qs sensor module (qsm) spec 369242 - lutron · pdf file®specifica al p age job name: job...
TRANSCRIPT
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 1 12.22.15
QS Sensor ModuleThe QS Sensor Module (QSM) is a ceiling-mounted device that integrates LutronR wireless and wired sensors and controls through the QS communication link to Energi Savr NodeTM (ESN) units, GRAFIK EyeR QS control units, QuantumR systems, SivoiaR QS shades / draperies, and myRoomT control modules.
Features•UsesClearConnectR RF Technology for communication
with Radio Powr SavrTM occupancy sensors, Radio Powr SavrT daylight sensors, and PicoR wireless controllers.
•QSMconnectstofourLutronR wired sensors or controls—occupancy sensors, daylight sensors, EcoSystemR infrared (IR) receivers, or EcoSystemR wallstations. Does not apply to wireless only models.
•PoweredbytheQSlink—nolinevoltageconnectionsarerequired.
•ContactLutronforcompatibilitydetailswiththeQuantumR system.
•CompatiblewiththeentireESN product family: — Allows LutronR wired occupancy sensors, daylight
sensors, EcoSystemR wall stations, EcoSystemR IR receivers, PicoR wireless controllers, Radio Powr SavrT wireless occupancy sensors and daylight sensors to control ESN units.
•CompatiblewithGRAFIK EyeR QS control units. — GRAFIK EyeR QS control unit models starting
with QSGR.
— Allows LutronR wired or Radio Powr SavrT wireless occupancy sensors and daylight sensors linked to a QSM to control the GRAFIK EyeR QS control unit.
—ContactLutronforcompatibilitywithPicoR wireless controllers, EcoSystemR wallstations, and EcoSystemR infrared (IR) receivers.
•CompatiblewithSivoiaR QS shades / draperies. — Allows PicoR wireless controllers to control SivoiaR QS
shades / draperies (QSM models with wireless inputs only).
•CompatiblewithmyRoomT power modules. — Allows Lutron wired & wireless occupancy sensors to
control power modules. — Allows PicoR wireless controls to control power
modules.
System Example
LUTRON
LUTRON
QS link
ControlPower120-277 V~
Emergency Contact Closure
Input
Programmable Contact Closure Input
Wireless Communication
Wired Daylight Sensors (up to 4) 2
Wired Daylight Sensors (up to 4) 1,2
EcoSystemR Digital Links (upto64ballastseach)
Wired Occupancy Sensors (up to 4)
Wired Occupancy Sensors (up to 4) 1
Wired EcoSystemR Wallstation or IR receivers (up to 4)
Wired EcoSystemR Wallstation or IR receivers (up to 4) 1
QSM
IR Transmitter
IR TransmitterOR OR
OR OR
seeTouchR QS Wallstation
Radio Powr SavrTM Occupancy Sensor (up to 10 per QSM)
Radio Powr SavrT Daylight Sensor (up to 10 per QSM)
Pico® Wireless Controller(upto10 per QSM)
Apple, iPhone, and iPod touch are trademarks of AppleInc.,registeredintheU.S.andothercountries.
Notes: 1 Upto4wiredinputstotal(ofanytype).2 Upto16wireddaylightsensorstotal
per EcoSystemR link.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 2 12.22.15
ModelsFrequency/ChannelCode* NumberofWiredInputs
QSMX-XW-X
Frequency/ChannelCode*2—431.5-436.6MHz U.S.A.,CanadaandMexico3—868.1-869.8MHz EuropeanUnionandUnitedArabEmirates4—868.1-868.5MHz SingaporeandChina5—865.5 - 866.5 MHz India7—433.0 - 434.7 MHz Hong KongX—No RF
*ContactLutronforfrequency/channelcodecompatibilitywith yourparticulargeographicregionifitisnotindicatedabove.
NumberofWiredInputs4—4X—None
Mounting MethodC—CeilingMount J—JunctionBoxCeilingMount
Availability/CompatibilityRefertothechartbelowtodetermineQSMmodelavailabilityandcompatibilitywithdifferentsensormodels.
LutronR Radio Powr SavrT
Models Available Occupancy / Vacancy Sensors
Daylight Sensors *
LutronR PicoR Wireless Controllers
QSM2-4W-C QSM2-XW-CQSM2-4W-JQSM2-XW-J
LRF2-OCRB-P, LRF2-OHLB-P, LRF2-OKLB-P, LRF2-OWLB-P, LRF2-VHLB-P, LRF2-VKLB-P, LRF2-VWLB-P, LRF2-OCR2B-WH, LRF2-VCR2B-WH
LRF2-DCRB MRF2-3BRL, MRF2-3B, MRF2-2BRL, MRF2-2B, QSR4P-3R, PJ-2B-Gxx-xxx, PJ-2BRL-Gxx-xxx PJ-3B-Gxx-xxx PJ-3BRL-Gx-xxx
QSM3-4W-C QSM3-XW-C
LRF3-OCRB-P LRF3-DCRB QSRKP-2, QSRKP-2R, QSRKP-3R
QSM4-4W-C QSM4-XW-C
LRF4-OCRB-P LRF4-DCRB QSRMP-2, QSRMP-2R, QSRMP-3R
QSM5-XW-C LRF5-OCRB-P LRF5-DCRB QSRNP-2, QSRNP-2R, QSRNP-3, QSRNP-3R
QSM7-4W-C QSM7-XW-C
LRF7-OCR2B-P LRF7-DCRB QSRQP-2, QSRQP-2R QSRQP-3, QSRQP-3R
QSMX-4W-C N/A N/A N/A
Mounting Method
*Daylightsensorscan'tbeusedaspartofmyRoomT solutions.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 3 12.22.15
Specifications
QS Sensor Module (QSM)Power
•24–36V •Currentdraw: max400mA(modelswithwiredinput)
max100mA(modelswithoutwiredinput)•PowerDrawUnits:(PDU) RefertotheQSLinkPowerDrawUnitsspecificationsubmittal(LutronR P/N 369405) for information concerning PDUsontheQSLink.UseonlyLutronR approved power sources.
•10-yearpowerfailurememory:restoressettingsand programming after power interruption.
Regulatory•LutronR Quality Systems registered to ISO 9001.2008.
QSM2 –•cULUSListed(USAandCanada).•FCCCompliant.ComplieswiththelimitsforaClassBdigitaldevice,persuanttoPart15oftheFCCRules(USA).
•ICCertified.(Canada).•SCTCertified(Mexico).
QSM3 –•CEMarked(EuropeanUnion).•TRATypeApproved(UnitedArabEmirates).
QSM5 –•WPCTypeApproved(India).
QSM7 –•FCCCompliant.ComplieswiththelimitsforaClassBdigitaldevice,pursuanttoPart15oftheFCCRules(USA).
Environment•AmbientTemperatureOperatingRange:32ºFto104ºF (0ºCto40ºC).
•Relativehumidity:lessthan90%non-condensing.•Forindooruseonly.
Terminals•Inputwiring:22AWGto12AWG(0.5mm2 to 4.0 mm2)•QSlinkwiring:22AWGto12AWG(0.5mm2 to 4.0 mm2)
Mounting•QSM units shouldbemountedinthemiddleofnon-metalceilingtileordrywall,visiblefrominsidethespace.
•InstallationnearmetalotherthanaJunctionBoxmayreduce RF range.
Wireless Communication (models with wireless inputs only)
•RFRange:60ft(18m)lineofsight,or30ft(9m)through typical construction materials.
•Toensureoptimalwirelessrange,installtheQSMintheceilinginavisiblepositionfrominsidethespace.
•LutronR Radio Powr SavrTM Occupancy sensor (up to 10)
•LutronR Radio Powr SavrT daylight sensor (up to 10)•LutronR PicoR wireless controllers (up to 10)
Wired Inputs
•Thereare4universalwiredinputs.Eachinputcanaccept one of the following:- LutronR EcoSystemR wallstations- LutronR occupancy sensors (LOS- series)- LutronR daylightsensors(EC-DIR-series)- LutronR EcoSystemRinfrared(IR)receivers(EC-IR,EC-DIR-series)
- LutronR Wired PicoR Controls•UseofboththeinfraredreceiveranddaylightsensorontheEC-DIR-seriessensorsisconsideredtwowired inputs on a QSM
•Maximumwiringdistance=150ft(46m)•Onlywired(LOS-series)andwirelessoccupancysensorsmaybeusedinmyRoomT; no EcosystemR wallstations, daylight sensors, EcosystemR IR receivers or wired PicoR controls
QS Link Limits
•The QS link can have up to 100 devices.•EachQSMcountsas1devicetowardsthe
100 device limit.•EachQSMdraws3PowerDrawUnits(PDUs)on
the QS link. •WiredsensorsaddtothePDUdrawofaQSM.RefertotheQSLinkPowerDrawUnitsspecificationsubmittal(LutronR P/N 369405) for information concerningPDUs.
•QSlinkmaximumwirerunlengthis2000ft(610m).•Seethecommercialsystemrulesspec(P/N369821)forsystemspecificlimitations.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 4 12.22.15
Mechanical Dimensions (All Models)Front View Side View Back View
(QSM2-4W-Cshown)
Mounted (-C Models) Mounted (-J Models)
1.17 in (30 mm)
Ceilingthicknessrangefor-CmodelsMin 0.30 in (8 mm) to Max1.20in(30mm)
Ceiling Ceiling
4.04 in (103 mm)
UseappropriateMudRingforceilingtilethickness
UseMudRingwithholespacingshownbelow.(Mud Ring not included with any QSM models)
Ceiling Ceiling
2.75 in (70 mm)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 5 12.22.15
Wiring: QS Link and Wired Inputs1
Input 11,2,3
Daylight sensor
EcoSystemR infrared (IR) receiver
Occupancy sensor
EcoSystemR wallstation or PicoRWiredControls
22 AWG to 14 AWG (0.5 mm2 to 2.0 mm2)
Lutron®CableStandard:C-CBL-522S-WH-1
Plenum:C-PCBL-522S-CLMax.WiredInputwire
length 150 ft (46 m)per input
22 AWG to 14 AWG (0.5 mm2 to 2.0 mm2) Lutron®CableStandard:C-CBL-522S-WH-1Plenum:C-PCBL-522S-CLMax.WiredInputwire length 150 ft (46 m)per input
22 AWG to 14 AWG (0.5 mm2 to 2.0 mm2) Max.QSlinkwire length 2000 ft (610 m)
Input 31,2
Input 21,2
QS Link
Input 41,2
Com
mon
V
+
MUX
MUX
Red
+20
–20V
+20
–20V
+20
–20V
+20
–20V
Bla
ckCOM–Com
mon
COM–Com
mon
COM–Com
mon
COM–Com
mon
Yello
wS1 –Signa
lS2–Signa
l
S4–Signa
lS3–Signa
lB
lue
or G
ray
Bla
ck
Red
Red
Red
Bla
ck
Bla
ck
Whi
te
Whi
te
1 Only on QSM models with wired inputs.2 Note: Forreferenceonly.Eachinputisuniversalandcanacceptanyoftheinputsshownabove.3OnlydaylightsensorsignalconnectedtoQSMshownabove.UseofIRsignalcountsasan
additional input on the QSM.
Back View (QSM2-4W-Cshown)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 6 12.22.15
Wiring: Device PowerSingle QSM powered by an ESN unit
Multiple QSMs powered by an ESN unit and a QS Link Power SupplyNote:AQSLinkPowerSupplymaybenecessaryifPDUsrequiredbyQSMsexceedavailablePDUsfromthedevice supplying power.
ESN unit
ESN unit
QSM QSM
COM
COM
COM
COM
COM
MUX
MUX
MUX
MUX
MUX
V+
V+
V+
V+
MUX
MUX
MUX
MUX
MUX
ESN unit
QSM A
The ESN unit powers QSM A; no terminal 2 connection betweenQSMAandQSLink Power Supply
The QS Link Power Supply powersQSMBandC;
QS Link Power Supply
QSM B
QSMC
MUXand_ occupy terminals 2 and 3 on the QS Link Power Supply.