NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the Alliance for Sustainable Energy, LLC. PV System Codes and Standard Northwest Solar Communities Distributed Generation Interconnection Workshops Michael Sheehan, Michael Coddington July, 2014

Upload: vodat

Post on 31-Jan-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the Alliance for Sustainable Energy, LLC.

PV System Codes and Standard

Northwest Solar Communities

Distributed Generation Interconnection Workshops

Michael Sheehan,

Michael Coddington

July, 2014

Page 2: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Agenda NEC Codes and Standards

• NEC Codes and Standards

• Inverters History Functions

• NEC New and Pending Changes

• Technology Trends

• Q&A and Parking Lot Issues

Page 3: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Organization and Standards That Cover

Interconnection

Page 4: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Germans Solar

Page 5: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Types of PV System

• Grid-Tie.

• Grid-Tie with Battery Backup.

• Stand Alone.

Page 6: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Components

Page 7: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Typical Net Meter PV System

Page 8: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Wiring Diagram

Page 9: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC 2014 Adoption

Page 10: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

State Full Code Name Edition

California NFPA 70®: National Electrical Code® (NEC®) 2008 Edition

Idaho NFPA 70®: National Electrical Code® (NEC®) 2008 Edition

Wyoming NFPA 70®: National Electrical Code® (NEC®) 2011 Edition

Utah NFPA 70®: National Electrical Code® (NEC®)

2008 Edition

Effective 7/1/2012. It should be noted however

that Utah recognizes and adopts the electrical

provisions of the International Residential Code.

That means that the NEC does not apply to

residences covered by the IRC: one and two-

family dwellings and townhouses.

Oregon NFPA 70®: National Electrical Code® (NEC®) 2011 Edition

Washington NFPA 70®: National Electrical Code® (NEC®) 2008 Edition

Washington 2014

The 2014 National Electrical Code, with

Washington State amendments, becomes

effective on July 1, 2014

NEC Adoption Northwest States

Page 11: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Sections Applicable to PV Systems

• Article 110: Requirements for Electrical Installations

• Chapter 2: Wiring and protection

- Most of the chapter—especially

- Article 250 Grounding

• Chapter 3: Wiring Methods and Materials

- Most of the chapter especially

- Article 300: Wiring Methods

- Article 310: Conductors and General Wiring

• Article 480: Storage of Batteries

• Article 690: Solar Photovoltaic Systems

Page 12: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Article 690:

Solar Photovoltaic Systems

I. General (definitions, installation)II. Circuit Requirements (sizing, protection) III. Disconnect Means (switches, breakers)IV. Wiring methods (connectors)V. Grounding (array, equipment) VI. Markings (ratings, polarity, identification)VII. Connection to Other SourcesVIII. Storage batteriesIX. Systems over 600 volts

Page 13: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Article 690:

Solar Photovoltaic Systems

I. General (definitions, installation)- 690.1 Scope – PV systems (only)- 690.2 Definitions– PV Output Circuit, Inverter Circuit Input- 690.3 “Wherever the requirements of other articles of the Code and Article 690 differ, the requirements of Article 690 shall apply”

- 690.4 Installation “Equipment” shall be identified and listed

for the application”

- 690.5 Ground-Fault Protection– to reduce fire hazards- 690.6 AC Module – dc wiring is considered internal

Page 14: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Electrical Equipment Listing

• Authority Having Jurisdiction (AHJ’s) generally require

listing for components and electrical hardware

• Some components available for PV systems may not have

applicable or any listing.

• Recognized testing laboratories include:

• UL

• CSA

• ETL Semko (Intertek)

• TUV

Page 15: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Article 690:

Solar Photovoltaic Systems

II. Circuit Requirements (sizing, protection) - 690.7 Maximum voltage– Table 690.7 and manufactures data. Max. 600 Vdc for residential

- 690.8 Circuit Sizing and Current• 690.8(A) Max current = rated Isc x 1.25 = Max

• 690.8(B) Min ampacity and overcurrent = Imax x 1.25

- 690.9 Overcurrent Protection

• 690.9(A) Generally required on all source circuits – exception:

a.) no back feed b.) total Imax less than conductor ampacity.

