Legal Booklet Electric Fencing and
Labour Department
By
PSI Security Group
Document Number PSI-TECH-PRO-0001 Rev 01
Introduction
On the 25th of March 2011 the Department of Labour promulgated certain
amendments to the Electrical Machinery Regulations within the Health and Safety
Act 1993 (Act No. 85 of 1993). Some of these amendments relate specifically to
the electric fencing industry and are therefore relevant to any electric fence
installer and end user.
What is the purpose of this Act?
The Act was promulgated to ensure the safety of the citizens of South Africa with
regards to all electrical systems and appliances. Thus the section of the Electrical
Machinery Regulations, 2011, to which this ready reference refers, is meant to
protect the public from receiving inadvertent and possibly dangerous shocks from
badly sited or poorly erected electric fences. A second objective of this section of
the regulations is to prevent radio, T.V. and telephone interference caused by non-
compliant energizers, poor earthing, and other unacceptable installation practices.
Thirdly, the Act aims to protect the consumer by specifying minimum fencing material
quality standards.
It is the goal of this handbook to provide electric fence installers and end users with
a condensed, easy-to-consult, explanation of the Act, its related regulations and the
South African National Standards (SANS) relevant to the Act. This booklet does not
profess to cover every aspect of the regulations as applicable to electric fencing as
to do so would simply mean reprinting the Act and all the SANS regulations in full. It
merely attempts to extract from the Act for your convenience what is most relevant
to your daily activities to give you an easy-to-read reference.
Please note that at the time of compilation of this booklet the government structures
for installer training are not yet in place and although the Act states in Clause 12 (4)
that, as from the 1st October 2012, ‘every user or lessor of an electric fence system
shall have an electric fence certificate’, there are at present no ‘registered installers’
available to issue these required certificates because there are as yet no registered
training courses available for an installer to take in order to qualify as a registered
installer.
The Act and Relevant SANS Standards and
Codes of Practice Applicable to
Non-Lethal Electric Fencing
The legislation covering the safety standard requirements for the manufacture
of electric fence energizers and for the erection and installation of electric fence
systems, as well as the laws relevant to installers, users, and lessors of such
systems, is to be found under Section 12 to 16 Electric Fences, in the
Government Gazette of the Republic of South Africa:
Regulation Gazette No 9509, Vol. 549, published in Pretoria 25th March 2011,
No. 34154
This Act then refers to a number of SANS Standards, namely:
SANS 60333–2-76:2006 Edition 2.1 Household and similar electrical appliances –
Safety Part 2-76 Particular requirements for electric fences.
(This publication is basically the same as IEC 60333-2–76: 2006 Edition 2.1 which
is the internationally accepted safety standards document recognized by most
countries around the world.)
These Standards lay down the stringent requirements that have to be met by
manufacturers of nonlethal electric fence energizers in order to receive a certificate
of compliance for their energizers. This certificate is important as the new Act
requires that all nonlethal energizers now sold must have been tested and certified
by an internationally recognized test laboratory confirming that they comply with
these standards.
At the back of SANS 60333276 there are some annexures relating to the installation
of electric fence systems. These are the generally accepted international standards.
However, due to the unusual security situation in South Africa which has resulted in
a proliferation of nonlethal electric fences in urban areas, the Department of Labour
has felt that it is necessary to add to these codes of practice. The result is:
SANS 10222-3:2011 Electric security installations Part 3: Electric fences (non-
lethal) and SANS 10222-4:2010 Electric security installations Part 4 Electric
fence energizers.
These codes of practice relate to the installation of non-lethal electric fences. Again,
at the time of releasing this booklet, SANS 10222-4:2010, which relates more
specifically to the installation of security energizers and monitoring systems, has not
yet been finalized. When finally approved it is intended that it will be incorporated
into the SANS102223:2011 document.
The above are all the documents that relate to nonlethal electric fencing and are
the ones we have endeavored to condense and simplify for you.
Definitions from the Act and
SANS Documents
‘A registered person’ means a person registered in terms of regulation 14 as an
electric fence installer. In other words, s/he has passed the Department of Labour’s
requirements to become a registered installer and is in possession of a Certificate
of Registration issued by the Department.
‘Accreditation authority’ means the South African National Accreditation System
(SANAS).
‘Circuit’ means an arrangement of conductors for the purpose of carrying electrical
energy.
‘Conductor’ means an electrical conductor so arranged as to be electrically
connected to a source of electrical energy.
