r3 services
TRANSCRIPT
We help in delivering power to the last person in the line
Retrofit, Refurbishment, Rejuvenation
Automation service
Engineering Services
Training & Assessment service
Warranty & non warranty service
Modernisation of HV substation
Asset Management
R3 Services
S&S Power Switchgear Limited
2
What is “R3 Services”“R3 Services” consist of:
● Retrofit● Refurbishment● Rejuvenation● AutomationServices● Engineeringservices● Warrantyandnonwarrantyservices● Trainingandassessment● ModernizationofHVsubstation● AssetManagement RETROFIT:Retrofitprojectsarecustomizedtomeetourcus-tomerspecificrequirements.Itinvolvesassess-ingtheconditionofexistingequipmentandde-cidingthecomponentsthatneedtobereplaced,modified,reusedetc.,basedontherequirement.
REFURBISHMENT:Refurbishmentreferstorepairingoldequipmentwithnewavailablesparematerialsfromtheorig-inalmanufacturer.After repairing the defects itensuresproperfunctionoftheequipment.
REJUVENATION:Theactionorprocessofmakingoldequipment’slookandperformancebetterormorevitalwith-outchanging the technology.Rejuvenation isa“tune-up”ofanexistingserviceequipment thatbringsituptothecurrentelectricalsafetyauthor-itystandards.
MODERNIZATION OF HV SUBSTATIONThemodernizationofhigh-voltagesubstationsisoneofourmaindirectionsinwhichS&SPOWERSWITCHGEARisdevelopingitsactivitiestoourdelibratecustomers.ThespecialpointofourcompanyindealingwithmodernizationofHVsubstationsisprovidingbyourexperiencewith theassembly,manufactur-ingof parts, steel support structuresand com-missioningofhighvoltagedisconnectors.Weoffertoourclients:• Projectsdesignanddeliveryofequipment.• MountingofnewHVequipment-disconnec-
tors,circuitbreakers.Productionanddeliv-eryofrelevantconcretesupportstructuresforthem,accordingtoprojectrequirements;
• Layingandconnectionofnewcontrolcablesandwiring.
• Mountingandconnectionofcommandandcontrolcabinets.
• Electricalmeasurements,testingandcom-missioning.
• Refurbishment,renovation,retrofittingandmanufacturinganddeliveryofspareparts.
TRAINING:We havemanufacturedmore than50000dis-connectors and switches inmedium, high andvery high voltage networks worldwide. Withmorethan45yearsofdisconnectingandswitch-ingknow-how,weunderstandtheclients’needs.S&SPowerswitchgearcanofferbespoketrain-ingcoursestohelpthestaffoperateandmain-taintheswitchgearsafely,correctlyandefficient-ly. S&S offers specialized designed packages/coursemodulesonthetrainingprogram,meetingalltheindustrialstandards.S&Salsocustomizescoursebothon-siteandOff-sitemodulesuponspecificrequirements.S&Sisinserviceforthepastfourdecades.Therearetremendousexperienceandknowledgeinthecompany.Weoffertsharethisprecioustreasurewithourcustomers.Weoffertrainingtocustom-ersthroughourregulartrainingprogrameesandalso through customized trainingProgrammes,conductedatcustomers’premiseson-site.
ASESSMENT:Thelifeofequipmentcouldbewellextendediftheregularassessment isdoneonthestateoftheequipment.Weofferassessmentservicesofallequipmentbyourtrainedmaintenanceengi-neers,Assessmentalsoprovidesanopportunityforretrofittingandrefurbishment.
AUTOMATION SERVICESS&Spowerhelps inservingautomation in fourdifferent categories to the people around theworld.• Servicestationautomation.• Factoryautomation.• Distributionautomation.• Processautomation.
SUBSTATION AUTOMATION:S&S Subtation automation is the process thatworksasasupportingsystemforintegratingalldomainandfunctionalitytoolsintovariousauto-mation layers inorder tohaveunified interface
3
forallworkflows.Infrastructure,Data,Devices,andSoftwarearethekeycomponentsofS&SSubstationautoma-tion.Thebenefitsthatprovidedbyoursubstationautomationare:• ReductionofRepetitiveTasks.• IncreasedProductivity.• GreaterCompetitiveness.• ReducedResponseTime.• CostReduction.• Standardization&ReductionofFailures.FACTORY AUTOMATION:S&S Factory automation is incorporated withautomationfromend-to-endmanufacturingpro-cesses.Themotivation to automateprocesseshasbeenfundamentallyto:• makemoreproduct.• improvequality.• reducedirectlabor.• increaseflexibility.wewouldappreciateanopportunitytoputourexperiencetoworkforourcustomers.
