r407c cellar cooling - airconscotland.comairconscotland.com/beermaster_brochure.pdf · 2...
TRANSCRIPT
2
IntroductionThe New R407C Beermaster from ClimateCenter is a flexible packaged cooling system,designed to fully incorporate the demands oftodays cellar cooling industry. An extensive rangeof reliable, energy efficient, service friendlycondensing units and evaporators catering forcooling capacities between 3 and 15 kW, withrated ambient temperatures up to 38°C.Selections are available with cellar temperaturesfrom 4°C to 12°C, which will meet the increasingrange of cooling requirements for pubs, clubsand wine bars. In addition sound levels havebeen minimised throughout the range of BMOcondensing units and BMI evaporators.
The RangeConsisting of compact BMO outdoor, weatherproof,housed units aligned with space saving BMIevaporators, the Climate Center Beermaster rangeis the solution to all cellar cooling applications.Operating two BMI evaporators will successfullycool cellars with irregular shapes (with one BMOcondensing unit.) Temperature is controlled fromone evaporator, the other acting as a slave unit.Beermaster BMO condensing units are designed tominimise sound levels, which together with anacoustic kit option enables a further 6 dB(A)reduction, in noise sensitive locations.The BMI evaporator compact design incorporates an external rotor fan set, reducingsound, resonance and vibration, thereforeminimising sound break out into bar andaccommodation areas.
BMO Condensing Unit SpecificationNominal sound pressure levels:41 to 49 dB(A) at 10m. Lower sound levels areachieved using the acoustic kit.Housing: Fully weatherproof, with powder coatgrey gloss finish (RAL7036).Compressor: BMO 100 – Hermetic complete withcrankcase heater BMO 120 to 550 – Scrollcomplete with crankcase heater.Liquid Line: Receiver and sightglass.Controls: Externally accessible mains isolator.Contactor. HP and LP pressure switches.Fully wired and enclosed electrical assembly.Fansets: Single phase, high efficiency, low noiseexternal rotor design, rated to IP44.Service: Maximum access for servicemaintenance. Simple hinged and removable panelsLid lifts up and latches, with two positions-full openor front access only.Connections: Liquid and Suction angle servicevalves, pre-fitted with solder adaptors. Externalcharging/gauge access ports.Installation: Easy brazing to unit connections.Access without need to remove fixings.All components fully accessible from one side.
BMI Evaporator SpecificationNominal sound pressure levels:53 to 58 dB(A) at 3m.Construction: Compact steel chassis design.White, single piece highly durable ABS front panel,incorporating fan mounting and controls.Drain tray: Durable ABS with 3/4 inch BSPconnection. Simple removal for cleaning. Fittingseasily available to connect to speedfit, copper,polypipe etc. as a standard drain fitting.Wolseley part number 517588Controls: Electronic controller, mounted in a subassembly with the fan capacitors and pre-madewiring connections. Incorporates an off cycledefrost regime, which automatically initiates if the optional defrost sensor is fitted. Expansion valveand solenoid valve.Fansets: Single phase, high efficiency, low noiseexternal rotor design, rated to IP44 complete with air straightener.Air Throw: Up to 17m for even cellar temperatures Energy saving: Option to operate twin and threefan evaporators on a single fan during off cycle or heating mode. An off cycle defrost will initiate all fans.Air heater: Single fan - 1.1 kw, twin/triple fan - 2.2kw, operated by controller, whichincorporates a dead band control.
Liquid Line: Inlet connection with filter drier and solenoid valve.Service: Front panel, drain tray and end panels are fully removable providing full access to unit,without the need to release from the ceiling or wall brackets. Front mounted controller allowsaccess without removing platework.Connections: End plates wrap around back of evaporator. Removal provides full access to the pipework connections.Installation: Easily accessible endplates.All components fully accessible from one side.
OptionsWall Bracket: Universal design suitable for all BMOcondensing units and BMI evaporators.Acoustic Kit: Minimum sound pressure levels areachieved on the BMO condensing units using thisoption, with reductions up to 6 dB(A) at 10m, whenrunning the fan at minimum speed.The kitcomprises the fan speed controller and acousticlining to the compressor compartment.Defrost sensor: Required on all cellar selections at4°C and some at 8°C, as indicated in theselection data on page four. Electronic controllerincorporates an off cycle defrost regime, which automatically initiates if the defrost sensor is fitted.
