of a checkbox, use the space bar to activate/deactivate it. In the case of a numeric value, use the arrow keys to alter it. Once satisfied, press ‘F1’ to save

any changes, or ‘F2’ to undo any changes made.

The options at the bottom of the screen allow the settings to be Refreshed (F3), or a report of any

changes to be viewed (F9). Choosing ‘Refresh’ updates the current on-screen values.

Page 32: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 32

7.1.1: General Variables:

Selecting ‘General Variables’ allows miscellaneous settings for the plant to be edited.

General variables include the following:

Belt Scale Pulser – when ticked, the system will ignore the belt scale signal

Kgs or Lbs / Pulse – Defines how many Kgs or Lbs is used for each pulse of the aggregate belt scale.

G or Oz / Pulse – Defines how many Grams or Oz is used for each pulse of the various pulsers – admix 1, admix 2 and water pulser

Density – This is used to set the density of the admix material being used.

Next Docket Number – this is used to set the next docket number the plant will batch. This will be printed on the ticket and stored with the load in the production screen.

Record Interval (Tns) – this defines how frequently the aggregate moisture will be recorded both in the events log (shown below) and also in the load report (which can be

accessed from the production screen)

Page 33: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 33

7.1.2: Drives: Selecting ‘Drives’ allows the manual drive speeds to be edited.

The following settings can be edited:

Manual Speed – This allows the user to set what speed they would like each drive to run at when using the plant in manual mode.

On/Off Speed – This allows the user to set the speed of water pump 1 at which water pump 2 will turn on and off.

Page 34: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 34

7.1.3: Times: Selecting ‘Times’ allows timing variables for the plant to be edited.

The following settings can be edited:

Aeration – this defines the length of time the cement silo aeration comes on for when weighing into the cement weigh hoppers in manual.

Gob Door Open/Close – these times defines how long the gob opens and closes for when running the plant in auto mode.

UPS shutdown delay - after power has been lost to the UPS, it will automatically shut down after 5 minutes. The UPS Shutdown Delay here defines how long the HMI will stay

on after genset power has been lost to the UPS.

Page 35: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 35

7.1.4: Drain Times: Selecting ‘Drain Times’ allows drain times and discharge delay times for the plant to be edited.

The following settings can be edited:

Drain Time – Drain time defines the time the system should take the plant to discharge its contents after reaching the empty signal.

Discharge Delay – Discharge delay defines the time delay (in secs) the system is to wait after receiving the discharge signal, before discharging a particular bin or weigh hopper

into the mixer. The discharge delay is also used as a run on time for each item after

discharging has finished.

Page 36: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 36

7.1.5: Alarm Times: Selecting ‘Alarm Times’ allows alarm time settings for the plant to be edited. When an error is

detected in the plant, alarm times are the amount of time the system will allow the plant to rectify

the error before raising the alarm. If, after this time the error still exists, the alarm will be raised.

Here follows definitions of the most common alarm times:

Run/Stop – This defines the amount of time before the system alarms once the mixer/belts have failed to either start or stop when requested.

Flow/No Flow – This defines the amount of time before the system alarms after a flow or no flow fault condition has occurred.

Low Flow – This defines the amount of time before the system alarms after a low flow fault has occurred.

Page 37: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 37

7.1.6: Tolerances: Selecting ‘Tolerances’ allows the flow percentage tolerances to be set.

Tolerances are used to define how accurate the system weighments must be. They apply to each

material being weighed or measured in the plant. The main tolerance is:

Flow (%) – each materials flow percentage can be set and if the actual flow rises above or falls below this percentage from its target, the system will alarm to notify the user.

Flow (Tns/Hour) – The target tns/hour flow rate not being reached. This tolerance is for alarm only

Low Flow (Tns/Hour) – The actual tns/hour goes below this tolerance. Sytem will alarm and holds the batch so operator can check out why flow not being reached.

NOTE: The plant will attempt to stay within the tolerance limits set at all times regardless.

Page 38: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 38

7.1.7: Rates: Selecting ‘Rates’ allows the maximum Kgs or Lbs/sec for the plant to be edited.

The following variables can be edited:

Kg or Lb/sec (Max Hz) – This allows the user the enter the maximum flow of each material per second when weighing at maximum speed. The aggregate and additive both

have a maximum speed of 60 Hz, the cement has a maximum speed of 100 Hz.

Litres or Gals/sec (Max Hz) – This allows the user to enter the maximum flow of the water pulser per second when weighing at maximum speed. The water has a maximum

speed of 60 Hz.

Page 39: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 39

7.1.8: Drive Comms Control: Selecting Drive Comms Control allows the user to configure variable speed drive settings:

We have provided a check box to provide a simple method for the user to disable any of the

Variable Speed Drives (VSD’s) installed in the plant. To remove a VSD from operation, simply

untick the checkbox beside the relevant drive you wish to disable.