DISTRIBUTION AUTOMATION:S&S power provides services of Distributionautomation (DA) by using digital sensors andswitcheswithadvancedcontrolandcommunica-tiontechnologies.Reliability of energy supply primarily dependson the distribution network, and its importanceisgrowing.Inmanycases,explicitpowerqual-itycriteriaareevenbeing included incontractsbetweencustomersandutilities.Thisbeingthecase,powerqualityisbecomingmoreandmoreofafocus.Operatorsarerequiringsuitablemeasuresthatallowthemtoacquireinformationfromthedistri-butionnetworkatany time,and thus tocontrolthe distribution networkmore efficiently.Know-ing which measures supply which measurableaddedvaluefornetworkoperation isbecomingincreasingly important. Our company take allthese topics into account and provide all pos-siblefunctionsfor faultdetection, fault location,andfaultcorrectionwithinanetworksegment.
PROCESS AUTOMATION:S&Spowerusethestrategyofprocessautoma-tion technology to organize the personnel andsystems throughworkflows.We implement thisprocessautomationinSales,marketing,produc-tion,supplychain,inventorycontrol,administra-tion,andmanagementprocess.
ENGINEERING SERVICES:Utiliseourdesignandbuildcapabilitiestoreduceyouroverallprojecttimeandcost.Inadditiontomanufacturinghighqualitysubstationprotectionandcontrolequipment,OurgroupcompanyAc-rastylecandesignyoursystemsonyourbehalf.WehaveateamofexperiencedApplicationsEn-gineerswhoareablysupportedbyourMechan-ical and Electrical Engineers, meaning we areabletocaterforallyourdesignandbuildneeds”.WeusethelatestAutoCAD2015software&canprovidedrawings&designsinallreleasesofAu-toCADDWGfile in addition toDXF,DWFandAdobePDFfiles.DrawingscanalsobeprovidedforcompatibilitywithotherCADpackagesonre-quest.Ourdesignservicesaresupportedbyourlargeformatscanningcapabilities,bothonandoffsite,and also our large format plotting/printing ser-vices(uptoA0incolourorB/W).
• Have ability to design the Switchgear fromblack box stage concept to commercializa-tion.
• Absorbedtechnologyfromworld-classcom-paniesandbuiltover40years.
• Usecontemporarydesignsoftware, reputedlabsandassociatewithUniversities,interna-tionalconsultantsandPrivateResearchCen-ters.
• OurLeanInnovationOrganizationleveragesconsultantsanduniversities.
• Application&InterfaceEngineeringIncludingLogicandSingleLineDiagrams,ProtectionConfiguration,SettingResistorCalculations,CablingDiagramsandSchedules.
DCS INTEGRATION:Including I/OMapping, Interlock Logic, ScreenDesignsandControlPhilosophy.
DRAWINGS & DIAGRAMS:• PreparationofWiringDiagrams,• UnitComprehensiveand• RoutingDrawings.• Redrawoflegacydrawings• Generationofdiagramsfromexistingequip-
ment.• CADfacilities
Mechanical EngineeringIncluding Bespoke Designs, General Arrange-mentsandLayoutDrawings.
4
WE ARE HERE TO ESTABLISH OUR NEW SERVICES TO OUR CUSTOMERS
AROUND THE WORLD
“Giving A New Life To Your Equipment”
REGION DISCONNECTOR CHANNEL PARTNER ADDRESS LOCATION NAME MOBILE No E-mail ID
NORTH IPPL GLOBAL
T1/113,AssotechBusinessCresterra,PlotNo.22,Sector135,Expressway,Noida,India
NOIDA Mr.GSGoel 9893391977 [email protected]
SOUTH GALAXY MARKETING BlockNo.52,majesticcolony,TirupurKumaranStreet,Valasaravakkam,Chennai-87
CHENNAI Mr.Srinivasan 9282176174 [email protected]
WEST SUNIRMAL ENGINEERS RaneNagarRd,GaneshColony,Chetananagar,RaneNagar,Nashik,Maharashtra422501
NASHIK Mr.BharatkumarWagh 8511734909 [email protected]
UNIQUE SALES CORPORATION 232,ParadiseComplexB/HYashkamalBuildingSayajigunj,Vodadara-390020
GUJARAT Mr.JigishaAnilbhaiShah98240107817227093666 [email protected]
EAST VINGIRI POWERTECH 234,SantoshpurAvenue,Santoshpur,Kolkata-700075KOLKATTA Mr.KASingh 9433229494 [email protected]
5
Disconnectors - R3 ServicesS&Spoweroffersafull lineofdisconnectorstohelpmeetmanyofyourapplicationneedswithvoltage range upto 420KV,current range upto4000A and these disconnectors are in serviceworldwide.
Toaidourcustomer,S&SPowerhasdevelopedtheR3ServiceforHighVoltageDisconnectors.To integrate theoutdated technology supply ofS&Smakeoranymakeproductswith thecur-rently employed technology to extend the lifeof theageingsupplies in initiallycommissionedsubstationsandsites.