R407C Cellar Cooling
3
Cellars at Room Temperature of 10˚C Above GroundCellar Condensing Part Number Part Number Evaporator Part Number CapacityVolume m3 Unit Model 230V 1ph 50hz 415V 3ph 50hz Model (watts)15 - 28 BMO-100-1 684200 - BMI407-37 684213 293028 - 40.5 BMO-120-1 684201 - BMI407-37 684213 374440.5 - 45 BMO-120-1 684201 - BMI407-48 684215 393545 - 55 BMO-150-1/3 684202 684203 BMI407-48 684215 466755 - 60.5 BMO-150-1/3 684202 684203 BMI407-69 684216 501560.5 - 66 BMO-150-1/3 684202 684203 BMI407-89 684218 521066 - 78 BMO-200-1/3 684204 684205 BMI407-69 684216 615978 - 84.5 BMO-200-1/3 684204 684205 BMI407-89 684218 644984.5 - 91 BMO-250-1/3 684206 684207 BMI407-69 684216 693291 -105 BMO-250-1/3 684206 684207 BMI407-89 684218 7468105 - 112.5 BMO-300-1/3 684208 684209 BMI407-89 684218 8252112.5 - 120 BMO-300-1/3 684208 684209 BMI407-104 684219 8500120 - 128 BMO-300-1/3 684208 684209 BMI407-133 684221 8923128 - 153 BMO-350-3 - 684210 BMI407-104 684219 10454153 - 200 BMO-450-3 - 684211 BMI407-133 684221 12628200 - 235 BMO-550-3 - 684212 BMI407-133 684221 14548
Cellars at Room Temperature of 10˚C Below Ground15 - 50 BMO-100-1 684200 - BMI407-37 684213 293050 - 66 BMO-120-1 684201 - BMI407-37 684213 374466 - 72 BMO-120-1 684201 - BMI407-48 684215 393572 - 91 BMO-150-1/3 684202 684203 BMI407-48 684215 466791 - 98 BMO-150-1/3 684202 684203 BMI407-69 684216 501598 - 105 BMO-150-1/3 684202 684203 BMI407-89 684218 5210105 - 128 BMO-200-1/3 684204 684205 BMI407-69 684216 6159128 - 136 BMO-200-1/3 684204 684205 BMI407-89 684218 6449136 - 144.5 BMO-250-1/3 684206 684207 BMI407-69 684216 6932144.5 - 162 BMO-250-1/3 684206 684207 BMI407-89 684218 7468162 - 180.5 BMO-300-1/3 684208 684209 BMI407-89 684218 8252180.5 - 190 BMO-300-1/3 684208 684209 BMI407-104 684219 8500190 - 200 BMO-300-1/3 684208 684209 BMI407-133 684221 8923200 - 231 BMO-350-3 - 684210 BMI407-104 684219 10454231 - 288 BMO-450-3 - 684211 BMI407-133 684221 12628288 - 345 BMO-550-3 - 684212 BMI407-133 684221 14548
Cellars at Room Temperature of 4˚C Above Ground15 - 21 BMO-120-1 684201 - BMI407-37 684213 307721 - 28 BMO-150-1/3 684202 684203 BMI407-48 684215 383028 - 32 BMO-150-1/3 684202 684203 BMI407-69 684216 414632 - 40.5 BMO-200-1/3 684204 684205 BMI407-69 684216 506440.5 - 45 BMO-200-1/3 684204 684205 BMI407-89 684218 531845 - 50 BMO-250-1/3 684206 684207 BMI407-69 684216 582250 - 55 BMO-250-1/3 684206 684207 BMI407-89 684218 617355 - 60.5 BMO-300-1/3 684208 684209 BMI407-89 684218 663260.5 - 66 BMO-300-1/3 684208 684209 BMI407-104 684219 705366 - 84.5 BMO-350-3 - 684210 BMI407-104 684219 857184.5 - 105 BMO-450-3 - 684211 BMI407-133 684221 10238105 - 130 BMO-550-3 - 684212 BMI407-133 684221 11928