Page 40: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 40

7.1.9: Cement Calibration

Along the bottom of all the plant setup screens you will find there are two options: F5 Cement 1 Calibration and F6 Cement 2 Calibration. This provides the user with a means to calibrate the

cement flow (note cement 1 is the silo incorporated onto the chassis of the machine). Before

beginning the calibration, it is important there is a calibration tray put in place to capture all

cement dispensed through the Rotoloc feeder during the calibration. To start calibration press

one of the two buttons along the bottom, the following dialogue box will appear:

The user is asked to specify the cement low running speed. Normally this is set to 20 Hertz, when

‘Next’ is clicked on, a dialogue box appears for setting the Low calibration time:

The user is asked to specify the cement low calibration time. Normally this is set to 30 seconds,

when ‘Next’ is clicked on, the cement rotary valve will start up, allowing the system to run cement

through the system for this period of time - it is important the user captures all cement discharge

from the silo, as the amount of material ran through the plant must be weighed after the low

calibration has finished. As the low calibration time is running, you will see the following dialogue box:

Page 41: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 41

The remaining time countdown timer allows the user to clearly see how long is left to run on the

low calibration time. After the low calibration time has completed, the following dialogue box will

appear:

The system displays confirmation that the low cement calibration has been completed. After Next

is selected, the finish low calibration screen appears as below:

The user must now enter the actual weight of cement run through the rotary feeder during the

low calibration time. On this dialogue box you will notice the average weigh value appears – this is to allow the user to compare the most recent low calibration with other calibrations – this is a

quick way to flag a problem with the calibration just performed – if the reading was significantly

different to similar low calibrations, this would point to a blockage or other mechanical problem.

The user also has the ability to ‘Repeat LOW Calibration’ if required.

Page 42: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 42

Next the user must specify the high cement calibration speed:

Usually this would be set for the maximum speed of the screws – in most cases this will be 60

Hertz. The user must now click on the ‘Next’ button to set the duration for the high calibration as shown below:

Above, the user must set how long the high calibration is to run for. Normally this would be set

for 60s. The plant will start-up and run for the pre-set time using the drive speeds set previously.

It is important the user captures all cement discharge from the silo once again, as the amount of

cement ran through the plant must be weighed after the full calibration time has finished. Once again, the user will be able to view the high calibration countdown timer as shown below:

Page 43: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 43

After the full calibration timer has finished, the following dialogue box will appear:

The above dialogue box confirms the calibration has completed successfully. The user must now

click ‘Next’ again to be taken to the finish calibration dialogue box:

The user must now enter the weight of cement ran through the plant during the 60s high calibration time after it has been weighed into the first text box. Again the average weigh value

appears – this is to allow the user to compare the most recent high calibration with other

calibrations – as before this is a quick way to flag up a problem with the calibration just

performed – if the reading was significantly different to similar high calibrations, this would point

to a blockage or other mechanical problem. Again the user also has the ability to ‘Repeat HIGH Calibration’ if required.

Finally you will be asked to confirm you are happy for the calibration details to be saved.

Page 44: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 44

7.2: Material Setup:

From the setup menu, select ‘Materials’ to view the material setup screen. From this screen, the

operator can configure materials used within the plant – aggregates, cements, admixture and

water.

Simply arrow up and down through the material types on the left of the screen to display all

materials defined under that category. Press ‘tab’ to highlight the list of defined materials. Use the

up/down arrows to select a particular material. Pressing ‘tab again allows the different material properties to be altered, such as ‘Name’, ‘Short Name’, ‘Weigh Units’, ‘Delivery Units’ and ‘Density’.

A new material can be added to the list by pressing ‘F1’. A name and short name should be

entered for the new material. If the material is an admixture, the other properties should also be

given values. Press ‘F1’ to save or ‘F2’ to undo the changes. Highlighting any material using ‘tab’

and arrow keys and pressing ‘F2’ can delete a material. The user will be asked for confirmation before the deletion takes place.

All changes made to Materials are recorded and these reports will appear in the usual format by

pressing ‘F9’.

Page 45: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 45

7.3: Supplier Setup:

From the setup menu, select ‘Supplier Setup’ to view the bin setup screen. From this screen, the

operator can assign a material to a bin for – aggregates, cements, admixture and water.

The course materials used within a 600C plant are aggregate and cement. It also has at least 1

admix flow meter and a water flow meter. A list of the materials and flow meters will be visible on

the left hand side of the screen. Use the arrow keys to select the material group to be configured. Then press ‘tab’ to highlight the large central area to set the material used. Use the up/down

arrows to select the material for that bin you wish to change. Press the ‘Tab’ key to move to the

next field. The ‘Enabled?’ check box indicates if the bin is available to use.

When all required changes are made, press ‘F1’ to save or ‘F2’ to undo the changes.

All changes made to Materials are recorded and these reports will appear in the usual format by

pressing ‘F9’ and may be printed.

Page 46: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 46

7.4: Moisture Setup:

From the plant configurations menu, select ‘Moisture Setup’ to access the moisture screen. This

screen allows the engineer to configure how aggregate moisture readings are taken.

To change the values in the text boxes use the 'tab' key to high-light the value to be changed. Type

in the new value and press enter. On leaving the screen you will be asked to confirm your changes

if you have made any. If the value is a check-box use the space bar to check/uncheck it.

Descriptions: Channel - changing probe channels should only be done by the commissioning engineer or under

supervision of the engineer. It allows you to select the bins which have the moisture probes

installed. Auto On - this allows you to select either automatic or manual moisture. You can only set auto

moisture on a particular bin if a probe channel has been assigned to that bin. Minimum - (auto minimum value) sets the lower moisture limits which the computer will adopt if

the probe reads below this value, i.e., probe failure. This will only affect the auto moisture

reading. Maximum - (auto maximum value) sets the highest moisture limits which the computer will adopt

if the probe reads above this value, i.e., probe failure. SSD – This is a Saturated-surface-dry (SSD) value which a moisture probe can not read as it is

absorbed within the particles of the material. This value will be subtracted from the moisture value being produced by the moisture probe. Manual - (manual moisture value) enables you to change the manual moisture figures.

Page 47: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 47

Calibrate:

The ‘Calibrate’ tab beside each moisture value allows the calibration values for the moisture probe

to be altered. If you click on ‘Calibrate’ a new window will appear.