R3 OFFERINGS FOR DISCONNECTOR:• Replacementofoldcurrentcarryingassem-
bly(Arms)• Existingoldtophampersarereplaced.• Midlifeextension.• Enablingsmartdrivebox.• Flexible connections are replaced with the
improveddesignoftransfercontactswithfin-gerstomaintainconsistencyincontactresis-tance
• ReplacementofOldEarthSwitch.• ConversionofMechanicalGangtoElectrical
Gangof245kVand400kV• ReplacementofExistingTandempipesand
Downpipes.• Enhancement of mechanical interlocks and
accessoriesforexistingDisconnectors.• ThroughretrofittingweenhancetheCurrent
ratingandShort time ratingofexistingDis-connectors.
• RefurbishmentofexistingS&SmakeDiscon-nectorserviceresultsinMidlifeextension.
• SparepartsandServicework.• RejuvenationofS&Smakesdisconnectors.• Equipment and component parts of discon-
nectors.• Overhaulofdisconnectors.
• Trainingofutilitymanpoweronmaintenanceandservicingofdisconnectors.
• Current leveland fault levelupgradationre-quirements.
MODERNIZATION OF HV SUBSTATION MAIN-TENANCE:• Siteorproductassessment.• Criticalsparessupply.• Annualmaintenanceofcontracts.• Trainingonsiteandinfactoryforallproduct
line.• Facilitatedigitalizationofoldsubstation.
SITE ISSUES:• Nonavailabilityofmechanical Interlocks for
Main&EarthSwitch• RustingofoldMSPowdercoateddrivemech-
anisms• Rustingofbaseassembly,connectingpipes
andtubes.• RustingandhardoperationofDisconnectors.• Agingofcurrentcarryingparts.Hotspotsand
meltingportionsofcurrentcarryingparts.• Highcontactresistance&temperaturerising
issue•
CUSTOMER BENEFITS:• Shortimplementationtimesforreplacement• Minimuminterruptionstoservice• Prolongationofremainingservicelife• Improved operator protection during opera-
tion• Enhanced operator convenience from re-
moteend• Minimisation of maintenance and materials
costs • Minimum time and manpower for mainte-
nance• Extendedwarrantyontheconversionwork
6
DISCONNECTOR PROBLEMS FACED CHALLENGES SOLUTION PROVIDED
Retrofitting 220 KVCENTRE BREAKDISCONNECTOR atMAPS,Kalpakkam
Not able to get spareparts fromOEM, sincetheOEMisnotexisting.
1. Old Torque bear-ing arrangement gotrusted
2. High contact resis-tanceandHightem-peraturevalues.
3. Hard&Jerking4)op-erationduringopen/close
4. No Motor operation.Onlymanual.
1. 35yearsoldDis-connector
2. Current carryingparts and drivemechanismneedto be replacedwithS&SSpares
3. R e p l a c eme n twithin stipulatedtimeperiod
Disconnector CurrentcarryingpartsandMo-tor operating mech-anism designed andManufactured accord-inglytomatchterminalconnectionandMount-ingposition.
Retrofiting 420 KVCENTRE BREAK DIS-CONNECTOR at PG-CIL,KADAPA
1. Main contacts Dam-age / Hot spot pitsandBurns
2. Ageingofcontacts
1 ) D i s c o n n e c t o rLive parts changedmatching the exist-ingTerminalconnec-tors2)Manufacture andDeliver within stipu-latedtimeframe
Live parts changedwithout changing theTerminal connectorsandbusbars
Retrofiting420KVPAN-TOGRAPH DISCON-NECTORatNeyvelilig-nitecorporationlimited
1. Not able to operatetheswitch
2. Failureofgearbox3. BreakageofOperat-
ingrodisolators
1. D isconnec -tor fixing Withoutchange in existingstructure and insu-lator2. Matching theDriveboxfixingposi-tionasperstructuresuitability
1)Complete set ofisolator replacementalongwithDriveboxFixedcontactreplacedwith copper tube and‘L’bracket.
Retrofiting 220 KVCENTRE BREAK &DOUBLE BREAK DIS-CONNECTOR at JSWEnergy
1. Centrebreak–Maincontact damage/HotspotpitsandBurns
2. Doublebreak–Mov-ing blade & Extru-siongothotpitsandburns, InsufficientContactPressure.
3. Difficulties in turnand twist operations&HardOperation.
S&Swere tasked toreplacingtheoldEL-PRO & SMC makecurrent carryingpartsWithout change interminal pad andConnectorsManufacture andDeliver within time-frameandbudget
S&S Disconnectorsweredesigned&man-ufactured to matchexisting mounting po-sitionandterminalcon-nection.