- 690.10 Stand-Alone Systems

• Inverter output need only meet demand.

• No multi-wire circuits on 120 V inverters.

Page 16: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Article 690:

Solar Photovoltaic Systems

III. Disconnect Means (Switches, Breakers) - 690.13 Need to disconnect all conductors connected to building. No Disconnect in Ground conductor.

- 690.14 Location—details and options

- 690.17 Switch or Circuit Breaker – Warning sign when line and load energized in open position.

Page 17: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Commercial PV System

Page 18: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Article 690:

Solar Photovoltaic Systems

IV. Wiring Methods- 690.31(A) FPN PV modules get HOT! - 690.31 – single conductors outside conduit allowed in array- Table 690.31 – temperature correction must be applied to

conductors- 690.33 -- requirements for connectors- 690.35 – Underground PV Power Systems

Page 19: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC Article 690:

Solar Photovoltaic Systems

V. Grounding (system, equipment)

- 690.41 – System Grounding

● Over 50 Vdc must be grounded or comply with 690.35

- 690.42 – Point of System Grounding Connection—one point at GFP

device

- 690.43 – Equipment Grounding—metal likely to become energized

must be grounded – listed equipment can be used to bond

modules to support structure

Page 20: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Systems and the NEC

Articles 690 addresses safety standards for

the installation of PV systems

Equipment/System NEC Article

Generators 445

Solar Photovoltaic Systems 690

Fuel Cells 692

Wind Electric Systems 694

Emergency Systems 700

Legally required Standby Systems 701

Optional Standby Systems 702

Page 21: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

New/Pending Code Requirements

NEC 2008•No Arc-Fault Requirement

•The Danger Zone

NEC 2011• Arc-Fault (690.11)

• Fuse Servicing Disconnects (690.16)

NEC 2014• Grounded Conductor Ground Fault (690.5)

•Rapid Shutdown (690.12)

Page 22: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

What is Arc-Fault?

Page 23: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

690.11 Arc-Fault Circuit Protection (DC)

1) The system shall detect and interrupt arcing faults resulting from a failure in the

intended continuity of a conductor, connection, module, or other system component

in the dc PV source and dc PV output circuits.

2) The system shall require that the disabled or disconnected equipment be manually

restarted.

3) The system shall have an annunciator that provides a visual indication that the circuit

interrupter has operated. This indication shall not reset automatically

Photovoltaic Systems with dc source circuits, dc output circuits, or both,

operating at a PV system maximum system voltage of 80 volts or greater,

shall be protected by a listed (dc) arc- fault circuit interrupter, PV type, or

other system components listed to provide equivalent protection. The PV arc-

fault protection means shall comply with the following requirements:

Page 24: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Arc-Fault Detection

Page 25: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

NEC 2014--Rapid Shutdown 690.12 (C) Facilities

with Rapid Shutdown

NEC 690.12 (C) states: PV system circuits installed on or in buildings

shall include a rapid shutdown function that controls specific

conductors in accordance with 690.12(1) through (5) as follows:

(1) Requirements for controlled conductors shall apply only to PV system

conductors of more than 1.5m (5 ft) in length inside a building , or more than

3m (10 ft) from a PV array.

(2) Controlled Conductors shall be limited to not more than 30V and 240 volt-

amperes within 10 seconds of rapid shutdown initiation.

(3) Voltage and power shall be measured between any conductor and ground

(4) The rapid shutdown initiation methods shall be labeled in accordance with

690.56(B)

(5) Equipment that performs the rapid shutdown shall be listed and identified.

Page 26: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Inverter Roots in Washington

Early 80’s Pre-MOSFET

–B-Series (Battery) Square wave inverters available from 500W to 6kW

–SCR –push-pull design with modified

McMurray-Bedford commutation

–90-94% efficiency –45% Thd–120V/240 split phase

–24, 36, 120V DC models 3kW, 6kW

–Idle power about 120W!

–CMOS logic state machine –binary ripple counter

–No Voltage regulation!