At the top of the screen there is a ‘Current Raw Value’ which the system is receiving from the

probe. Below the ‘Current Raw Value’ are the calibration points. Up to 12 different calibration

points can be entered to make the calibration more accurate. Only the calibration points which have the check box beside it enabled will be used. When more than two calibration points are

entered and enabled press ‘F2’ to view the line of the graph. When more than two points are being

used the best line of fit will be used. Press ‘F1’ when you are happy with the calibration values or

‘ESC’ to cancel and return to the moisture setup screen. The calibration values will only take

affect once ‘F1’ is pressed to save the changes.

NOTE: For more information on how to calibrate the moisture probes, please see section 15.9.

Page 48: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 48

7.5: Printer Setup:

From the setup menu, select ‘Printer Setup’ to access the printer settings screen. This screen

allows the operator to choose which printers to use for batch printing and report printing. It also

allows the operator to choose what details to print and what to ignore.

Again these details should only be altered or adjusted under the instruction.

Page 49: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 49

The paper this printer uses is 36mm diameter thermal paper (approximately 13m long). The

paper should be installed as the picture below demonstrates with the paper unrolling from the

bottom side of the printer. If in any doubt there are additional installation graphics inside the actual printer itself when the print lid has been lifted.

Page 50: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 50

7.6: IO Status:

From the setup menu, select ‘I/O Status’ to view the I/O list. This screen is used to show the

plant inputs and outputs which the controller uses to run the plant. Below is a picture of the

Micrologix SLC used in the Rapidmix C600 machines, I have labelled the items of interest:

The I/O Screen is shown in the graphic below:

The I/O screen and the information displayed is useful for plant engineers should a fault arise.

Active inputs and outputs are highlighted green. Each input/output displays the name complete

and wire number, so fault finding can be conducted easily.

Main SLC Inputs Slot 1 (Inputs) Slot 2 (Output) Slot 3 (Analogs)

SLC Display

Screen

Main SLC Outputs Slot 4 (Inputs)

SLC Display

Screen

Page 51: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 51

7.7: Users:

From the setup menu, select ‘Users’ to view and edit users on the system.

Only authorised users are allowed to access the system. Once logged on, different areas of the

system support different levels of security access.

Password protection for different areas of the system.

3 different levels of security – full/modify/read only.

Only users with an authorised user name and password can log on to the system.

To add a new user press ‘F1’. Enter in a user name and password for the new user to log on with.

Tick the ‘Enabled’ check box to activate the new user. Set the user control as either ‘Admin’,

‘Mangers’, ‘Batchers’, ‘Guests’, or ‘None’. Each user has different default rights. These rights can

also be modified by selecting each check box for different areas.

Then, press ‘F1’ to save or ‘F2’ to undo your changes.

Page 52: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 52

8: CHARTS: From the main menu, select ‘Charts’ to view the setup menu screen.

This gives us the following options:

Historical

Real-Time

Page 53: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 53

8.1: Historical Chart: From the main menu, select ‘Historical Chart’ to access the first charting screen. This screen

allows the operator to view historical data of loads previously completed.

The historical chart displays a chart showing x and y axis and a smooth line showing various pieces of information which can be selected by the user.

By pressing F1, the user can choose to show any number of items (up to a maximum of 6) on the

graph as shown below:

Page 54: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 54

As shown on the pop up above, the user can select the start and end times of the graph and also

some additional axis options. Finally the graph can be exported into csv file format by clicking

Export (F2).

Page 55: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 55

8.2: Real Time Flows Chart:

From the main menu, select ‘Real Time’ to access live charting of the current plant flows.

When the plant is running in automatic or manual, the user can look at this screen to view the actual live real time trending of the various materials. This screen is helpful when setting up the

machine and also for checking the blend is within required parameters.

By pressing F1, the user can choose to show any number of items (up to a maximum of 6) on the

graph as shown below:

Page 56: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 56

As shown on the pop up above, the user can select the start and end times of the graph and also

some additional axis options. Finally the graph can be exported into csv file format by clicking

Export (F2) as before.

Page 57: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 57

9: MANUALS:

From the main menu, select ‘Manuals’ to view all plant manuals.

After selecting the Manuals button, Windows Explorer will launch a new window where the user

will be able to browse and view all manuals relating to the plant and plant operation as well as all

components:

Page 58: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 58

10: BACKUP DATABASE:

From the main menu, select ‘Backup Database’ to backup plant databases onto USB memory stick:

After the Backup Database option has been selected, the following pop up box will appear:

The user must navigate using the standard Windows navigator as shown above, where to save the

databases. You must ensure a USB memory stick has been plugged into the HMI, then navigate to this USB memory stick, normally this is displayed is shown above as ‘Removable Disk’. After

the correct location has been selected, press OK for the system to go ahead and backup the

databases to this location.

Page 59: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 59

11: REMOTE LAPTOP The remote laptop is a standard feature. This remote laptop will provide backup should the main

HMI PC become faulty. The software is designed such that should the main HMI become faulty, databases can be copied on to the remote laptop, and this laptop can control the plant wirelessly

(using the Wi-Fi installed on top of the cement silo).

The laptop also provides users with the ability to remote view and control the plant within the Wi-

Fi range. When the laptop is turned on, it will automatically log in to the desktop as shown below:

Sometimes if the laptop is not used for a long period of time it can automatically lock itself or go

into sleep mode. On using the laptop you will then be asked for a username and password. The

username is pil, the password is also pil.

You will need to ensure the Wi-Fi is active and that the laptop has connected onto the Wi-Fi

network. If connected the icon highlighted in red above will appear white. If you need to connect

to the Wi-Fi network, the network identification name is Rapidmobile, the password to connect

onto the local Wi-Fi network is Rapid1234.