REFERENCES:• PGCIL,KOLAR–Upgradationof420kV2000Ato3150ADisconnector-ExistingSiemensmake• PGCIL,KADAPA–Upgradationof420kV,2000ADisconnector-ExistingELPROMake.• NLC,Neyveli–Upgradationof420kV2000APantograph-ExistingSiemensMake• JSW,Bellary–220kVDoubleandCentrebreakDisconnector–ExistingELPRO&SMCMake.• MAPS,Kalpakkam–220kVCentrebreakDisconnector–ExistingTMGMake.• BPCL,Bhutan–220kVCentreBreakDisconnector–ExistingSMCMakewithS&SMake
7
Disconnectors - Case Studies
1. RETROFITTING420KVCENTREBREAKDISCONNECTOR,DELHITRANSMISSIONLTDBAWAN
2. RETROFITTING145KVDOUBLEBREAKDISCONNECTOR,LANCOINFRATECHUDIPIINDIA
3. RETROFITTING230KVCENTREBREAKDISCONNECTOR,GETCOKADANA
4. RETROFITTING420KV&220KVDOUBLEBREAK&CENTREBREAKDISCONNECTORPGCILMALERKOTLA
5. RETROFITTING132KVCENTREBREAKDISCONNECTOR,TENAGANASIONALMALAY-SIA
6. RETROFITTING145KVDOUBLEBREAKDISCONNECTOR,AMBUJACEMENTSLIMITEDPUNJAB
7. RETROFITTING420KVCENTREBREAKDISCONNECTOR,PGCILHYDERABAD
8. RETROFITTING420KVPANTOGRAPH&CENTREBREAKDISCONNECTOR,PGCILVIND-HYACHAL
9. RETROFITTING420KVPANTOGRAPHDISCONNECTOR,NEYVELILIGNITECORPORA-TIONLIMITED
10.RETROFITTING420KV2000ACENTREBREAKDISCONNECTOR,PGCILKOLAR
11.RETROFITTING245KVPANTOGRAPH&245KVCENTREBREAKDISCONNECTOR,THEWESTBENGALPOWERDEVELOPMENTCORPORATIONLIMITEDBAKRESHWAR
12.RETROFITTING145KVDOUBLEBREAKDISCONNECTOR,SALTHOLMEUK
13.RETROFITTING145KVCENTREBREAKDISCONNECTOR,NTPC-SAIL
14.RETROFITTING420KV2000ACENTREBREAKDISCONNECTOR,PGCILINDORE
15.RETROFITTING145KVCENTREBREAKDISCONNECTOR,STEELAUTHORITYOFINDIALIMITEDBHILAI
16.RETROFITTING420KV2000ACENTREBREAKDISCONNECTOR,PGCILKADAPA
17.RETROFITTING132KVDOUBLEBREAKDISCONNECTOR,NUCLEARFUELCOMPLEXHYDERABAD
18.RETROFITTING220KVCENTREBREAKDISCONNECTOR,BPC-SEMTOKHASUBSTA-TIONBHUTAN
19.RETROFITTING22OKVDOUBLEBREAK&CENTREBREAKDISCONNECTOR,JSWEN-ERGYTORANAGALLU
20.RETROFITTING220KVCENTREBREAKDISCONNECTOR,MAPSKALPAKKAM.
8
MV Circuit Breakers - R3 ServicesWespecializeinprovidingcompletedesign,buildandprojectmanagementofmediumVoltageIn-door andOutdoor VCBs andRetrofit solutionsfor electrical distribution power systems. Since1975,we have earned a unique reputation forproductquality,technicalexpertiseandexcellentcustomerservice.Currently focusedonRetrofit&ServiceOfferingsandspecialprojects.
Fullycertifiedto:• ISO9001• ISO14001• ISO45001
S&SPowerhasbeendesigning,manufacturingand installing vacuum retrofit circuit breakers(andconductingswitchgear refurbishments) formore than 25 years and is considered a spe-cialistinthisfield.Throughourextensiveexpe-rience, S&S Power have developed methodstocombatagingequipmentbyutilizingmodernmanufacturingmethods,pairedwithcuttingedge3Dprintingtechniques.
S&SPowersoffers2linesofcircuitbreakers:1.INDOORVACUUMCB2.OUTDOORVACUUMCB
Withvoltagerangeupto36kv,currentrangeupto2000A
R3 services in VCB(Retrofitting, Refurbishment, Rejuvenation)
Retrofit activities involve rehabilitation of agedbreakersintomodernunitssatisfyingclient’scu-biclerequirementsthroughproperassembling&installing.
OFFERINGS:• Improved insulated framewithSuperior an-
ti-tracking characteristics & MechanicalStrength.
• Reductioninnumberofparts(50%ofthatofpreviousmodel).
• High Mechanical & Electrical life comparewithagedCB.
• RetrofitElectromechanicalrelaystoNumeri-calrelays.