‘Dead’ means at or about zero potential and isolated from any positive wires.
‘Earthed’ means connected to the general mass of earth in such a manner as to
ensure at all times an immediate safe discharge of electrical energy.
‘Electric fence’ means an electrical barrier consisting of one or more conductors
erected against trespass of persons or animals.
‘Electric fence energizer’ means electrical machinery arranged so as to deliver a
periodic nonlethal amount of electrical energy to an electric fence connected to it.
‘Electric fence system’ means an electric fence and an electric fence energizer.
‘Bracket’ means a device normally fabricated out of metal with attached fence
insulators that can be attached to a building with the objective of supporting electric
fencing wires.
‘Bracket or pole facet’ means a flat section on the electric fencing pole or bracket.
‘Dynamic bracket or pole’ means a bracket/pole that fulfills the function of a
passive bracket and additional mechanical features/functions. (It may have an
additional detection device built into it.)
‘Partitioning’ (Sectorisation) this means an electric fence installation that
consists of one energizer connected to an electric fence which is then divided into
sections for monitoring purposes. One energizer powers a zone, and the zone is
then sectorised (partitioned).
‘Urban Area’ this means an area with an increased density of human created
structures and would include, but not be limited to, residential, business, industrial
zoned areas. (Population density in an urban area would exceed 400 or more
persons per square kilometer.)
‘Public area’ This means an area within a secure area to which any person can
gain legal access without permission from the land owner or where members of the
public are allowed to enter.
Requirements of the Act
The new regulations came into effect on the 1st of July 2011 and, as from the
1st October 2012, when the requirements for fence and installer certification
will come into effect, the Act requires that:
1. You abide by these new regulations if you want to design,
manufacture, sell, install or use an electric fence energizer.
2. The seller, importer, and manufacturer of an electric fence energizer must
be able to prove compliance with SANS 60335-2-76 by producing a
certificate issued by an accredited test laboratory (In South Africa, at this
point in time, Test Africa is the only recognized local test laboratory).
3. You make sure, if you are using auxiliary charging apparatus with your
energizer, that it is double wound.
4. In the future every user of an electric fence system shall have a
Certificate of Compliance (See Annexure 1) which proves that their
installation complies with the law:
This does not apply to fences that were erected prior to these new regulations
coming into force; in other words prior to 1 October 2012, which is the date
when installers are supposed to be registered. (As already mentioned, this
is going to be difficult to enforce considering that there is as yet no training
course available for installers.) Fences that were installed prior to this date
must however have complied with the requirements of the old law, one
requirement of which is that an electric fence has to be positioned so that
the general public will not make ‘inadvertent contact’ with it. This clause
has been flagrantly ignored by many installers and this could cause some
problems in the future.
If an alteration or extension is made to an existing fence line, a certificate
will have to be issued for the extension.
Any property sold after this date, (1st October 2012) will require a certificate
of compliance. This certificate is similar to the electrical certificate currently
issued by electricians for the electrics of premises.
5. Only a registered person may issue an electric fence system Certificate
of Compliance i.e. an installer who has passed the Department of
Labour’s examinations and is in possession of a Certificate of
Competence.
To summarise: The new Act requires that any electric security fence system, in
stalled after the 1st October 2012, must have certification showing that it complies
with all the requirements of the new Act and the end user must be issued with a
Certificate of Compliance.
This certificate can be issued only by a registered person who has been approved
by the chief inspector and who has been issued with a Certificate of Registration.
This brings us to the question – How does one become a registered electric fence
installer?
How Does One Become a Registered
Electric Fence Installer?
The Electrical Machinery Regulations 2011 promulgated under the Occupational Health and Safety Act (Act. No. 85 of 1993) state:
Application for registration as registered person
14 (1) ‘Application for registration as a registered person shall be made to the chief
inspector in the form of Annexure 2 (see page 12) and shall be accompanied by the
registration fee prescribed by regulation 23. (The current fee is R120.00 and the
address of the chief inspector is: Department of Labour, Occupational Health and
Safety, PB X117 Pretoria 0001)
(2) Any natural person who satisfies the chief inspector that he or she has sufficient
knowledge of the safety standards applicable to electric fence systems may be
registered by the chief inspector as a registered person.
(3) The chief inspector shall furnish a registered person with a certificate of
registration, and enter such registration into the national database.
(4) A registered person shall on request produce his or her certificate of registration
to any inspector and any supplier or any person for whom he or she intends to install
an electric fence system and issue an electric fence certificate.