Below I have explained the 2 main laptop uses in a little more detail.

Page 60: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 60

11.1: Remote Viewing on Laptop:

The laptop provides the ability for users to remotely connect onto the HMI PC and be able to

control the plant from laptop within the range of the Wi-Fi system. Remote viewing software

called VNC is installed and configured on the laptop, there is an icon for VNC on the desktop.

To connect onto the HMI, simply click on the icon on the desktop called ‘Tight VNC Viewer’, the

following dialogue box will appear:

The IP address shown in the Remote Host box should be OK as it will always be pre-configured

before going to site. Lest the IP address has been lost, you should type in 192.168.2.102. The user should then press ‘Connect’ – assuming the laptop has connected to the Wi-Fi, a connection

will be made to the HMI.

The full screen will automatically be taken up with the connection onto the HMI. To toggle full

screen on and off, press Ctrl+Alt+Shift+F together on the laptop keyboard. You will see the following:

Page 61: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 61

From this point the user has the ability to close VNC or go back to full screen if required.

11.2: Laptop Assuming Main Control of Plant: Should the HMI fail, the laptop has the capability to assume full control of the plant. If the HMI

fails, it is imperative that the first thing the user does is unplug the network cable from the back

of the HMI. It is crucial to the machines running that there are not 2 different PC’s trying to

control the plant.

The next step is to back up the databases from the HMI, it is recommended this be done once a

week as a minimum to ensure minimum information is lost. The USB memory stick containing

the most recent databases should be inserted into the laptop. An explorer window should be

opened by clicking on the icon below circled in red:

Page 62: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 62

When the explorer icon has been clicked on, a new window will open as shown below:

The user should navigate to the (C:) drive, then enter the ‘PilV3’ folder. The contents of the PilV3

folder are as above.

The user should double click on the ‘BatchingSystem.RestorePdb’ file as is highlighted above. The

following dialogue box will appear:

The user is provided with the ability to navigate to the USB memory stick using the standard

Windows navigations system as described above, and select the most recent backup of the

databases.

Page 63: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 63

After ‘Open’ has been selected, the system will automatically begin the process of restoring the

databases from the USB memory stick onto the laptop. After this has completed, the following

dialogue box will appear:

After the databases have been successfully restored, the user should then click on the ‘Start

Dynamix’ icon as shown below:

After this icon has been double clicked, the laptop will automatically launch the PIL Dynamix

control system. Full control of the plant is now available through the laptop. It is imperative that

before any batching commences – all recipes, calibrations and plant settings must be checked.

When the HMI is fully operational again, you must restart the laptop completely, this will close

the software running on the laptop. The user is then free to plug back in the HMI and continue using the plant.

WARNING – The process described above should only be carried when in an emergency situation,

the system is not designed to switch between operation modes regularly.

Page 64: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 64

12: DIAGNOSTICS/ALARMS:

12.1: Alarms Screen:

The system has various diagnostic tools in order to simplify fault detection. All information in the

system can be saved to disk as back up. Only Pneutrol engineers should modify how the system backup works. Plant IO states and full diagnostics are available.

Alarms occur to inform or warn the operator of certain system states. Any problems can be

immediately diagnosed. The alarms screen is accessible from any point in the system by selecting

1 Alarms, along the top of any screen.

The alarms screen provides the following features:

Alarms are immediately viewable.

Alarm screen gives full alarm details with exact dates and times.

Simple quick fault detection.

From here, the operator can accept any non-critical alarms (F1), View an alarms report between given dates (F2), or an events report between given dates (F3). As for all reports, you will be given

the options to print them or export them to alternate media such as a text file. The events report

also gives the user indication of who was logged in when any plant setup or recipes were changed.

Page 65: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 65

Below is an example of the printer log report – as you can see, every action the plant has completed is logged and time stamped. This is very useful for fault diagnosis:

Dealing with Alarms:

An alarm is dealt with as follows:

From the HMI;

1. Press ‘1 Alarms’ to display the Alarm screen. This will show a list of all the active alarms.

2. If the alarm is an out of tolerance alarm or similar, check the screen to see which item was out

of tolerance and by how much. If it is not serious then the weight may be accepted by pressing

‘F1’. If there is a serious weight discrepancy then the system may need to be switched into MANUAL and all existing materials put through the system until the system is clear. Investigate

the cause of the discrepancy and when the cause has been eradicated, abort the process and

restart the system in auto.

3. If you are confident that you know the cause of the alarm then pressing the 'F1' key on the

keyboard will accept the alarm.

PLEASE REVIEW APPENDIX 3 AT THE BACK OF THIS DOCUMENT FOR FULL ALARMS LIST

13: REMOTE ACCESS:

There has been a remote access Wi-Fi receiver installed at the top of the cement silo. The

customer must provide a suitable SIM card which should be installed in the Wi-Fi unit, allowing

remote access for management, PIL technical staff, your distributor or your agent:

Technicians can interrogate the system and assist in fault finding/fixing from their headquarters

PIL Technicians can download new software updates

Management/accounts staff can view/receive production reports

from their own offices as required

System can be started from a remote interface

Page 66: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 66

The Wi-Fi unit is installed at the top of the cement silo as the picture below shows:

To install the SIM card you must open the white outer box, inside you will see the Wi-Fi unit

itself. At the top of the unit, beside where the aerials connect in, there are 2 screws holding a protective cover in place, this cover should be removed and a SIM installed as the picture below

shows:

The Wi-Fi unit comes pre-setup and configured, but should any additional configuration be

required, to change the setup of the Wi-Fi unit the username is admin, the password is RILMobile.

