Page 1: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

Creating an effective workspace environment

Public SectorData CentreCase Studies

Data Centre Solutions...energy efficient by design

TORFAENCOUNTYBOROUGH

BWRDEISTREFSIROL

TORFAEN

West Yorkshire Police

Page 2: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

EcoDesign™ is based on the implementation of a set of “common sense” design principles whichwhen deployed intelligently contribute significantly to the energy efficiency and performance of adata centre.

Principles of EcoDesign™

Without measurement it canbe hard to understand whyand where energyperformance is poor and howto improve it. It is arecommendation of theCarbon Trust that submetering of high energyconsumption infrastructure isimplemented

Modular, scalable power andcooling architecture thatallows deployment asneeded. This is the crucialelement for improving datacentre efficiency.

The implementation of modernenergy efficient coolingtechnologies reduceoperational energy overhead.

The configuration of ACsystem set points moreappropriate to moderncomputer technology, will havea surprising contribution todata centre energy savings.

Measurement “Right Size” Architecture Efficient CoolingTechnology

Creating an effective workspace environment

“Workspace Technology’s commitment to help clientsreduce their carbon footprint through the deployment ofenergy efficient technology and design”

Speaking to staff at the Department of Energy and Climate Change on the 14th May 2010, the Prime Minister said:

“I don't want to hear warm words about the environment, I want to seereal action. I want this to be the greenest government ever. So today,taking our lead from 10:10, I commit us to a ten percent reduction incarbon emissions across central government in the next twelvemonths” The Rt Hon David Cameron, Prime Minister, 14 May 2010

The intelligent application of EcoDesign™ data centre solutions and servicesby Workspace Technology will deliver a measurable reduction in CO2 for anydata centre infrastructure.

2

Page 3: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

Ensuring a clear airflow pathwhilst eliminating the mixing ofhot and cold air through thedeployment of appropriateducting, aisle containment andairflow managementtechnology will contribute tosignificant reductions in theenergy demand of the coolingsystem.

Clear SegregatedAirflow

An efficient room layout willfacilitate the deployment ofappropriate cooling, allow for amodular growth strategy andassist airflow separation.Correctly positioned grille tileswill ensure airflow toequipment inlet positions.

Efficient Room Layout

The installation of modernmodular transformerless UPStechnology significantlyimproves efficiency and alsosaves on floor space at typicaloperating loads.

The installation of welldesigned power pathscombined with energy efficientlighting reduces energyconsumption.

Efficient UPS &Electrical Installation

Workspace Technology provides expertenergy efficient Data Centre, Server andCommunications Room solutions andservices for corporate and public sectorclients across the UK.

This brochure details three Public Sector Case Studies where Workspace Technology’s havehelped make meaningful reductions in CO2 emissions.

3

Page 4: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

Creating an effective workspace environment4

Dudley Metropolitan Borough Council’s existing datacentre estate was aging and inefficient, it no longeraddressed the demands of modern high performanceIT. Workspace Technology, in partnership with DudleyMBC’s ICT and Facilities teams worked to understandand address all commercial, strategic and technicalbusiness drivers. As a result, a highly energy efficientdata centre design was the preferred solution andincluded innovative ultra efficient rear rack coolingtechnology combined with free cooling chillers and amodular ‘right size’ UPS solution.

The facility was designed around an annualised PUE rating of 1.3 falling below 1.2 during colder weather periods.

The data centre investment made by the Council was in line with its ongoing strategy to improve compute performance throughvirtualization and technology refreshes. It is predicted that thecombined installation will reduce operational energy costs bynearly 50% compared to their previous data centre real estate.

The partnership with Workspace Technology introduced DudleyMBC to our strategy to reduce operational expenditure and carbonemissions in the data centre. Within our portfolio of products wehave selected industry leading and ‘best of breed’ manufacturersoffering a broad range of high efficiency data centre technologies.

Remaining Vendor-neutral at all times our designers andconsultants work to complete data centre designs which are rightfor the individual client and ensure each design proposed meets allof the business drivers.

REAR RACK COOLING TECHNOLOGY FOCUS:

Where high density cabinet cooling is required Rear Rack Coolingor Rear Door Heat Exchanger technology provides an idealsolution. Workspace Technology design and install “Coldlogik” theUK’s leading rear rack heat exchange technology by U Systems.

Ambient air is drawn through an impressive 80% air efficient serverrack front door gaining in temperature as it passes through. Six Hotswap/N+1 fans mounted in the rear door draw the hot exhaust airover a chilled water coil. This acts as the heat exchanger andremoves 100% of the delta T, passing the air back into the room atambient temperature.