• Upgrade Panel by Close Door OperationSafetyKIT.
• Servicing of existing component in PanelChambers such asCT,CABLEand verminproofing.
• Increased the current carrying capacity ofBUSBARandVCB..
• ReplaceAir,Oil,SF6byVacuumTruck/Cas-sette.
• MVcomponentreplacementinpanel.• OthermakesOutdoorpoleretrofitinoutdoor.• Othermakesmechanismretrofitinoutdoor.
AdvantagesofRetrofitVacuumCircuitBreakers:
• Significant reduction in time and resources
9
needed for planning, compared with com-pleteswitchboard
• replacement• Considerableoverallcostsavingscompared
withswitchboardreplacement• Enables a phased replacement, spreading
costoveranumberofyears• Reducedsitedisruption• Installationinvolvesnocivilwork• Removal of oil from the substation reduces
theriskoffireandexplosion,whichleadstolowerinsurance
• premiums• Increased operating reliability and reduced
maintenancecosts• NoneedtodisturborreplaceHVcables• Canbeoperatedremotely• Suitableforfrequentswitchingduties• Replacesthedangerousandenvironmental-
ly-damagingSF6gas• Significantly extends the service life of the
fixedhousing• Contributes tocompanyenvironmental sus-
tainabilitypolicyandreducescarbonfootprintthroughthebetteruse
• ofnatural resourcesanda reduction in rawmaterials
ENGINEERING DESIGN SERVICES:• Our groups of company give us a strong
backupinengineeringdesignservices.• Ourcompanyhasapoolofqualifiedandex-
perience engineers, offers application engi-neeringandcircuitdesign,singleline, logic,inter locking diagram preparations, generalarrangement and equipment specifications,wiring,terminalblocklayoutsandcablewir-ingdiagrams.
• WeofferR3engineeringservicesglobally
CLIENTS OFFERED WITH FOLLOWING EN-GINEERING SERVICES:
• ABB-INDIA• ABB-UK• ALSTOM-DUBAI• GE-SAUDIARABIA• REYROLLE-UK• RLF-UK• SIEMENS-INDIA• SIEMENS-UK• VaTECH-UK
MODERNIZATION OF HV SUBSTATION MAIN-TENANCE:• Siteorproductassessment.• Criticalsparessupply.• Annualmaintenanceofcontracts.• Trainingonsiteandinfactoryforallproduct
line.• Facilitatedigitalizationofoldsubstation.• R3ofDS,CB,CRPorothersubstationequip-
ment.
BENEFITS:• Increasedoperatingreliabilityandsafety.• Enhancedshortcircuitratingsavailable.• SavingonCAPEXbyrenewingonlytheworn-
outpartswhilebenefitingfromnewtechnol-ogies.
• OPEXwasreducedduetothemodernmain-tenancefreeS&SPowerVCB.
• Increasedpersonnelsafety:1.Mitigaterisksofelectricalflashfatalities.2.Mitigaterisksofpoweroutagesresultingindangerousaccidents.• 10yearsofmaintenance-freeoperation.
10
• Reduced maintenance and environmentalimpact.
• Elimination of hazardousmaterials such asasbestos
• Decreased insurancecostsdue toabsenceofoil
• VCBcanbeeasilyinstalledinanyswitchgearpaneltype.Environmentfriendly.
• HighoperationalspeedwithSF6-freevacu-umcircuitbreakers.
• ThefastestVCBonthemarketwithOpening/Closingtimeof35(12*)/60(24*)msLonglifeandhighreliabilityVCBs:
1.10000close-opencycles.2.Servicelifecanbeextendedbyupto30years
BenefitsoverReplacingCompleteSwitchboards:● Significantoverallcostsaving● Minimaldisruptiontositeandsupply● NoneedtodisturborreplaceHVcables.
REFERENCES:• HPSEB- Repair/Overhauling & Service of
33kVVCBforexistingS&SmakeVCBs• IGCAR, Kalpakkam – Retrofitting of Jyothi
existing IndoorNGEFMOCB toNew12kV,1250A,25KA/3SecofS&SVCBs.
• KSEB-Sparessupplied toexisting11kV in-doorVCB
• NuclearFuelComplex-ServicingofHTGasCircuitBreaker
• ONGC,Ahmedabad-Retrofitting&Repairof12kVVCBandsuppliedSparesto12kVVCB
• ONGC,Assam – Retrofit, Spares and ser-vicesforexistingS&SMakeVCBs.
• MAPS Kalpakkam – Retrofitting of HBBABCB to S&S VCB Indoor Type – 6.6KV,2500A,40KA/3Sec.
• RetrofittingofCFLSF6 toS&SVCBIndoorType–7.2KV,2500A,40KA/3Sec.
• Replacement of existing HG36 with newOFVP36.