Cellars at Room Temperature of 4˚C Below Ground15 - 21 BMO-100-1 684200 - BMI407-37 684213 237021 - 32 BMO-120-1 684201 - BMI407-37 684213 307732 - 40.5 BMO-150-1/3 684202 684203 BMI407-48 684215 383040.5 - 45 BMO-150-1/3 684202 684203 BMI407-69 684216 414645 - 50 BMO-150-1/3 684202 684203 BMI407-89 684218 429750 - 60.5 BMO-200-1/3 684204 684205 BMI407-69 684216 506460.5 - 66 BMO-200-1/3 684204 684205 BMI407-89 684218 531866 - 72 BMO-250-1/3 684206 684207 BMI407-69 684216 582272 - 78 BMO-250-1/3 684206 684207 BMI407-89 684218 617378 - 84.5 BMO-300-1/3 684208 684209 BMI407-89 684218 663284.5 - 91 BMO-300-1/3 684208 684209 BMI407-104 684219 705391 - 98 BMO-300-1/3 684208 684209 BMI407-133 684221 740698 - 112.5 BMO-350-3 - 684210 BMI407-104 684219 8571112.5 - 144.5 BMO-450-3 - 684211 BMI407-133 684221 10238144.5 - 175 BMO-550-3 - 684212 BMI407-133 684221 11928
R407C Quick Selection Guide
ParametersAmbient temperature: Above ground Cellars 32°C Below ground Cellars 21°C Product cooling time: 24 hoursInsulation: 1.42 w/m2 - equal to an average cellar wall Occupancy and pump load: 6 w/m2
Floor: Concrete to earth Lighting: 10 w/m2 for 10 hoursProduct loading: 16 l/m3 Plant running time: nominal 18 hours, maximum 19 hoursProduct entering temperature : 25°C maximum
4
R407C Selection DataCondensing Nominal Weight Evaporator Balanced Capacity in Watts - 32°C Ambient Balanced Capacity in Watts - 38°C Ambient
Model Cellar Temperature Cellar Temperature
4°C 8°C 10°C 12°C 4°C 8°C 10°C 12°CBMO-100-1 1.0 61 BMI407-37 2370 2803 2930 3238 2235 2543 2748 2953
BMO-100-1 1.0 61 BMI407-48 2492 2902 3128 3232 2407 2609 2823 3033
BMO-120-1 1.2 61 BMI407-37 3077 3436 3744 3967 2879 3300 3479 3698
BMO-120-1 1.2 61 BMI407-48 3261 3713 3935 4160 3010 3535 3655 3984
BMO-120-1 1.2 61 2 x BMI407-37 3497 3970 4209 4419 3302 3748 3973 4199
BMO-150-1/3 1.5 68 BMI407-48 3830 4288 4667 4823 3547 4088 4331 4589
BMO-150-1/3 1.5 68 BMI407-69 4146 4729 5015 5301 3915 4462 4609 5049
BMO-150-1/3 1.5 68 BMI407-89 4297 4891 5210 5489 4081 4596 4877 4964
BMO-150-1/3 1.5 68 2 x BMI407-37 4190 4776 5069 5359 3961 4522 4777 4927
BMO-200-1/3 2.0 71 BMI407-69 5064 5804 6159 6540 4712 5370 5879 6047
BMO-200-1/3 2.0 71 BMI407-89 5318 6076 6449 6821 5016 5738 5926 6239
BMO-200-1/3 2.0 71 2 x BMI407-48 5376 6139 6520 6898 5082 5812 6153 6324
BMO-250-1/3 2.5 75 BMI407-69 5822 6720 6932 7522 5582 6234 6600 6993
BMO-250-1/3 2.5 75 BMI407-89 6173 7039 7468 7899 5683 6432 6910 7320
BMO-250-1/3 2.5 75 2 x BMI407-48 6261 7134 7565 7999 5675 6664 7174 7401
BMO-300-1/3 3.0 76 BMI407-89 6632 7855 8252 8787 6338 7256 7693 8142
BMO-300-1/3 3.0 76 BMI407-104 7053 8084 8500 9051 6533 7435 7910 8353
BMO-300-1/3 3.0 76 BMI407-133 7406 8417 8923 9448 6983 7819 8406 8669
BMO-300-1/3 3.0 76 2 x BMI407-48 6972 7955 8424 8659 6466 7347 8037 8241
BMO-350-3 3.5 102 BMI407-104 8571 9895 10454 11086 8023 9204 10029 10336
BMO-350-3 3.5 102 2 x BMI407-69 9160 10445 11076 11714 8729 9784 10537 10872
BMO-450-3 4.5 110 BMI407-133 10238 11893 12628 13369 9548 11368 11724 12474
BMO-450-3 4.5 110 2 x BMI407-69 10414 11987 12742 13481 9972 11087 11816 12539
BMO-550-3 5.5 118 BMI407-133 11928 13735 14548 15014 11117 12814 13561 14317
BMO-550-3 5.5 118 2 x BMI407-89 12786 14577 15424 16391 11999 13491 14420 15103