The selection of Rear Rack Cooling technology was one of the keycontributors to the energy efficiency of the Dudley MBC data centresolution.

It’s just got greener in Dudley

Data Centre InfrastructureHighlights:

� Ultra Efficient “Rear Rack” CloseCoupled Cooling Technology.

� Extended “Free Cooling” due tohigher water temperatures.

� 160kW High Efficiency ModularAPC UPS Solution.

� Intelligent rack APC PDU’sdelivering rack level powerusage.

� ‘EcoMeasure’ comprehensivepower management & monitoring

� PUE Category 2 status foraccurate CRC reporting.

� Design PUE of 1.3.

Page 5: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

5

TORFAENCOUNTYBOROUGH

BWRDEISTREFSIROL

TORFAEN

Workspace Technology partner with Torfaen CountyBorough to design and build a shared services 3Megawatt Tier 3 Data Centre facility. This initiativelead by Torfaen County Borough has been designedto provide a true Public Sector Shared ResourceCentre located in the heart of South Wales.

Informing Healthcare’s were one of the first customers to takeadvantage of this facility, locating its core I.T functions. InformingHealthcare is a Welsh Assembly Government programme set up toimprove health services in Wales by introducing new ways ofaccessing, using and storing information. Informing Healthcarebecame part of the NHS Wales Informatics Service on 1 April 2010.

Additional data centre halls will support I.T Infrastructure for GwentPolice, Torfaen County Borough, Monmouthshire Council as well asthe Welsh Assemblies 14 to 16 Education programme. It isintended for this facility to expand as more public sector bodiesbenefit from its ability to reduce operational costs by effective useof resources combined with the energy efficiency of a modern“best practice” data centre design.

As this project is a flagship government initiative and housed withinone of the governments largest independent Data Centre facilities itwas critical that it was designed to manage and measure thepower usage of the facility effectively, as well as accurately reportannual power usage trends for full compliance to the CRC EnergyEfficiency Scheme.

Embedded in the Electrical and Mechanical Design of this facility isa bespoke power management and measurement solutionincluding intelligent metering of all critical electrical maindistribution and sub distribution points.

ECOMEASURE ENERGY MEASUREMENT OVERVIEW

EcoMeasure® from Workspace Technology is a Scalable DataCentre Energy Management & Efficiency Measurement Solutionwhich enables I.T and data centre managers to accuratelybenchmark, track and trend the Power Usage Effectiveness (PUE),Data Centre Infrastructure Efficiency (DCiE) and usage of the DataCentre environment through direct analysis of power and energyconsumption. EcoMeasure® is also an invaluable tool to help datacentre managers demonstrate CO2 emission savings wheninvestments are made in either infrastructure or technology.

The measure ofsuccess at Torfaen

Data Centre InfrastructureHighlights:

� Excellent “Shared Services”facility

� Denco Toscana Perimeter AHU’swith “free cool” technology

� 4 x 1.1Mva Generator SetsDelivering 3Mva N+1 Capacity

� Schneider Electric LV Switchgear

� APC InfrastruXure CentralManagement Platform

� FlexAisle “Hot Aisle ReturnPlenum” aisle containment

� Design PUE of 1.5 with “GreenGrid” L3 monitoring capability

� 40% energy savings based onprevious Data Centre

EcoMeasure™ deployment benefits:

� Assists in reducing energyconsumption, minimisingenvironmental and economicimpacts associated withexcessive energy use

� Instant reporting of data centreDCiE / PUE efficiency ratings

� Power usage trends for fullcompliance to the CRC EnergyEfficiency Scheme

� Accurate proof of theeffectiveness of any “claimed”energy efficiency deploymentsthroughout the life of the facility

� Measurement of energyconsumption, critical load trends,power quality and response timeof emergency power plant

� Opportunities to improve a serverroom or data centres operationalefficiency

Page 6: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

Creating an effective workspace environment6

In September 2009, West Yorkshire Police released aformal Request for Quotation for the completerefurbishment of the main Data Centre. The existingfacility, although less than 8 years old, had not beendesigned to accommodate the IT architecture beingdeployed today and after a number of technicalissues and interim design ‘fixes’, it was decided thatthe facility needed to be completely rebuilt.

There were 2 major challenges to this project, firstly theexisting IT architecture had to remain operational within the DataCentre during the build programme, and the incoming electricalsupply could not be increased even though the IT load at fullcapacity was to dramatically increase.

In a highly competitive tender process, Workspace Technology’sdemonstration of capabilities, overall design scheme (utilising ourinnovative FlexAisle® Technology) and commitment to the projectled to success and award of contract.