• APEPDCLVIZAG–retrofitof12KVoutdoorABBmechanismwithS&Smechanism.
• APEPDCL VIZAG – Retrofitting spares ofvariousmake’s 11KV&33KVoutdoorVCBpoles(onetoonereplacement).
REGION CIRCUIT BREAKERCHANNEL PARTNER ADDRESS LOCATION NAME MOBILE No E-mail ID
NORTH IPPL GLOBAL
T1/113,AssotechBusinessCresterra,PlotNo.22,Sector135,Expressway,Noida,India NOIDA Mr.GSGoel 9893391977 [email protected]
STERLING SYSTEMSSterlingSystem&Controls,S-35,ChambalIndustrialArea,Oppo.MultimetalsLtd.NearPunjabElectrical,Kota(Raj.)India-324003.
KOTA Mr.PuneetGupta 9929410118 [email protected]
CONSULTANT 2524A/Obliquesector-3,Ballabgarh,Faridabad,Haryana-121005
FARIDABAD Mr.MohanSinghBist 7358274111 [email protected]
SOUTH GALAXY MARKETING BlockNo.52,majesticcolony,TirupurKumaranStreet,Valasaravakkam,Chennai-87
CHENNAI Mr.Srinivasan 9282176174 [email protected]
INEL POWER New,No.103,DharumanSt,WestJafferkhanpet,Chennai,TamilNadu600083
CHENNAI Mr.RajendraPrasad 9841055783 [email protected]
BRINDA ELECTRICALS 112,SriColony(West),3rdStreet,NeredmetCrossRoad,NeredmetCrossRoad,Hyderabad,Telangana500056HYDERABAD Mr.Srikanth 9848131584 [email protected]
WEST SUNIRMAL ENGINEERS RaneNagarRd,GaneshColony,Chetananagar,RaneNagar,Nashik,Maharashtra422501
NASHIK Mr.BharatkumarWagh 8511734909 [email protected]
KK SALES CORPORATION 220,ParadiseComplex,BehindYashkamalBuilding,NearKalaGhoda,Sarod,Sayajiganj,Vadodara,GujaratVADODARA Mr.I.K.Pandya 9824076410 [email protected]
EAST VINGIRI POWERTECH 234,SantoshpurAvenue,Santoshpur,Kolkata-700075
KOLKATTA Mr.KASingh 9433229494 [email protected]
CONSULTANT Kolkatta KOLKATTA Mr.NabaDas 9748743693 [email protected]
11
Particulars Problem Faced
Challenges Faced
Solution Provided
MOCBTOVCB •Increaseinnumberofacci-dents.•Increaseinnumberofmain-tenancework.•Increaseofdamageduetopowerfailure.
•Deterioration.•Increaseinthemaintenancecost.•Nosparepartsareavailable.•Introductionofnewinformationsystem.
•Improvementinreliabilityofpowersupply.•Savingofrunningcost,maintenanceworkanddura-tion.•Preventionofpowerfailureaccidentsbyadoptingacom-municationnetwork.•Minimumornodowntime.
12
1. RETROFITTINGOFNGEFMOCBTOS&SVCBINDOORTYPE-12KV,630A,25KA/3SEC–ATIGCARKALPAKKAM
2. RETROFITTINGOFJYOTIMOCBTOS&SVCBINDOORTYPE-12KV,1250A,25KA/3SEC–ATIGCARKALPAKKAM
3. RETROFITTINGOFHBBABCBTOS&SVCBINDOORTYPE-6.6KV,2500A,40KA/3SEC–ATMAPSKALPAKKAM
4. RETROFITTINGOFCGLSF6TOS&SVCBINDOORTYPE-7.2KV,2500A,40KA/3SEC5. RETROFITOF12KVOUTDOORABBMECHANISMWITHS&SMECHANISM–AT
APEPDCLVIZAG
MV Circuit Breakers - Case Studies
13
Automation - R3 ServicesOFFERINGS:• Relaycommissioningandtesting• Relaycoordination• Protectionarchitectconsultancy• Powersystemautomationservice• IndustrialAutomationservices• Machineautomationservice• FactoryautomationinLVsideofelectricity
delivery• Protectiondesignservices• EngineeringservicesRetrofit, Refurbishment, Rejenuvation:We offer retrofit of all types of Protective Re-lays by completely re-working the ProtectinSchemes, aesthetically re-designing the panellayout,re-wiring,testing,andcommissioning.
Automation Services:WithourvastexperienceinAutomation,weofferinnovative solutions for Industrial applicationsby offering PLC based automation systems toeffectivelyautomateandcontroltheprocesstoincrease theefficiencyof thesystem.Ourser-vices includean in-depth studyof the system,assessmentofthepresentsystem,engineeringthenewdesiredAutomationSystem,implemen-tationofthenewautomationsystem,program-ming,testing,andcommissioning.WearealsoworkingtogetherwithM/SSchnei-derElectricforAutomationSystems.
