Espa Pumps (UK) Ltd, have been building booster and Pressurisation sets for over twenty years and have
been supplying pumps, as a subsidiary of tne ESPA Group, since 1990. All booster & pressurisation sets
are built fully tested and all have a documented performance at our UK premises in Manningtree, Essex.
Our booster & pressurisation sets are built to the highest traditional principals of quality engineering
whilst at the same time always looking at costs, resulting in a cost saving that can be passed on to you
or your clients.
ESPA offers a large range of solutions in pumping requirements for automatic water supply in housing,
apartment blocks, service buildings, hotels, hospitals, agricultural and industrial process.
All of our booster sets come as standard on a steel chassis which is epoxy coated with anti vibration
mountings fixed underneath and in each corner.
The frequency converters used in our CKA variable speed booster sets are made by Danfoss and
they conform to the requirements of the EU directive relating to EMC (Electro Magnetic Compatibility
EN50081-2). They are approved on the Enhanced Capital Allowance Scheme.
The stainless steel pumps, valves and pressure vessels that we use have a W.R.A.S approved reference
number and other components, using the same materials as used in the manufacture of W.R.A.S
certified equipment.
Each set comes with a two year warranty from date of invoice.
We offer a first class back up service, our service department being an hour away from the center of
London. We also have the facility to use other engineers in different areas of the country so that we have
good service coverage of the UK.
We operate our own quality control system, which enables us to trace back any component used in the
manufacture of one of our sets.
ESPA booster & pressurisation sets are an equal and approved packaged set.
ESPA Efficient Engineering sums up the spirit of innovation. It focuses on studying & applying the most
suitable technologies, plus the concept of efficient equipment for the pumping and Building Services
sector.
ESPA Pumps (UK) Ltd
4
IndexBooster Sets (Domestic)Building ServicesPressure Sets
Aquabox
Tecnoplus 15
Tecnoplus 25
Cat 5 Pump SetsBuilding ServicesSub-Tank 100AP
Sub- Tank 100/05
Sub-Tank 270/05
Sub-Tank 270.I
Sub-Tank 270/480 D.I
Tecno Booster Sets
Cat 5 Booster Sets
Booster Sets (Commercial)Building ServicesCKE Booster Sets
Booster Sets
Water GRP break tanks
Fire SetsBuilding ServicesFire Sets
Pressurisation UnitsBuilding ServicesES 1000
Wallpres Mini/Midi
Espres/Espres Delux
Espres Delux Twin System
Espres Delux Plus 150 D
Espres Delux Plus 250/280 D
Espresmat
AFE/ACS/AFOSB/AFESB Series
Pressure Wave
Challenger
Other Vessels
t66
7
9
10
t1212
13
14
15
16
17
18
t2121
23
24
t2626
t3030
31
32
33
34
35
36
37
39
40
41
AccessoriesBuilding ServicesAccessories
RBX Surge Arrestor
Air & Dirt separation
PumpsBuilding ServicesGlandless Circulators
FL/FL4
FLD/FLD4
AP/AKP/AEP Series
AEP/LP/ALP Series
AE/L/AL/AKN Series
T/AT Series
t4444
45
46
t4848
61
67
70
71
72
73
5
BOOSTER SETS(DOMESTIC)
6
Pressure Sets Building Services
Domestic single pump boosting units
ApplicationsAutomatic supply of water whilstmaintaining constant system pressure.
ConfigurationThese domestic booster units can bebuilt in various configurations usingdifferent types of pumps, larger vesselsand alternative control devises.
For further assistance/selectionplease contact our sales team.
Technical features
ModelCode P2 Size Vessel
PositionWith Vessel With Optimatic 05 [kW] [HP] Vessel Optimatic
Per 50/03 P50/30 P50 0.37 0.5 3 ltr 05 Vertical
Delta 505 D505/08 D505/05 0.37 0.5 8 ltr 05 Vertical
Delta 505 D505/24 0.37 0.5 24 ltr Horizontal
Delta 755 D755/08 D755/05 0.5 0.75 8 ltr 05 Vertical
Delta 755 D755/24 0.5 0.75 24 ltr Horizontal
Delta 1005 D1005/08 D1005/05 0.75 1 8 ltr 05 Vertical
Delta 1005 D1005/24 0.75 1 24 ltr Horizontal
Delta 1755 D1755/08 D1755/05 0.75 1 8 ltr 05 Vertical
Delta 1755 D1755/24 0.75 1 24 ltr Horizontal
Tecno 25.3 T25.3/18 T25.3/05 0.75 1 18 ltr 05 Vertical
Tecno 25.3 T25.3/24 0.75 1 24 ltr Horizontal
Tecno 25.4 T25.4/18 T25.4/05 0.9 1.25 18 ltr 05 Vertical
Tecno 25.4 T25.4/24 0.92 1.25 24 ltr Horizontal
Tecno 25.5 T25.5/18 T25.5/05 1.1 1.5 18 ltr 05 Vertical
Tecno 25.5 T25.5/24 1.1 1.5 24 ltr Horizontal
Aspri 25.3MB C25.3/18 C25.3/05 0.75 1 18 ltr 05 Vertical
Aspri 25.3MB C25.3/24 0.75 1 24 ltr Horizontal
Aspri 25.4MB C25.4/18 C25.4/05 0.92 1.25 18 ltr 05 Vertical
Aspri 25.4MB C25.4/24 0.92 1.25 24 ltr Horizontal
Aspri 25.5MB C25.5/18 C25.5/05 1.1 1.5 18 ltr 05 Vertical
Aspri 25.5MB C25.5/24 1.1 1.5 24 ltr Horizontal
Aspri 35.3 C35.3/24 1.1 1.5 24 ltr Horizontal
Aspri 35.3 C35.3/05 1.1 1.5 05
Aspri 35.4 C35.4/24 1.5 2 24 ltr Horizontal
Aspri 35.4 C35.3/05 1.5 2 05
Jet 100 J100/24 0.75 1 24 ltr Horizontal
7
Aquabox Building Services
Compact storage tank and pressurisation unit (with air gap)
Aquabox is ESPA’s advanced solution for buildings with low pressure or volumes of flow. It is a competitive, efficient alternative to traditional pressurisation units, eliminating the typical fluctuations in flow, complex mechanical designs and their excessive electrical consumption.Aquabox is a compact, well proportioned pressurising unit, with an integrated design and maximum energy efficiency. It comprises two basic elements: a latest-generation automatic ESPA pump and a storage tank. The result of the advanced engineering of these two components combined is an innovative unit offering high levels of convenience in water use, guaranteeing not only its permanent availability (even when the water supply is cut off), but also strong, regular, constant pressure. The 200 ltr tank can be used as a backup system in the event of restrictions on the use of water from the mains. In line with regulation EN 1717, the outer casing incorporates a safety partition to safeguard against the pollution of drinking water.
Applications Aquabox is multi-purpose and can be used on sites with water supply problems. Rural areas: second homes, village dwellings, rural tourism, etc. Urban areas: housing developments, houses, commercial premises, restaurants, etc.
Model: Aquabox 350 Acuaplus N Incorporating the reliable advanced electronic Espa speed driver, which enables the submersible pump to operate at variable speeds while automatically regulating itself to maintain constant pressure according to needs. Besides saving energy, this technological innovation makes minimal noise and provides remarkable regularity in the water supply flow.
Model: Aquabox 350 AcuapresAutomatic pressurisation system incorporating the submersible Acuapres pump with built-in pressure control.
With Variable Speed PumpAn advanced technology option: maximum pressure control convenience, low noise levels and considerable saving in electrical consumption.
With Fixed Speed PumpThe most competitive, versatile and efficient alternative for all types of buildings.
Ventilation grille
Flexible hose Cover
Kit
Coupling
Tray
Overflow connection
Pump
DrainTank
Float
Coupling
8
Performance curves at 2900 rpm
Acuapres07 4
Pump options for the Aquabox unit / DimensionsA
B
C
Aquabox Building Services
Acuaplus N
Pump model
All overflow outlet has been built into the tank to safeguard against the possible contamination of drinking water in the public network, in the case of back flow, in compliance with European standard EN 1717.
Description Description
Aquabox 350 Acplus 230 50 Aquabox 350 Acuapres
Pump model
Acuaplus N 230 50 Acuapres07 4
Submersible
Surface
Constant pressure-variable speed
Automatic control
Dry operation protection
Inlet float
Overflow duct in accordance with regulation EN1717
Water supply/outlet connection
Overflow connection
Width A [mm]
Depth B [mm]
Height C [mm]
Empty tank weight [Kg]
Useful tank capacity
Working pressure [bar]
Flow at working pressure [l/min]
Installed capacity at P1 [kW]
Drain connection
Acuaplus N
X
X
X
X
X
X
3/4”
DN 50
600
600
1150
25.5
200
3
40
0.95
1/2”
Acuapres07 4
X
X
X
X
X
3/4”
DN 50
600
600
1150
25.5
200
2.5
30/45
0.6/0.95
1/2”
Pump model
9
Performance curves at 2900 rpm
Hydraulic performance table
I [A]
1~230 V
ModelP2
[kW] [HP]
P1 [kW]
1~230 V
c[µF]
m3/h
l/min
0.3
5
0.6
10
0.9
15
1.5
25
1.8
30
2.1
35
2.7
45
3
50
3.6 0.75 0.55 0.75 1236
15
36
15
32
15
25.5
15
36
15
28
15
18.5
15
15
15
MAX
MINTecnoplus 15
Tecnoplus 15 Building Services
Centrifugal multi-stage with speed control
A horizontal, multiphase, centrifugal pump with electronic regulation for changing speed and with built-in pressure sensor. It contains a device for detecting and protecting against dry operation, with sequential re-starts in event of failure. Absorbs water hammer effect on the installation.
ApplicationsPressurising with constant pressure of domestic water for houses, semi-detached homes, apartments, chalets and rural homes, etc.
MaterialsHydraulic body and impellers in AISI 304.Diffusers in thermoplastic.Mechanical seal in graphite and ceramic.O-nngs in NBR.
MotorAsynchronous, two poles.IP 55 protection.Class F insulation.Continuous operation.Built-in thermal protector inside the windings.With 2 m cable H07 RNF 3 x 1 mm2. Display with push button to increase or decrease working pressure (150 kPA - 350 kPA).
LimitationsMaximum suction lift 5 m for installation with foot valve.Maximum working pressure 6 bar.Maximum suction pressure 2 bar intake at suction point.Water temperature from 4 °C to 35 °C.Room temperature from -10 °C to 50 °C.Motor characteristics 230 V / 50 Hz.
ElectronicsAdvanced ESPA Speed Drive technology, enabling variable speed operation, with automatic self-regulation which maintains the constant pressure required at all times in the home, thanks to its pressure sensor.
EquipmentComplete with kit press and pressure gauge.Noise level 60-62 dBa at 1 meter.You must install a pressure vessel on the discharge pipework minimum 18 ltrs.
Model
Tecnoplus 15/4 M
[Kg]
10.5
I
9
J
243
M
G1”
L
G1”
K
196
A
439
H
88
G
253.8
F
241
E
216
D
200
C
261108
B
A
K J
L
B
C
D
M
F
EG
HI
The pump can operate atv any point inside the indicated area. The characteristic curves depend on the delivery pressure. By way of example, the curves are shown for delivery pressures of 150, 200 and 300 kPa. The operating limit curve corresponds to the maximum rotating speed.
Dimensions and weights
10
Tecnoplus 25 Building Services
A horizontal, multistage, centrifugal pump with frequency converter
ApplicationsCompact unit providing constant pressure without fluctuations for domestic applications, saving electricity.Easy to install and plug&pump design.
MaterialsPump body and impellers in stainlesssteel AISI 304.Diffusors in thermoplastic.Mechanical seal in graphite and ceramic.O-rings in NBR and EPDM.
MotorAsynchronous two poles 50/60 Hz.IP 55 Protection.Insulation class F.Built-in thermal protectorinside the windings.Continuous operation.Three-phase motor 230 V and single-phase supply 230 V.
Voltage rangeLow voltage: Disconnect at 180 V.Automatic Reset at 200 V. High voltage: Disconnect at 260 V.Automatic Reset at 240 V.
EquipmentA horizontal, multistage, centrifugal pump with frequency converter with keypad. Built-in pressure sensor. Built-in dry running control, pressure gauge and dry running control with sequential re-starts in the event of failure. Reduces water hamer effect on the installations. With 2 m cable HO7RNF 3 x 1 mm2.You must install a pressure vessel on the discharge pipework minimum 24 ltrs.
LimitationsMaximum suction 5 m lift when installed with foot valve. Maximum working pressure 6 bar. Maximum intake pressure 2 bar.Water temperature from 4 °C to 40 °C.Room temperature from -10 °C to 50 °C.Noise level dBa at l mtr.
Model
Tecnoplus 25 4M
[Kg]
15.5
A
277.5
H
148.5
G
1 1/4”
I
216
J
88
K
Ø 9
F
1”
E
190
D
107
C
467.5221
B
I [A]
1~230 V
ModelP2
[kW] [HP]
P1 [kW]
1~230 V
c[µF]
2.7
45
3.6
60
4.5
75
5.4
90
6.3
105
7.2
120
6.8 1522283337401.5 0.92 1.25 16
m3/h
l/min
Tecnoplus 25 4M
J
K
H
I
C
E A
G
F
D
B
Performance curves at 2900 rpm
Hydraulic performance table
Dimensions and weights
11
CAT 5 PUMP SETS
12
Performance curves at 2900 rpm
4
6
Technical features
Model
I [A]
P1 [kW] P2 c
1~230 V
1~230 V [kW] [HP] [µF]
S T07.4/100AP 3.5 0.8 0.5 0.75 12
ApplicationsTo restore system pressure when themains supply is insufficient, a pumpmay be used. However to comply withWater Authority Byelaws, a break tankmust be incorporated, as the pumpmay not be connected directly to themains water supply.The ESPA Sub-tank system hasbeen designed to solve this problem.A fully automatic unit, the Sub-Tankhas a submersible stainless steelpump with a built-in pressure controlincorporated into the break tank givingspace saving advantages in smallplant rooms. Control is provided by a constant pressure deviceintegrated in the submersible pump. Electronics preventstarting without water. Installation isstraightforward, with only threeconnection required.
EquipmentST07.4/100AP start pressure 2,0 Bar.
DimensionsST07.4/100AP.500 mm x 240 mm x 800 mm height.Outlet connection 3/4’’ bspm.
Materials100 Litre actual capacity high density. Polyethylene break tanks (EN 13077).WRAS approved.
Fitted with a 3/4’’ ball valve and Type “AB” air gap, protecting incoming mains supply from a class 5 designated risk of contamination.
Float valve DN13 with proportional behaviour (50L/min at 3.0Bar) with stainless steel bowl.
Built-in pressure control starts and stopspump automatically which supplies waterat constant pressure.
Prevents starting in the absence of waterand avoids water hammer.
Does not require any maintenance orpre-charge.
OptionsExtra pressure vessel to be installed in the discharge pipework.
LimitationsMaximum temperature 40 °C.Power supply 230 V / 1ph / 50 Hz.