However, at present (September 2012) there is no recognized governmental course
for an installer to attend and no examinations that they can take which will enable
them to be recognized as a competent installers (‘registered person’). Interim
measures are being put in place by the government in order to meet the requirements
of the regulations and will involve the cooperation of those companies that regularly
run training courses in Basic Electric Fence Installation.
It is envisaged that there will be Theory and Practical sections to the training and
testing. For those installers who have years of experience in the field there will
be Recognition of Prior Learning (RPL) which for them will short circuit some of
the learning and testing. For those who are new to the industry, a third section is
envisaged – Experiential Learning which will require a period of Internship.
Withdrawal of Registration
If a Registered Person fails to comply with the new laws s/he can have their
certificate revoked. They will however first be warned and after due process, if they
fail to respond to the inspectors requests, their certificate can be revoked. If the
installer feels s/he has grounds to appeal they can do so.
The Act then goes on to list the penalties for people contravening the Act: basically
imprisonment for up to 12 months, and in the case of continuous offence, an
additional fine of R200 (current) per day up to three months.
Safety and Installation Requirements of
the SANS standards
The following are the most important points extracted from the SANS codes of
practice that an installer must observe when erecting and installing an electric
security fence system.
A Planning Principles
1. Because electric fences have the potential to cause electromagnetic
interference on communication lines, cognizance must be taken of the
location of any communication lines when planning an installation. Always
keep the distance between the electric fence and communication lines as far
as possible.
2. Do not install an electric fence around communication poles or in a way
that it could cause a safety hazard to the employees of the communication
company.
3. It is good practise not to have the top wire on an electric fence electrified
where a communication line runs above and parallel to the fence.
B The Energizer
1. As required by the Act, the energizer must comply with SANS 603335276
and the supplier of the product must be able to produce a certificate issued
by an internationally recognized laboratory to verify this.
2. You may not put more than one energizer on the same fence line.
3. In urban areas (population exceeds 400 per Sq. Km) the electric fence
energizer output shall be limited to a maximum of 8 joules under any load
condition.
4. There must be a 2.5m distance between adjacent electric fences fed
from separate energizers. If this gap is to be closed, this shall be affected
by means of electrically nonconductive material or an isolated metal
barrier.
5. A vertical separation of not less than 2m shall be maintained between
pulsed conductors fed from separate energizers.
6. If two electric fences are closer together than 2.5m and there is no
insulating barrier between them, the energizers feeding the two fences
must be synchronized.
7. You may not electrify barbed or razor wire with an energizer.
8. The energizer must be installed in such a position as to be out of reach
of children and in a dry, dust free environment.
9. The energizer should be operated only by persons competent to do so.
C Earthing
1. Earth electrodes shall be a minimum of 1,2m long with a minimum
diameter of 10mm.
2. Earth electrodes shall be manufactured out of galvanized steel, copper,
or stainless steel (we recommend hot dipped galvanized steel as this will
prevent electrolysis when connected to galvanized wire.)
3. Three earth electrodes shall be installed in close proximity to the electric
fence energizer and be a minimum distance of the earth spike’s length from
each other. The earth electrodes must all be linked together.
4. On security fences additional earth stakes should be inserted at a
maximum distance of 30 meters apart.
5. On game, strip grazing, and general agricultural fences additional
earth electrodes should be inserted at a maximum distance of 100 meters
apart, measured from the energizer.
6. Earth electrodes shall be inserted vertically into the ground. If the ground
is rocky they can be inserted at a maximum angle of 45 degrees.
7. All the earth wires of an electric fence must be connected together when connected to an earth electrode.
8. The wire connecting the earth electrode must be of a similar, or of a
thicker diameter, than the fence wires.
9. The energizer’s earth electrodes should be at least 2 meters away from
any other earth systems, e.g. Eskom, Telkom, etc.) However, the standard
then goes on to say that this distance should preferably be at least 10m.
10. To test if the energizer earth is adequate, apply the following test. (Still
in draft stage with SANS 102224 2010). Create a short on the fence line
that is sufficiently severe to reduce the voltage on the fence line to below
2,000 volts. Then install another earth spike and measure the voltage
between the existing earth system and the newly installed earth electrode.
If the voltage reading exceeds 300 volts, the system requires additional
earth electrodes.
D Lead-Outs
An insulated fence high tension cable shall not run:
1. In the same trench or wire way with a mains A.C. current supply.
2. In the same wire way with cables or wires of telecommunication, radio or
signaling circuits.
3. Where it is likely to be damaged by corrosive liquids.
4. Within 150mm of hot surfaces if heat is likely to damage it (hot water pipes).
5. Where it is likely to be damaged unless mechanically protected.
6. Connecting leads that are run inside a building shall be effectively
insulated from the earthed structural parts of the building (use insulated HV
cable).
E Barrier Fences
The general public should be protected by a barrier fence from making inadvertent
contact with a free-standing (stand-alone) electric fence.
The barrier fence must have the following features:
1. A minimum height of 1500mm.
2. At least one dimension in any opening should not be greater than 130mm.
3. The separation between the electric fence and the barrier fence should be:
within the range of 100mm to 200mm or greater than 1000mm where
at least one dimension in each opening of the physical barrier is not
greater than 130mm
Greater than 1000mm where any opening in the physical barrier has
all dimensions greater than 50mm
F Minimum Clearance from Power Lines for Electric
Security Fences
Power line voltage V
Clearance M
Less than or equal to 1,000
1,000 and less than 33,000 Greater than 33,000
2
4 8
If connecting leads and electric fence security wires are installed near overhead
power lines, their height above ground shall not exceed 3m.
G Joints and Terminations
To ensure good electrical contact and carrying capacity and to avoid any
communication interference, it is mandatory that all joints must be clamped either
using ferrules, line clamps or soldered.
H Warning Signs
The following regulations apply:
1. Size shall be at least 100mm × 200mm.
2. Background colour on both sides shall be yellow.
3. A symbol of a black hand touching a wire with flashes (See Figure 1).
4. Warning signs must be placed in clearly visible positions and 1.5 to 2m
above ground level.
5. Not more than 200mm from each corner or bend in a straight length of
fence.
6. Shall be displayed on an access gate if present, and not more than
200mm on either side of access area on which an electric fence is
erected.
7. Spacing between warning signs must not exceed 10m apart in urban areas.
8. Spacing for warning signs on game and rural agricultural fences should
not exceed 100m.
I Lightning Arrestors
A lightning arrestor must be attached as close to the connection from the energizer
and the electric fence as possible, and in the case of a security energizer, two
arrestors must be used. (One on the output wire and one on the return wire.)
J Wall-Top Fencing
1. A walltop fence must be at least 1500mm above walking ground level.
2. Walltop brackets are to be installed at a maximum of 3000mm apart.
3. The maximum distance between wires on the bracket must be 100mm.
4. Strain brackets must be adequately stayed.
5. Fastening devices must penetrate a minimum of 50mm into the supporting wall.
K Free-Standing Electric Fence (Stand-Alone)
A free-standing electric fence shall not be installed in a public area unless the lowest
wire of its live strands is 1500mm above walking ground level or the public are
protected from inadvertent contact with the fence by a barrier fence with a minimum
height of 1500mm. (See Figures 2, 3 and 4)
Figure 2: Typical constructions where the electric security fence is exposed to the public
Figure 3: Typical fence constructions where the electric security fence is
installed in windows and skylights.
Key: Electric security fence Physical barrier
Figure 4: Prohibited zone for pulsed conductors.
Key:Electric security fence
Physical barrier Prohibited zonE
L The Materials Used for the Construction of Electric Fences
There are many specifications in SANS 102223 that cover almost every material
that an installer would use in order to erect an electric fence. If you are purchasing
your materials from a reputable supplier they will no doubt ensure that they are
supplying you with products that meet the required specs. This should cover
products such as insulators, cabling, wire types, line clamps or any other commonly
used products for the erection and installation of an electric fence.
Conclusion
As stated at the beginning, this summary does not presume to cover every
aspect in the gazetted legislation and SANS standards. It is recommended, that
every registered installer of security electric fencing systems be in possession of
a copy of the Act and of the SANS standards mentioned in this document.
In the SANS standards there are also special specifications for Pet Control fences,
Strip Grazing, Game Control fences and general Agricultural fences but as these are
mostly, with the exception of game fences, DIY installations, they are not included
in this summary as they are adequately covered in the literature that accompanies
these products when they are purchased.
We hope that this little pocket book will be of use to you as a ready reference in the
field. Annexure C below is an actual EFSI registration documents from the
Department of Labour and Annexure D below is an actual Certificate of
Compliance that was issued for a client.
Should you require further information please do not hesitate to contact us at our
Head Office on (021) 790 2109 and ask for James.