Blue figures indicate a defrost sensor is required - Part number 684226If controller set point is reduced below 8˚C without the defrost sensor fitted, then the set point will default to 8˚CDual Evaporator Options - Data is for combined evaporator performance. Both evaporators operating in the same cellar under master/slave control
BM0 Technical Data
Condensing UnitModel Nominal Weight
hp kg
5
Sound DataSound Pressure Levels Air Volume
Condensing Standard Minimum dB(A) at 10m NominalUnit Model dB(A) at 10m with acoustic kit (m3/s)
BMO-100-1 41 35 0.57 BMO-120-1 41 35 0.57BMO-150-1 42 36 0.69BMO-150-3 42 36 0.69BMO-200-1 46 41 0.96BMO-200-3 46 41 0.96BMO-250-1 46 41 0.89BMO-250-3 46 41 0.89BMO-300-1 47 42 0.89BMO-300-3 47 42 0.89BMO-350-3 49 44 1.91BMO-450-3 49 44 1.91BMO-550-3 49 44 1.78
Sound Pressure levels measured over a single semi-reverberant plane inotherwise free field conditions.
Minimum sound pressure levels are achieved using the acoustic kit, with the fan running at minimum speed.
The acoustic kit comprises the fan speed controller and acoustic lining to thecompressor compartment.
The fan speed controller modulates both fans on the BMO 350 to 550 models.
Acoustic kit
BMO 100 to 300 models – Part Number 684223BMO 350 to 550 models – Part Number 684224The acoustic kit can be supplied fitted. Please specify at time of order.
Electrical DataCompressor Fan Motor
Condensing Model Supply FLC LRA Start Run No. Dia Speed Power FLC LRA CapUnit Model (A) (A) Cap Cap (mm) (Poles) (watts) (A) (A) (µF)
(µF) (µF) 230V 1phBMO-100-1 AJ5513C 230V 1ph 50hz 9.3 32.0 21 17.5 1 360 4 115 0.6 1.0 3BMO-120-1 ZR18-K3E-PFJ 230V 1ph 50hz 10.0 35.0 - 35 1 360 4 115 0.6 1.0 3BMO-150-1 ZR22-K3E-PFJ 230V 1ph 50hz 11.0 37.0 - 40 1 400 6 120 0.6 1.4 3BMO-150-3 ZR22-K3E-TFD 415V 3ph 50hz 3.9 21.9 - - 1 400 6 120 0.6 1.4 3BMO-200-1 ZR28-K3E-PFJ 230V 1ph 50hz 15.0 61.0 - 45 1 400 4 160 1.0 2.1 6BMO-200-3 ZR28-K3E-TFD 415V 3ph 50hz 4.8 31.0 - - 1 400 4 160 1.0 2.1 6BMO-250-1 ZR34-K3E-PFJ 230V 1ph 50hz 17.0 36.0 - 50 1 400 4 160 1.0 2.1 6BMO-250-3 ZR34-K3E-TFD 415V 3ph 50hz 5.7 38.5 - - 1 400 4 160 1.0 2.1 6BMO-300-1 ZR40-K3E-PFJ 230V 1ph 50hz 23.0 100.0 - 55 1 400 4 160 1.0 2.1 6BMO-300-3 ZR40-K3E-TFD 415V 3ph 50hz 6.6 43.5 - - 1 400 4 160 1.0 2.1 6BMO-350-3 ZR48-K3E-TFD 415V 3ph 50hz 10.0 50.0 - - 2 400 4 160 2.0 4.2 6BMO-450-3 ZR61-K3E-TFD 415V 3ph 50hz 11.0 65.5 - - 2 400 4 160 2.0 4.2 6BMO-550-3 ZR72-K3E-TFD 415V 3ph 50hz 13.0 74.0 - - 2 400 4 160 2.0 4.2 6
BMOCondensing Units
6
98
158
SUCTION CONNECTIONø 1/2” – BM0-100
LIQUID CONNECTIONø 3/8” – BM0-100 to 300
ø 3/4” – BM0-120 to 300
Roof panel fixed with No 10 self tapping screws
Hinged access doorto compressor
Isolator access
Hinged roof panel
g13.8mm long x 8.8mm widefor M8 bolts
566
Cas
ewor
k H
eigh
t
690 MNTG CTRS 18518590
70˚RoofOpening
98
158
SUCTION CONNECTIONø 7/8”
LIQUID CONNECTIONø 1/2”
Roof panel fixed with No 10 self tapping screws
Hinged access doorto compressor
Isolator access
Hinged roof panel
4 mounting holes13.8mm long x 8.8mm widefor M8 bolts
View of roofpanel inopen positionshowing latch
1074
Cas
ewor