Sub-Tank 100AP Building Services
Fixed speed booster and tank package
13
ApplicationsTo restore system pressure when themains supply is insufficient, a pumpmay be used. However to comply withWater Authority Byelaws, a break tankmust be incorporated, as the pumpmay not be connected directly to themains water supply.The ESPA Sub-tank system hasbeen designed to solve this problem.A fully automatic unit, the Sub-Tankhas a submersible stainless steelpump with a built-in pressure controlincorporated into the break tank givingspace saving advantages in smallplant rooms. Control is provided by a constant pressure device integrated in the submersible pump. Electronics preventstarting without water. Installation isstraightforward, with only threeconnection plus power cable required.
EquipmentST07.3/100.05 complete with pressure stat 05.Adjustable start pressure between1.5 - 2.5 Bar.
DimensionsST07.3/100.05.500 mm x 240 mm x 990 mm height.Outlet connection 3/4’’ bspm.
Materials100 Litre actual capacity high density. Polyethylene break tanks (EN 13077).WRAS approved.
Fitted with a 3/4’’ ball valve and Type “AB” air gap, protecting incoming mains supply from a class 5 designated risk of contamination.
Float valve DN13 with proportional behaviour (50L/min at 3.0Bar) with stainless steel bowl.
Built-in pressure control starts and stopspump automatically which supplies waterat constant pressure.
Prevents starting in the absence of waterand avoids water hammer.
Does not require any maintenance orpre-charge.
OptionsExtra pressure vessel to be installed in the discharge pipework.
LimitationsMaximum temperature 40 °C.Power supply 230 V / 1ph / 50 H
Sub-Tank 100/05 Building Services
Fixed speed booster and tank package
Performance curves at 2900 rpmTechnical features
Model
I [A]
P1 [kW] P2 c
1~230 V
1~230 V [kW] [HP] [µF]
S T07.3/100.05 2.8 0.6 0.37 0.5 12
14
Performance curves at 2900 rpm
ApplicationsTo restore system pressure when themains supply is insufficient, a pumpmay be used. However to comply withWater Authority Byelaws, a break tankmust be incorporated, as the pumpmay not be connected directly to themains water supply.The ESPA Sub-tank system hasbeen designed to solve this problem.A fully automatic unit, the Sub-Tankhas a submersible stainless steelpump incorporated into the break tank giving space saving advantages in smallplant rooms. Control is provided by a constant pressure device, with a built in pressure gauge. Electronics preventstarting without water. Installation isstraightforward, with only threeconnection required.
Dimensions490 mm x 585 mm x 1675 mm height.Outlet connection 1’’ bspf.
Materials270 Ltrs capacity high density. Polyethylene break tanks (EN 13077).WRAS approved.
Fitted with a 3/4’’ ball valve and type “AB” air gap, protecting incoming mains supply from a class 5 designated risk of contamination.
Pressure stat stars and stops pump automatically which supplies water at constant pressure. Prevents starting in the absence of water and avoids water ham-mer. Does not require any maintenance or pre-charge.
LimitationsStart pressure 1.5 -3 Bar (adjustable).Working pressure range: 2 - 8 Bar.Maximum temperature 40 °C.Maximum working pressure 10 Bar.Noise levels are 65dB whwn filling set of water and 60 dB when pump set is running at 1 metre.Power supply 230 V / 1ph / 50 Hz.PS = Pressure switch version.
Sub-Tank 270/05 Building Services
Fixed speed booster and tank package
Technical features
ModelI [A] P1 [kW] P2 Dry Weight
[Kg]1~ 230 V 1~ 230 V [kW] [HP]
S T07.3M/270 2.8 0.6 0.37 0.5 44
S T07.4M/270 3.5 0.8 0.5 0.75 45
S T07.5M/270 4.1 1 0.75 1 46
S T07.6M/270 5 1.2 0.9 1.2 47
S T07.7M/270 5.5 1.4 1.1 1.5 48
S T17.5M/270 7.4 1.6 0.9 1.25 49
S T17.7M/270.PS 10.7 2.2 1.5 2 50
S T27.4M/270 7 1.5 0.9 1.25 52
S T27.6M/270.PS 10.8 2.2 1.5 2 53
ST07 ST17
ST27
7
5
6
4
7
6
5
4
3
15
ApplicationsTo restore system pressure when themains supply is insufficient, a pumpmay be used. However to comply withWater Authority Byelaws, a break tankmust be incorporated, as the pumpmay not be connected directly to themains water supply. The ESPA Sub-tank system has been designed to solve this problem. A fully automatic unit, the Sub-Tank has a submersible stainless steel pump with a built-in pressure controlincorporated into the break tank givingspace saving advantages in small plant rooms. An in-line inverter with built in pressure transducer provides control. Electronics prevent pump starting without water and the digital displays online pump operation, standby and fault status. Installation is straightforward, with only three connections required.
LimitationsThe pressure vessel requires a pre-charge with air 0.3 -0.5 bar below the working pressure. This charge should be checked and adjusted every six months.Adjustable working pressure 2 – 8 Bar.Maximum temperature 40 oC.Maximum working pressure 10 Bar.Noise levels are 65dB when filing set of water and 60 dB when pump set is running at 1 metre.Power supply 230v/1ph/50hz and 400v/3ph/50hz options.
Materials227 Litre actual capacity high density. Polyethylene break tanks (BS 4213).WRAS approved.Byelaw 30 top tank fitted with 3/4’’ ball valve complying with (Byelaw 11) Type “AA & AB” air gap, protecting incoming mains supplyfrom a class 5 designated risk ofcontamination. (Byelaw 25)Inverter starts and stops pumpautomatically and supplies water at a constant pressure.Prevents starting in the absence of water and avoids water hammer.Inverter displays rotation frequency,system pressure,motor absorption & pump alarm.5’’ submersible pump made of stainless steel AISI 304, withinternal capacitor.
Dimensions635 mm x 510 mm x 1750 mm height.Outlet connection 1’’ bspf.
Sub-Tank 270.I Building Services
Fixed speed booster and tank package
Technical features
Model I [A] P1 [kW] P2 Dry Weight[Kg]Single Phase Three Phase 1~ 230 V 3~ 230 V 3~ 400 V 1~ 230 V 3~ 400 V [kW] [HP]
ST40.08M/270.I ST40.08T/270.I 4.3 3.3 1.9 1 0.95 0.6 0.8 53
ST40.10M/270.I ST40.10T/270.I 5.7 3.8 2.2 1.25 1.18 0.75 1 54
ST40.12M/270.I ST40.12T/270.I 6.8 4.2 2.4 1.42 1.33 0.9 1.2 55
ST40.15M/270.I ST40.15T/270.I 7.3 5.2 3 1.6 1.55 1.1 1.5 56
ST80.12M/270.I ST80.12T/270.I 6.4 4 2.3 1.33 1.22 0.9 1.2 54
ST80.15M/270.I ST80.15T/270.I 7.5 5.4 3.1 1.62 1.52 1.1 1.5 55
ST80.20M/270.I ST80.20T/270.I 6.1 3.5 1.9 1.5 2 56
Performance curves at 2900 rpm
16
Performance curves at 2900 rpm
Twin variable speed booster and tank package
Technical features
Model I [A] P1 [kW] P2 Dry Weight [Kg]
Single tank 1ph Twin tank 1ph 3~ 230 V 1~ 230 V [kW] [HP] Single Twin
ST40.08M/270.DI ST40.08T/480.DI 3.3 1 0.6 0.8 53 80
ST40.10M/270.DI ST40.10T/480.DI 3.8 1.25 0.75 1 54 81
ST40.12M/270.DI ST40.12T/480.DI 4.2 1.42 0.9 1.2 55 82
ST40.15M/270.DI ST40.15T/480.DI 5.2 1.6 1.1 1.5 56 83
ST80.12M/270.DI ST80.12T/480.DI 4 1.33 0.9 1.2 54 81
ST80.15M/270.DI ST80.15T/480.DI 5.4 1.62 1.1 1.5 55 82
ST80.20M/270.DI ST80.20T/480.DI 6.1 1.5 2 56 83
ApplicationsTwo in-line inverters with built-in pressure transducers provides control.Duty/standby or duty/assist configuration.
LimitationsThe pressure vessel requires a pre-charge with air 0.3 -0.5 Bar below the working pressure.This charge should be checked and adjusted every six months.Adjustable working pressure 2 – 8 Bar.Maximum temperature 40 °C.Maximum working pressure 10 Bar.
Noise levels are 65 dB when filing set of water and 60 dB when pump set is running at 1 metre.
Dimensions480.DI. 1300 mm x 750 mm x 1650 mm height.270.DI. 650 mm x 520 mm x 1740 mm height.Outlet connection 11/2’’ bspf for ST40 & 2’’ bspf for ST80 models.
Three phase versions available on request.
Materials270 Litre actual capacity high density polyethylene break tanks (BS 4213). WRAS approved. Byelaw 30 top tank fitted with 3/4’’ ball valve(s) complying with (Byelaw 11). Type “AA & AB” air gap, protecting incoming mains supply from a class 5 designated risk of contamination. (Byelaw 25).Inverter starts and stops pump automatically and supplies water at a constant pressure.Prevents starting in the absence of water and avoids water hammer.Inverter displays rotation frequency, system pressure, motor absorption & pump alarm.5’’ submersible pump(s) made of stainless steel AISI 304, with internal capacitor.
Sub-Tank 270/480.DI Building Services
17
Tecno Booster sets Building Services
Unit with a Tecnoplus 15 variable speed pump, 24 Ltr PEWBpressure vessel, 100 Ltrs (95Ltr actual) break tank with type AB air gap, all mounted on a steel black epoxy coated chassis with anti vibration mounts.
Unit with a Tecnopres 25.5 fixed speed pump, 24 Ltr PEWBpressure vessel, 240 Ltrs (227 Ltr actual) break tank with type AB air gap all mounted on a steel black epoxy coated chassis with anti vibration mounts.
Unit with a Tecno 25.5/ESD variable speed pump, 24 m/Ltr PEWBpressure vessel, 240 Ltrs (227 Ltr actual) break tank with type AB air gap, all mounted on a steel black epoxy coated chassis with anti vibration mounts.
For pump duties please see the relevant catalogue page for each pump.
Be-spoke variable/fixed speed booster and tank package
18
Cat 5 Booster sets Building Services
Economical variable speed sets (CKE) with break tanks
Motor mounted Inverter controlled booster sets with breaktank and support frame. Fully automatic variable speedunits, for commercial and domestic applications. ErPcompliant.
Standard range with twin or triplevariable speed pumps with either750/1000/1500 or 2000 Ltr break tanks
Other sizes and pump arrangements on request.
19
BOOSTER SETS(COMMERCIAL)
20
ESPA offers a large range of solutions to provide the best answer to th more challenging applications in pumping requirements
for automatic water supply in housing, service buildings, hotels, hospitals, agricultural and industrial process.
ESPA evaluates, designs, and manufactures booster sets for the automatic supply water. The ESPA range of products can
be adapted to the installation requirements. The ESPA Applications Engineering Department adjusts the standard range
of ESPA booster sets to the specific requirements in every installation.
The standard range of ESPA booster sets offers several posibilities of mechanical configuration and various operational
systems: fixed sped DOL, variable speed, duty assist in cascade operation or duty pumps with reserve pumps, all of them
ready to give the best solution to the pumping needs in each installation. Each standard model has been designed for a
main application. As a result, the standard ranges of ESPA sets has ben designed from the smallest and compact sets for
domestic applications, booster sets for collective uses and the largest for commercial or utilities applications. Evidently,
every set can be adapted to any specific demand: industrial, irrigation, etc.
The standard range of booster sets in variable speed or fixed speed present twin pumps booster sets, 3 or 4 pumps in duty - assist
configuration or duty assist - standby pumps. A part from the standard range of 4 pumps the ESPA control panels are designed to
control the operation up to 8 pumps, variable speed and fixed speed in any operation system required.
The standard range includes horizontal and vertical multisage pumps. These pumps are manufactured in stainless steel
materials (AISI 304 or AISI 316 optional). All wet components in the booster sets (valves, fittings, manifolds and expansion
vessels) are made in suitable materials for drinking water, brass or stainless steel, and the joints and seals composed with
materials accepted for the WRAS requirements.
ESPA offers the best solutions in energy saving using variable speed pump controlers. The target of these controllers is to drive
the booster set at the BEP (Best Efficient Point in the performance curve) for any flow demand in the installation.
According with the technical specifications, ESPA can be assemble different mechanical configuration of booser sets. The
ESPA Engineering Application Service is ready to design and manufacture customised solutions for any required application,
modifying the standard range increasing the flow, the heat or changing operation mode. If any other operational system
is needed. ESPA can provide different types os booster sets; fro example, constant flow booster sets using variable speed
devices and proportional flow-meters instruments for special applications as for example golf course irrigation.
The ESPA Applications Engineering Department offers the assistance service for booster set selection and sizing, also analysis
the best option in LCC (Life Cycle Cost). The ESPA after Sells Service offes, on request, the commissioning and the aid for the
maintenance to keep the booster set and the installation in the best point of efficiency and reliability.
ESPA has also a standard range of fire fighting booster set designed manufactured and tested according several rules as
EN 12845 and European fire organizations as APSAD or CEPREVEN or other technical homologations as NFPA 20. The standard
range includes duty standby and jockey pump, electric motor or engine driven pumps.
Water supply booster sets, fire fighting units and special solutions in pumping systems.
21
CKE Booster sets Building Services
Economical variable speed sets (CKE)
ApplicationsA range of variable speed booster sets for commercial and domestic applications.
Materials Stainless steel AISI 304 manifolds.WRAS approved pumps.WRAS approved valves.WRAS approved pressure vessel with 5 year warranty.Steel chassis finished in Black epoxy coating.Glycerine filled pressure gauge.Stainless steel pressure transducer 4-20 ma.
FeaturesAn innovative system that can be with vertical or horizontal pumps.Saves energy up to 50%.Quiet running and small footprint.Interface is user friendly allowing easy use to calibrate pressure set points, view error messages.Multipunp capability one to four pumps.Control box housing motor mcb’s, common volt free contact and low water contacts for break tank float switch.ErP Compliant.