Engineering services:Ourdedicatedteamofengineerswithanenor-mous amount of hands-on experience in thefieldofProtection,Control,andAutomationhasthecapability tocompletelydotheengineeringof complex Control and Automation Systems.Ourdesignsofferworld-class time-testedsolu-tionsfollowingInternationalstandardsfordesignandquality.
Warranty and non-warranty services:We takeupAnnualMaintenanceContracts forControlandAutomationServices.Routinetest-ingofRelays,Calibration,andcertificationcanbeundertaken.Wealsoofferhot-stand-byinven-toryofsparestocatertotheemergencybreak-downrequirements.Ourtrainedengineersswift-lyrespondtothemaintenancecallsandresolvetheissueseffectivelattheearliest.
Training and assessment:Customers can immensely benefit by trainingtheirengineersintheEngineering,Schemede-signs, Operation, and maintenance of ControlandAutomationSystems.Ourtrainingmodulesdesignedwithcontentfromdecadesoffieldex-perienceanddeliveredbytrainedengineersof-fertremendousvalue.Wealsooffercustomizedon-site training programs for our customers attheir premises with training programmes cus-tomizedfortheirspecificrequirements
14
Modernization of HV substation:
Themodernizationofhigh-voltagesubstationsisoneofourmaindirections. Weoffertoourclients:• Projectsdesignanddeliveryofequipment.• Mounting of new HV equipment – discon-
nectors,circuitbreakers.Productionandde-liveryofrelevantconcretesupportstructuresforthem,accordingtoprojectrequirements;
• Layingandconnectionofnewcontrolcablesandwiring.
• Mountingandconnectionofcommandandcontrolcabinets.
• Electricalmeasurements, testingand com-missioning.
• Refurbishment, renovation, retrofitting andmanufacturing and delivery of spare partsforminimumoilhighvoltagebreakers typeMMO110kV.
OurnetworkofServicePartnersprovidescom-pletecapabilityofallactivitiesforHVSubstationmodernization. We offer engineering, execu-tion, installationandcommissioningofall sys-tems involved in themodernization of theHVSubstations.
Our present Service Network for Modernisa-tion of HV Substations includes:
SouthernRegion:INEL Power System Engineers (P) Ltd103,DharumanStreet,Jafferkhanpet,Chennai-600083,TamilNadu,India.https://www.inelpse.com/
CentralRegion:Sunirmal EngineersRaneNagarRd,GaneshColony,Chetananagar,RaneNagar,Nashik,Maharashtra422501
NorthernRegion:Sterling System & Controls,S-35, ChambalIndustrialArea,Oppo. Multimetals Ltd. Near Punjab Electri-cal,Kota(Raj.)India-324003. Our Automation Service Partner:
Pothigai Power Solutions Pvt Ltd.,3C,PothigaiRoad,GandhiNagar,Urapakkam,Chennai-603210http://www.pothigai-power.com
Why S&S ?
15
ABOUT US:S&SPowerSwitchgearLtd(S&S)wasestablished in1975 inTechnicalcollaborationwithBrushFusegear, UK formanufacture of Fuses. S&S introducedHigh VoltageDisconnecting Switchesin1978collaboratingwithSouthwales,UK.S&SindigenouslydevelopedOutdoorPorcelainCladVacuumCircuitBreakerandintroducedforthefirsttimeinIndianmarket.S&Sbecametheindus-tryleaderinthecountryinsalesandmarketsharesintheMediumVoltageandHighVoltageDis-connectorIndustry.Thefactoryhasstate-of-the-artmanufacturingfacilitiestoproducehighqualityequipment.AworldclassFactoryinPuducherryhousesallthirdgenerationequipmentandprovideslowcosthighqualitymanufacturingfacilityforDisconnectors.TheproductsofS&Shavebeen tested in internationally renownedLaboratories-KemaHolland,CESI-Italy,andCERDA,France.ThetypetestconductedincludesIceBreakingtest.SpecialtestconductedforHighAltitudeinstallationoftheseDisconnectors.S&ScontinuesitssuccessmarchbackedbyastrongteamofqualityEngineersandafullyequippedinhouseResearchandDevel-opmentdepartment.
OUR COMPANY:S&SistheonlycompanyinIndiatohavesoldmorethan18,000nosofCircuitBreakersandmorethan25,000nosofDisconnectorstoallmajorUtilitiesinIndiaandWorldwide.RepeatedordersfromesteemedcustomersprovetheirconfidencereposedonS&Sproductsandtimelydelivery.S&Scontinuesitsthrustandintroducesawiderangeofproductstomeetthecustomer’schangingneedswhicharetheircorestrengthinstayingaheadsuccessfullyinthecompetitivemarket.CarefulselectionofautomaticandsemiautomaticmachinesenablesS&Stomanufacturequalityproducts
WHY US:• Qualityproductsandservices.• Timelyexecutionofprojects.• Completeaftersalesservices.• Providecustomizedsolutions.• Flexibilitytoadapttocustomerneeds.• Longtermexperienceindisconnectors.• Regularupgradationofservices.