k H
eigh
t33
8 C
asew
ork
Wid
th
384
Cas
ewor
k W
idth
354
Fixi
ng C
entr
es
1060 Casework Width
690 Fixing Centres 185185
15
OPENSUP TO90˚
Removable front panel
70˚RoofOpening
15
BMO350-550
BMO100- 300OutlineDimensions (mm)
OutlineDimensions (mm)
Supply Data Minimum Cable Size
Condensing Total Unit Total Unit Motor Rated Motor Rated Up to 25m 25m to 50mUnit Model FLC (A) LRA (A) Fuse Size (A) MCB Size (A) (mm2) (mm2)
BMO-100-1 9.9 33.0 16 16 2.5 2.5BMO-120-1 10.6 36.0 25 25 2.5 2.5BMO-150-1 11.6 38.4 25 25 2.5 2.5BMO-150-3 4.5 23.3 10 10 2.5 2.5BMO-200-1 16.0 63.1 25 25 2.5 4.0BMO-200-3 5.8 33.1 16 16 2.5 2.5BMO-250-1 18.0 38.1 25 25 4.0 6.0BMO-250-3 6.7 40.6 16 16 2.5 2.5BMO-300-1 24.0 102.1 32 32 6.0 6.0BMO-300-3 7.6 45.6 16 16 2.5 2.5BMO-350-3 12.0 54.2 20 20 2.5 4.0BMO-450-3 13.0 69.7 20 20 2.5 4.0BMO-550-3 15.0 78.2 25 25 2.5 4.0
These values are recommendations and for guidanceonly. Additional site factors may need to be taken into consideration.
No allowance has been made for derating and correctionfactors within this guide.
If you are in any doubt over the fuse or cable sizeselection, please consult a qualified electrician orelectrical engineer.
BMO Condensing Units
7
Air Movement DataAir Throw Air Volume
Evaporator At Ceiling Level At 300mm below NominalModel (m) Ceiling Level (m) (m3/s)BMI407-37 16.0 18.1 0.51BMI407-48 12.5 13.8 0.40BMI407-69 17.0 19.7 0.98BMI407-89 12.6 14.3 0.73BMI407-104 17.5 20.2 1.47BMI407-133 13.0 15.1 1.10
Air throw values are measured in free conditions with a terminal velocity of 0.25m/s
Sound DataEvaporator Sound Pressure LevelModel db(A) at 3mBMI407-37 53BMI407-48 53BMI407-69 56BMI407-89 56BMI407-104 58BMI407-133 58
Sound Pressure levels measured overa single semi-reverberant plane inotherwise free field conditions
WeightsEvaporator WeightModel (Kg)BMI407-37 25BMI407-48 29BMI407-69 38BMI407-89 46BMI407-104 51BMI407-133 62
Electrical DataFan Motor Heater
Evaporator Number Diameter Speed Power (Watts) FLC LRA Capacitor Power (Watts) FLCModel (mm) (Poles) 230V 1ph (A) (A) (µF) 230V 1ph (A)
BMI407-37 1 330 4 125 0.6 1.2 4 1100 4.8BMI407-48 1 330 4 125 0.6 1.2 4 1100 4.8BMI407-69 2 330 4 250 1.2 2.4 4 2200 9.6BMI407-89 2 330 4 250 1.2 2.4 4 2200 9.6BMI407-104 3 330 4 375 1.8 3.6 4 2200 9.6BMI407-133 3 330 4 375 1.8 3.6 4 2200 9.6
Supply DataMinimum Cable Size
Evaporator Total Unit Motor Rated Motor Rated Up to 25m 25m to 50mModel FLC (A) Fuse Size (A) MCB Size (A) (mm2) (mm2)
BMI407-37 5.4 16 16 2.5 2.5BMI407-48 5.4 16 16 2.5 2.5BMI407-69 10.8 25 25 2.5 2.5BMI407-89 10.8 25 25 2.5 2.5BMI407-104 11.4 25 25 2.5 2.5BMI407-133 11.4 25 25 2.5 2.5
These values are recommendations and for guidance only. Additional site factors may need to be taken into consideration
No allowance has been made for derating andcorrection factors within this guide
If you are in any doubt over the fuse or cable sizeselection, please consult a qualified electrician orelectrical engineer
BMIEvaporatorsBMI Technical Data
8
197
180
304
370
36.5
295
Fixi
ng C
entr
es
153.5
112.