Field of application at 2900 rpm
Curves obtained in accordance with ISO9906, appendix A
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE2M TEC15.5T11-24 0.75 60 54
CKE2M TEC25.5T11-24 1.1 240 55
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE2 TEC15.5T11-24 0.75 60 54
CKE2 TEC25.5T11-24 1.1 240 55
Technical specifications
Single pump sets (400 V/3 PH/50 Hz)
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE1 TEC15.5T11-24 0.75 60 54
CKE1 TEC25.5T11-24 1.1 240 55
Twin pump sets (400 V/3 PH/50 Hz)
Single pump sets (230 V/1 PH/50 Hz)
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE1M TEC15.5T11-24 0.75 60 54
CKE1M TEC25.5T11-24 1.1 240 55
Twin pump sets (230 V/1 PH/50 Hz)
22
CKE Booster sets Building Services
Technical specifications
Single pump sets (230 V/1 PH/50 Hz)
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE1M VX309F07T-24 0.75 80 60
CKE1M VX313F11T-24 1.1 80 88
CKE1M VX317F15T-24 1.5 80 112
CKE1M VX505F07T-24 0.7 140 36
CKE1M VX508F11T-24 1.1 140 58
CKE1M VX510F15T-24 1.5 140 71
CKE1M VX1004F15T-24 1.5 220 40
Single pump sets (400 V/3 PH/50 Hz)
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE1 VX309F07T-24 0.75 80 60
CKE1 VX313F11T-24 1.1 80 88
CKE1 VX317F15T-24 1.5 80 112
CKE1 VX505F07T-24 0.75 140 36
CKE1 VX508F11T-24 1.1 140 58
CKE1 VX510F15T-24 1.5 140 71
CKE1 VX516F22T-24 2.2 140 115
CKE1 VX1004F15T-24 1.5 220 40
CKE1 VX1006F22T-24 2.2 220 61
CKE1 VX1009F30T-24 3 220 91
CKE1 VX1012F40T-24 4 220 123
CKE1 VX1503F30T-48 3 400 42
CKE1 VX1504F40T-48 4 400 56
Twin pump sets (230 V/1 PH/50 Hz)
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE2M VX309F07T-24 0.75 160 60
CKE2M VX313F11T-24 1.1 160 88
CKE2M VX317F15T-24 1.5 160 112
CKE2M VX505F07T-24 0.7 280 36
CKE2M VX508F11T-24 1.1 280 58
CKE2M VX510F15T-24 1.5 280 71
CKE2M VX1003F11T-24 1.1 440 30
CKE2M VX1004F15T-24 1.5 400 40
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE2 VX309F07T-24 0.75 160 60
CKE2 VX313F11T-24 1.1 160 88
CKE2 VX317F15T-24 1.5 160 112
CKE2 VX505F07T-24 0.75 280 36
CKE2 VX508F11T-24 1.1 280 58
CKE2 VX510F15T-24 1.5 280 71
CKE2 VX516F22T-24 2.2 280 115
CKE2 VX1003F11T-24 1.1 440 30
CKE2 VX1004F15T-24 1.5 440 40
CKE2 VX1006F22T-24 2.2 440 61
CKE2 VX1009F30T-24 3 440 91
CKE2 VX1012F40T-24 4 440 123
CKE2 VX1503F30T-48 3 800 42
CKE2 VX1504F40T-48 4 800 56
Twin pump sets (400 V/3 PH/50 Hz)
Triple pump sets (230 V/1 PH/50 Hz)
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE3M VX309F07T-24 0.75 240 60
CKE3M VX313F11T-24 1.1 240 88
CKE3M VX317F15T-24 1.5 240 112
CKE3M VX505F07T-24 0.75 420 36
CKE3M VX508F11T-24 1.1 420 58
CKE3M VX510F15T-24 1.5 420 71
CKE3M VX1003F11T-24 1.1 660 30
CKE3M VX1004F15T-24 1.5 660 40
ModelP2
[kW]
Max flow
rate l/min
Max
head mtrs
CKE3 VX309F07T-24 0.75 240 60
CKE3 VX313F11T-24 1.1 240 88
CKE3 VX317F15T-24 1.5 240 112
CKE3 VX505F07T-24 0.75 420 36
CKE3 VX508F11T-24 1.1 420 58
CKE3 VX510F15T-24 1.5 420 71
CKE3 VX516F22T-24 2.2 420 115
CKE3 VX1003F11T-24 1.1 660 30
CKE3 VX1004F15T-24 1.5 660 40
CKE3 VX1006F22T-24 2.2 660 61
CKE3 VX1009F30T-24 3 660 91
CKE3 VX1012F40T-24 4 660 123
CKE3 VX1503F30T-48 3 1200 42
CKE3 VX1504F40T-48 4 1200 56
Triple pump sets (400 V/3 PH/50 Hz)
Other models and CKE4 four pump sets available on request
23
Auxiliary input for low water via probe in suction manifold.Volt-free contacts for BMS output.Full documentation is provided with each booster set.
ESPA Control Panel advantagesMajor feature – Every time power to the booster set is interrupted, on resumption of power the controller cycles through a “filling system” programme. This eliminates pipework failure due to hydraulic shock.Can control up to six frequency-controlled pumps directly via inverter “data bus”.
Booster sets Building Services
CKA high specification variable speed
ApplicationsESPA Inverter booster sets are designed to provide an efficient solution to water boosting applications where existing supplies are unreliable or insufficient to meet the demands of commerce and industry.ESPA variable speed booster sets embrace the best in modern control techniques, whilst holding true the traditional principles of quality engineering.Due to the compact design, ESPA booster sets offer a small footprint in relation to performance. Installation is straightforward, with site work usually limited to connecting site pipe work and the provision of a suitable electrical supply.
FeaturesStainless steel suction and discharge manifolds AISI 304 – Copper (optional steel) finished in black epoxy coating.WRAS approved nickel-plated brass ball valves on each pump providing individual isolation if necessary.Anti-vibration mounts as standard.Steel enclosed panel IP 54, incorporating the following features: One or more Danfos inverter(s) (depending on control choice).Door interlocked isolator.Pump controller via transducer.Manual/Off/Auto parameter for each pump.Duty pump alternation by software control.
CPA high specification fixed speed
Fixed speed booster setsTransducer-controlled booster series. Fully automatic units for commercial and domestic applications.Espa fixed-speed boosters can be built to customer specifications providing automatic control of multiple-phase, single-phase and three-phase pumps, in either Duty/Standby, Duty/Assist and Duty/Assist/Standby.Low cost fixed speed booster sets available on request.
Two jockey pumps can be controlled in variable speed or fixed speed operation.On a large pump system – has a “standard anti-cavitation programme” to prevent damage occurring to pumps on large multi-pump sets.Pump alternation can be time of day/week OR on hours run. Total flexibility.Password protection.
Please ask our sales team for a quotation or e-mail on: [email protected]
24
Sectional Tanks Full range of hot press moulded panels.Designed and manufactured to BS 280:2001, European standards EN.13280:2001.The wide range of panels consist of 2 m x 1 m, 1.5 m x 1 m, 1 m x 1 m, 1 m x 0. 5m and 0.5 m x 0.5 m sizes in varying configurations for use in side, bottom and top, which enables tank assemblies.Up to 2 million litres capacity.All joints & bolts are sealed with WRAS approved materials.Standard ball valve chambers are supplied and fitted with reinforced ball valve area(s).These chambers can be pre-insulated.Standard size 800 x 800 x 400 mm.Other features are: Ladders, manways & inspection hatches, maintenance dividers and internally flanged panels.
Water GRP break tanks Building Services
One & two piece GRP break tanks
One Piece TanksManufactured from top quality glassfibre/impregnated with polyester resin. All materials are WRAS & WRC approved.Raised ball valve chambers are supplied with a reinforced ball valve area (s). These chambers can be preinsulated.Each tank is supplied with a screen overflow to BS 6700 whilst tanks supplied to the requirements of Byelaw 30 are complete with an additional 22 mm early warning screen having a 0.65 mm micromesh filter. Maintenance dividers can be installed within the tank (s) to enable maintenance work without a complete shut down.Capacities from 36 to 4903 Ltrs actual.Maximum water temperature 60 °C.
Two piece TanksHorizontal split tanks can be made manufactured in both standard and custom made versions.These tanks are used where access is restricted and the majority are designed to pass through standard door-ways.General as above specification.Capacities from 36-4903 Ltrs actual.Maximum water temperature 60 °C.GRP tanks are Light grey in colour (BS10A05).Tanks should be situated on a continuous solid base i.e. marine plywood, TG board, concrete and not rely on cross bracing alone.
25
FIRE SETS
26
Fire sets Building Services
Espa manufactures a complete range of firefighting booster sets according with the following rules.
Booster sets to feed sprinklersEN 12845: 2003.CEPREVEN RT2 ABA.APSAD R5.
ModelsCE: jockey pump + electric pump.CD: jockey pump + engine driven pump.C2E: jockey pump + electric service pump + electric auxiliary pump.CED: jockey pump + electric service pump + engine driven auxiliary pump.
Fire fighting booster sets. Range overview
Booster sets to feed fire hose reelsBooster sets according with the following rules: EN 23-500-90. APSAD R1.
ModelsUE: jockey pump + electric pump.UD: jockey pump + engine driven pump.U2E: jockey pump + electric service pump + electric auxiliary pump.UED: jockey pump + electric service pump + engine driven auxiliary pump.
27
Fire sets Building Services
Components
UE
Jockey pump: Multi.Electrical driven Service pump. Monobloc.Control panel.Pressure vessel 50 l.4 pressure switches: 3 service pump + 1 jockey.Fittings and valves.
U2E
Jockey pump: Multi.Service and auxiliary electrical driven pump. Monobloc.Control panel.Pressure vessel 50 l.7 pressure switches: 3 service pump + 3 auxiliary pump + 1 jockey.Fittings and valves.
64
2
10
8
0 ESPA
UD
Jockey pump: Multi.Diesel engine driven Service pump. Monobloc.Control panel.Pressure vessel 50 l.4 pressure switches: 3 service pump + 1 jockey.Fittings and valves.
LOMBARDINI
UED
Jockey pump: Multi.Service electrical driven pump + Diesel engine driven pump.Control panel.Pressure vessel 50 l.7 pressure switches: 3 service pump + 3 auxiliary pump + 1 jockey.Fittings and valves.
LOMBARDINI
ESPA010
2
4
8
6
28
Fire sets Building Services
Components
CE CD
Jockey pump: Multi.Electrical driven Service pump.Control panel.Pressure vessel 50 l.4 pressure switches: 3 service pump + 1 jockey.Fittings and valves.
Jockey pump: Multi.Diesel engine driven Service pump.Control panel.Pressure vessel 50 l.4 pressure switches: 3 service pump + 1 jockey.Fittings and valves.
C2E CED
Jockey pump: Multi.Service and auxiliary electrical driven pump.Control panel.Pressure vessel 50 l.7 pressure switches: 3 service pump + 3 auxiliary pump + 1 jockey.2 control panel.Fittings and valves.
Jockey pump: Multi.Service electrical driven pump + Diesel engine driven pump.2 control panel for engine driven pump and control panel for electric pump.Pressure vessel 50 l.7 pressure switches: 3 service pump + 3 auxiliary pump + 1 jockey.Fittings and valves.
29
PRESSURISATIONUNITS
30
ES1000 Building Services
Open pressurisation set
ApplicationsOpen pressurisation sets that are designed to replace water that has been lost through system leakage and to maintain the system design fill pressure in sealed & chilled water systems in accordance with BS 7074 parts 1.2 & 3.
OptionsTwo pump options with Prisma horizontal multistage pump or with Per 50 m peripheral pump.High & low pressure switch assembly.
High & low pressure switch assembly.
Technical features
ModelI [A] P2
Outlet CF Max Length Width Height1~ 230 V [kW]
ES1000 2.1 0.37 1/2’’ 3 Bar 600 550 450
ES1000P 3.53 0.55 1/2’’ 3.5 Bar 600 550 450
ES1000P ES1000
Performance curves at 2900 rpm
5
4
3
2
31
FeaturesA simple to use controller that offers single or twin pump control with standard pumping requirements in a single controller.Many features in the unit are automatic and parameters are pre-set to the most common requirements.
Event logging for pump start, individual pump runs hours counter, electrical interruption & common alarm.Volt free contacts for common fault, high pressure, low pressure, pump fault & pressure transducer.Password protection for parameter entry.Pressure settings in 0.1 bar increments.Pump pulse option (2 second pulse if inactive for 60 days).Flood protection options.Service reminder option (12 months).Wall Mounted.Single (1000) & Twin (2000) pump options.System quick-fill mode (Midi only).Maximum vessel size 300 Ltr (Mini only).4 Ltr break tank (Midi only).
Electrical ConnectionsThe unit should be connected to 230 V single phase supply, via a fused switched outlet fitted with a 3 amp fuse.Packaged units complete with vesselavailable on request.
Wallpres Mini/Midi Building Services
Wall mounted pressurisation unit
Technical features
ModelPump Max. P2 FLC Connections [mm] Dimensions [mm] Weight
Quantity Pressure [kW] [Amps] System Mains Supply Drain Width Depth Height [kg]
Wallpres Mini 1000 1 3.0 0.035 0.3 15 (1/2’’) 15 (1/2’’) 22 245 155 485 7
Wallpres Mini 2000 2 3.0 0.035 0.3 15 (1/2’’) 15 (1/2’’) 22 245 155 485 8
Wallpres Midi 1000 1 2.5 0.37 2.6 15 (1/2’’) 15 (1/2’’) 22 240 230 485 14
Wallpres Midi 2000 2 2.5 0.37 x2 2.6 x2 15 (1/2’’) 15 (1/2’’) 22 360 240 485 19
32
FeaturesSet point and differential can be adjusted with an accuracy of 0.1 bar. High pressure and Low pressure alarms can be set with an accuracy of 0.1 bar. Alarm relay and onboard buzzer, with auto reset. Dry run protection with auto reset. (Low level switch). Flood protection-Maximum pump run timer can be set in increments of 10 minutes up to 990 minutes and 0 to disable function. Single or dual pump, configurable in the parameters. Auto change over on dual pump setting. Pump current monitoring will detect a fault (excess current) and will isolate the pump and sound alarm. On dual pump versions it will automatically activate the second pump until the process is complete.Continuous pressure displayed on screen. Hours run for each pump. Log of number of alarms. Alarm messages displayed on screen. Internal buzzer with mute and reset. Activation delay to stop false starts.Common alarm volt free or poweredoutput . Switch able between N/O or N/C.3 digit high visibility LED display.Intelligent overrun on pump to preventrepetitive starts and guarantee set point is achieved. 60 Day pulse of pump to prevent seizing and flush pump. Keypad lock function to prevent tampering. Safe low voltage user interface. CE and EMC approved.Proven reliable technology.
ApplicationsESPA Pressurisation equipmentautomatically controls the pressure in asealed system delivering water at a predetermined pressure.Once the system has been filed theESPRES will take over and maintainthe optimum system conditions.Should a loss of water occur in the system, for any reason, the builtin electronic pressure sensor will detectthe drop in pressure and automaticallystart the pump restoring the system tothe original cold fill pressure.All units incorporate dry run protection.If the supply tank should run dry the pump will automatically stop,preventing serious damage.
Espres Delux versions have additional volt free contacts:Common fault.High pressure.Low pressure.Pump fault.Pressure transducer.
Espres/Espres Delux Building Services
Floor mounted pressurisation unit
C F 5 BarC F 3.5 Bar
Performance curves at 2900 rpm Performance curves at 2900 rpm
Technical features
ModelI [A] P2
Outlet CF Max Length Width Height Weight1~ 230 V [kW]
Espres 1000F/Espres 1000F Delux 2.3 0.37 1/2’’ 3.5 Bar 310 470 790 30
Espres 2000F/Espres 2000F Delux 2.3 2x 0.37 1/2’’ 3.5 Bar 310 470 790 38
Espres 1000FH/Espres 1000FH Delux 3.4 0.5 1/2’’ 5 Bar 310 470 790 32
Espres 2000FH/Espres 2000FH Delux 3.4 2x 0.5 1/2’’ 5 Bar 310 470 790 44
33
ApplicationsCompact, totally enclosed digital pressurisation units with pressure transducers and a user friendly microprocessors for use on the two sealed systems in order to provide a minimum system pressure requirement to each application.