–100-120lbs

First manufacturer of inverters for off-grid use was Dynamote–founded in

1976

Page 27: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Industry responded with voltage regulation

Solution –quasi-square wave (quasi-sine wave) where the output

voltage was regulated at the expense of varying peak voltage.

•Advent of lower cost Planar MOSFETs drove the solution

•Trace U-Series, Legend, and DR

•Dynamote Bravo

•Vanner

Page 28: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Page 29: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Trace responds with the Swiss army knife

SW4024 –early 90’s production strong in 94

–First grid tied battery based inverter

–Stepped sine wave –32 steps max –reduces idle

power

–Two AC inputs

–Single phase 120V only

–Series stacking

–Low idle ~ 20W

Page 30: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Inverter Technology Trends

•Digital Signal Processing –High performance computing power is being used to more precisely control power

conversion, and lower the cost of inverter systems

•Power semiconductor technology–Advances in semiconductor performance increases system efficiency and lowers cost

•High power, integrated form factors, increasing system

size–High levels of integration means reduced installation costs and fewer problems

•Integrated energy storage–Energy storage is a key component of battery based inverters which provides back-up

power and load management

•Communications–Real time communications of performance data and inverter parameters is crucial to

system management and Smart Grid readiness

Page 31: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Grid-Tie Systems

• Simplest and cheapest entry.

• Displace power usage from Utility.

• Exchange (Net Metering).

• No backup if Utility power fails.

Page 32: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Grid-Tie Components

• PV Array– Convert Sunlight in to electricity.

• Inverter– Change DC from Solar Array to 120V AC electricity used by the utility.

• Safety Switch– Utility can shut system off in emergency

Page 33: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Grid Tied

Page 34: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Major Components and Array Electrical

Information

• Inverter Information

• Module Information

• Combiner Box

• Disconnects

Page 35: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Module Information

• Manufacturer’s “cut sheet” for the specific model • Listing – The module should be listed to UL 1703. For a current list of modules that are listed to UL 1703 visit the California website www.gosolarcalifornia.com

• Listing label information

Page 36: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Array Electrical Information

• Number of modules in series

• Array operating voltage

• Array operating current

• Maximum system voltage

• Array short circuit current

Page 37: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

What are the applicable codes and standards

for PV systems?

• Electrical codes - NEC Article 690 – Solar• Building Codes – ICC ASCE 7• UL Standard 1741, standard for Inverters, Converters, Controllers and Interconnection Systems Equipment and Use With Distributed Energy Resources• IEEE 1547-2008 Standard for Interconnecting Distributed Resources with Electric Power Systems

Page 38: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Home PV System

Page 39: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

One-line Diagram

• Should have sufficient detail to call out theelectrical components, the wire types andsizes, number of conductors, and conduit typeand size where needed.• Should include information about PV modules and inverter(s).• Should include information about utilitydisconnecting means (required by manyutilities).

Page 40: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Typical PV System One Line Diagram

Page 41: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Typical Utility Process

Page 42: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Structural Review of PV Array Mounting

Systems

• Roof Information• Mounting System Information• Electrical Review• Site Diagram

Failte Group

Page 43: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Electrical System Grounding

● The NEC defines grounding as a connection to the earth with sufficiently low impedance and having sufficient current-carrying capacity to prevent buildup of voltage

● Grounding of electrical systems offers personnel safeyand minimizes the effect of lighting and surges on equipment

Page 44: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Electrical Grounding Types

Confusion Over These Terms

● System Ground (grounding): Connecting the circuit to ground (i.e. the negative of a dc array, the neutral of a split single-phase system, or the neutral of a bi-polar dc system

● Equipment Ground (bonding): Connecting all non-current carrying metal parts to ground (metal enclosure, module frame, etc.)

