POWER FAULT SYSTEM FAULT Radio Hub Taktis Control Panel 230V AC Radio Network Communicator POWER FAULT SYSTEM FAULT Radio Hub Taktis Control Panel 230V AC Radio Network Communicator RNC For Taktis Quick Start Guide Iss 2 - MK282 AJM www.emsgroup.co.uk QUICK START GUIDE RADIO NETWORK COMMUNICATOR (RNC) For Taktis®

Upload: others

Post on 30-Oct-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RADIO NETWORK COMMUNICATOR (RNC) For Taktis®

Radio Network CommunicatorFC-TAK-438

POWER

NETWORK FAULT

FAULT

POWERFAULT

SYSTEMFAULT

Radio Hub

TaktisControl Panel

230V AC

Radio Network Communicator

POWERFAULT

SYSTEMFAULT

Radio Hub

TaktisControl Panel

230V AC

Radio Network CommunicatorFC-TAK-438

POWER

NETWORK FAULT

FAULT

Radio Network Communicator

RNC For Taktis Quick Start Guide Iss 2 - MK282 AJM

www.emsgroup.co.uk

QUICK START GUIDE

RADIO NETWORK COMMUNICATOR (RNC)For Taktis®

Page 2: RADIO NETWORK COMMUNICATOR (RNC) For Taktis®

FC-TAK-438

Step 1 Identify RNC Locations:If a radio survey has already been carried out, the survey will detail the recommended location of the Radio Network Communicators (RNCs) and also any aerial positions if required.

600mm away from metal*

*300mm is a worst case minimum requirement

2m awayfrom otherelectrical

equipment

2m awayfrom otherelectrical

equipment

2m awayfrom otherelectrical

equipment

RNC

The recommended distance between metal objects from the aerial is 600mm. The recommended distance to any other electrical equipment is 2m.

RNC

POWERFAULT

SYSTEMFAULT

2mminimumdistance

Plastic conduit should be used. Panel earth

faults will be shown if metal conduit is used.

Never site RNC within 2m of the panel or Radio

Hub.

Control Panel Control Panel

POWERFAULT

SYSTEMFAULT

©2018 EMS Ltd. All rights reserved Page 2 of 4 Mk282 Iss 2 13/09/2018 AJM

Page 3: RADIO NETWORK COMMUNICATOR (RNC) For Taktis®

NETWORK FAULT

FAULT

POWER

RESET

UPENTER

DOWN

BACK

NETWORK FAULT

FAULT

POWER

RESET

UPENTER

DOWN

BACK

NETWORK FAULT

FAULT

POWER

RESET

UPENTER

DOWN

BACK

Step 2 Identify Cable Entry Location:Open the unit to show the inner PCB. The cable entries can now be made. See entry points below:

NO CABLE ACCESS AT

TOP OF UNIT

ALL CABLES TO BE ROUTED NEATLY AT THE BOTTOM OF THE BOX, AND NOT OVER THE PCB BOARD

Step 3 Fix The RNC To The wall:The unit can now be �xed to the wall. The RNCs �xing positions are as below:

Fixing Position 1 Fixing Position 2

Fixing Position 3 Fixing Position 4

Step 4 RNC To Control Panel Wiring:The cable must be passed through the entry points provided. Connections are detailed below:

Please Note: Care must be taken to ensure that connections are made correctly before applying power to the unit. Damage may occur if cables are incorrectly connected.

RS485 BUS & POWER CONNECTIONS

RS485 OUTRS485 OUTRS485 INRS485 INPOWER INPOWER IN

NETWORK INNETWORK IN

NETWORK OUTNETWORK OUT

AUX 24VAUX 24V

+-+-+-

+-+-+-

TAKTIS CONTROL PANEL

REMOTE NETWORKCOMMUNICATOR

AUX24V

- +OUT IN

+ - + -

NETWORKTaktis Control Panel

NO

Fault input / outputfor remote fault

monitoring / remote PSU (optional)

©2018 EMS Ltd. All rights reserved Page 3 of 4 Mk282 Iss 2 13/09/2018 AJM

Page 4: RADIO NETWORK COMMUNICATOR (RNC) For Taktis®

Step 5 RNC Con�guration:

Setting up of the RNC is carried out by completing the following:

MASTER CONTROL PANEL’S RNC SLAVE CONTROL PANEL’S RNCSTEP A: At the master control panel, set the network address to 1. From Taktis panel front Screen> Activate Controls> Enter PIN> Engineer Options> Con�guration> Edit Con�guration> Panel Settings>

STEP B: At the RNC, ‘Set Node Number’ to 1 via menu. From front Screen> Node Setup> Set Node NumberNOTE: The Taktis network address & the RNC address (node number) must match.

STEP C: Set Site ID via menu. From front Screen> Node Setup> Set Site IDNOTE: Site id is taken from this RNC’s ident label.

STEP A: At the slave control panel, set the network address between 2 & 16. From Taktis panel front Screen> Activate Controls> Enter PIN> Engineer Options> Con�guration> Edit Con�guration> Panel Settings>

STEP B: At the RNC, ‘Set Node Number’ between 2 & 16 via menu.From front Screen> Node Setup> Set Node NumberNOTE: The Taktis network address & the RNC address (node number) must match.

STEP C: Set Site ID via menu.From front Screen> Node Setup> Set Site IDNOTE: Site id must match master control panel RNC’s ident.

Once steps A to C have been carried out at all RNCs, go to step D.

Step D: From the master control panel’s RNC menu, a ‘Con�gure System’ action must be performed to �nalise con�guration:From front Screen> Node Setup> Con�gure System

Step 6 Signal Checks:Once con�gured, all RNCs will require a signal level check to ensure they are at an adequate level. The level received must be 30dB or greater.From front Screen> Node Status> Signal Level

©2018 EMS Ltd. All rights reserved Page 4 of 4 Mk282 Iss 2 13/09/2018 AJM

The information contained within this literature is correct at time of publishing. EMS reserves the right to change any information regarding products as part of its continual development enhancing new technology and reliability. EMS advises that any product literature issue numbers are checked with its head o�ce prior to any formal speci�cation being written.