InstalationThe Espres Delux Twin system unit should be connected to the system at the same point as the expansion vessel to provide a neutral pressure reading.
OptionsFlood protection.Pump pulse.Service reminder.
FeaturesSystem quick fill mode.Password protection for parameter entry.Pressure settings in 0.1 bar increments.Event logging for pump start, pump runhours counter, electrical interruption &common alarm.Volt free contacts for common fault, highpressure, low pressure, pump fault andpressure transducer.
Espres Delux Twin System Building Services
Floor mounted pressurisation unit
Technical specifications
Espres Delux Twin System
Order code Espres Delux Twin System
Pump quantity 2
Maximum delivery pressure 2.5 bar (g)
Maximum working pressure 10 bar (g)
Electricalr requirements 230 V, 50 Hz, 1 phase
Power consumption 2x 0.37 kW
Full load current 2x 2.5 a
Noise output < 75 dBA
Break tank capacity 18 Litres
Fluid category protection 5 AB Weir overflow air gap
Model System Mains supply Drain Widht Depth Height [Kg]
Espres Delux Twin System 2x 15 (1/2’’) 15 (1/2’’) 22 470 320 800 28
Dimensions and weights
34
ApplicationsCompact, totally enclosed digital pressurisation units with vacuum degasser for use sealed systems in order to provide a minimum systempressure requirement and effective dissolved gas removal.
InstalationThe Espres Delux Plus unit should be connected to the system at the same point as the expansion vessel to provide a neutral pressure reading.The two system connections must be installed on the return header to the heat exchanger approx 0.5 m apart.
OptionsFlood protection.Pump pulse.Service reminder.
FeaturesSystem quick fill mode.Password protection for parameter entry.Pressure settings in 0.1 bar increments.Event logging for pump start, pump runhours counter, electrical interruption &common alarm.Volt free contacts for common fault, highpressure, low pressure, pump fault andpressure transducer.Individual controllers for pressurisationand degassing function.Vacuum degassing, turbo and normalInterval modes.
Espres Delux Plus 150D Building Services
Wall mounted pressurisation units with vacuum degasser
Technical specifications
Espres Delux Plus 150D
Maximum system volume 50.000 litres
Working pressure range 1 - 5 bar (g)
System temperature range 0 - 90 °C
Ambient temperature range 0 - 45 °C
Noise rating Approx. 75 dB(A)
Electrical requirements 230 V / 50 Hz
Full load current 3.4 amps
Power used 0.5 kW
Fuse rating 13 amps
Model System Mains supply Overflow Widht Depth Height [Kg]
Espress Delux Plus 150 D 2x 15 (1/2’’) 15 (1/2’’) 22 410 290 485 22
Dimensions and weights
Espres Delux Plus 150D
Safety rating IP 54
Maximum turbo rutine 168 hours (1 week)
Maximum normal downtime 180 minutes (3 hours)
Control interface RS 485
Volt free contacts Common fault contact
Maximum delivery pressure 5 bar(g) Cold fill
Maximum working pressure 10 bar(g)
Break tank capacity 4 Litres
Fluid category protection 5 AB Weir overflow air gap
35
ApplicationsCompact, totally enclosed digital pressurisation units with vacuum degasser for use sealed systems in order to provide a minimum systempressure requirement and effective dissolved gas removal.
InstalationThe Espres Delux Plus unit should be connected to the system at the same point as the expansion vessel to provide a neutral pressure reading.The two system connections must be installed on the return header to the heat exchanger approx 0.5 m apart.
OptionsFlood protection.Pump pulse.Service reminder.
FeaturesSystem quick fill mode.Password protection for parameter entry.Pressure settings in 0.1 bar increments.Event logging for pump start, pump runhours counter, electrical interruption &common alarm.Volt free contacts for common fault, highpressure, low pressure, pump fault andpressure transducer.Individual controllers for pressurisationand degassing function.Vacuum degassing, turbo and normalInterval modes.
Espres Deluxe Plus 250/280D Building Services
Floor and wall mounted pressurisation units with vacuum degasser
Technical specifications
Espres Delux Plus 250 D
Maximum system volume 300.000 Litres
Working pressure range 1 - 6 bar(g)
System temperature range 0 - 90 °C
Ambient temperature range 0 - 45 °C
Noise rating Approx. 75 dB(A)
Electrical requirements 1x 230 V / 50 Hz
Full load current 2x 3.4 amps
Power used 2x 0.5 kW
Fuse rating 13 amps
Safety rating IP 54
Maximum turbo rutine 168 hours (1 week)
Maximum normal downtime 180 minutes (3 hours)
Control interface RS 485
Volt free contacts Common fault contact
Maximum delivery pressure 6 bar(g) Cold fil
Maximum working pressure 10 bar(g)
Break tank capacity 18 Litres
Fluid category protection 5 AB Weir overflow air gap
Espres Delux Plus 280D
Maximum system volume 300.000 litres
Working pressure range 1 - 8 bar (g)
System temperature range 0 - 90 °C
Ambient temperature range 0 - 45 °C
Noise rating Approx. 75 dB(A)
Electrical requirements 1x 230 V / 50 Hz
Full load current 2x 5.6 amps
Power used 2x 0.75 kW
Fuse rating 13 amps
Safety rating IP 54
Maximum turbo rutine 168 hours (1 week)
Maximum normal downtime 180 minutes (3 hours)
Control interface RS 485
Volt free contacts Common fault contact
Maximum delivery pressure 8 bar(g) Cold fill
Maximum working pressure 10 bar(g)
Break tank capacity 18 Litres
Fluid category protection 5 AB Weir overflow air gap
Model System Mains supply Overflow Widht Depth Height [Kg]
Espres Delux Plus 250D 2x 15 (1/2’’) 15 (1/2’’) 22 480 330 1160 51
Espres Delux Plus 280D 2x 15 (1/2’’) 15 (1/2’’) 22 600 330 1160 61
Dimensions and weights
36
ApplicationsThe Espresmat balanced pressureexpansion units are sized according tothe total system volume and the boiler/chiller load. The Espresmat vessel is 80% efficient irrespective of the staticheight of the system. It is ideal solutionfor large/tall installations wherestandard membrane expansion vesselsare limited.
Description
The Espresmat is an advanced productthat combines a balanced pressuresystem with an effective pressure stepde-aerator function and an inter-linkto a top up pressurisation unit.The real time LCD display shows the status of the mechanical componentswhile monitoring the vessel contentsand the system pressure.
FeaturesOn/Off switch with indicator neon.WRAS approved break tank.WRAS approved float valve.AB air gap with weir overflow,fluid category 5.Pump 230 V / 1ph / 50Hz.Electronic pressure transducer.Normally closed, common faultvolt free boiler interlock.Normally open high pressure,low pressure, transducer healthand pump health volt free contacts.System jogging.Easy setup and commissioning.
Espresmat Building Services
Floor mounted pressurisation unit
8.587.576.565.554.543.532.521.510.50 Flow Rate [m3/h]
Power Fload [MW]9876543210
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
PN 16
PN 10
PN 6
Field of application at 2900 rpm
Curves obtained in accordance with ISO9906, appendix A
37
ApplicationsAccumulation of pressurised waterfor all hydraulic domestic, agriculturaland industrial applications.
FeaturesWRAS approval for drinking water usage, CE marked.The EPDM variable geometry replaceablemembrane provides longer life by eliminating membrane stress throughoutnormal operational cycles. A Schrader valve is fitted to each vessel to provide air pressure adjustment, which should be periodically checked.
AFE/ACS/AFOSB/AFESB Series Building Services
Accumulation of pressurised water
OptionsStainless steel vessels.Stainless steel flange.Fixed membrane.
LimitationsTemperature range:3 to 500 lt (-10 to +100 °C)750 to 4000 lt (-10 to +50 °C)
Technical features
Vertical In-Line
Model Capacity[Ltr]
Max PressBar
Working Temp°C
ConnectionBSPM
Ø[mm]
Length[mm]
Weight[Kg]
ACS 3 3 10 -10 to +100 3/4’’ M 170 245 1.3
ACS 8 8 10 -10 to +100 3/4’’ M 220 305 1.8
ACS CE 18 18 10 -10 to +100 3/4’’ M 260 380 3.2
ACS CE 24 24 10 -10 to +100 1’’ M 260 490 3.6
ACS CE 24 24 10 -10 to +100 3/4’’ M 260 490 3.6
AFC/CAR CE 24 24 16 -10 to +100 3/4’’ M 265 490 7.5
AFE CE 35 35 10 -10 to +100 1’’ M 380 475 5.8
Vertical c/w legs
Model Capacity[Ltr]
Max PressBar
Working Temp°C
ConnectionBSPM
Ø[mm]
Length[mm]
Weight[Kg]
AFE CE 50 50 10 -10 to +100 1’’ M 380 720 8.4
AFE CE 60 ct 60 10 -10 to +100 1’’ M 380 830 10.7
AFE/CAR CE 60 60 16 -10 to +100 1’’ M 380 830 21.5
AFE CE 80 ct 80 10 -10 to +100 1’’ M 460 760 12.2
AFE CE 100 ct 100 10 -10 to +100 1’’ M 460 880 13.5
AFE/CAR CE 100 100 16 -10 to +100 1’’ M 460 880 30.1
AFE CE 150 150 10 -10 to +100 1’’ M 510 1030 23.4
AFE CE 200 200 10 -10 to +100 11/4’’ M 590 1100 33
AFE/CAR CE 200 200 16 -10 to +100 11/4’’ M 590 1100 48.4
AFE CE 300 300 10 -10 to +100 11/4’’ M 650 1280 44.5
AFE/CAR CE 300 300 16 -10 to +100 11/4’’ M 650 1280 67
AFE CE 500 500 10 -10 to +100 11/4’’ M 750 1600 58.5
AFE/CAR CE 500 500 15 -10 to +100 11/4’’ M 750 1600 78.1
AFE CE 750 d750 750 8 -10 to +100 2’’ F 750 2045 153.5
AFE CE 1000 1000 10 -10 to +50 21/2’’ F 800 2130 183.5
AFE CE 1500 1500 10 -10 to +50 21/2’’ F 1000 2130 230.5
AFE CE 2000 2000 10 -10 to +50 DN 65 1100 2550 367
AFE CE 2500 2500 10 -10 to +50 DN 66 1100 2845 440
AFE CE 3000 3000 10 -10 to +50 DN 67 1250 2930 603
AFE CE 4000 4000 10 -10 to +50 DN 68 1450 3030 880
AFE CE 5000 5000 10 -10 to +50 DN 69 1450 3800 980
38
AFE/ACS/AFOSB/AFESB Series Building Services
Technical features
Horizontal
Model Capacity[Ltr]
Max PressBar
Working Temp°C
ConnectionBSPM
Ø[mm]
Length[mm]
Weight[Kg]
AFOSB CE 24 24 8 -10 to +100 3/4’’ M 260 485 4.7
AFOSB CE 24 24 8 -10 to +100 1’’ M 260 485 4.7
AFESB CE 60 ct 60 10 -10 to +100 1’’ M 380 690 10.4
AFESB CE 80 ct 80 10 -10 to +100 1’’ M 460 655 12.3
AFESB CE 100 ct 100 10 -10 to +100 1’’ M 460 780 14
AFESB CE 150 150 10 -10 to +100 1’’ M 510 950 23.5
AFESB CE 200 200 10 -10 to +100 11/4’’ M 590 1000 34.2
AFESB CE 300 300 10 -10 to +100 11/4’’ M 650 1150 44
AFESB CE 500 500 10 -10 to +100 11/4’’ M 750 1420 58
Replacement membranes
Vertical In-Line
Model Capacity[Ltr]
Max PressBar
Working Temp°C
ConnectionBSPM
Ø[mm]
Length[mm]
Weight[Kg]
UMB-8 LX 8 25 90 1’’ M 203 313 3.5
UMB-24 LX 24 25 90 1’’ M 290 447 8.8
Vertical c/w legs
Model Capacity[Ltr]
Max PressBar
Working Temp°C
ConnectionBSPM
Ø[mm]
Length[mm]
Weight[Kg]
SF 60 V 60 25 90 1’’ M 380 810 33
SF 100 V 100 25 90 1’’ M 460 990 51
SF 200 V 200 25 90 11/4’’ M 590 1120 112
SF 300 V 300 25 90 11/4’’ M 640 1230 130
SF 500 V 500 25 90 11/4’’ M 750 1550 202
SF 750 V 750 25 90 2’’ M 750 1950 328
SF 1000 V 1000 25 90 2’’ M 800 2180 344
Model Material dm Tie Rod/Hole
ACS18-24-AFOSB-24 EPDM 110 NO
AFE35 EPDM 110 NO
AFE-AFESB-60-80-100 EPDM 110 NO
AFE-AFESB-AFE/CAR-60-80-100 EPDM 110 YES
AFE-AFESB-150-200 EPDM 110 YES
AFE/CAR-200 EPDM 200 YES
AFE-AFESB-AFE/CAR-300 EPDM 200 YES
AFE-750-1000-1500 EPDM 200 YES
AFE-AFESB-AFE/CAR 500 EPDM 200 YES
Stainless steel flange.Galvanized steel flange.With PP protection.
Tie Rod connection.On top of vessel.
39
ApplicationsSuited for a wide range of applications, including booster systems, thermal expansion, irrigation systems and hydraulic hammer arresting.
MaterialsConstructed of a virgin polypropylene liner combined with an FDA approved high grade butyl diaphragm, which is held against the wall of the tank with a steel clench ring.All internal parts including the air valve are rounded to prevent piercing of the diaphragm.The water connection uniquely provides a dual water/air seal ensuring a complete leak & maintenance free pressure vessel.