Page 45: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Inverter Basics

UL 1741 Inverter Testing and Certification

Page 46: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

How Inverters Work

How Inverters WorkBy James Worden and Michael Zuercher-MartinsonWhat Goes on Inside the Magic Box

SolarPro | April/May 2009

Page 47: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Inverter Thermal Requirements

Page 48: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Commercial PV System

Page 49: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Inverter Electrical Requirements

Page 50: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Inverter Design Performance

Page 51: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Impact on Grid

Page 52: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

IEEE 1547 Voltage and Frequency

Tolerances

Voltage Range(% Nominal)

Max. ClearingTime (sec)*

V < 50% 0.16

50%< V < 88% 2.0

110% < V < 120% 1.0

V > 120% 0.16

Frequency Range(Hz)

Max. ClearingTime (sec)*

f > 60.5 0.16

f < 57.0* 0.16

59.8 < f < 57.0** Adjustable (0.16 and 300)

(*) Maximum clearing times for DG < 30 KW;Default clearing times for DG > 30 kW

(*) 59.3 Hz if DG < 30 kW(**) for DG > 30 kW

Additional Requirements-Cease to energize for faults on the utility system-Cease to energize prior to circuit reclosure-Detect island condition and cease to energize within 2 seconds of the formation of an island (“anti-islanding”)

Page 53: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

UL Testing

Page 54: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Normal UL 1741 Safety Test

Page 55: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Normal UL 1741 Safety Test

Page 56: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Abnormal UL 1741 Safety Test

Page 57: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Performance Related UL 1741 Test

- Software

● Voltage and Current Harmonics Test

● Thermal De-rating Test

● Power Limiting Test

● MPPT Tracking Test

Accuracy

Response Time

●Wakeup Strategy Test

Page 58: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Inverter Information

• Mode; number and manufacturer’s “cut

sheet” for the specific model• Listing-is the inverter listed to UL 1741 and labeled “Utility-interactive”? For current list of compliant inverters, visit California Solar Program website www.gosolarcalifornia.com

• Maximum continuous output power at 40° C

Page 59: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

DC to AC Conversion

Page 60: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Module Performance

Page 61: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

One Line Diagram of Inverter

Page 62: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

DC to AC Inverter

Page 63: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Solar Bear

Failte Group

Page 64: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV systems shall be marked in accordance

with NFPA 70

Direct Current (DC) Circuits. All interior and exterior DC conduits,raceways, enclosures, cable assemblies, and junction boxes associated with the PV system shall be marked to alert individuals that DC power is present. The marking shall be placed every ten (10) feet or fraction thereof, at turns and above and below penetrations, and on all DC combiner and junction boxes.

Content. The marking shall contain the text “CAUTION: PV CIRCUIT ENERGIZED” in capital letters a minimum of 3/8 inches in height with white letters on a red background. The materials used for marking shall be reflective and weather resistant. UL 969 shall be used as a standard for weather rating.

Page 65: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

One Line Diagram

Page 66: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Large PV System

Page 67: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Micro Inverter

Page 68: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Micro Inverter

Micro Inverter

Page 69: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Micro Inverter One Line Diagram

Page 70: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Micro Inverter Installation

Page 71: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Three Line Diagram Micro Inverter

Page 72: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Zero Energy Homes

Page 73: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Impact on Summer

Residential Load Profile

Failte Group

Page 74: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV impact on Load

Failte Group

Page 75: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Energy Source

Failte Group

Page 76: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Florida Power & Light

Page 77: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Systems are Larger

Page 78: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Commercial PV, Battery & Portable Generator

Page 79: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Grid Tie with Battery Backup

• More flexibility on power management.

• Provides limited power for critical loadsincase of power failure.

• Requires Battery maintenance schedule.

Page 80: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

Components

• Batteries– Store Energy for night time or power failure• Battery Cutoff Switch– Shutoff batteries for maintenance and safety• Other (depends on Inverter)• Solar Array• Inverter• Safety Switch

Page 81: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Production Meter Requirements

Page 82: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV Wiring Diagram

Page 83: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

PV and Battery Wiring Diagram

Page 84: PV System Codes and Standard, Interconnection and …solarplusnw.org/wp-content/uploads/2014/07/PV... · –CMOS logic state machine –binary ripple counter ... • Electrical Review

NATIONAL RENEWABLE ENERGY LABORATORY

The Future Grid