5
246
LIQUID INLET CONNECTION – ø 3/8”
SUCTION/OUTLET CONNECTION – ø 3/4”
550 Fixing Centres
740 Overall Length
3/4” BSPM DrainConnection
380 Overall Depth
AIRFLOW
8mm Wide FixingSlots (4 off)
483
Ove
rall
Hei
ght
BMO and BMI Interconnecting Pipework SizingEquivalent Interconnecting Line Length with 1k Pressure Drop
Cellar Temperature 4°C Cellar Temperature 10°C
Condensing Unit Connections Evaporator 10m 20m 30m 10m 20m 30mModel Suction Liquid Model SUCTION LIQUID SUCTION LIQUID SUCTION LIQUID SUCTION LIQUID SUCTION LIQUID SUCTION LIQUID
BMO-100-1 1/2" 3/8" BMI407-37 1/2" 3/8" 5/8" 3/8" 5/8" 3/8" 1/2" 3/8" 5/8" 3/8" 5/8" 3/8"
BMO-100-1 1/2" 3/8" BMI407-48 1/2" 3/8" 5/8" 3/8" 5/8" 3/8" 1/2" 3/8" 5/8" 3/8" 5/8" 3/8"
BMO-120-1 3/4" 3/8" BMI407-37 5/8" 3/8" 3/4" 3/8" 3/4" 3/8" 5/8" 3/8" 3/4" 3/8" 3/4" 3/8"
BMO-120-1 3/4" 3/8" BMI407-48 5/8" 3/8" 3/4" 3/8" 3/4" 3/8" 5/8" 3/8" 3/4" 3/8" 3/4" 3/8"
BMO-150-1/3 3/4" 3/8" BMI407-48 5/8" 3/8" 3/4" 3/8" 3/4" 3/8" 5/8" 3/8" 3/4" 3/8" 3/4" 3/8"
BMO-150-1/3 3/4" 3/8" BMI407-69 5/8" 3/8" 3/4" 3/8" 3/4" 3/8" 5/8" 3/8" 3/4" 3/8" 3/4" 3/8"
BMO-150-1/3 3/4" 3/8" BMI407-89 5/8" 3/8" 3/4" 3/8" 3/4" 3/8" 5/8" 3/8" 3/4" 3/8" 3/4" 3/8"
BMO-200-1/3 3/4" 3/8" BMI407-69 3/4" 3/8" 3/4" 3/8" 7/8" 3/8" 3/4" 3/8" 7/8" 3/8" 7/8" 3/8"
BMO-200-1/3 3/4" 3/8" BMI407-89 3/4" 3/8" 3/4" 3/8" 7/8" 3/8" 3/4" 3/8" 7/8" 3/8" 7/8" 3/8"
BMO-250-1/3 3/4" 3/8" BMI407-69 3/4" 3/8" 7/8" 3/8" 7/8" 3/8" 3/4" 3/8" 7/8" 3/8" 7/8" 3/8"
BMO-250-1/3 3/4" 3/8" BMI407-89 3/4" 3/8" 7/8" 3/8" 7/8" 3/8" 3/4" 3/8" 7/8" 3/8" 7/8" 1/2"
BMO-300-1/3 3/4" 3/8" BMI407-89 3/4" 3/8" 7/8" 3/8" 7/8" 3/8" 3/4" 3/8" 7/8" 3/8" 1 1/8" 1/2"
BMO-300-1/3 3/4" 3/8" BMI407-104 3/4" 3/8" 7/8" 3/8" 1 1/8" 3/8" 3/4" 3/8" 7/8" 1/2" 1 1/8" 1/2"
BMO-300-1/3 3/4" 3/8" BMI407-133 3/4" 3/8" 7/8" 3/8" 1 1/8" 1/2" 3/4" 3/8" 7/8" 1/2" 1 1/8" 1/2"
BMO-350-3 7/8" 1/2" BMI407-104 7/8" 3/8" 1 1/8" 3/8" 1 1/8" 1/2" 7/8" 3/8" 1 1/8" 1/2" 1 1/8" 1/2"
BMO-450-3 7/8" 1/2" BMI407-133 7/8" 3/8" 1 1/8" 1/2" 1 1/8" 1/2" 7/8" 3/8" 1 1/8" 1/2" 1 1/8" 1/2"
BMO-550-3 7/8" 1/2" BMI407-133 7/8" 3/8" 1 1/8" 1/2" 1 1/8" 1/2" 1 1/8" 1/2" 1 1/8" 1/2" 1 1/8" 1/2"
The pipework sizes above are suited for the nominal duty of the BMO and BMI matched together as shown in the table.Pipework should be selected based on the total equivalent run length of the interconnecting pipe between the two units, not the dimensional length.Additional equivalent lengths for all bends, vertical rises etc, should be added to the basic run lengths to achieve the equivalent run lengths.If the equivalent run length exceeds the 10m setting use 20m, if the run exceeds 20m use 30m, do not uprate or interpolate the readings above.Please consult your Climate Center technical engineer for selections of line lengths over 30m.