The remote laptop, which is covered in more detail in section 11 will already be configured to

automatically connect to the Wi-Fi, the network identification name is Rapidmobile, the password

to connect onto the local Wi-Fi network is Rapid1234.

Page 67: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 67

13.1: Modifying Network Providers’ APN Settings:

Any device connecting to the internet using a mobile network must have the correct Access Point

Name (APN) setting configured which your SIM card provider will supply you with. After the SIM

card has been inserted into the Wi-Fi unit as described above, you must then configure the APN

setting in the unit to be suitable for your SIM card supplier.

1. Using either the Touch Screen HMI or the remote laptop, open Internet Explorer and type

192.168.2.1 into the address bar as shown below:

2. The screen above should appear. Now enter the login details:

Username: admin

Password: RILMobile

The following screen should appear:

Page 68: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 68

3. Along the top of the web page click on ‘Network’, then select ‘3G’ as shown below:

4. Now enter the APN setting and password (if required) as provided by your network SIM

card provider:

5. After all details have been entered, please click ‘Save’ in the bottom left of the screen to save and confirm your changes.

Page 69: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 69

14: SHUTDOWN SYSTEM:

At the end of a day or to simply switch off the computer go to the Main Menu and select ‘Shut Down’. The HMI will display a message box asking you to confirm the shutdown. Press ‘y’ if it is

ok to shut down, otherwise press ‘’n’ to cancel the shutdown. Always allow the computer time to

shut down properly.

15: USEFUL INFORMATION:

15.1: Pausing The System: Should it be necessary to pause the system for any reason, choose the HOLD/RUN option on the

running screen. All screws, motors etc will be stopped and the plant will stay in its present state.

To resume again from the running screen choose the HOLD/RUN option again. Below is a

screenshot of the plant on HOLD:

Note: Do NOT press the ABORT option as this will completely reset the Controller to the start

position and the load will be aborted. The system will then have to be completely cleared before

you can start any more batches.

Note: This in no way removes power from the equipment and should not be used to enable

someone to work at a piece of equipment. If work must be done then the system should be

"Cleared", all the mix passed through the system in the normal way, placed in RESET and the

equipment then ELECTRICALLY ISOLATED, both on the CONTROL PANEL (Key Switch) and the

STARTER Panel (Mains Isolator).

Page 70: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 70

15.2: Emergency Stop:

When it is imperative that the system be shut down immediately, i.e. as in the case of an accident

then the "Red" EMERGENCY STOP button on the front of the HMI panel should be pressed. There

are also “Emergency Stop” buttons on the left and right sides of the plant ahead of the aggregate

bin. An example of an emergency stop is shown in the picture below:

When any emergency stop is pressed, this will stop the plant batching operation completely i.e.

stop belts, mixer, screws etc. If an emergency stop has been pressed, the ‘Em Stop Reset’ button

on the front of the main HMI panel will become illuminated solid blue. This highlights to the user

that an emergency stop is active. All emergency stops should be checked to ensure none are pressed, when satisfied the plant is safe, the user should press the ‘Em Stop Reset’ button to

reset all emergency stops.

If the blue ‘Em Stop Reset’ button on the front of the main HMI panel is flashing, this alerts the

user that it is not an emergency stop that is active, rather it is the mixer Castell lock. Section 15.4 explains the Mixer Castell system in more detail.

Further isolation can be carried out by turning the Isolator handle on the starter panel to the OFF

position. Should this facility be used, then it is necessary, on starting up again, to clear the

system manually.

Page 71: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 71

15.3: Safety Pull Switches

In addition to emergency stops, there are also a number of safety pulls switches installed on

moving belts around the plant, an example of which is shown below:

The safety pull above demonstrates what the safety pull should look like when in normal running

mode. If the safety pull has been activated, it will look like the picture shown below:

Page 72: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 72

The safety pull is reset by pushing the blue switch from the zero/off graphic to the 1/on graphic.

Page 73: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 73

15.4: Mixer Castell Interlocking System The mixer has its own interlocking system to protect users from entering or accessing the mixer.

The Castell key is taken from the electrical lock which is found on the front of the main panel door

(the main panel is located immediately to the left of the HMI panel), as shown below:

The key is then taken to unlock the Castell lock mounted on top of the mixer lid door.

The picture below shows the Mechan guard switches which provide feedback to the control

system that the mixer lid doors are definitely closed. These switches are automatic reset and it is imperative that when the mixer lids have been opened, that the user ensures the mixer lid is

closed properly and that these switches are within 5mm of each other.

Page 74: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 74

If the mixer Castell has been removed from the electrical lock on the main panel door, and assuming no emergency stops are active, the blue ‘Em Stop Reset’ button on the HMI panel will

flash, to alert the user that no emergency stops are pressed and that only the mixer Castell is

unlocked.

WARNING! – No one should ever stand on top of the mixer or the mixer lids.

WARNING! – Hydraulic power pack and therefore the hydraulic mixer doors are outside the

emergency stop circuit, the hydraulic power pack should be isolated before work commences

inside, on or around the mixer.

Page 75: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 75

15.5: How To Reset VSD’s If any drive fails within the plant, an alarm will be displayed on the HMI screen alerting users of

the problem. If you need to reset any drive there are 2 options. The user can either press an

emergency stop and leave activated for approximately 1 minute, allowing time for the drives to

power down or the user can choose to open the electrical panel and press the red 0 button on the

front of the drive as the picture below shows:

Page 76: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 76

15.6: Compressor

The compressor is started from the main HMI panel pushbuttons as the picture below illustrates:

As you can see from the picture above, the main HMI panel has Compressor Start and

Compressor Stop pushbuttons.

In addition to the Compressor Start and Stop buttons on the control panel shown above, there are

also Start and Stop buttons on the actual compressor itself as shown below:

Page 77: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 77

Page 78: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 78

15.7: Pneumatic Valve Box Lubricators/Air Pressure Setup

The main pneumatic regulator located beside the pneumatic valve panel (as shown below) should

be set and maintained at 6 Bar (90 PSI).

Aeration regulators should not be set at more than 0.7 Bar (10 PSI). All pneumatic valve box

lubricators should be kept topped up with pneumatic oil. The picture below shows your

pneumatic valve box:

Page 79: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 79

The lubricator is circled red above. The user should make sure the air has been turned off, this can be done by closing the hand valve on the side of the valve box panel. The outer protective

bowl and the inner glass bowl are removed as described below – it is important the glass bowl is

kept approximately three quarters full with pneumatic oil.

15.8: HMI

The HMI comes complete with flush panel and 5 wire touch screen. It can be cleaned using a

damp cloth. Use of strong detergents/cleaning agents is strongly advised against.

In the rare event that the HMI freezes, the operator should plug a keyboard into the USB port of

the front of the main HMI panel. After this has been plugged in the operator should press Control-Alt-Delete on the keyboard. The user should then select Shutdown and then Restart.

Page 80: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 80

15.9: How to Calibrate Moisture Probes

Pre-Calibration Checks

Before any moisture probe is calibrated, it is important to ensure the ‘floating’ bracket holding the

moisture probe in place is free and able to move up and down with material. Secondly it is

important to ensure the ceramic face of the probe is clean and does not have any material build-up.

Calibration Theory

To determine the calibration line, two points are required, the Raw 1 and Real Moisture % 1 on

the Moisture Setup screen of the PIL computer are default settings and should not be changed.

The values are Raw 1 = 6240, Real Moisture % 1 = 0.01. It is the Raw 2 and Real Moisture % 2 figures we will focus on. These are derived by flowing material over the sensor and noting down

the Current Raw Value on the moisture calibration screen (as shown below), at the same time

taking a sample of material, which will be dried out to find its true moisture content. This gives

us the ‘Raw 2’ and ‘Real Moisture % 2’ figures.

Calibrate:

The ‘Calibrate’ tab beside each moisture value allows the calibration values for the moisture probe

to be altered. If you click on ‘Calibrate’ a new window will appear.

At the top of the screen there is a ‘Current Raw Value’ which the system is receiving from the

probe. Below the ‘Current Raw Value’ are the calibration points. Up to 12 different calibration

points can be entered to make the calibration more accurate. Only the calibration points which have the check box beside it enabled will be used. When more than two calibration points are

entered and enabled press ‘F2’ to view the line of the graph. When more than two points are being

used the best line of fit will be used. Press ‘F1’ when you are happy with the calibration values or

‘ESC’ to cancel and return to the moisture setup screen. The calibration values will only take

affect once ‘F1’ is pressed to save the changes.

Page 81: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 81

Hints and Safety - Wear safety glasses and protective clothing to guard against expulsion of

material during the drying process

- Do not attempt to calibrate the sensor by packing material on the face. The readings

obtained will not be representative of those from a real application

- Whilst recording the sensor Current Raw Value, always take a sample as close to the sensor as possible

- Ensure a representative sample is taken for moisture testing

Equipment

- Weighing scales – accurate to 0.1g

- Heat source – for drying samples, such as oven or microwave - Container – such as glass bowl, tin for drying samples in

- Safety Equipment – including glasses, heat resistant gloves and protective clothing

Calibration Procedure

(i) Weigh and write down the sample dish weight (ii) On the PIL computer, go to the Moisture Setup as described in Section 7.4 and find the

Current Raw Value

(iii) Weigh up approximately 750kg of material to be calibrated, monitoring the Current Raw

Value as the material is weighed. Take an average of the Current Raw Value when the

weighing is finished. (iv) Collect a sample of material in the dish, and weigh.

(v) Completely dry out material and weigh again.

Calculating the Moisture Content

To summarise then the calculation: wet weight – dry weight

dry weight – weight of dish x 100

Inputting Figures To PIL system

Now the moisture calculation is complete, we can input the calibration figures to the system. The Current Raw Value we wrote down earlier is typed into the Raw 2 column and the moisture we

just calculated is typed into the Real Moisture % 2 column (as shown above). Please note if the

saturated surface dry (SSD) of the material is known, this can be entered on the Moisture Setup

screen. The calibration is complete.

Page 82: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 82

15.10: Admix Dispenser

If fitted, the admix dispenser installed is similar to the unit shown below with each component

labelled:

Component 4 shown above, the bucket filter, should be checked regularly to ensure there is no

build-up of dirty material. To ensure the admix pump does not need bled, it is crucial that all

pipes in to and out of the admix pump are filled with liquid prior to initial running.

A foot valve and strainer must be fitted to the suction hose if using a barrel of admixture, if connecting to a bulk tank, an in-line non-return valve should be fitted at the tank outlet.

Page 83: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 83

15.11: Hydraulic Controls

Each Rapid mobile machine has hydraulic controls to facilitate folding up and folding down the

plant. For the hydraulic controls to function, the user must first start the generator. Since the

hydraulic power pack is outside the emergency stop circuit, the hydraulic power pack will

function immediately, by pressing the start button as shown in the picture below:

After the ‘Hydraulic Power On’ button has been pressed, the user can control the manual levers

on the machine as shown below in the picture below. Full description of these levers operation

can be found in the accompanying Rapid International manual.

Page 84: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 84

WARNING! – Hydraulic power pack and therefore the hydraulic mixer doors are outside the

emergency stop circuit, the hydraulic power pack should be isolated before work commences

inside, on or around the mixer.

15.12: What to Do If You Have a Problem?

In the event of a system failure, immediately take a picture of the running screen on the HMI with

a camera phone or small camera. Also take a picture of the inputs/outputs using the facility

provided in the 'INPUT/OUTPUT' screen. Carry out a visual inspection of the plant and write

down any faults and correct if possible.

If no faults are noted, clear the system completely in manual mode and attempt the next job or

batch in automatic mode. Observe plant functions and record data as necessary. Relay all

findings to Rapid International Limited or your local dealer.

The more comprehensive the information supplied, the easier it will be to provide a solution to the

fault. Also have available all plant control drawings to discuss with Support Engineers.

Page 85: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 85

16: APPENDIX 1 – Best Practice/Regular Checks There are various key points that we recommend are carried out on the plant regularly to ensure

ease free operation, in conjunction with the various mechanical checks recommended in the mechanical manual.

Hourly Checks 1. Check around aggregate gate for material build up and that aggregate is flowing freely

2. Check around cement screw socks for material build up and that cement is flowing freely

3. Check the oversize material grill in the mouth of the mixer for material build up

Daily Checks

1. Check weight of load

2. Check the water spray bar is unrestricted

3. Check for build-up in gob hopper

4. If 24 hour batching pc must be shut down and restarted

Weekly Checks

1. Check calibration of aggregate

2. Check calibration of cement 3. Check pneumatic valve panel filter and lubricator (filter should be clear of water,

lubricator should contain pneumatic oil)

4. Test all safety pulls

5. Test all emergency stops

6. Test cement high level 7. Examine silo filter cartridges

8. Check silo pressure relief valve (PRV)

9. Check silo pressure switch

10. Drain all water out of the compressor

11. Backup HMI databases to USB memory stick

On Start-up

1. Plant must have power turned on a minimum of 20 minutes before start-up

On Plant Relocation

1. All transport bolts must be remove from each weigh hopper/belt

2. Earth spike must be fitted to plant at all times. Maximum earth spike resistance – 5

Ohms 3. Full calibration check must be completed

4. If control panel is unplugged, both ends should be covered to prevent water/dust ingress

5. The cement screw fill butterfly valves must be checked prior to starting up the plant. The

compressor should be turned on and these valves tested to ensure air piping etc has been

reconnected correctly after plant relocation.

After plant has been moved, a full electrical inspection should be carried out, if the plant remains

stationary, a full electrical inspection should be carried in accordance with current country laws,

we would suggest a minimum of once per year.

Page 86: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 86

17: APPENDIX 2 – Full Alarm List Plant Safety Fail These alarms become active when either an

Safety Switch Tripped Emergency Stop (EMS) or Safety Pull cord is EMS - Panel Active activated.

EMS - Remote 1 Active

EMS - Remote 2 Active

Safety Pull Switch 1 Active

Safety Pull Switch 2 Active

Mixer Castell Switch Off The Castell interlock for the mixer lids has been turned off

Mixer Safety Switch Trip The mixer safety switch has tripped – check safety switch

Mixer Motor Protector Trip

Mixer Motor 1 Protector Trip Mixer Motor 2 Protector Trip

Cem 1 Screw Motor Protector Trip These alarms become active when a

Cem 2 Screw Motor Protector Trip motor protector overload is tripped.

Water Pump 1 Motor Protector Trip Each alarm is clearly marked,

Water Pump 2 Motor Protector Trip appropriate motor protector should Agg Feeder Motor Protector Trip be reset inside the electrical panels.

Agg W/C Motor Protector Trip

Cleanout Conv. Motor Protector Trip

Outload Conv. Motor Protector Trip

Power Pack Motor Protector Trip

Compressor Motor Protector Trip Silo Filter Fan Motor Protector Trip

Air Healthy Failed Air supply to plant has failed – check plant compressor

Agg Feeder Not Reaching Target When running, the plant is not

reaching its preset target rate

Agg Feeder Not Stopped The Feeder or W/C has not stopped -

possible electrical fault

Cement 1 Not Reaching Target

Cement 2 Not Reaching Target

Additive 1 Not Reaching Target When running, the plant is not

Additive 2 Not Reaching Target reaching its preset discharge target

Water Not Reaching Target rate – check for blockages or Agg Start Hz Not Enough to Reach Batch Target restrictions to the flow of material

Cem 1 Start Hz Not Enough to Reach Batch Target

Cem 2 Start Hz Not Enough to Reach Batch Target

Adm 1 Start Hz Not Enough to Reach Batch Target

Adm 2 Start Hz Not Enough to Reach Batch Target

Wtr Start Hz Not Enough to Reach Batch Target

Cement 1 Screw Not Stopped The SLC is still receiving signal to say

Cement 2 Screw Not Stopped the piece of equipment is still running

Additive 1 Pulser Not Stopped check for electrical fault Additive 2 Pulser Not Stopped

Water Pulser Not Stopped

Mixer Not Running The various items of equipment have

Cleanout Conveyor Not Running not started to run after the relevant Outload Conveyor Not Running outputs have come on to run them.