Pressure Wave Building Services
Irrigation systems and hydraulic hammer arresting
FeaturesSingle diaphragm design.NSF standard 61, CE/PED, WRAS, ACS, ISO:9001.Gost approved.Patented stainless steel water connection.Virgin polypropylene liner.Two part polyurethane, epoxy primed paint finish.Leak free, o-ring sealed air valve cap.Comprehensive testing.No maintenance.5 Year warranty
Technical features
Vertical In-Line
Model Capacity[Ltr]
Max PressBar
Connection GBSPM
Ø[cm]
Length[cm]
Weight[Kg]
PWB 2 LX 2 10 1’’ M 12.7 18.3 1
PWB 4 LX 4 10 1’’ M 16.2 25.8 1.7
PWB 8 LX 8 10 1’’ M 20.3 31.7 2.6
PWB 12 LX 12 10 1’’ M 24.4 36.6 3.2
PWB 18 LX 18 10 1’’ M 27.9 36.8 4.3
PEWB 24 LX 24 10 1’’ M 28 36 4.5
PWB 35 LX 35 10 1’’ M 31.8 48.1 7.1
Vertical c/w base
Model Capacity[Ltr]
Max PressBar
Connection GBSPM
Ø[cm]
Length[cm]
Weight[Kg]
PWB 35 LV 35 10 1’’ M 31.8 55.5 7.5
PWB 60 LV 60 10 1’’ M 38.8 62.6 12.3
PWB 80 LV 80 10 1’’ M 38.8 79 16.7
PWB 100 LV 100 10 1’’ M 43 80.4 18.9
PWB 150 LV 150 10 1’’ M 43 107 26
Horozontal
Model Capacity[Ltr]
Max PressBar
Connection GBSPM
Ø[cm]
Length[cm]
Weight[Kg]
PWB 20 LH 20 10 1’’ M 43.9 28.9 6.1
PWB 24 LH 24 10 1’’ M 44.4 31,7 6.5
PWB 35 LH 35 10 1’’ M 48.1 35.4 7.9
PWB 60 LH 60 10 1’’ M 52.8 41.4 12.5
PWB 80 LH 80 10 1’’ M 72.4 41.4 17.5
PWB 100 LH 100 10 1’’ M 72.4 48.2 19.2
40
ApplicationsSuited for a wide range of applications, including booster systems, thermal expansion, irrigation systems and hydraulic hammer arresting.
MaterialsEfficient and cost effective.Designed with a patented controlled action CAD2.Diaphragm assembly.Features a chlorine resistant 100% butyl diaphragm.With a precision moulded copolymer polypropylene.Liner for superior air and water separation.Constructed with a FDA approved high grade butyl.The diaphragm assembly seals water in a true non-corrosive chamber.
Challenger Building Services
Irrigation systems and hydraulic hammer arresting
FeaturesSingle diaphragm design.NSF standard 61, CE/PED, WRAS, ACS, ISO:9001.Gost approved.Stainless steel water connection.Virgin polypropylene liner.Two part polyurethane, epoxy primed paint finish.Leak free, o-ring sealed air valve cap.Comprehensive testing.No maintenance.5 Year warranty.
Technical features
Vertical c/w base
Model Capacity[Ltr]
Max PressBar
Connection GBSPM
Ø[cm]
Length[cm]
Weight[Kg]
GCB 200LV 200 10 11/4’’ M 53.3 103.3 34.3
GCB 250LV 240 10 11/4’’ M 53.3 121.2 36.5
GCB 300LV 310 10 11/4’’ M 53.3 150 45.4
GCB 450LV 450 10 11/4’’ M 66 152.9 69.3
41
Other Vessels Building Services
Irrigation systems and hydraulic hammer arresting
Pressure Wave vertical & horizontal pressure vessels 16 bar.Versions with EPDM membranes.Maximum temperature 90 °C.Vertical range 8, 18, 24, 60, 80, & 100 litres.Horizontal range 24.Five year warranty.
Pressure Wave vertical & horizontal pressure vessels 25 bar.versions with EPDM membranes.Maximum temperature 90 °C.Vertical range 8, 18, 24, 60, 80, & 100 litres.Horizontal range 24.
Pressure vessels for solar system available on request.
A range of stainless steel expansion vessels in AISI 304 or AISI 316, horizontal or vertical with Butyl or EPDM membranes.Maximum service pressure of 14 bar, with a high pressure 16 & 25 bar versions available on some models.The ranges are 2 to 500 Litres for vertical mounted and 20 to 500 litres for horizontal.
42
43
ACCESSORIES
44
Accessories Building Services
Flexible connectors (W.R.A.S Aproved)
Max workingJP20BS
350
Test
24 bar
24 bar
24 bar
24 bar
24 bar
24 bar
24 bar
24 bar
24 bar
24 bar
16 bar
16 bar
16 bar
16 bar
16 bar
16 bar
16 bar
16 bar
16 bar
16 bar
JP23VS
130
130
130
130
130
130
200
200
200
50 mm
50 mm
65 mm
80 mm
100 mm
125 mm
150 mm
200 mm
250 mm
300 mm
Model
Installed length
JP20BS: Stainless steel screwed connector c/w socket m/f.JP23VS: Stainless steel flanged PN 16 connector tied.Steel fanged flexibles with rubber belows available on request.
Floating level switchThe ZIN 15/10 T level regulator is a float switch which allows the booster set to not start when the breaktank is empty. (Low water protection).
Pressure transducersSeries 511 stainless steel pressure transducers c/w 1.5 m of cable and are available in several different pressure ranges: 0-4 bar, 0-6 bar, 0-10 bar, 0-16 bar and 0-25 bar.
Danfos stainless steal pressure transducer c/w 1.5 m of cable with pressure range
D06F
D06F
D06F
D06F
D06F
D06F
D15P
D15P
D15P
Model Size Material
1/2”
3/4”
1”
1 1/4”
1 1/2”
2”
50 mm
65 mm
80 mm
Brass
Brass
Brass
Brass
Brass
Brass
Cast iron
Cast iron
Cast iron
Pressure reducing valve
Brass and cast iron pressure reducing valves to reduce outlet pressure between 1.5 - 8 bar, maximum inlet pressure of 25 bar for brass and 16 bar for cast iron.
45
RBX Surge Arrestor Building Services
Combination Surge Arrestor & Air Release valve
ApplicationsDampens effect of water hammer at pump start up.Provides vacuum protection when the pump stops and the riser drains.
DescriptionIncorporates three design features toautomatically protect building risers under all operating conditions, surgeand water hammer phenomena.Effective de-aeration under all pipelineflow and operating conditions.Ensures the least possible resistance tothe intake of air and the least possiblenegative pressure within a draining riser.Developed to provide the optimum usable and safe performance relative to al functions.
InstallationTo be installed at the top of each riserto protect the complete riser systemAn isolating valve should be installedto facilitate maintenance.The riser must be chlorinated andthoroughly flushed before surge arrestors are fitted.
BenefitsVery low milli second reaction time spanWRAS approved.
Dimensions and weights
Model Pressure Size Max riser Ø A [mm] B [mm] C [Kg]
025RBX PN25 1’’ 200 120 335 1’’BSP 9
050RBX PN25 2’’ 400 165 395 2’’BSP 9.5
A
B
Locking NutsStainless Steel AISI 304
Locating LugsStainless Steel AISI 304
Top CoverKumbo ABS 780
Assembly ScrewsCheeseheadStainless Steel AISI 304
Barrel SealKlingersil C4430Gasket
O - Ring SealEPDM Rubber
Anti Shock OrificeHigh Density Polyethylene
O - Ring SeatEPDM Rubber
BarrelStainless Steel AISI 304L
Lower FloatHigh Density Polyethylene
Float GuideStainless Steel AISI 304
Baffer SpacerHigh Density Polyethylene
Support ScrewCheeseheadStainless Steel AISI 304
Bias SpringStainless Steel AISI 304
NutsStainless Steel AISI 304
WasherStainless Steel AISI 304
Top FloatHigh Density Polyethylene
NozzleStainless Steel AISI 304
Nozzle SeatStainless Steel AISI 304
Tie RodsStainless Steel AISI 304
Baffle PlateStainless Steel AISI 304
Optional Test Cock Connection1/4’’ BSP/NPT Female
Lower FlangeMild Steel BS 4360 Grade 43AFusion Bonded Epoxy Powder Coatedalternatively Stainless Steel AISI 304Screwed BSP (ISO R7)/NPT male
Top FlangeMild Steel BS 4360 Grade 43AFusion Bonded Epoxy Powder Coatedalternatively Stainless Steel AISI 304
Materials
46
Air & Dirt separation Building Services
For Heating & Venitilation Industry
MAGVENT – An aid to system cleaning. Removalof potentially damaging particles from hot & cold watersystems. All magnetite which flows through this unit willbe removed 100%. Sizes range between 50-450 mm forcombined unit air (de-aerator) & dirt separator or just dirt separator. Fixed or demountable models.
CLEANVENT – Combines the removal of air anddirt through a single unit. Installed at the hottestpoint in the system, the CLEANVENT will eliminatethese microbubbles from heating & chilled watersystems. Will also remove dirt particles down to 10 microns.
DOSING POTS – Are required to feed liquid chemicals such as corrosion inhibitors into closed systems.The DOSING POTS consist of a mild steel vessel with inlet (return) and outlet (flow) valves, drain valve, filling valve, steel tundish, air release valve, wall mounting brackets and a non-return valve. Sizes range from 3.5-25 Ltrs.
PLEASE ASK A MENBER OF OUR SALES TEAM FOR MORE INFORMATION
47
PUMPS
48
Glandless Circulators Building Services
MMT high efficiency ECM canned motor and permanent magnets. Variable pressure control and constant speed.
ApplicationsAll heating systems, air conditionsystems, closed loop cooling systemsand industrial circulatory systems.
MaterialsHousing-Cast iron.Impeller-Polyamide.Shaft-Ceramics.Ventricular wall=Stainless Steel.Rotor Can-Stainless steel.
DescriptionHigh efficiency EMC technology.Energy savings.Proportional pressure control.Constant speed.Automatic venting.Low noise operation.
Operation∆p-Proportional pressure controlAfter selecting level, pump recognises thelowest resistance of the system andautomatically adjusts it’s own strain.∆p- Constant speedAfter selection, pump works in threedifferent speeds.
MotorWith permanent magnets.Energy index EE≤0.20.Built-in motor protection.Control ∆p or constant speed.IP 44 protection.Class F insulation.Voltage 1~230 V, 50-60 Hz.Optional analogue input signal 0-10 V.
EquipmentUnions (optional extra).
LimitationsLiquid temperature range +5 to +95 °C. Water mixed with glycol, parameters must be checked with over 20% of glycol.Pure non-explosive liquid media freefrom mineral oils and without solids.Minimum inlet pressure 0.05 bar <75 °C,0.28 bar <90 °C.
Performance curves
NMT-/40 NMT-/60 NMT-/80
49
Glandless Circulators Building Services
Dimensions
Model DN D2 L [mm] b1 [mm] b2 [mm] l [mm] a [mm]
NMT40 15/20/25/32 1’’/5/4’’/6/4’’/2’’ 130/180 80 48 108 27/29/32
NMT60 15/20/25/32 1’’/5/4’’/6/4’’/2’’ 130/180 80 48 108 27/29/32
NMT80 15/20/25/32 1’’/5/4’’/6/4’’/2’’ 130/180 80 48 108 27/29/32
D2
L
b1 b2
a I
DN
Technical features
Model EEI Connection DN Pump lenght[mm] N. Pressure Weight [Kg]
NMT 15/40-130 0.2 Rp 1/2” 15 130 PN 10 bar 1.9
NMT 15/60-130 0.22 Rp 1/2” 15 130 PN 10 bar 1.9
NMT 20/40-130 0.2 Rp 3/4” 20 130 PN 10 bar 2
NMT 20/60-130 0.22 Rp 3/4” 20 130 PN 10 bar 2
NMT 25/40-130 0.2 Rp 1” 25 130 PN 10 bar 2.1
NMT 25/60-130 0.22 Rp 1” 25 130 PN 10 bar 2.1
NMT 20/40-180 0.2 Rp 3/4” 20 180 PN 10 bar 2.3
NMT 20/60-180 0.22 Rp 3/4” 20 180 PN 10 bar 2.3
NMT 25/40-180 0.2 Rp 1” 25 180 PN 10 bar 2.4
NMT 25/60-180 0.22 Rp 1” 25 180 PN 10 bar 2.4
NMT 32/40-180 0.2 Rp 11/4” 32 180 PN 10 bar 2.5
NMT 32/60-180 0.22 Rp 11/4” 32 180 PN 10 bar 2.5
NMT 32/80-180 0.24 Rp 11/4” 32 180 PN 10 bar 2.5
NMT ER versions available with analogue signal 0-10 V.
50
Glandless Circulators Building Services
MMT SMART high efficiency ECM canned motor and permanent magnets. Variable pressure control and constant speed.
MotorWith permanent magnets.Energy index EE1≤0.21.Built-in motor protection.Three control modes (proportional head,constant head & constant speed).IP 44 protection.Class F insulation.Voltage 1~230 V, 50-60 Hz.Optional NMTC pump withcommunication module (c).
EquipmentUnions (optional extra).Counter flanges (optional extra).
LimitationsLiquid temperature range +5 to +95 °C. Water mixed with glycol, parameters must be checked with over 20% of glycol.Pure non-explosive liquid media freefrom mineral oils and without solids.Minimum inlet pressure 0.05 bar <75 °C,0.28 bar <90 °C.
ApplicationsAll heating systems, air conditionsystems, closed loop cooling systemsand industrial circulatory systems.
MaterialsHousing-Cast iron.Impeller-PES.Shaft-Stainless steelBearings-Graphite.Ventricular wall=Stainless steel.Rotor Can-Stainless steel.
DescriptionHigh efficiency EMC technology.Energy savings.LED display for control.Proportional pressure control.Constant speed.Automatic venting.Low noise operation.
OperationAuto mode (default).Proportional pressure control.Constant pressure control.Constant speed.Night mode.
SMART 60 SMART 80
Performance curves
SMART 40
New twin pump models NMTD 32-100R & NMTD 40-100F, check with our sales team for more information.
51
Glandless Circulators Building Services
Performance curves
SMART 100 SMART 100F SMART 120F
Technical features and dimensions
Model EEI Connection DN D2 I [mm] N. Pressure Weight [Kg]
SMART 25-40/60/80 0.21 25 mm 25 6/4” 190 PN 10 bar 4
SMART 32-40/60/80 0.21 32 mm 32 2” 190 PN 10 bar 4.1
SMART C 25-40/60/80 0.21 25 mm 25 6/4” 222 PN 10 bar 4.2
SMART C 32-40/60/80 0.21 32 mm 32 2” 222 PN 10 bar 4.3
DND2
D2
117 53 I
180
52
Glandless Circulators Building Services
Technical features and dimensions
Model EEI Connection DN h [mm] a [mm] N. Pressure Weight [Kg]
SMART 40-100F 0.21 40 mm 40 222 75 PN 10 bar 7.4
SMART 50-100F 0.21 50 mm 50 222 82.5 PN 10 bar 8.5
SMART C 40-100F 0.21 40 mm 40 222 75 PN 10 bar 7.6
SMART C 50-100F 0.21 50 mm 50 222 82.5 PN 10 bar 8.7
100
h
a I
117 DN
Technical features and dimensions
Model EEI Connection DN h [mm] I [mm] a [mm] N. Pressure Weight [Kg]
SMART 40-120F 0.21 40 mm 40 250 228 75 PN 10 bar 9
SMART C 40-120F 0.21 40 mm 50 250 260 82.5 PN 10 bar 9
H
a I
53
Glandless Circulators Building Services
MNT LAN F high efficiency ECM canned motor and permanet magnets. Variable pressure control and constant speed
MotorWith permanent magnets.Energy index EE1≤0.21.Built-in motor protection.Three control modes (proportional head,constant head & constant speed).IP 44 protection.Class F insulation.Voltage 1~230 V, 50-60 Hz.Optional NMTC pump withcommunication module.
EquipmentCounter flanges (optional extra).
LimitationsLiquid temperature range +2 to +110 °C. (with max outside temperature up to +40 °C. Water mixed with glycol, parameters must be checked with over 20% of glycol.Pure non-explosive liquid media freefrom mineral oils and without solids.Minimum inlet pressure 0.05 bar <75 °C,0.28 bar <90 °C.
ApplicationsAll heating systems, air conditionsystems, closed loop cooling systemsand industrial circulatory systems.
MaterialsHousing-Cast iron.Impeller-PES.Shaft-Stainless steelBearings-Graphite.Ventricular wall=Stainless steel.Rotor Can-Stainless steel.
DescriptionHigh efficiency EMC technology.Energy savings.LED display for control.Proportional pressure control.Constant speed.Automatic venting.Low noise operation.
OperationAuto mode (default).Proportional pressure control.Constant pressure control.Constant speed.Night mode.
Performance curves
LAN 40 LAN 50
54
Glandless Circulators Building Services
Performance curves
LAN 65 LAN 80/100
Technical features and dimensions
Model Connection DN L [mm] A [mm] B [mm] C [mm] a [mm] N. Pressure Weight [Kg]
NMT LAN 40 40 mm 40 250 189 321 65 PN 10 bar 24
NMTD LAN 40 40 mm 40 250 403 321 65 PN 10 bar 47
NMT LAN 50 50 mm 50 280 189 355 70 PN 10 bar 31
NMTD LAN 50 50 mm 50 280 403 355 70 PN 10 bar 60
NMT LAN 65 65 mm 65 340 189 369 80 PN 10 bar 36
NMTD LAN 65 65 mm 65 340 403 369 80 PN 10 bar 63
NMT LAN 80 80 mm 80 360 189 403 100 PN 6 bar 44
NMT LAN 80 80 mm 80 360 403 403 100 PN 10 bar 44
NMTD LAN 80 80 mm 80 360 189 403 100 PN 6 bar 81
NMTD LAN 80 80 mm 80 360 403 403 100 PN 10 bar 81
NMT LAN 100 100 mm 100 360 189 403 105 PN 10 bar 47
255
DNb1
b4 DN
255h
h1
a I
a
h
h/2
I
55
Glandless Circulators Building Services
SAN high efficiency ECM canned motor and permanet magnets for domestic hot water
MotorWith permanent magnets.Built-in motor protection.Shaftless spherical motor withECM technology.IP 44 protection.Class F insulation.Voltage 1~230 V, 50-60 HzOption with thermostat withtemperature range 20-70 °C.Option with timer.
EquipmentBrass unions (optional extra).
LimitationsLiquid temperature range 95 °C.Water mixed with glycol, parameters must be checked with over 20% of glycol.Pure non-explosive liquid media freefrom mineral oils and without solids.Minimum inlet pressure 0.05 bar <75 °C,0.28 bar <90 °C.
ApplicationsDomestic hot water secondarysystems.
MaterialsHousing-Bronze.Impeller-Polyamide.Bearings-Ceramic.
DescriptionHigh efficiency EMC technology.Energy savings.Four possible performances:B version with bronze housing.BU version with bronze housingand timer.BTU model with bronze housingthermostat & timer.GT version with bronze housingand thermostat.Specially adapted to the independence of lime scale.
OperationThe pump automatically adjusts thepressure according to the systemresistance. The timer installation ispossible for selecting the starting time of the operation and adjusting the thermostat.
Model Connection DN Pump Lenght N. Pressure A [mm] B [mm] C [mm] Weight [Kg]
ECO SAN 15/15B 1/2’’ 15 65mm PN 10 bar 163 150 110 0.9
ECO SAN 15/15BU 1/2’’ 15 65mm PN 10 bar 163 150 110 1
ECO SAN 15/15BTU 1/2’’ 15 65mm PN 10 bar 163 150 110 1
ECO SAN 15/15BTU 1/2’’ 15 65mm PN 10 bar 163 150 110 1
Technical features and dimensions
Performance curves
0.90.750.60.450.30.150 Q [m3/h]
1
1
1.2
0.8
0.6
0.4
0.2
0
H[m]A
118
G1/2’’
105
B
C
76
35
65 72
56
Glandless Circulators Building Services
SAN NMT high efficiency ECM canned motor and permanet magnets for domestic hot water
EquipmentUnions (optional extra).
LimitationsLiquid temperature range +5 to +95 °C.Water mixed with glycol, parameters mustbe checked with over 20% of glycol.Pure non-explosive liquid media freefrom mineral oils and without solids.Minimum inlet pressure 0.05 bar <75 °C,0.28 bar <90 °C.
ApplicationsDomestic hot water secondarysystems.
MaterialsHousing-Bronze.Impeller-Polyamide.Shaft-Ceramics.Ventricular wall=Stainless steel.Rotor Can-Stainless steel.
DescriptionMulti speed control.
MotorWith permanent magnets.Built-in motor protection.IP 44 protection.Class F insulation.Voltage 1~230 V, 50-60 Hz.
Technical features and dimensions
Performance curves
SAN NMT 40 SAN NMT 80SAN NMT 60
Model Connection DN Pump Lenght D2 b1 [mm] b2 [mm] l [mm] a [mm] N. Pressure [Kg]
SAN NMT ECO 20/40-130 3/4’’ 20 130 mm 11/4’’ 80 48 108 29 PN 10 bar 2.1
SAN NMT ECO 25/40-130 1’’ 25 130 mm 11/2’’ 80 48 108 32 PN 10 bar 2.2
SAN NMT ECO 20/60-130 3/4’’ 20 130 mm 11/4’’ 80 48 108 29 PN 10 bar 2.1
SAN NMT ECO 25/60-130 1’’ 25 130 mm 11/2’’ 80 48 108 32 PN 10 bar 2.2
SAN NMT ECO 20/80-130 3/4’’ 20 130 mm 11/4’’ 80 48 108 29 PN 10 bar 2.1
SAN NMT ECO 25/80-130 1’’ 25 130 mm 11/2’’ 80 48 108 32 PN 10 bar 2.2
57
Glandless Circulators Building Services
SAN NMT ECO high efficiency ECM canned motor and permanet magnets. Variable pressure control and constant speed
MotorWith permanent magnets.Energy index EE≤0.20.Built-in motor protection.Control ∆p or constant speed.IP 44 protection.Class F insulation.Voltage 1~230 V, 50-60 Hz.Optional analogue input signal 0-10 V.
EquipmentUnions (optional extra).
LimitationsLiquid temperature range +5 to +95 °C. Water mixed with glycol, parameters must be checked with over 20% of glycol.Pure non-explosive liquid media freefrom mineral oils and without solids.Minimum inlet pressure 0.05 bar <75 °C,0.28 bar <90 °C.
ApplicationsDomestic hot water secondarysystems.
MaterialsHousing-Bronze.Impeller-Polyamide.Shaft-Ceramics.Ventricular wall=Stainless steel.Rotor Can-Stainless steel.
DescriptionHigh efficiency EMC technology.Energy savings.Proportional pressure control.Constant speed.Automatic venting.Low noise operation.
Operation∆p-Proportional pressure controlAfter selecting level, pump recognises the lowest resistance of the system and automatically adjusts it’s own strain.∆p- Constant speedAfter selection, pump works in threedifferent speeds.
SAN NMT ECO 60 SAN NMT ECO 80
Performance curves
SAN NMT ECO 40
58
Glandless Circulators Building Services
Technical features and dimensions
Model Connection DN Pump Lenght D2 b1 [mm] b2 [mm] l [mm] a [mm] N. Pressure [Kg]
SAN NMT ECO 20/40-130 3/4’’ 20 130 mm 1 1/4’’ 80 48 108 29 PN 10 bar 2.1
SAN NMT ECO 25/40-130 1’’ 25 130 mm 1 1/2’’ 80 48 108 32 PN 10 bar 2.2
SAN NMT ECO 20/60-130 3/4’’ 20 130 mm 1 1/4’’ 80 48 108 29 PN 10 bar 2.1
SAN NMT ECO 25/60-130 1’’ 25 130 mm 1 1/2’’ 80 48 108 32 PN 10 bar 2.2
SAN NMT ECO 20/80-130 3/4’’ 20 130 mm 1 1/4’’ 80 48 108 29 PN 10 bar 2.1
SAN NMT ECO 25/80-130 1’’ 25 130 mm 1 1/2’’ 80 48 108 32 PN 10 bar 2.2
D2
L
b1 b2
a I
DNDN 20
D2
L
b1 b2
a I
DNDN 25
59
Glandless Circulators Building Services
GHN SOL canned motor and permanet magnets for domestic solar systems
EquipmentUnions (optional extra).
LimitationsLiquid temperature range -10 to +110 °C. Environment temperature range 0- +40 °C.Max working pressure at 50/80/100.
ApplicationsDomestic solar systems.
MaterialsHousing-Cast Iron.Impeller-Polyamide/Noryl.Shaft-Ceramics.Ventricular wall=Stainless steel.Rotor Can-Stainless steel.
DescriptionSingle head glandless.Flow range 3 – 5.5.m3/h.Max head 7 mtr.System pressure PN 10 bar.Two speed.Port to port length 130 & 180 mm.
MotorWith permanent magnets.IP 44 protection.Class H insulation.Power supply 230 V / 1ph / 50Hz.
GHN SOL 60 GHN SOL 70
Performance curves
GHN SOL 40
60
Glandless Circulators Building Services
Technical features and dimensions
D2
L
b1 b2
a I
DNDN 15
D2
L
b1 b2
a I
DNDN 25
Model Connection DN Pump Lenght N. Pressure [Kg]
GHN SOL 15/40-130 1/2’’ 15 130 mm PN 10 bar 2.1
GHN SOL 15/60-130 1/2’’ 15 130 mm PN 10 bar 2.1
GHN SOL 15/70-130 1/2’’ 15 130 mm PN 10 bar 2.3
GHN SOL 25/40-130 1’’ 25 130 mm PN 10 bar 2.3
GHN SOL 25/60-130 1’’ 25 130 mm PN 10 bar 2.3
GHN SOL 25/70-130 1’’ 25 130 mm PN 10 bar 2.4
GHN SOL 25/40-180 1’’ 25 180 mm PN 10 bar 2.6
GHN SOL 25/60-180 1’’ 25 180 mm PN 10 bar 2.6
GHN SOL 25/70-180 1’’ 25 180 mm PN 10 bar 2.7
61
ApplicationsWater supply and pressure boosting, irrigation. Circulation of hot water and liquid refrigerants in air conditioning systems.
MotorThree-phase asynchronous motor. IP 55 protection. Class F insulation. Standard voltage:230/400 V 50 Hz up to 4 kW,400/690 V 50 Hz for higher power. FL: 2 pole motors (2900 rpm).FL4: 4 pole motors (1450 rpm).Efficiency IE2.Counter flanges available on request.
FL/FL4 Building Services
Single In line electric monobloc pumps in cast iron
MaterialsPump body, shield, lantern and cover in cast iron.Impeller: in cast iron (stainless steel or bronze on request at extra cost).Shaft: AISI 420 stainless steel.Mechanical seal: silicon carbide/silicon carbide.
LimitationsMaximum ambient temperature: +40 °C. Temperature of pumped liquid:-10 °C +130 °C.Maximum operating pressure: 10 bar. Maximum liquid viscosity: 5 °C.
Field of application at 2900 rpm
8
10
15
20
25
30
40
50
H[m]
FL
1.2 3 6 12 24 60 120 Q [m3/h]
Field of application at 1450 rpm
1.23
4
5
6
8
10
15
20
H[m]
3 6 12 24 60 120 180 Q [m3/h]
FL4
Curves obtained in accordance with ISO9906, appendix A
62
FL/FL4 40 Building Services
Hydraulic performance table at 2900 rpm
ModelI [A] P2 l/min 0 100 125 150 175 200 225 250 300 350 400 450 500
3~ 400 V [kW] [HP] m3/h 0 6 7.5 9 10.5 12 13.5 15 18 21 24 27 30
FL 40x100B 1.5 0.55 0.75
mw
c
12.1 11.8 11.4 11 10.5 9.9 9.3 8.6 7
FL 40x100A 1.7 0.75 1 14 13.5 13.3 13 12.5 12 11.4 10.7 9 7
FL 40x125C 1.7 0.75 1 17 15.3 14.5 13.7 12.7 11.6 10.4 9 6
FL 40x125B 2.5 1.1 1.5 21.5 20.5 20 19 18 17 15.8 14.5 11.3 7.5
FL 40x125A 3.4 1.5 2 25 24.5 24.1 23.5 22.8 22 21 19.5 16.5 13
FL 40x160C 4.4 2.2 3 29 28.5 28 27.5 26.5 25.5 24.4 23 20 15
FL 40x160B 5.9 3 4 34.2 33.5 33 32.5 32 31 30 29 26 22.5
FL 40x160A 5.9 3 4 38.5 38 37.5 37 36 35 34 33 30 26.5
FL 40x200C 7.8 4 5.5 47 47 46.5 45.8 45 44 43 42 39.5 36.3 33
FL 40x200B 10.4 5.5 7.5 55 55 54.7 54.3 53.5 53 52 51 48.5 45.7 42.3
FL 40x200A 14.2 7.5 10 62.5 62 61.5 61 60 59.2 58.2 57.3 55 52.5 49 45 40
Hydraulic performance table at 1450 rpm
ModelI [A] P2 l/min 0 40 50 75 100 125 150 175 200 225 250 300
3~ 400 V [kW] [HP] m3/h 0 2.4 3 4.5 6 7.5 9 10.5 12 13.5 15 18
FL4 40x100X 0.9 0.25 0.33
mw
c
3.7 3.65 3.6 3.45 3.3 2.9 2.5
FL4 40x125Y 0.9 0.25 0.33 4.8 4.5 4.4 4 3.5 2.95 2.2
FL4 40x125X 0.9 0.25 0.33 6.2 6.2 6.1 5.8 5.3 4.6 3.8 2.9
FL4 40x160X 1.3 0.37 0.5 9.5 9.4 9.2 8.9 8.4 7.7 6.9 5.8 4.7
F4L 40x200Y 1.8 0.75 1 13.5 13 12.8 12.4 11.9 11.3 10.6 9.8 9 8 6
FL4 40x200X 2.5 1.1 1.5 15 14.6 14.3 13.9 13.3 12.6 11.8 10.9 10 8
Dimensions and weights
Model DNmDNa A B C D E F G H I [Kg]
FL 40x100B 40 PN6 445 90 355 184 77 107 260 140 120 16
FL 40x100A 40 PN6 445 90 355 184 77 107 260 140 120 16
FL 40x125C 40 PN16 425 100 325 200 93 107 300 160 140 24
FL 40x125B 40 PN16 445 100 345 211 93 118 300 160 140 25
FL 40x125A 40 PN16 445 100 345 211 93 118 300 160 140 26
FL 40x160C 40 PN16 445 100 345 226 108 118 320 170 150 30
FL 40x160B 40 PN16 485 100 385 257 108 149 320 170 150 35
FL 40x160A 40 PN16 485 100 385 257 108 149 320 170 150 36
FL 40x200C 40 PN16 525 100 425 286 127 159 380 200 180 50
FL 40x200B 40 PN16 535 100 435 286 127 159 380 200 180 55
FL 40x200A 40 PN16 535 100 435 286 127 159 380 200 180 55
FL4 40x100X 40 PN6 445 90 355 184 77 107 260 140 120 16
FL4 40x125Y 40 PN6 425 100 325 200 93 107 300 160 140 20
FL4 40x125X 40 PN16 425 100 325 200 93 107 300 160 140 20
FL4 40x160X 40 PN16 425 100 325 215 108 107 320 170 150 23
F4L 40x200Y 40 PN16 445 100 345 245 127 118 380 200 180 30
FL4 40x200X 40 PN16 445 100 345 245 127 118 380 200 180 31
DN a b c d e
40 PN6 80 100 130 4 14
40 PN10 88 110 150 4 18
n°d1 holes ø e
DN a b c
G
I H
F
C
F
B
D
A
63
FL/FL4 50 Building Services
Hydraulic performance table at 2900 rpm
Hydraulic performance table at 1450 rpm
Dimensions and weights
n°d1 holes ø e
DN a b c
G
I H
F
C
F
B
D
A
ModelI [A] P2 l/min 0 250 300 350 400 450 500 600
3~ 400 V [kW] [HP] m3/h 0 15 18 21 24 27 30 36
FL 50x125C 3.4 1.5 2
mw
c
16.5 15.5 15 14.1 13 11.8 10.5 7
FL 50x125B 4.4 2.2 3 20 19 18.5 17.5 16.5 15.5 14.5 10.5
FL 50x125A 5.9 3 4 25 24.5 24 23.5 23 22 20.5 17
FL 50x160B 5.9 3 4 31 30 29 28 26.5 25 23 18
FL 50x160A 7.8 4 5.5 38 36.5 35.5 34.5 33.5 32.5 31 27
FL 50x200C 10.4 5.5 7.5 47 45.7 44.2 42.8 41.1 39.2 37 31
FL 50x200B 14.2 7.5 10 51.5 51 50 49 47.5 45 42.5 37
FL 50x200A 14.2 7.5 10 58.5 56.5 55.5 54.5 53 51 49 44
ModelI [A] P2 l/min 0 100 125 150 175 200 225 250 300 350 400
3~ 400 V [kW] [HP] m3/h 0 6 7.5 9 10.5 12 13.5 15 18 21 24
FL4 50x125Y 0.9 0.25 0.33
mw
c
4.8 4.6 4.5 4.3 4.1 3.9 3.6 3.3 2.4
FL4 50x125X 1.3 0.37 0.5 6.4 6.3 6.2 6.1 6 5.8 5.6 5.25 4.4 3
FL4 50x160X 1.6 0.55 0.75 9.2 8.8 8.6 8.3 8 7.7 7.3 6.9 5.9 4.5
F4L 50x200Y 2.5 1.1 1.5 13 12.7 12.4 12.1 11.7 11.2 10.7 10 8.6 6.8
FL4 50x200X 2.5 1.1 1.5 14.5 14.2 14 13.8 13.4 13 12.5 11.8 10.2 8.3 6
DN a b c d e
50 102 125 165 4 18
Model DNmDNa A B C D E F G H I [Kg]
FL 50x125C 50 455 110 345 221 103 118 320 180 140 27
FL 50x125B 50 455 110 345 221 103 118 320 180 140 28
FL 50x125A 50 495 110 385 252 103 149 320 180 140 32
FL 50x160B 50 495 110 385 262 113 149 340 180 160 32
FL 50x160A 50 535 110 425 272 113 159 340 180 160 42
FL 50x200C 50 545 110 435 290 131 159 400 220 180 56
FL 50x200B 50 545 110 435 290 131 159 400 220 180 57
FL 50x200A 50 545 110 435 290 131 159 400 220 180 64
FL4 50x125Y 50 435 110 325 210 103 107 320 180 140 21
FL4 50x125X 50 435 110 325 210 103 107 320 180 140 22
FL4 50x160X 50 435 110 325 220 113 107 340 180 160 25
F4L 50x200Y 50 495 110 385 280 131 149 400 220 180 36
FL4 50x200X 50 495 110 385 280 131 149 400 220 180 36
64
FL/FL4 65 Building Services
Hydraulic performance table at 2900 rpm
Dimensions and weights
n°d1 holes ø e
DN a b c
G
I H
F
C
F
B
D
A
ModelI [A] P2 l/min 0 400 450 500 600 700 800 900 1000
3~ 400 V [kW] [HP] m3/h 0 24 27 30 36 42 48 54 60
FL 65x125C 4.4 2.2 3
mw
c
18.5 17 16.5 16 15 13 11 9
FL 65x125B 5.9 3 4 22.5 21 20.5 20 19 17.5 16 14 12
FL 65x125A 7.8 4 5.5 26.5 25.5 25.3 25 24 23 21.5 20 18
FL 65x160B 10.4 5.5 7.5 33 32.5 32 31.5 30.5 29.5 28 26 23.5
FL 65x160A 14.2 7.5 10 37 37 36.5 36 35 34 32.5 31 29
FL 65x200B 19.8 11 15 52 50.7 50.2 49.5 48 45.6 42.9 39.7 37
FL 65x200A 27 15 20 58.5 58 57.5 57 55 53 50 46.5 42.5
Model DNmDNa A B C D E F G H I [Kg]
FL 65x125C 65 485 140 345 226 108 118 360 205 155 32
FL 65x125B 65 525 140 385 257 108 149 360 205 155 39
FL 65x125A 65 565 140 425 267 108 159 360 205 155 43
FL 65x160B 65 575 140 435 281 122 159 400 220 180 54
FL 65x160A 65 680 140 540 306 122 184 400 220 180 61
FL 65x200B 65 680 140 540 320 136 184 440 240 200 70
FL 65x200A 65 680 140 540 320 136 184 440 240 200 77
FL4 65x125Y 65 465 140 325 215 108 107 360 205 155 25
FL4 65x125X 65 465 140 325 215 108 107 360 205 155 26
FL4 65x160Y 65 480 140 345 240 122 118 400 220 180 32
FL4 65x160X 65 480 140 345 240 122 118 400 220 180 33
F4L 65x200Y 65 525 140 385 285 136 149 440 240 200 38
FL4 65x200X 65 525 140 385 285 136 149 440 240 200 40
DN a b c d e
65 122 145 185 4 18
Hydraulic performance table at 1450 rpm
ModelI [A] P2 l/min 0 200 225 250 300 350 400 450 500 600 700
3~ 400 V [kW] [HP] m3/h 0 12 13.5 15 18 21 24 27 30 36 42
FL4 65x125Y 1.3 0.37 0.5
mw
c
5.4 5.2 5.1 5 4.8 4.5 4.05 3.5
FL4 65x125X 1.6 0.55 0.75 6.5 6.2 6.1 6 5.8 5.5 5.2 4.9 4.4
FL4 65x160Y 1.8 0.75 1 8.2 8.2 8.1 7.9 7.7 7.4 7 6.5 5.9 4
FL4 65x160X 2.5 1.1 1.5 9.1 9 8.9 8.8 8.6 8.4 8.1 7.7 7.2 5.5
F4L 65x200Y 2.5 1.1 1.5 12.5 12.4 12.2 12 11.5 10.8 10 9 8 5.8
FL4 65x200X 3.4 1.5 2 14.4 14.3 14.2 14.1 13.7 13 12.3 11.3 10.2 7.8 5
65
FL/FL4 80 Building Services
Hydraulic performance table at 2900 rpm
Dimensions and weights
n°d1 holes ø e
DN a b c
G
I H
F
C
F
B
D
A
ModelI [A] P2 l/min 0 700 800 900 1000 1250 1500 1750 2000 2250
3~ 400 V [kW] [HP] m3/h 0 42 48 54 60 75 90 105 120 135
FL 80x160C 19.8 11 15
mw
c
31 30.3 30 29.5 29 26.5 24 20.5 16
FL 80x160B 27 15 20 37 36.5 36 35.2 34.5 32.7 30.1 27 23 19
FL 80x160A 27 15 20 42 40.8 40.5 40 39.4 38 35.5 33 29 24
FL 80x200D 27 15 20 44 44 43.5 43 41.5 39 35.5 31.5
FL 80x200C 33.3 18.5 25 51 50.2 49.9 49.5 48.5 46.5 43.5 39.5 35
FL 80x200B 38.6 22 30 57 57 56.5 56 55 53.5 51 47.7 42.5
Hydraulic performance table at 1450 rpm
ModelI [A] P2 l/min 0 300 350 400 450 500 600 700 800 900 1000 1100 1200
3~ 400 V [kW] [HP] m3/h 0 18 21 24 27 30 36 42 48 54 60 66 72
FL4 80x160Y 2.5 1.1 1.5
mw
c
8.7 8.6 8.5 8.4 8.3 8.2 8 7.5 6.8 6 5
FL4 80x160X 3.4 1.5 2 10.3 10.2 10.1 10 9.9 9.8 9.4 9 8.5 7.7 6.5
F4L 80x200Y 5.1 2.2 3 12.6 12.5 12.4 12.3 12.1 11.7 11.1 10.5 9.6 8.5
FL4 80x200X 6.5 3 4 15.4 15.2 15 14.6 14.3 13.6 12.8 12 11
Model DNmDNa A B C D E F G H I [Kg]
FL 80x160C 80 455 110 345 221 103 118 320 180 140 27
FL 80x160B 80 455 110 345 221 103 118 320 180 140 28
FL80x160A 80 495 110 385 252 103 149 320 180 140 32
FL 80x200D 80 495 110 385 262 113 149 340 180 160 32
FL 80x200C 80 535 110 425 272 113 159 340 180 160 42
FL 80x200B 80 545 110 435 290 131 159 400 220 180 56
FL4 80x160Y 80 435 110 325 210 103 107 320 180 140 21
FL4 80x160X 80 435 110 325 210 103 107 320 180 140 22
F4L 80x200Y 80 495 110 385 280 131 149 400 220 180 36
FL4 50x200X 80 495 110 385 280 131 149 400 220 180 36
DN a b c d e
80 138 160 200 4 18
66
FL/FL4 100 Building Services
Hydraulic performance table at 2900 rpm
Dimensions and weights
n°d1 holes ø e
DN a b c
G
I H
F
C
F
B
D
A
ModelI [A] P2 l/min 0 1000 1250 1500 1750 2000 2250 2500 2750 3000 3500
3~ 400 V [kW] [HP] m3/h 0 60 75 90 105 120 135 150 165 180 210
FL 100x160D 19.8 11 15
mw
c
24.8 23.8 23.1 22 20.8 19.5 18 16.5 15
FL 100x160C 27 15 20 29.4 28.5 27.8 27 25.8 24.5 23.2 21.7 20.1 18.5
FL 100x160B 27 15 20 35 34 33.3 32.6 31.7 30.6 29.2 27.6 26 24.2
FL 100x200D 33.3 18.5 25 42 42 41 40 38.5 37 35.2 33 30.5 28
FL 100x200C 38.6 22 30 47 47 46.5 45.5 44.5 43 41.2 39 36.5 34
FL 100x200B 52.7 30 40 55.8 54.8 54 53.2 52 50.5 49 47 45 42.5 37
FL 100x200A 65 37 50 57 57 56.6 56.4 55.8 55 54 52.5 50.5 48 42
FL 100x250D 65 37 50 68.2 68 67 66 65 63.2 61 58.3 55 47
Hydraulic performance table at 1450 rpm
ModelI [A] P2 l/min 0 600 700 800 900 1000 1100 1200 1300 1500 1750 2000
3~ 400 V [kW] [HP] m3/h 0 36 42 48 54 60 66 72 78 90 105 120
FL4 100x160Y 3.4 1.5 2
mw
c
8 7.7 7.5 7.3 7 6.7 6.4 6.1 5.8 5
FL4 100x160X 5.1 2.2 3 10 9.7 9.5 9.3 9 8.8 8.5 8.2 7.9 7.1 6
FL4 100x200Y 8.5 3 4 12.8 12 11.7 11.5 11.3 11 10.5 10 9.5 8.5 7
FL4 100x200X 6.5 4 5.5 15 14.5 14.2 14 13.8 13.5 13.1 12.7 12.2 11 9 6.5
FL4 100x250Y 10.8 5.5 7.5 20 19 18.5 18 17.5 17 16 14 12
FL4 100x250X 14.4 7.5 10 23.5 22.2 21.9 21.6 21.2 20.9 20 18.5 16.8
Model DNmDNa A B C D E F G H I [Kg]
FL 100x160D 100 730 190 540 320 136 184 525 300 225 76
FL 100x160C 100 730 190 540 320 136 184 525 300 225 84
FL 100x160B 100 730 190 540 320 136 184 525 300 225 91
FL 100x200D 100 890 190 710 386 156 230 550 300 250 135
FL 100x200C 100 890 190 710 386 156 230 550 300 250 153
FL 100x200B 100 995 190 805 413 156 257 550 300 250 195
FL 100x200A 100 995 190 805 413 156 257 550 300 250 213
FL 100x250D 100 995 190 805 433 176 257 600 320 280 220
FL4 100x160Y 100 575 190 385 285 136 149 525 300 225 45
FL4 100x160X 100 615 190 425 295 136 159 525 300 225 50
FL4 100x200Y 100 615 190 425 315 156 159 550 300 250 66
FL4 100x200X 100 625 190 435 315 156 159 550 300 250 73
FL4 100x250Y 100 730 190 540 360 176 184 600 320 280 96
FL4 100x250X 100 730 190 540 360 176 184 600 320 280 106
DN a b c d e
100 158 180 220 8 18
FL 125 models available on request
67
ApplicationsWater supply and pressure boosting, irrigation. Circulation of hot water and liquid refrigerants in air conditioning systems.
MotorThree-phase asynchronous motor. IP 55 protection. Class F insulation. Standard voltage:230/400 V 50 Hz up to 4 kW,400/690 V 50 Hz for higher power. FL: 2 pole motors (2900 rpm).FL4: 4 pole motors (1450 rpm).Efficiency IE2.Counter flanges available on request.
FLD/FLD4 Building Services
Twin In line electric monobloc pumps in cast iron
MaterialsPump body, shield, lantern and cover in cast iron.Impeller: in cast iron (stainless steel or bronze on request at extra cost).Shaft: AISI 420 stainless steel.Mechanical seal: silicon carbide/silicon carbide.
LimitationsMaximum ambient temperature: +40 °C. Temperature of pumped liquid:-10 °C +130 °C.Maximum operating pressure: 10 bar. Maximum liquid viscosity: 5 °C.
Field of application at 2900 rpm
Field of application at 1450 rpm
Curves obtained in accordance with ISO9906, appendix A
FLD
40
30
25
20
15
10
8
6
H[m]
12060241263 Q [m3/h]
120602412631.20.6 Q [m3/h]
15
10
8
6
5
4
3
2
H[m]
FLD4
68
FLD/FLD4 Building Services
Hydraulic performance table at 2900 rpm
FLD 40, 50, 65
ModelI [A] P2 l/min 0 100 150 200 225 225 225 225 225 225 500 600 700 800 900 1000
3~ 400 V [kW] [HP] m3/h 0 6 9 12 13.5 13.5 13.5 13.5 13.5 13.5 30 36 42 48 54 60
FLD 40x125D 1.7 0.75 1m
wc
25 12.5 10.5 8.1 6.8 5.2
FLD 40x125C 1.7 0.75 1 17 16.5 14.5 12.3 11 9.5 6
FLD 40x125B 2.5 1.1 1.5 21.5 20.5 19 17 16 15 11.5 7.5
FLD 40x125A 3.4 1.5 2 25 24.5 23.5 22 21 20 16.5 13
FLD 50x125C 3.4 1.5 2 16.8 15.5 15 14.1 13 11.8 10.5 7
FLD 50x125B 4.4 2.2 3 20 19 18.5 17.6 16.6 15.5 14.2 10.5
FLD 50x125A 5.9 3 4 25 24.5 24 23.5 23 22 20.5 17
FLD 50x160B 5.9 3 4 31 30 29 28 26.5 25 23 18
FLD 50x160A 7.8 4 5.5 38 36.5 35.6 34.6 33.5 32.3 30.7 26.5
FLD 65x160D 5.9 3 4 24 23 22.5 22 21.5 19.8 17.5 15
FLD 65x160C 7.8 4 5.5 27.5 26.5 26 25.5 24.3 22.6 20.2 18
FLD 65x160B 10.4 5.5 7.5 33 32.5 32 31.5 30.5 29.5 28 26 23.5
FLD 65x160A 14.2 7.5 10 37 37 36.5 36 35 34 32.5 31 29
FLD 80, 100
ModelI [A] P2 l/min 0 700 800 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000
3~ 400 V [kW] [HP] m3/h 0 42 48 60 75 90 105 120 135 150 165 180 195 210 225 240
FLD 80x160D 14.2 7.5 10
mw
c
26.1 25.3 24.9 23.4 20.5 17 12.7
FLD 80x160C 19.8 11 15 31 30.5 30 28.9 26.8 24 20.5 16
FLD 80x160B 27 15 20 37 36.5 36 34.5 32.5 30 27 23 19
FLD 80x160A 27 15 20 42 41 40.5 39.5 37.7 35.5 32.5 28.8 24
FLD 100x200F 27 15 20 34 33 32.2 30.7 29 26.8 24.5 22 19
FLD 100x200E 27 15 20 39 37.5 36.5 35 33 31 28.5 26
FLD 100x200D 19.8 11 15 25.3 24.5 23.5 22 20.5 18.5 16 13.5 10.5 7 3
FLD 100x200C 27 15 20 28 27.5 26.5 25.5 24 22 20 17.5 15 12 8.6 5
FLD 100x200B 27 15 20 29 28 27 25.5 23.5 21.5 19 16.5 13.8 10.8 7.5 3
FLD 100x200A 27 15 20 31 29 27.7 26 24.3 22 19.6 17.2 14.3 11.3 7.5 3.5
FLD4 80, 100
Hydraulic performance table at 1450 rpm
FLD4 40, 50, 65
ModelI [A] P2 l/min 0 40 50 75 100 125 150 175 200 225 250 300 350 400 450 500 600
3~ 400 V [kW] [HP] m3/h 0 2.4 3 4.5 6 7.5 9 10.5 12 13.5 15 18 21 24 27 30 36
FLD4 40x125Z 1.4 0.25 0.33
mw
c
4 3.7 3.6 3.15 2.6 1.9
FLD4 40x125Y 1.4 0.25 0.33 6.2 4.6 4.5 4.1 3.6 3 2.2
FLD4 40x125X 1.4 0.25 0.33 6.3 6.2 6.05 5.7 5.2 4.6 3.9 3
FLD4 50x125Y 1.4 0.25 0.33 4.8 4.6 4.5 4.3 4.1 3.9 3.6 3.3 2.4
FLD4 50x125X 2.2 0.37 0.5 6.4 6.3 6.2 6.1 6 5.8 5.5 5.2 4.4 3
FLD4 50x160X 2.7 0.55 0.75 9.2 8.8 8.6 8.3 8 7.7 7.3 6.9 5.9 4.5
FLD4 65x160Z 1.8 0.55 0.75 6.8 6.6 6.5 6.4 6.1 5.7 5.1 4.3 3.3
FLD4 65x160Y 1.8 0.75 1 8.3 8.1 8 7.9 7.7 7.4 7 6.5 5.8 4
FLD4 65x160X 2.5 1.1 1.5 9.1 9 8.9 8.8 8.6 8.4 8.1 7.7 7.1 5.5
ModelI [A] P2 l/min 0 300 350 400 450 500 600 700 800 900 1000 1100 1200 1300 1500 1750 2000
3~ 400 V [kW] [HP] m3/h 0 18 21 24 27 30 36 42 48 54 60 66 72 78 90 105 120
FLD4 80x160W 1.8 0.75 1
mw
c
6.4 6.3 6.2 6.1 5.9 5.6 4.9 4.1 3.2
FLD4 80x160Z 2.5 1.1 1.5 7.3 7.3 7.2 7.1 7 6.8 6.3 5.6 4.8 3.9
FLD4 80x160Y 2.5 1.1 1.5 8.6 8.6 8.5 8.4 8.3 8.2 7.9 7.4 6.8 6 5
FLD4 80x160X 3.4 1.5 2 10.3 10.2 10.1 10 9.9 9.8 9.45 9 8.4 7.5 6.5
FLD4 100x200W 3.4 1.5 2 8.5 8.1 7.8 7.4 7 6.5 6 5.3 4.6 3.8
FLD4 100x200Z 5.1 2.2 3 10.4 10 9.7 9.3 8.9 8.5 8 7.5 7 6
FLD4 100x200Y 6.5 3 4 12.8 12 11.8 11.6 11.3 10.9 10.5 10 9.5 8.5 7
FLD4 100x200X 8.5 4 5.5 15 14.4 14.2 14 13.8 13.5 13.1 12.7 12.2 11 9 6.5
69
FLD/FLD4 Building Services
A
D
C
B
F
E
M
M
G
H I
A
D
C
B
F
E
M
M
G
H I
Dimensions and weights
FLD 40, 50, 65, 80, 100
FLD4 40, 50, 65, 80, 100
n°d1 holes ø e
DN a b c
DN a b c d e
40 88 110 150 4 18
50 102 125 165 4 18
65 122 145 185 4 18
80 138 160 200 8 18
100 158 180 220 8 18
Model DNmDNa A B C D E F G H I M [Kg]
FLD 40x125D 40 425 100 325 397 200 197 340 130 210 100 50
FLD 40x125C 40 425 100 325 397 200 197 340 130 210 100 50
FLD 40x125B 40 445 100 345 397 200 197 340 130 210 100 52
FLD 40x125A 40 445 100 345 397 200 197 340 130 210 100 54
FLD 50x125C 50 455 110 345 427 217 210 365 145 220 105 56
FLD 50x125B 50 455 110 345 427 217 210 365 145 220 105 58
FLD 50x125A 50 495 110 385 427 217 210 365 145 220 105 66
FLD 50x160B 50 535 110 425 480 245 235 410 170 240 120 86
FLD 50x160A 50 455 110 345 427 217 210 365 145 220 105 56
FLD 65x160D 65 485 130 345 543 275 268 450 180 270 140 81
FLD 65x160C 65 565 130 435 543 275 268 450 180 270 140 101
FLD 65x160B 65 670 130 540 543 275 268 450 180 270 140 125
FLD 65x160A 65 495 110 385 480 245 235 410 170 240 120 67
FLD 80x160D 80 690 150 540 550 280 270 510 205 305 135 141
FLD 80x160C 80 690 150 540 550 280 270 510 205 305 135 162
FLD 80x160B 80 690 150 540 550 280 270 510 205 305 135 175
FLD 80x160A 80 565 130 435 543 275 268 450 180 270 140 110
FLD 100x200F 100 720 180 540 670 325 345 630 240 390 165 162
FLD 100x200E 100 720 180 540 670 325 345 630 240 390 165 162
FLD 100x200D 100 720 180 540 670 325 345 630 240 390 165 162
FLD 100x200C 100 720 180 540 670 325 345 630 240 390 165 162
FLD 100x200B 100 720 180 540 670 325 345 630 240 390 165 162
FLD 100x200A 100 720 180 540 670 325 345 630 240 390 165 162
Model DNmDNa A B C D E F G H I M [Kg]
FLD4 40x125Z 40 425 100 325 397 200 197 340 130 210 100 41
FLD4 40x125Y 40 425 100 325 397 200 197 340 130 210 100 41
FLD4 40x125X 40 425 100 325 397 200 197 340 130 210 100 41
FLD4 50x125Y 50 435 110 325 427 217 210 365 145 220 105 44
FLD4 50x125X 50 435 110 325 427 217 210 365 145 220 105 46
FLD4 50x160X 50 435 110 325 480 245 235 410 170 240 120 52
FLD4 65x160Z 65 475 130 345 543 275 268 450 180 270 140 65
FLD4 65x160Y 65 475 130 345 543 275 268 450 180 270 140 65
FLD4 65x160X 65 475 130 345 543 275 268 450 180 270 140 67
FLD4 80x160W 80 485 150 335 550 280 270 510 205 305 135 72
FLD4 80x160Z 80 485 150 335 550 280 270 510 205 305 135 74
FLD4 80x160Y 80 535 150 335 550 280 270 510 205 305 135 79
FLD4 80x160X 80 535 150 335 550 280 270 510 205 305 135 83
FLD4 100x200W 100 535 180 355 670 325 345 630 240 390 165 110
FLD4 100x200Z 100 605 180 425 670 325 345 630 240 390 165 130
FLD4 100x200Y 100 605 180 425 670 325 345 630 240 390 165 138
FLD4 100x200X 100 615 180 425 670 325 345 630 240 390 165 150
FLD4 125 & 150 models available on request
70
ApplicationsDomestic hot water circulation.
MaterialsPump housing = Bronze CuSn10Zn2.Impeller = Noryl GFN2.Seal = Carbon/Silicon carbide/Viton.Housing O-ring = Nitrile.
RangeDimensions = Threaded G ½ - G ¼ .Max motor power = 1.5 kW.Max capacity = 16 m3/hr.Max head = 28 mwc.Max temperature = -15/100 deg c (120 °C with a bronze impeller).
FeaturesHigh efficiency, low noise, simplicity,reliability and ease of maintenance &servicing.
AP/AKP/AEP Series Building Services
In-line glanded bronze circulation pumps
OptionsDifferent seal options.Non standard surface treatment.Motor thermal protectors,Specail voltage.
MotorIP 54 protectionClass F insulation.Efficiency IE2.2 pole & 4 pole.
Field of application at 2900 rpm
H[m]
10
5
2
10.8
0.6
0.4
10543210.8 Q [m3/h]
Q [l/s]3210.80.60.40.2 4
71
ApplicationsDomestic hot water circulation.
MaterialsPump housing = Bronze CuSn10Zn2.Impeller = Noryl GFN2.Seal = Carbon/Silicon carbide/Viton.Housing O-ring = Nitrile.
RangeAEP = Threaded G1¼ .LP/ALP = DN50-100.Max motor power = 0.75kW.Max capacity = 16 m3/hr.Max head = 20 mwc.Max temperature = +40 °C.
FeaturesIntegrated SCA frequency converterwith low energy consumption.
AEP/LP/ALP Series Building Services
In-line glanded bronze c/w integrated inverter circulation pumps
MotorIP 54 protectionClass F insulation.Efficiency IE2.2 pole & 4 pole.Highly efficient with low noise.
Field of application at 2900 rpm
H[m]
20
10
5
2
1Q [l/s]2010521
72
ApplicationsHeating and air-conditioning, booster/transfer, heat recovery, power plant, district heating, condensate, paper & pulp and the chemical industry.
Seal SolutionsStandard single seal + 120 °C.Internal flush + 150 °C.External flush for sizes DN50-300.External seal for sizes DN65-300 ALS.Double seal system + 180 °C.
MaterialsAL/AE/AKN/L = Grey cast iron EN-GJL200 PN10.ALH/LH/AKNH = Nodular cast iron EN-GJS-400 PN16.ALP/AEP/LP = Bronze CuPb5Sn5Zn5 PN10.ALS/LS = Stainless steel AISI 316 PN16.
RangeDimensions = DN 32-300.Max motor power = 160 kW.Max capacity = 1000 m3/hr.Max head = 80 mwc.Max temperature = -35/180 deg c.
AE/L/AL/AKN Series Building Services
In-line glanded circulation pumps
Available in version C/W inverter
MotorIP 54/55 protection.Class F insulation.Efficiency IE2.2 pole & 4 pole.
FeaturesHigh efficiency, low noise, simplicity,reliability and ease of maintenance &servicing.
OptionsEnclosures IP 54, IP 55 ,IP 56.Voltage 230 V, 400 V, 500 V, 600 V, 690 V.Tropical protection.Belzona molecular technology coating.Anti-condensation heather of motor.Atex-pumps.TempCoat coating for sealing flange(for liquid temperatures below 0 °C).Painting according to customerspecifications.
The pumps are painted according tostandard SFS-EN ISO12944-5,AY1001-FeSa21/2 , colour RAL3020.
Field of application at 2900 rpm
H[m]
30
20
10
5
2
1
0.5
4050
40030020010050403020105 Q [m3/h]
Q [l/s]50 100403020105210.5
73
ApplicationsHeating and air-conditioning, booster/transfer, heat recovery, power plant, district heating.
Seal SolutionsStandard single seal + 120 °C.Internal flush + 120 °C (H).External flush for sizes DN50-250.
MaterialsT/AT = Grey cast iron EN-GJL200 PN10 orNodular cast iron EN-GJS-400 PN16.Shaft = Stainless steel SS2324 (AISI 329).
RangeDimensions = DN 32-250.Max motor power = 110 kW.Max capacity = 650 m3/hr.Max head = 80 mwc.
MotorIP 54/55 protection.Class F insulation.Efficiency IE2.2 pole & 4 pole.
T/AT Series Building Services
In-line glanded twin head circulation pumps
Available in version C/W inverters
OptionsEnclosures IP 54, IP 55 ,IP 56.Voltage 230 V, 400 V, 500 V, 600 V, 690 V.Tropical protection.Belzona molecular technology coating.Anti-condensation heather of motor.Atex-pumps.TempCoat coating for sealing flange(for liquid temperatures below 0 °C).Painting according to customerspecifications.
LimitationsMaximum working pressure 10 barOperating temperature + 120 °C. Propylene glycol mixture no greaterthan 50%.
The pumps are painted according tostandard SFS-EN ISO12944-5,AY1001-FeSa21/2 , colour RAL3020.
Field of application at 2900 rpm
H[m]
30
20
10
5
2
1
0.5
4050
40030020010050403020105 Q [m3/h]
Q [l/s]50 100403020105210.5
74
Notes
75
76
CAT
1007
UK
BS 0
2/14
ESPA Pumps (UK) Ltd15-16 Riverside Avenue WestLawfordManningtreeEssexCO11 1UNTel +44 1206 391291Fax +44 1206 391239