To satisfy the clients design drivers for increased efficiency,maximising use of the existing electrical supply and minimisingimpact on capital expenditure, Workspace Technology’s DesignTeam proposed a Power and Cooling infrastructure designedaround traditional methodologies but with careful product selectionand deployment to maximise efficiency but ensure a cost effectivedelivery.

The cooling infrastructure utilised traditional DX-based perimetercooling units, with higher efficiency, together with an innovative andflexible aisle containment system (FlexAisle®) which ensures no hotexhaust air can contaminate the cool supply air in the Data centreto ensure predictive and efficient use of the cooling infrastructure.

The power infrastructure included a redundant N+1 Solutionselected as it increased levels of efficiency, especially at part load.An EcoMeasure solution was also installed to report power usagetrends.

FlexAisle Sealed it for West Yorkshire Police

West Yorkshire Police

Data Centre InfrastructureHighlights:

� 106 Rack deployment

� Data Centre subdivided into3 areas – West YorkshirePolice IT, Regional IT andComms Room.

� N+1 Perimeter DX basedCRAC Cooling System.

� Complete AirflowManagement includingFlexAisle® Hot AisleContainment system tomaximise efficiency.

� N+1 High efficiency UPSSolution.

� External Standby Generator

� APC MGE Perimeter UPSSystems

Page 7: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

7

FLEXAISLE VENDOR INDEPENDENT AISLE CONTAINMENT

FlexAisle®, by Workspace Technology, provides asimple and cost effective passive method foreliminating the mixing of hot and cold airflows within adata centre or server room environment. The goal ofFlexAisle® is to maximise the performance, uptime andlife expectancy whilst reducing operating costs.

FlexAisle® can be installed as new, or retrofitted withinexisting data centre and server room environments.FlexAisle® is a non intrusive easy fit solution whichprovides data centre managers with the ability to re-organise and expand facilities in line with businessrequirements.

FlexAisle® uniquely provides the ability to supportmultiple cooling configurations and is independent ofcabinet vendors. This enables data centre managersto support a mix and match of server andcommunication rack systems.

Workspace Technology deployed the “HARP”configuration within the West Yorkshire Police datacentre. The deployment of this solution significantlycontributed to improved airflow and energy efficiency.In the old data centre it was estimated that over 30%of cold air simply short cycled back to the AC unit. The deployment of FlexAisle® within the designvirtually eliminates short cycle of cold AC air.

FlexAisle® Summary Configuration Options

Cold Aisle CorridorYes No No Yes No(CAC)

Hot AisleNo Yes Yes Yes YesContainment (HAC)

Hot Aisle Return Yes Yes Yes Yes YesPlenum (HARP)

FlexAisle®

Configuration

PerimeterDownflowCooling

In-Row Cooling

Rear RackCooling

Self ContainedRack Cooling

Room AirflowExchange

If cold aisle/hot aisle corridor is employed there will be a clash of air temperatures due to the inversenature of each containment system. This can be overcome with additional room segregation..

In a highly competitivetender process, WorkspaceTechnology’s demonstrationof capabilities, overall designscheme and commitment tothe project led to successand award of contract.

Page 8: Public Sector Data Centre Case Studies · 2016. 7. 27. · This brochure details three Public Sector Case Studies where Workspace Technology’s have helped make meaningful reductions

The Carbon Reduction Commitment (CRC) levy’s tax’s against high energy users.As part of CRC initiative the European Commission directive introduced theEuropean Code of Conduct on Data Centre’s in 2008. This code of conductprovides a set of rules which help drive down energy use and improve energyefficiency within the data centre environment.

Workspace Technology understands the impact that the CRC will have within thedata centre market. The implementation of the EU Code of Conduct “Best Practice”recommendations will help improve the energy efficiency of data centreenvironments.

Workspace Technology is proud to be an approved “Endorser” for the European Commissions “Code of Conduct for Data Centre Efficiency”Workspace Technology is committed to help clients reduce their carbon footprintthrough the deployment of “Best Practice” energy efficient technology anddesign, for new and existing data centre environments.

Further details of Workspace Technology’s products and services can be found atwww.workspace-technology.com.

Workspace Technology’s Data Centre Solutions division provideexpert data centre, communications and server room solutions andservices for public sector and corporate clients across the UK.

Approved “Endorser” EU “Code ofConduct on Data Centre Efficiency”

Workspace Technology’s “Commitment to help clientsreduce their carbon footprint through the deploymentof energy efficient technology and design”.