CORE VALUES:• Committedtoachievesuccessfocusingon
customersatisfaction.• Deliveringvalue.• Excellenceinoperations.• Provisionofsuitableplatformforbestelec-
tricaldeals.• Qualityfocusedteam.
VISION:
To be recognized as preferred Switchgear & P&C Solutions Company to our partners.
MEASUREDBY;1.Customerssay:“WewanttodomorebusinesswithS&SPower.”2.Shareholderssay:``S&SPowerisoneofmybestinvestments.”3.Employeessay:“IamproudtobeapartofS&SPower.”4.SuppliersSay:“S&SPowerisoneofourmostvaluedcustomers.”5.PublicAuthoritiessay:“S&SPowerisCompliant&Responsible.”
MISSION:• Transformintoabestcostbusinessmodelcreatingsocialimpacts.• Achievesignificantmarketshareintargetmarketswithcommercialintensity,alliance&service
focus.• Expandspecificproductsportfoliofortargetmarketandsecurehighrevenueperproduct.• Modernizemanagement practice, its tools, manufacturing technology & systems, innovation
toolsandtalentdevelopmentprograms.• Grow3X+withdoubledigitprofitandpositivecashinfiveyears.
© S&S Power India Limited. February 2021 ver 0.316
CERTIFICATIONS OF OUR COMPANIES:
◊ ACRASTYLEPOWER(INDIA)LIMITEDhasbeencertifiedby the bodyofTAVSUDSouthAsiaPrivate limitedhas implementedaqualitymanagement system inaccordancewith ISO9001:2015forthescopeof:
◊ Engineering design andmanufacturing of control, relay and protection solutions and LV/MVSwitchgearforgeneration,transmission&distributioninthepowersector.
◊ S&SPOWERSWITCHGEAREQUIPMENTLIMITED(PUDUCHERRY)hasbeencertifiedbythebodyofTUVSUDSouthAsiaPrivatelimitedhasimplementedaqualitymanagementsysteminaccordancewithISO9001:2015forthescopeof:
◊ Manufacturer ofHighVoltageDisconnecting switches from33KV to800KVwithandwithoutearthswitch.
◊ S&SPOWERSWITCHGEAREQUIPMENTLIMITED(CHENNAI)hasbeencertifiedbythebodyofTAVSUDSouthAsiaPrivatelimitedhasimplementedaqualitymanagementsysteminaccor-dancewithISO9001:2015forthescopeof:
◊ Design ofHighVoltageDisconnecting switches from33KV to 800KVwith andwithout earthswitch.
◊ S&S POWERSWITCHGEAR LIMITED has been certified by the body of TAV SUD SouthAsiaPrivate limitedhas implementedaqualitymanagement system inaccordancewith ISO9001:2015forthescopeof:
◊ EngineeringDesign,Manufacturingandsalesofindoor/outdoorMVSwitchgearfrom3.3KVto36KV.
◊ ACRASTYLEPOWER (INDIA)LIMITEDhasbeen certifiedby the bodyofTAVSUDSouthAsiaPrivate limitedhas implementedaqualitymanagement system inaccordancewith ISO9001:2015forthescopeof:
◊ EngineeringDesign andManufacturing of control, relay and protection solutions and LV/MVSwitchgearforgeneration,Transmission&Distributioninpowersector.
◊ S&SPoweristheonlydisconnectormanufacturingcompanycertifiedbyENA(EnergyNetworkAssociation)
S&S Power Switchgear LimitedRegd.Office&Works:PlotNo:14,CMDAIndustrialArea-II,ChithamanurVillage,MaraimalaiNagar-603209,Kancheepuram-Dist,TamilNadu,IndiaTel:04447431625Email:[email protected]:www.sspower.com
Acrastyle Limited (UK)NorthLonsdaleRoadUlverstonCumbriaLA129EB,UnitedKingdomTel:+44-1229-583232Fax:+44-1229-582586Web:www.acrastyle.co.uk
S&S Power Switchgear Equipment LimitedNo.4EVRstreet,Sedarapet,Puducherry–605111,IndiaTel:+91-413-2677122Fax:+91-413-2677374Web:www.sspower.com
Acrastyle Power (India) LimitedRegd.Office&Works:PlotNo.14,CMDAIndustrialArea-PartII,ChithamanurVillage,MaraimalaiNagar-603209,Kancheepuram-DistTel:+91-44-47431626Email:[email protected]:www.acrastyle.com
OurAddresses: