pvc - renergypower.comour pvc batteries obtained iec 60896-21 2004iec 60896-22 2004 and...

5
PVC batteries www.renergypower.com

Upload: others

Post on 23-Jan-2021

9 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: pvc - renergypower.comOur PVC batteries obtained IEC 60896-21 2004IEC 60896-22 2004 and internationally recognised certificates and passed successfully all the international tests

PVC batteries

www.renergypower.com

Page 2: pvc - renergypower.comOur PVC batteries obtained IEC 60896-21 2004IEC 60896-22 2004 and internationally recognised certificates and passed successfully all the international tests

PVC is a Maintenance free and easy to use. Contemporary advanced technology research and development of new high-performance batteries, It can be widely used in solar energy, wind energy, telecommunication systems,off-grid systems ,UPS and other fields. The designed life for the battery could be twelve years up for float use.

Test and certificates:Our PVC batteries obtained IEC 60896-21 2004 and IEC 60896-22 2004 internationally recognised certificates and passed successfully all the international tests by a third party organisation.

www.renergypower.com

APPLICATION

PVC

UPSWind energy

Off-grid systemsTelecommunication systems

Solar energy

Page 3: pvc - renergypower.comOur PVC batteries obtained IEC 60896-21 2004IEC 60896-22 2004 and internationally recognised certificates and passed successfully all the international tests

www.renergypower.com

PERFORMANCE CHARACTERISTICS

0

2.5

5

7.5

10

0-10 10 20 30 40 50 60

Temperature (ºC)

Serv

ice

Life

(yea

rs)

Temperature and Service life

40

60

80

100

120

-30-40 -20 -10 0 10 20 30 40 50 60

Temperature (ºC)

Cap

acit

y (%

C10

)

Temperature and discharge capacity

0.01 2 4 0.1 0.2 0.5 2 5 10 5020

Dischrage Time (h)

Term

inal

Vol

tage

(V)

Discharge Characteristics at Various Rates (250C/770F)

1.36

1.52

1.68

1.84

2.00

2.16

0.5HR1HR

3HR 5HR8HR

10HR 20HR

0

40

60

80

100

20 4 6 8 10 12 14 16 18 20

Effe

ctiv

e ca

paci

ty (%

)

Self Discharge Parameters Characteristics

400C 300C 200C

50C

Constant-potential Charge

Time (h)

1.80

2.00

1.90

2.10

2.20

2.30

25

0

50

75

100

2.40

0.3

0

0.6

0.9

1.2

1.5

1.8

40 8 12 16 24 32 4840

VoltageCurrent(V/cell)(I10A) Capacity (%)

Charged Current

Battery Voltage

Charge Quanity

50% DOD

100% DOD

0%10%20%30%40%50%60%70%80%90%

100%

5000 1000 1500 2000 2500 3000 3500

Number of Cycles (times)

DO

D (%

)

Cycle Service Life (250C/770F)

Page 4: pvc - renergypower.comOur PVC batteries obtained IEC 60896-21 2004IEC 60896-22 2004 and internationally recognised certificates and passed successfully all the international tests

www.renergypower.com

TECHNICAL SPECIFICATION

PVC 12V- 100Ah

Discharge:-45°C~50°C Charge: -20°C~45°C Storage: -30°C~40°C

Float Charge:13.4V-13.7V Average Charge: 14.1-14.4V

100%DOD 840 times50%DOD 2130 times30%DOD 2359 times

105 % @ 40°C85 % @ 0°C60 % @ -20°C

Float TemperatureCompensation Coefficient-3mV/Cell°C Equalization TemperatureCompensation Coefficient- 4mV/Cell°C

Using Temperature Charge Voltage (25°C)TemperatureCompensationCoefficient(25°C)

Cycle lifeCapacity Affectedby Temperature

Rated Voltage Capacity(10hr,1.8 0V/Cell)

Weight Max Discharge Current

Max Charge Current

Self- Discharge

(25°C)

Recommended Using

Temperature

Cover Material Separator

12V 100Ah 37Kg 30I 10A (3min) ≤0.25C10 <3%/month 15°C~25°C ABS PVC

1.7 53.10

1.75 52.04

1.8 51.00

1.85 48.96

1.9 47.01

1.95 44.94

24.14

23.89

23.67

23.53

23.33

22.86

16.13

15.85

15.60

15.30

15.07

14.76

10.41

10.26

10.00

9.59

9.39

8.87

5.38

5.25

5.13

4.88

4.79

4.46

2.26

2.17

2.10

2.01

1.95

1.81

1.23

1.15

1.10

1.03

0.99

0.94

1.09

1.01

0.95

0.89

0.85

0.81

0.57

0.53

0.51

0.46

0.43

0.41

Constant current discharge coefficient (25°C,A)

Terminal Voltage(v/Cell)

1H 3H 5H 10H 20H 50H 100H 120H 240H

PVC 12V- 150Ah

Rated Voltage Capacity(10hr,1.8 0V/Cell)

Weight Max Discharge Current

Max Charge Current

Self- Discharge

(25°C)

Recommended Using

Temperature

Cover Material Separator

12V 150Ah 57,5Kg 30I 10A (3min) ≤0.25C10 <3%/month 15°C~25°C ABS PVC

Page 5: pvc - renergypower.comOur PVC batteries obtained IEC 60896-21 2004IEC 60896-22 2004 and internationally recognised certificates and passed successfully all the international tests

PVC 12V- 200Ah

1.7

1.75

1.8

1.85

1.9

1.95

79.65

78.06

76.50

73.44

70.51

67.41

36.21

35.84

35.50

35.30

34.99

34.29

24.20

23.77

23.77

22.95

22.61

22.14

15.61

15.39

15.00

14.38

14.08

13.30

8.06

7.88

7.69

7.31

7.19

6.69

3.39

3.26

3.15

3.02

2.93

2.72

1.84

1.72

1.65

1.54

1.49

1.41

1.63

1.52

1.42

1.33

1.27

1.21

0.86

0.80

0.76

0.69

0.65

0.62

Constant current discharge coefficient (25°C,A)

Terminal Voltage(v/Cell)

1H 3H 5H 10H 20H 50H 100H 120H 240H

Rated Voltage Capacity(10hr,1.8 0V/Cell)

Weight Max Discharge Current

Max Charge Current

Self- Discharge

(25°C)

Recommended Using

Temperature

Cover Material Separator

12V 200Ah 72Kg 30I 10A (3min) ≤0.25C10 <3%/month 15°C~25°C ABS PVC

1.7

1.75

1.8

1.85

1.9

1.95

106.20

104.08

102.00

97.92

94.01

89.88

48.28

47.79

47.33

47.07

46.65

45.72

32.27

31.69

31.20

30.60

30.15

29.52

20.81

20.52

20.00

19.17

18.77

17.73

10.75

10.50

10.25

9.75

9.58

8.92

4.52

4.35

4.20

4.03

3.91

3.63

2.45

2.29

2.20

2.05

1.99

1.88

2.17

2.03

1.89

1.77

1.69

1.61

1.15

1.07

1.01

0.92

0.87

0.83

Constant current discharge coefficient (25°C,A)

Terminal Voltage(v/Cell)

1H 3H 5H 10H 20H 50H 100H 120H 240H

[email protected]

(0044) 1908920612

500 Avebury Boulevard, Milton Keynes,Buckinghamshire, MK9 2BE

PVC 12V- 150Ah