Cement Screw 1 Not Running

Cement Screw 2 Not Running

Page 87: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 87

Mixer Not Stopped The SLC is still receiving signal to say Cleanout Conveyor Not Stopped the piece of equipment is still running

Outload Conveyor Not Stopped check for electrical fault

Agg Feeder Drive Not Ready

Agg W/C Drive Not Ready The various VSD’s are not ready to run Cement 1 Screw Drive Not Ready Check fault code on front of VSD

Cement 2 Screw Drive Not Ready

Additive 1 Pump Drive Not Ready

Additive 2 Pump Drive Not Ready

Water Pump Drive Not Ready

Water Level Low There is a low level of water in the water tank

Agg Feeder Drive Comms Fail

Agg W/C Drive Comms Fail Ethernet communications have failed

Cement W/H 1 Screw Drive Comms Fail to the VSD – check Ethernet network

Additive Pump Drive Comms Fail Water Pump Drive Comms Fail

Cement W/H 2 Screw Drive Comms Fail

Agg Feeder Drive Not At Speed

Agg W/C Drive Not At Speed The VSD has not reached required Cement 1 Screw Drive Not At Speed speed – check there are no blockages

Cement 2 Screw Drive Not At Speed

Additive 1 Pump Drive Not At Speed

Additive 2 Pump Drive Not At Speed

Water Pump Drive Not At Speed

Invalid Load Targets Recipes, calibration or load setup is incorrect, please re-enter

Silo Extreme High Level Active Silo has reached extreme high level

Silo Extreme Level Active

Silo Extreme High Level Tacho Fail

Silo Extreme Level Tacho Fail Silo component has failed, check

Silo PRV Switch Fail operation of specified component

Silo Air Pressure Fail

Silo Fill Valve Fail

Silo Pressure Switch Fail

Silo Fill Cover Open The Silo fill cover is not open – you cannot fill the silo

Silo Isolator Not On The silo filter isolator is turned off – you cannot fill the silo

Cement Silo Low Level The cement silo has a low level – re-order material

UPS Running on Battery Power has been lost to the UPS, the HMI and SLC are being

kept powered on by the UPS batteries – please shutdown HMI

and UPS or restore power as soon as possible

Redlion Comms Failure Communications have failed to the Red Lion loadcell

amplifier – stop batching and check local Ethernet network

Agg Material Flow Out of Tolerance System is not achieving desired flow

Load Flow Rate Below Tolerance rate – check for blockages

Load Flow Rate Above Tolerance

Load Flow Rate Too Low!

Page 88: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 88

SLC program loaded from memory module - ALL CALIBRATION AND SETTINGS MUST BE CHECKED BEFORE BATCHING!

An EPROM has been installed in the SLC, meaning that should the SLC lose its program, through

voltage surge, lightning or any other unforeseen act of God, the program will automatically be

reloaded into the SLC.

The alarm shown above comes on if the program has been automatically loaded from the EPROM

to the SLC after the program has been lost. As all calibrations and plant settings are stored

within the SLC, it is imperative calibrations, settings etc are checked before any further batching

is completed.

Page 89: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 89

Agg Running Hz Will Not Reach Batch Target The system has calculated that the

Cem 1 Running Hz Will Not Reach Batch Target calculated running speed in Hz is

Cem 2 Running Hz Will Not Reach Batch Target outside the minimum and maximum

Adm 1 Running Hz Will Not Reach Batch Target settings configured. Please adjust

Adm 2 Running Hz Will Not Reach Batch Target recipe accordingly Wtr Running Hz Will Not Reach Batch Target

Should the plant be batching and unable to stay within the minimum and maximum Hz settings,

the following alarm will be activated.

This could mean there is a blockage, material is not flowing in a suitable fashion or it could mean

that the tons per hour rate you are trying to produce to is not suitable for the recipe, for example,

if you are constantly below target, then you need to reduce the tons per hour rate. If material is

weighed up and waiting for the cement weigh hopper to switch over, then the tons per hour rate of

the plant can be increased.

Page 90: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 90

18: APPENDIX 3 – Troubleshooting Guide Below is a list of common problems and the best recommended course of action:

1. Weight of load incorrect Check all weighers for build up

Example of aggregate build up around the end of the feeder belt

2. Agg Kgs/s Flow Out of Tolerance Check material build up around weigher

Check there is no blockage in the aggregate feed bin

Check the transport bolts are loose

Is there a problem with inconsistent aggregates?

If all of the above are ok – repeat calibration of

aggregate weigher

3. Wet and dry patches in load Check aggregate moisture is constant

Check cement is flowing freely

4. Water not reaching target Check water jets are clean + not blocked inside mixer

5. Using small or large qty of cement Not ideal for the plant to be running at the minimum

or the maximum speed of the plant as there is no

room for movement. If you see alarm for this, adjust

tons per hour being batched to control speed of plant

better.

6. Moisture probes giving false readings Check ceramic face for build-up /or damage

7. Cement slow to discharge out of silo Empty silo, check for lumps in bottom of silo

Check aeration is operational and set correctly

(10PSI)

8. Cement discharging out of silo too fast Check aeration is set correctly (10PSI)

Modify slide valve control times to suit the material

Adjust cement jog on time to suit material

9. HMI has frozen Restart – see section 15.8 for description

10. Manual Motor Protector Tripped Before appropriate motor protector is reset, the

Page 91: Rapid 600C Continuous Mixing Plant User Manualrapidintl.com/userfiles/701/specs/Rapid-600C-Manual-v1.3.pdf · Rapid 600C Continuous Mixing Plant User Manual ... Cement Calibration

Issue 1.3 91

electrical circuit should be inspected and tested to confirm it is electrically sound and there are no

electrical circuit faults.

11. Pneumatic doors slow to operate Check compressor is turned on

Check air pressure is satisfactory (should be 6 Bar at regulator)