BMI407-37 and 48
OutlineDimensions (mm)
9
197
180
425 Fan Centres
36.5
295
Fixi
ng C
entr
es
153.5
112.
5
246
LIQUID INLET CONNECTION – ø 3/8”BMI 407-69SUCTION/OUTLET CONNECTION – ø 3/4”BMI 407-89SUCTION/OUTLET CONNECTION – ø 7/8”
975 Fixing Centres
1165 Overall Length
3/4” BSPM DrainConnection
380 Overall Depth
AIRFLOW
8mm Wide FixingSlots (4 off)
483
Ove
rall
Hei
ght
304
582.5 582.5
197
180
425 Fan Centres
36.5
295
Fixi
ng C
entr
es
153.5
112.
5
246
LIQUID INLETCONNECTION – ø 3/8”
BMI 407-104SUCTION/OUTLETCONNECTION – ø 7/8”
BMI 407-133SUCTION/OUTLETCONNECTION – ø 11/8”
1400 Fixing Centres
1590 Overall Length
3/4” BSPM DrainConnection
380 Overall Depth
AIRFLOW
8mm Wide FixingSlots (4 off)
483
Ove
rall
Hei
ght
304
795 795
425 Fan Centres
BMI407-104 and133
BMI407-69 and 89OutlineDimensions (mm)
OutlineDimensions (mm)
10
6 x ø 10 holesfor M8 or
M10 fixingsuse top
andbottomfixing
positions
1510
215
015
013
5
401 55
1
975
1400
550
BMI 104 & 133
BMI 69 & 89
BMI 37 & 48
AIRFLOW
275 370
55
400
45
647
551
740 Overall Length
592 137
1165
1590
1017
1442
BMI EvaporatorThe Beermaster universal support bracket incorporates an innovative design,allowing one solution for all the BMO units and BMI evaporators. Its easy to assembleand locate in position, with minimal profile, for specific locations where space is at a premium.
Universal Support Bracket
Mounting position for theBMI evaporatorsUniversal wall mounting Kit: Part No. 684222
Bracket shown supporting the BMI 37 or 48 size evaporator.
11
6 x ø 11 holesfor M8 or
M10 fixingsuse allfixing
positions
234
4630
0
610
30
690 Mounting Centres
552
338185 30
*716
610
566
106
BMO Condensing Unit
Universal Support Bracket
Bracket shown supporting the BMO 100 to 300condensing unitUniversal wall mounting Kit: Part No. 684222
*Bracket is also suitable for the BMO 350-550 condensing unts.The overall height increases to 1224mm.
Mounting Position for the BMO condensing units
For further information telephone 01282 834498 or visit our website atwww.climatecenter.co.uk
Whilst every care has been taken to ensure that the information included in thisdocument was accurate at the time of printing, we reserve the right to changespecifications at any time. The photographs reproduced in this publication arewithin the constraints of the printing process and are NOT to be used for matchingpurposes. E&OE.
Ref: 834 ~ April 2006
Please contact your local Sales Engineer or Branch for more information: