professional insulation & covering systems for marine, offshore, energy & heavy industries · 2014....
TRANSCRIPT
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
PROFESSIONAL INSULATION & COVERING SYSTEMSfor Marine, Offshore, Energy & Heavy Industries
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
Tough requirements for insulation in heavy industrial environments
>> CORROSION UNDER INSULATIONOne of the greatest challenges of insulation in marine, offshore and heavy industrial environments is presented by the issue of corrosion under insulation (C.U.I). The traditional approach within these extreme environments has been to specify open cell fi brous materials clad with a metal covering.
Under these especially harsh conditions, system fail-ure is regularly encountered. Over time cladding systems rust and fall apart exposing the porous insulation material within. With the water vapour barrier breached the open cell insulation material becomes sodden, dra-matically increasing the risk of corrosion. As moisture migrates through the insulation it causes damage to the pipe through corrosion.
Although salt water proves particularly aggressive any form of moisture within an open cell insulation will attack pipes. The cost of replacing corroded pipes can run into the millions and often require processes to be taken off-line for signifi cant periods of time.
>> REGULAR INSPECTIONInsulation installed on heavy industrial applications should be inspected and evaluated on a regular basis. When the insulation in situ is of the open cell type these inspection regimes often result in the replacement of all insulation at signifi cant cost purely to slow the rate of pipe corrosion.
>> EXPOSURE TO AGGRESSIVE AGENTSIn industrial applications pipework insulation and clad-dings are often exposed to UV, grease, oil and chemical attack.
>> EXPERT INSTALLATIONSpecialised insulation contractors are required to install any insulation on heavy industrial projects.
>> INSULATION OF EQUIPMENTAll valves, fl anges and other unusual shapes must be in-sulated. This proves particularly diffi cult when using tra-ditional materials.
>> CLADDING OF INSULATIONIt is standard practice when insulating in a heavy industrial environment to fully clad the insulation. Traditionally ap-plied cladding systems often create in of themselves con-siderable risk on site (the requirement to weld metal can, for instance, generate potentially dangerous sparks).
>> NOISE REDUCTIONProduction processes - particularly in the offshore envi-ronment - create a serious noise hazard.
All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
For over 50 years Armafl ex has been the leading brand of elastomeric insulation. Repeatedly revolutionising the insulation industry, Armafl ex differs from other traditional insulation types by virtue of its in built water vapour bar-rier. This has implications when it comes to the covering and cladding requirements for Armafl ex.
Whereas traditional insulation types must incorporate a water vapour barrier into their covering systems this is not a requirement for Armafl ex with its built in water vapour barrier. Whilst some of the Arma-Chek systems do indeed offer an exceptional water vapour barrier this was not the foremost priority in their development.
Arma-Chek systems are designed to be particularly resil-ient against damage caused by mechanical impact, ad-verse weather and chemical attack.
Arma-Chek systems are specifi cally designed to help re-duce the risk of C.U.I in:
>> Offshore applications
>> Marine and ship building
>> Petrochemical industries
>> Energy plants & storage facilities
>> Cryogenic Applications (LNG)
In all industries the client demand is for a tough exterior surface to protect the insulation against mechanical im-pact and Arma-Chek systems are the ideal choice:
Signifi cantly minimising the risk of corrosion under insulation.
Increasing the insulation life expectancy by up to 40% compared with traditional materials.
Reducing the frequency and cost of monitoring and maintenance periods.
Representing a highly reliable and cost effective covering system.
Simplifying application with no need for specialised installation equipment.
Reducing safety risks during the application process.
Offering enhanced noise level reductions (particularly when used in combination with ArmaSound)
Providing exceptionally high resistance against UV, oil, chemical and extreme weather.
Meeting international standards.
Protect Your Investment with professional insulation and covering systems
All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
Covering Systems
Universally applicable, yet designed specifi cally to work in harmony with Armafl ex materials, Arma-Chek coverings are fl exible and non-metallic. Easy to install on site, they are suitable as an alternative to metallic surfaces.
As non-metallic systems with no risk of surface corrosion, Arma-Chek systems experience an enhanced life expect-ancy and require signifi cantly less monitoring and mainte-nance compared to metallic systems.
Arma-Chek RThe high performance non metallic covering sys-tem, designed for offshore and heavy industry, which provides extra security to your investment.
When integrated with an Armafl ex substrate, an Arma-Chek R system offers an exceptional resistance against salt water, mechanical impact and UV damage.
Often specifi ed as an alternative to metallic claddings, the non-metallic nature of Arma-Chek R eliminates the risk of galvanic corrosion.
Arma-Chek TThe easy to apply, reliable solution for irregular shapes and hard to access areas.
Arma-Chek T is a non-metallic, fl exible insulation and covering system developed for the hash environments of the oil, gas and petrochemical industries. Arma-Chek T is widely used for onshore and offshore applications. It offers the most reliable and time effective solution for irregular shapes and hard to access areas.
The Armafl ex substrate is covered with a durable terpoly-mer paint with an embedded layer of mat glass fi bre.
Arma-Chek DThe lightweight and easy to apply insulation system resistant to mechanical impact.
Designed for a diverse range of onshore and maritime applications, this black woven glass fi bre covering for Armafl ex substrate offers good resistance to UV, mechani-cal impact and under insulation corrosion when integrated into an Armafl ex system. Arma-Chek D remains fl exible in a moving environment and will not stain or mark.
All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
Acoustic Systems in Industrial environmentsWhen working in industrial environments noise is a major hazard to employees.
Increasingly government legislation requires organisa-tions to take measures to lower noise levels in working environments. This legislation covers most industrial en-vironments.
Recent years have seen the creation and implementation of industry wide standards such as ISO 15665 – “Acous-tic Insulation for pipes, valves and fl anges”. Adhering to the recommendations given in these standards is the best way of demonstrating an attempt to reduce noise levels in an industrial environment.
Industrial SystemsThe acoustic insulation systems that minimise the risk of under insulation condensation.
ArmaSound Industrial Systems represent a sandwich construction comprising different layers of Armafl ex, ArmaSound 240 and Arma-Chek R, each with a specifi c thermal or acoustic objective. Each system is designed to satisfy a particular ISO 15665 classifi cation in order to give a signifi cant noise reduction whilst simultaneously minimising heat losses, preventing moisture ingress and avoiding under insulation corrosion.
All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
Protects Your InvestmentWith its exceptional, inbuilt, water vapour barrier Armafl ex is particularly effective at preventing moisture ingress and ensuring long term thermal effi ciency. The thermal properties of Armafl ex will not rapidly deteriorate over time as other insulation materials may and, by keeping moisture as far from the pipe surface as possible, Armafl ex reduces the risk of expensive under insulation corrosion.
The in built water vapour of Armafl ex comes from its closed cell structure. Armafl ex comprises thousands of interconnected closed cells, each with an inherent re-sistance to water ingress. As such the vapour barrier of Armafl ex cannot be compromised by surface punctures or tears.
In addition Armafl ex is dust and fi bre free. It will not emit any particles or fi bres, even when cut into shapes and fi ttings.
Armafl ex can be easily and cost effectively fabricated into valve and fl ange boxes on site, allowing for the protection of these vulnerable components and the creation of a fully sealed system at signifi cantly reduced cost.
Where industries have specifi c requirements Armafl ex is often available in specialized variants which meet the need. This includes a high temperature Armafl ex suitable for use on heating and process lines in excess of 105 degrees. All Armafl ex variants are manufactured to the highest levels of quality making Armafl ex a product that can truly protect your investment.
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
Samples of industrial projects around the globe
Project Country (of construction) Products
Snohvit Belgium AF/Armafl ex
Spain AF/Armafl ex
Norway AF/Armafl ex
Sea Rose (FPSO) Korea NH/Armafl ex - Arma-Chek R
Canada NH/Armafl ex - Arma-Chek
Norway AF/Armafl ex - Arma-Chek T
Thunder Horse (Platform) Korea NH/Armafl ex - HT/Armafl ex - Arma-Chek R
Shah Deniz Platform Singapore HT/Armafl ex
Central Azeri Platform Azerbaijan Class O Armafl ex
Panyu (FPSO) China Class 1 Armafl ex - NH/Armafl ex - Arma-Chek D
Germany Arma-Chek D
Bozhong 25-1 FPSO China Class1 Armafl ex
Exxon South Venture Canada NH/Armafl ex - Arma-Chek T
BP Atlantis Platform Korea NH/Armafl ex - Arma-Chek R
Marathon Oil - Alpha Platform Ireland ArmaSound Industrial System C (EL)
Sangochal Terminal Azerbaijan ArmaSound Industrial System A & B (EL)
Sakhalin2 LUN-A / PA-B Platforms Korea HT/Armafl ex - AF/Armafl ex - ArmaSound - Arma-Chek R
BP Greater Plutonio FPSO Korea HT/Armafl ex - Arma-Chek R
Sable FPSO Korea NH/Armafl ex
Agbami FPSO Korea NH/Armafl ex
ICE CLASS VESSEL Korea NH Armafl ex
Chevron Tengiz Kazachstan HT/Armafl ex
Exxon Sakhalin1 Russia NH/Armafl ex
US Navy T-AKE USA NH/Armafl ex
Belanak FPSO China NH/Armafl ex - Arma-Chek R
CFD FPSO China Class 1 Armafl ex
Stena RoRo China NH/Armafl ex
South Sea Kaituo FPSO China Class 1 Armafl ex
Shengli platform CB25/26/20A China Class 1 Armafl ex - Arma-Chek D
PetroChina ZY3 platform China Class 1 Armafl ex - Arma-Chek D
NLNG Plus Nigeria Japan HT/Armafl ex
Sakhalin2 LNG Terminal Japan NH/Armafl ex
All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
Professional Technical Knowledge at your ServiceArmaPlus tec. is the technical service from Armacell. Dedicated to using our knowledge to your advantage, ArmaPlus continues to offer the full range of Armacell product technical information and provide technical calculations, specifi cation support and expert applications advice.
>> Technical Calculation
Giving you the tools to make project decisions.
• ArmWin AS - the powerful technical calculation program - available both online and on your desktop.
• Bespoke Calculations - tailored advice to meet your specifi c design requirements
>> Specifi cation & Design Support
Committed to supporting your specifi cation from its earliest steps through to its fi nal implementation.
• Bespoke specifi cations - including thickness calculations and design recom- mendations - based on your specifi c design requirements from our experienced team.
• Application specifi cations - providing detailed application procedure descrip- tions and an inspection list (punch sheet) for surveyer - all relevant to your specifi c project requirements.
>> Application & Project Site Support
Renowned for its expert applications advice, Armaplus tec. builds upon our existing reputation for excellence.
• Application videos and application guides - our expert application specialists have developed a range of easy to follow applications guides for standard applications as well as for special application areas with special needs.
• Certifi ed application trainings - our experienced applications specialists regularly conduct expert training courses which demonstrate fi rst hand the application of Armafl ex.
• Application Advice and support - Our ArmaPlus team operates a premium applications and advice support service specifi cally tailored to individual installa- tion concerns*.
>> Technical Advice & Information Service
Armacell gives all customers a comprehensive range of; technical datasheets, material safety data sheets, project reports, important Armacell news articles and technical information pieces
• Standard Technical Bulletins, FAQ and Best Practice Guides - offering detailed advice and assistance available online 24 hours a day.
• www.armacell.com/mo - Provides all relevant certifi cates, product information, technical data sheets and informing about insulation requirements and backgrounds.
• ArmaPlus tec. Line - Our in house technical teams will answer not only technical product related enquiries but also provide specifi c project support.
* This service is offered only as a premium. Contact your local Armacell representative for more details.
All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
-
PROFESSIONAL INSULATION & COVERING SYSTEMSFOR MARINE, OFFSHORE, ENERGY & HEAVY INDUSTRIES
Armacell UK LimitedMars Street · Oldham, Greater Manchester · OL9 6LYTel. 0161 287 7100 · Fax 0161 633 2685www.armacell.com/uk · [email protected]
Armacell provides this information as a technical service. To the extent the information is derived from sources other than Armacell, Armacell is substan-tially, if not wholly, relying upon the other source(s) to provide accurate information. Information provided as a result of Armacell’s own technical analysis and testing is accurate to the extent of our knowledge and ability, as of date of printing, using effective standardized methods and procedures. Each user of these products, or information, should perform their own tests to determine the safety, fi tness and suitability of the products, or combination of products, for any foreseeable purposes, applications and uses by the user and by any third party to which the user may convey the products. Since Armacell cannot control the end use of this product, Armacell does not guarantee that the user will obtain the same results as published in this document. The data and information are provided as a technical service and are subject to change without notice.All pictures in this brochure are from projects where Armafl ex and Arma-Chek have been installed. For more information please visit www.armacell.com/mo -references.
© Armacell UK Ltd. · Subject to alterations · Printed in UK · SOLIND-001-0707-EN (UK,IRL)
Armacell - The Global Leader for Advanced Insulation and Engineered FoamsWith globally integrated R&D and 20 manufacturing facilities worldwide, Armacell has the ability to service global markets through continuous innovation and unmatched production capacity to meet demand anywhere.
• Melbourne, Australia• Thimister-Clermont, Belgium• Pindamonhangaba, SP, Brazil• Panyu, China• SuZhou, China• Friesenhofen, Germany• Muenster, Germany
• Zeulenroda, Germany• Pune, India• Trezzano, Italy• Sroda Slaska, Poland• Begur, Spain• Pfaffnau, Switzerland• Bangkok, Thailand
• Oldham, UK• Atlanta (GA), USA• Mebane (NC), USA• Conover (NC), USA• South Holland (IL), USA• Spencer (WV), USA
-
Armacell Marine & Offshore Installations
Project Name Project Type Operator Builder ContractorAdventurer of the Seas Cruise Liner Royal Caribbean Kvaerner Masa-Yards Kvaerner Masa-Yards
Carnival Europe Cruise Liner Carnival Cruise Kvaerner Masa-Yards Kvaerner Masa-Yards
Carnival Legend Cruise Liner Carnival Cruise Kvaerner Masa-Yards Kvaerner Masa-Yards
Carnival Pride Cruise Liner Carnival Cruise Kvaerner Masa-Yards Kvaerner Masa-Yards
Carnival Spirit Cruise Liner Carnival Cruise Kvaerner Masa-Yards Kvaerner Masa-Yards
Costa Atlantica Cruise Liner Costa Crociere Kvaerner Masa-Yards Kvaerner Masa-Yards
Explorer of the Seas Cruise Liner Royal Caribbean Kvaerner Masa-Yards Kvaerner Masa-Yards
Navigator of the Seas Cruise Liner Royal Caribbean Kvaerner Masa-Yards Kvaerner Masa-Yards
Radiance of the Sea Cruise Liner Royal Caribbean Meyer Werft Bittner
Voyager of the Seas Cruise Liner Royal Caribbean Kvaerner Masa-Yards Kvaerner Masa-Yards
US Navy Destroyer US Navy Ingalls Shipyard Ingalls Shipyard
Naval Vessel Frigates Malaysia Marconi Marine Marconi Marine
Bruneii Military Ships Royal Bruneii Navy BAE Systems Rigblast
Borgland Dolphin Driller Trans Ocean Harland & Wolff Cape
Transworld Driller Trans Ocean
Cruising Ferry Ferry Aker Finnyards
Landing jetty for The Channel Ferry Aker Finnyards Kvaerner Masa-Yards
Minoan RoRo HN 1279 Ferry Samsung Heavy Industries Samjin
Minoan RoRo HN 1280 Ferry Samsung Heavy Industries Samjin
Minoan RoRo HN 1281 Ferry Samsung Heavy Industries Samjin
Nordsea Ferry North Sea Ferries Govan Shipbuilders Ticon
RoRo Ferries for the Irish Sea Ferry Aker Finnyards Kvaerner Masa-Yards
Alpha 23 A Fixed Platform BP Duffy McGovern
Alpha 27 A Fixed Platform BP Duffy McGovern
Armada Fixed Platform British Gas Kvaerner McGill
Caister Murdoch Fixed Platform Conoco Barmac McGill
Cleeton Fixed Platform BP Barmac McGill
Janice Fixed Platform Kerr McGee Aker McNulty Aker McNulty
Lan Tay Project (Nam Con Son) Fixed Platform BP Hyundai Heavy Industries Samjin
Liverpool Bay Fixed Platform BHP Rigblast
Rough Field Fixed Platform British Gas Amec Rigblast
Forties Field Fixed Platform BP Refurbishment Wood Group
Banff FPSO PGS Aker McNulty Aker McNulty
Bayu-Undan Project FPSO Philips Hyundai Heavy Industries Samjin
Cakerawala Gas Field Development, Malaysia FPSO Petronas Samsung Heavy Industries Samjin
EA Shell FPSO Shell Various in UK, Abu Dhabi, Singapore, Korea Sambawang, Samjin
Leadon FPSO Kerr McGee Swan Hunter C & D Insulation
Schiehallion FPSO BP Harland & Wolff Cape, Rigblast, Chieftrain
Shell Bonga FPSO Shell Samsung Heavy Industries Samjin
Terra Nova FPSO PetroCanada Barmac, Daewoo Cape, Samjin, Bull Arm
See reverse side for more installations
MO PROJ 01 07 NA NA © 2007 Armacell LLC Printed in United States of America
ARMACELL LLC 7600 Oakwood Street Extension P.O. Box 1038 • Mebane, NC 27302
TEL: 1 800 866-5638 • FAX: 919 304-3847 E-MAIL: [email protected] INTERNET: www.armacell.com
-
Armacell Marine & Offshore Installations
Project Name Country Product
Snohvit Belgium AF/Armaflex M99E
Belgium AF/Armaflex M99E
Spain AF/Armaflex M99E
Norway AF/Armaflex M99E
Sea Rose FPSO Korea NH/Armaflex tubes
NH/Armaflex sheets
Arma-Chek R
Canada NH/Armaflex
Arma-Chek
Norway
Thunder Horse Platform Korea NH/Armaflex sheets
NH/Armaflex tubes
HT/Armaflex
Arma-Chek R
Shah Deniz Platform Singapore HT/Armaflex sheets
HT/Armaflex tubes
Central Azeri Platform Azerbaijan Various Armaflex
Panyu FPSO China Class1 / NH
Arma-Chek D
Germany Arma-Chek D (AF)
Bozhong 25-1 FPSO China Class1 sheets
Exxon South Venture Canada NH/Armaflex
Arma-Chek T
BP Atlantis Platform Korea NH/Armaflex Tubes
NH/Armaflex Sheets
Arma-Chek R Black
Marathon Oil Alpha Platform
Ireland Arma-Chek Sound
System C
Sangochal Terminal Azerbaijan Arma-Chek Sound
System A/B
Sakhalin2 LUN-A / PA-B Platforms
Korea HT/Armaflex Sheets
HT/Armaflex Tubes
AF/Armaflex Sheets
AF/Armaflex Tubes
Armafoam Sound
Arma-Chek R Grey
BP Greater Plutonio FPSO Korea Arma-Chek R Grey
Sable FPSO Korea NH/Armaflex
Agbami FPSO Korea NH/Armaflex 25mm sheet
Ice Class Vessel Korea NH Armaflex 19mm sheet
Chevron Tengiz Kazachstan HT/Armaflex
Exxon Sakhalin1 Russia NH/Armaflex
US Navy T-AKE USA NH/Armaflex Rolls
NH/Armaflex Tubes
-
MO SEL 01 07 NA NA ©2007ArmacellLLC PrintedinUnitedStatesofAmerica
ARMACELL LLC 7600 Oakwood Street Extension P.O. Box 1038 • Mebane, NC 27302
TEL: 1 800 866-5638 • FAX: 919 304-3847 E-MAIL: [email protected] INTERNET: www.armacell.com
Insulation Application Performance Requirements Armacell Products
Chilled Water Systems, Refrigeration and Freeze Lines, Seawater Cooling Systems
• Energy saving• Thermally efficient• Moisture resistant• Mold resistant• Code compliant• IAQ friendly: Fiber-free and formaldehyde-free• Flexible• Shipboard, FPSO, Fixed Platforms:
Halogen-free or chlorine-free
• AP Armaflex• NH Armaflex (shipboard, FPSO,
fixed platform)
Process Piping • Resistance to Corrosion Under Insulation• Mechanical protection• Other requirements similar to chilled water
applications
• Arma-Chek• AP Armaflex• NH Armaflex
Air Handling Systems, Interior Ducts Above criteria plus:• Plenum rated• Acceptable noise reduction
• AP Armaflex Duct Liner• AP Armaflex Sheets• NH Armaflex (shipboard, FPSO,
fixed platform)
Exterior Ducts, Tanks • Durable: Protection against impact• UV resistance
• Arma-Chek R• Arma-Chek D
Any Applications Subject to Particularly Severe Conditions, Corrosion Under Insulation, UV Attack, Oil or Chemicals, and Mechanical Impact
• Durable protection for insulation system• Resistance to UV, oil, chemicals• Reduced risk of corrosion under insulation • No galvanic corrosion• Lightweight and flexible
• Arma-Chek R• Arma-Chek D
Higher Temperature and Low Pressure Steam Systems
• Armaflex performance with flexibility at temps up to 300°F
• Excellent UV resistance
• HT Armaflex
Loud HVAC Equipment, Machinery, Particularly LNG
• Combined thermal and acoustical protection• Noise attenuation sufficient to protect workers
and the environment
• ArmaSound
Personnel Protection • Reduced surface temperature• Impact protection or absorption
• AP Armaflex• NH Armaflex• HT Armaflex
Fire Mains • Moisture and condensation prevention• Reduced risk of Corrosion Under Insulation
• Arma-Chek• AP Armaflex• NH Armaflex
Pipe Hanger Locations (Chilled Water Systems)
• Total system integrity• Foam-to-foam bond• Prevent weak points, gaps and compression
at thermal bridges
• Armafix IPH (with AP Armaflex)• Armafix NPH (with NH Armaflex)
The products listed are the Armaflex insulations most frequently specified for marine, offshore and heavy industry applications. Please see separate technical data sheets for Arma-Chek covering systems, Arma-Chek Sound and ArmaSound.
ArmacellMarine&OffshoreProductSelector
Offshore Cruise Liners Marine & Shipbuilding Petrochemical LNG
-
The Versatile Flexible Insulation
THE VERSATILE FLEXIBLE INSULATION
» Specially Developed for Air-Conditioning and Refrigeration Installations
» Built-In Vapour Barrier Prevents Condensation
» Fast Application
-
The Versatile Flexible Insulation
Technical DataValues Remarks
Material Foamed nitrile rubber
Max. Surface Temperature +105° CFor temperatures below -50° C, please consult our Technical Department. Max. Temperature for Flat Surface +85° C
Min. Surface Temperature -50° C
Thermal Conductivity at 0° C 0.038 W/(m · K) Tested according to EN ISO 8497 (DIN 52613) for tubes and EN 12667 (DIN 52612) for sheets
Water Vapour Permeability Moisture Resistance Factor µ 5,000
Reaction to fi re Self-extinguishing, does not drip
Resistance toBuilding Materials Very GoodChemicals Consult Product Test ListOzone Very Good
Health Aspects Dust & Fibre Free
Outdoor applications should be painted with Armafi nish 99 paint to the recommended thickness. Two or more coats may be required.
Armafl ex AC is a highly fl exible elastomeric material which is quick and easy to install It has a closed cell structure with a built in vapour barrier and a high resistance to water vapour transmission enabling the insulation material to maintain a higher level of energy conservation effi ciency. Armafi x pipe supports are recommended for use where thermal bridging may occur. In heating installations the use of pipe supports will generally improve energy conservation.
» Prevention of condensation thanks to closed cell structure of the material
» Low thermal conductivity for an effective energy saving and CO2 reduction.
» High fl exibility allows easy & fast installation
» No shrinkage to minimize the risk of gaps between insulation
» Long life time expectancy
» Secure solution in case of fi re: non dripping and non contributing to fi re
Armacell GmbH · Robert-Bosch-Straße 10D-48153 Münster · Postfach 11 29 · 48001 MünsterTelefon +49 (0) 251 / 76 03 0 · Fax +49 (0) 251 / 76 03 448www.armacell.com · [email protected]
All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropri-ate for the specifi c use intended by the recipient. For updates to this document please refer to our website www.armacell.com.
© Armacell GmbH · Subject to alterations · Printed in UK 105-028-0306-EN (Iran)
-
The Versatile Flexible Insulation
© Armacell GmbH · Subject to alterations (TI 2006/Iran) 25
ARMAFLEX AC TubesLength 2 m, colour black
Copper pipeCu
Iron and steel pipe Fe
Min ID mm
6 mmInsulation Thickness
9 mmInsulation Thickness
Nom OD inch
Nom OD mm NB inch
Nom OD mm Reference m / carton Reference m / carton
1/4 6 6,5 AC-06X006 496 AC-09X006 352
3/8 10 1/8 10,2 10,5 AC-06X010 364 AC-09X010 266
1/2 12 12,5 AC-06X012 316 AC-09X012 234
5/8 15 1/4 13,5 16,0 AC-06X015 266 AC-09X015 192
3/4 18 3/8 17,2 20,0 AC-06X018 210 AC-09X018 166
7/8 22 1/2 21,3 22,5 AC-06X022 166 AC-09X022 136
26,0 AC-09X025 (1) 108
1 1/8 28 3/4 26,9 29,0 AC-06X028 112 AC-09X028 98
1 3/8 35 1 33,7 36,0 AC-09X035 76
1 5/8 42 1 1/4 42,4 43,5 AC-09X042 60
1 1/2 48,3 49,5 AC-09X048 50
2 1/8 54 54,0 55,0 AC-09X054 46
2 60,3 61,5 AC-09X060 36
2 5/8 64 63,5 65,0 AC-09X064 34
76,1 2 1/2 76,1 77,0 AC-09X076 26
3 1/2 88,9 3 88,9 89,0 AC-09X089 20
3 5/8 3 1/2 101,6 102,0
114 4 114,3 114,0 AC-09X114 20
5 139,7 140,0 AC-09X140 (1) 16
Copper pipeCu
Iron and steel pipe Fe
Min ID mm
13 mmInsulation Thickness
19 mmInsulation Thickness
Nom OD inch
Nom OD mm NB inch
Nom OD mm Reference m / carton Reference m / carton
1/4 6 6,5
3/8 10 1/8 10,2 10,5 AC-13X010 172 AC-19X010 98
1/2 12 12,5 AC-13X012 162 AC-19X012 88
5/8 15 1/4 13,5 16,0 AC-13X015 136 AC-19X015 78
3/4 18 3/8 17,2 20,0 AC-13X018 118 AC-19X018 72
7/8 22 1/2 21,3 22,5 AC-13X022 98 AC-19X022 64
26,0
1 1/8 28 3/4 26,9 29,0 AC-13X028 78 AC-19X028 48
1 3/8 35 1 33,7 36,0 AC-13X035 58 AC-19X035 36
1 5/8 42 1 1/4 42,4 43,5 AC-13X042 48 AC-19X042 32
1 1/2 48,3 49,5 AC-13X048 40 AC-19X048 24
2 1/8 54 54,0 55,0 AC-13X054 34 AC-19X054 24
2 60,3 61,5 AC-13X060 32 AC-19X060 18
2 5/8 64 63,5 65,0 AC-13X064 30 AC-19X064 18
76,1 2 1/2 76,1 77,0 AC-13X076 22 AC-19X076 12
3 1/2 88,9 3 88,9 89,0 AC-13X089 18 AC-19X089 12
3 5/8 3 1/2 101,6 102,0 AC-13X102 (1) 16 AC-19X102 (1) 12
114 4 114,3 114,0 AC-13X114 12 AC-19X114 12
5 139,7 140,0 AC-13X140 (1) 12 AC-19X140 (1) 8
-
The Versatile Flexible Insulation
26 (TI 2006/Iran) © Armacell GmbH · Subject to alterations
ARMAFLEX AC CoilsEasy to carry carton (600 x 600 x 220 mm), colour black
Copper pipeCu
Iron and steel pipe Fe
Min ID mm
6 mmInsulation Thickness
9 mmInsulation Thickness
Nom OD inch
Nom OD mm NB inch
Nom OD mm Reference m / carton Reference m / carton
1/4 6 6,5 AC-06X006/E 95 AC-09X006/E 70
3/8 10 1/8 10,2 10,5 AC-06X010/E 75 AC-09X010/E 50
1/2 12 12,5 AC-06X012/E 65 AC-09X012/E 45
5/8 15 1/4 13,5 16,0 AC-06X015/E 55 AC-09X015/E 40
3/4 18 3/8 17,2 20,0 AC-06X018/E 45 AC-09X018/E 38
7/8 22 1/2 21,3 22,5 AC-06X022/E 40 AC-09X022/E 30
1 1/8 28 3/4 26,9 29,0 AC-06X028/E 30 AC-09X028/E 26
ARMAFLEX AC Continuous SheetColour black, skin on both sides
ReferenceInsulation thickness
mmWidth
mLength
mCarton content
m2
AC-03X99/E (1) 3 1 30 30
AC-06X99/E (1) 6 1 15 15
AC-09X99/E 9 1 10 10
AC-13X99/E 13 1 8 8
AC-19X99/E 19 1 6 6
AC-25X99/E 25 1 4 4
AC-32X99/E 32 1 3 3
ARMAFLEX AC Continuous Sheet Self-AdhesiveColour black, with self-adhesive backing
ReferenceInsulation thickness
mmWidth
mLength
mCarton content
m2
AC-03X99/EA (1) 3 1 30 30
AC-06X99/EA (1) 6 1 15 15
AC-09X99/EA 9 1 10 10
AC-13X99/EA 13 1 8 8
AC-19X99/EA 19 1 6 6
AC-25X99/EA 25 1 4 4
AC-32X99/EA 32 1 3 3
ARMAFLEX AC Tape
ReferenceThickness
mmLength
mWidth mm Carton content
AC-TAPE/50 3 15 50 12 rolls
-
The Professional Insulation with Double Performance:
Reliable Condensation Control and Effective Energy SavingBuilt-In Vapour Barrier Prevents Condensation
Long-Term Thermal Performance / Energy Conservation
Ease Of Application
»
»
»
-
The Armaflex Assurance System - your peace-of-mind assurance that Armaflex is made to the strictest quality,technical performance and environmentally friendly standards.
Prevents Moisture PermeationMulti-layered closed wall cells provide a built-in vapour barrier which can’t be compromised by surface punc-tures or rips - this ensures the vapour barrier stays working for the lifetime of the insulation system.
Provides Long-Term Thermal PerformanceNon-wicking - No transmission of water vapour is pos-sible through the insulation due to the closed cell natureof Armaflex. Moisture will not migrate through profes-sionally installed Armaflex.
Long-Term DurabilityNo fragile water vapour barrier - The built-in vapour bar-rier can’t be “damaged” during installation or over thelifetime of the insulation.
Avoids Thermal BridgingArmaflex is a seamless insulation system - these sametechnical properties provide a secure system.
Long-Term Energy EfficiencyBy minimising the ingress of water vapour into theinsulation the multi-layered cells in Armaflex prevent thethermal conductivity from rising. Increased thermal con-ductivity can in the long term lead to increased energycosts and surface condensation.
Inhibits Growth of Mould• Minimises moisture permeation, the first require- ment for mould growth
• Minimises the second requirement: No cellulosic vapour jacket, and the smooth surface doesn’t trap
dust
Formaldehyde-FreeEnsures that Armaflex is a low-emitting product. It isalso low VOC.
Support Requirements of Health & IAQ (Indoor-Air-Quality)• Dust and Fibre-Free• Will not emit any particles or fibres - even when cut
into shapes and fittings• No outgassing - CFC & HCFC free manufacturing
process
Supervised Manufacturing & Technical ValuesFactory Mutual Approval Guide - guarantee consistentperformance to published values by monitoring• Fire Performance (FM pipe chase test, Flammability test)• Water Vapour Transmission• Thermal Conductivity
Supervised Quality StandardsISO Registration ensures that all Armacell manufactur-ing facilities consistently meet customer requirements. . . by managing all processes with ongoing qualityassessments.
The Armaflex Assurance System
The Insulation System which
Keeps your operating costs low
Protects yo Protects your investment Provide
Built-InVapour Barrier
FormaldehydeFree
Dust & FibreFree
-
The Right Tools For Professionals
ARMAFLEX Adhesive 520
ARMAFiXARMAFiX
PaintARMAFINISH COARMAFINISH CO
Class O Armafl ex is the fl exible, closed cell, elastomeric, nitrile rubber insulation that offers reliable protection against condensation and ef-fectively prevents energy loss.A highly effi cient method of insulating hot and cold water services, chilled water lines, heating systems, air conditioning duct work and refrigerated pipe work for frost protection, energy conservation and condensation control. Armafl ex is dust free, fi bre free and CFC free with an ODP of zero which means an environmentally friendly product.» Built in vapour barrier prevents condensation» Long-term thermal performance / energy conservation» Lightweight and fl exible, quick and easy installation with low maintenance requirements, resulting in time and cost savings» Excellent resistance to the effects of ozone, oil and chemicals (consult product test list)
ARMAFLEX Tape Self-Adhesive
Armaflex 520 adhesive is based on modified chloroprene rubber in a blend of flammable solvents. The material has low viscosity for ease of application and quick drying characteristics. In the dry state, Armaflex 520 Adhesive is not flammable. The adhesive is particularly suitable for joining Armaflex flexible elastomeric insulation and for bonding the material to clean prepared surfaces. When properly cured the adhesive maintains the resistance to water vapour expected of Armaflex.
Self-Adhesive tape (available in Class O Armaflex, NH/Armaflex or HT/Armaflex) which may be used for insulating difficult shapes or areas not easily accessible
Armafinish CO is a water-based coating using an advanced terpolymer resin system. When properly applied the coat-ing is suitable for the protection of Armaflex flexible thermal insulation materials against sunlight, UV radiation and chemical attack.The coating, when fully cured, maintains the flexibility, resistance to water vapour and fire performance of the Armaflex material. Where resistance to damage is a particular requirement the coating may be further strength-ened using a random mesh glass fibre scrim.
Glue pump enhanced to use with Armaflex adhesives. Metal can and brush in one with dose pump. Gluing is made faster and more efficient than manual application, requiring no manual “dunking” of an application brush. By adequately spreading the glue onto the surface Gluemaster provides savings by reducing waste to an absolute minimum.
Armafix Insulation Pipe Hangers (IPH) is quick, innovative alternative to traditional block and dowel pipe supports. The engineered, foam-to-foam solutions provide optimum load bearing while protecting against thinkness compression and condensation gaps that can compromise system integrity
Pipe Support Section
ARMAFLEX Gluemaster
-
Class O Armaflex Technical DataTemperature range
Thermal Conductivity (mean temperature)BS874 Part 2 1986Water vapour permeability Moisture Resistance factorBS EN ISO 9346:1996BS4370 Part 2 1973Water absorbtion, by volume after 28 days
Fire performance,surface spread of flame, BS476 Part 7 1997
*
*
Fire propagation, BS476 part 6 1989Total Index of Performance(I)Sub index(i)
Noise reductionResistance to building materialsResistance to chemicals
DimensionsOutdoor applications should be painted with Armafinish CO paint to the recommendedthickness. Two or more coats may be required.
Minimum line temperature-50 CMaximum line temperature +105 C
Flat surfaces and tape +85 C0 +20 +40 C
≤0.034 ≤0 ≤0.036 .039 W/(m.k)> 5,000
-143.6x10 kg/(m.s.Pa)0.13 gm/(N.h)0.9% average,1.5%maximum
Class 1
Less than 12Less than 6
Acoustic level to 30 dB(A)Very good
Consult product test list
Standard tube 2m lengths
*Chilled water lines
Heating systemsAir conditioning ductworkRefrigeration pipeworkand ancillary equipment
Armaflex is ideal for all thermal andacoustic insulation required on:
All statements and technical information are based
on results obtained under typical conditions. It is the
responsibility of the recipient to verify with us that
the information is appropriate for the specific useintended by the recipient.
* If lower temperatures, down to -200 C, areinvolved please consult our sales.
* This meets the 1991 Building Regulations(England and Wales) and the BuildingStandards (Scotland) Regulations 1990 for theClass O fire category.
Health Aspects Dust & Fibre Free
Reaction to fi re Self-extinguishing, does not drip
Hot and cold water services
Drainage pipe / rain water pipe
Technical Data and product rangeR
Armacell Asia Ltd.Room 1201, Tai Tung Building8 Fleming Road,Wanchai,Hong KongTel:852-25748420 Fax:852-25748394www.armacell.com
Copyright: Armacell International GmbH
Armacell Asia Ltd - Singapore Branch583 Ochard Road Forum Building#16-01/17-01Singapore 238884Tel:65-67372768 Fax:65-67372769www.armacell.com
007 - 001 /01 - 0609 -GB( RI, HK)
Tube Size Range
*Delivery quoted on request.
NominalThickness
mm
Sheet
mm
Continuous Sheet
691319 1,220 x 6,000
1,220 x 8,0001,220 x 10,0001,220 x 15,000
Copper Tube Iron & SteelPipe
MinimumID
Armaflex
DNominal
Thickness6mm
MNominal
Thickness19mm
RNominal
Thickness25mm
TNominal
Thickness32mm
UNominal
Thickness40mm
VNominal
Thickness50mm
FNominal
Thickness9mm
HNominal
Thickness13mm
NBin
NBin
NomODin
NomODmm
NomODmm
MinID
mm R m/cm m/cm m/cm m/cm m/cm m/cm m/cm m/cmef. Ref. Ref. Ref. Ref. Ref. Ref. Ref.
1/2
1/43/8
5/83/47/8
31 /8
11 /8
12 /8
52
4
/83
3/81/25/83/4
111 /411 /2
2
12 /2132 /16
4 1/4
51 /8
6101215
22283542
54
67
108
76.1
1/23/4
111 /411 /2
12 /2
2
3
45
21.326.933.742.448.3
60.3
76.188.9
114.3139.7
6.510.512.516.020.022.529.035.543.549.055.061.0
77.090.0109.0115.5142.0
68.0
CO-D-006 CO-F-006 CO-H-006
CO-H-010
CO-H-012
CO-H-015
CO-H-020
CO-H-022
CO-H-028
CO-H-035
CO-H-042
CO-H-048
CO-H-054
CO-H-060
CO-H-067
CO-H-076
CO-H- *089
CO-F-010
CO-F-012
CO-F-015
CO-F-020
CO-F-022
CO-F-028
CO-F-035
CO-F-042
CO-F-048
CO-F-054
CO-F-060
CO-D-010
CO-D-012
CO-D-015
CO-D-020
CO-D-022
CO-D-028
- - -
-CO-M-010
CO-M-006
CO-M-012
CO-M-015
CO-M-020
CO-M-022
CO-M-028
CO-M-035
CO-M-042
CO-M-048
CO-M-054
CO-M-060
CO-M-067
CO-M-076
CO-M-089
CO-M- *108CO-M- *114
CO-M- *140
CO-R-012
CO-R-010
CO-R-015
CO-R-020
CO-R-022
CO-R-028
CO-R-035
CO-R-042
CO-R-048
CO-R-054
CO-R-060
CO-R-067
CO-R-076
CO-R- *089
CO-R- *140
CO-R- *114CO-R- *108
CO-T-015
CO-T-012
CO-U-015
CO-T- *020 CO-U- *020 CO-V- *020
CO-T-022 CO-U-022 CO-V-022
CO-T-028 CO-U-028 CO-V-028
CO-T- *035 CO-U- *035 CO-V- *035
CO-T- *042 CO-U- *042 CO-V- *042
CO-T- *048 CO-U- *048 CO-V- *048
CO-T- *054 CO-U- *054 CO-V- *054
CO-T- *060 CO-U- *060 CO-V- *060
CO-T- *067 CO-U- *067 CO-V- *067
CO-T- *076 CO-U- *076 CO-V- *076
CO-T- *089 CO-U- *089 CO-V- *089
CO-T- *114
CO-T- *140
CO-U- *114 CO-V- *114
CO-U- *140 CO-V- *140
If any other size request,please contact sales
CO-T-108* CO-U-108* CO-V-108*
mmWidthx Length
CO-U- *168CO-T- *168CO-R- *168
Size
CO-R-006
CO-T-010 CO-U-010
CO-U-012 CO-V-012
CO-V-015
165.2 168.06 CO-V-168*
NominalThickness
mm
Sheet
mm mmWidthx Length
Size
25 Width:50mmThickness:3mm
Length:9.14m
1,220 x 4,00032
Armaflex Tapeself-adhesive
50 1,220 x 2,500
1,220 x 3,00040 1,220 x 3,000
612
440
352
264
220
180
144
352
264
220
180
144
128
98
82
60
50
48
32
180
144
128
112
90
90
72
58
48
40
36
28
24
22
18
112
100
90
80
72
60
40
36
28
24
24
20
16
14
12
10
10
6
70
60
56
48
40
40
32
24
22
20
20
16
14
12
12
8
6
4
4
32
32
24
24
22
18
16
12
10
10
8
8
8
8
4
4
4
22
22
18
16
16
12
12
8
10
8
8
8
6
4
4
4
12
12
12
10
8
8
8
8
6
4
4
4
4
4
4
-
RThe insulation system with extra system security that minimises the risk of Under Insulation Corrosion (UIC)
The insulation system with extra system security that minimises the risk of corrosion under insulation (CUI)
Extra System Security from the “Built-In Water Vapour Barrier” in the Covering
Non-Metallic Cladding - No Risk of Galvanic Corrosion
Highly Resilient Protection Against Mechanical Impact
R R
-
The insulation system with extra system security that minimises the risk of Under Insulation Corrosion (UIC) R
Developed for offshore and heavy industrial environments, Arma-Chek R is a high density rubber based covering Armafl ex that offers an excep-tional resistance against salt water, mechanical impact and UV attack.Arma-Chek R is fully weather proof with an exceptionally high water vapour resistance. Its non-metallic nature eliminates the risk of galvanic corrosion
Extra system security from the “inbuilt water-vapour-barrier” in the covering Substantially minimises the risk of under insulation corrosion Provides continuous long term thermal effi ciency No risk of galvanic corrosion Increasing the life expectancy of the insulation system by up to 40%* Reduces monitoring and maintenance by up to 60%* Easy application - no need for specialised machinery Withstands salt water (green water wash over) Exceptional impact resistance Highly resistant to UV, oil and chemicals Non metal cladding system - reduces health and safety risks Complies with international standards
* Compared to traditionally used insulation and cladding systems
Technical DataValues Remarks
Material Flexible polymeric barrier
Max. Surface Temperature+105° C (if based on Class O Armafl ex, NH/Armafl ex)+150° C (if based on HT/Armafl ex)
* For temperatures between -50°C and -200°C, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685
Max. Surface Temperature for Flat Surface
+85° C (if based on Class O Armafl ex, NH/Armafl ex)+130° C (if based on HT/Armafl ex)
Min. Surface Temperature -200° C*
Water Vapour PermeabilityCovering Moisture Resistance Factor µ > 50,000
Water Vapour PermeabilityInsulation No risk of Galvanic corrosion
Moisture Resistance Factor depending on the used Armafl ex substrate
Resistance toImpact Extremely GoodUV Good
For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685
Density 1.6 kg/ltr. (± 50g)For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685
Tensile Strength 5.0 MPa (± 1 MPa)
acc. to ISO 37For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685
Tear Strength 5.0 - 6.5 N/mm
acc. to ISO 34aFor more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685
ElongationArma-Chek R Black 450 - 650%Arma-Chek R Grey 150 - 250%
acc. to ISO 37For more information, please consult our Technical Department. Tel. +44 (0)161 287 7038 · Fax +44 (0)161 633 2685
Health Aspects Dust & Fibre Free
All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specifi c use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.54 2008/2009 (1) © Armacell UK Ltd. · Subject to alterations
R
-
RThe insulation system with extra system security that minimises the risk of Under Insulation Corrosion (UIC)
ARMA-CHEK R (Grey) Pre-coated TubesPrecoated tubes (slit); one butt end of tube with a 50mm overlap of covering material; 50mm selfseal overlap of covering material on seam (longitudinal) of tube; Covering: Grey; Length: 1 metre
Copper pipeCu
Iron pipesteel pipe
Fe
Min ID
mm
25 mm Insulation Thickness
Class O Armafl ex NH/Armafl ex HT/Armafl ex
NB inch
Nom OD inch
Nom OD mm
NB inch
Nom OD mm Reference
m / carton Reference
m / carton Reference
m / carton
1/2 5/8 15 16.0 COR-25X015-GY 25 NHR-25X015-GY 25 HTR-25X015-GY 25
18 3/8 17.2 NHR-25X018-GY 25 HTR-25X018-GY 21
5/8 3/4 20.0 COR-25X020-GY 25
3/4 7/8 22 1/2 21.3 22.5 COR-25X022-GY 21 NHR-25X022-GY 21 HTR-25X022-GY 18
1 1 1/8 28 3/4 26.9 29.0 COR-25X028-GY 20 NHR-25X028-GY 20 HTR-25X028-GY 16
1 1/4 1 3/8 35 1 33.7 35.5 COR-25X035-GY 12 NHR-25X035-GY 12 HTR-25X035-GY 12
1 1/2 1 5/8 42 1 1/4 42.4 43.5 COR-25X042-GY 11 NHR-25X042-GY 11 HTR-25X042-GY 12
1 1/2 48.3 49.0 COR-25X048-GY 9 NHR-25X048-GY 9 HTR-25X048-GY 10
2 2 1/8 54 55.0 COR-25X054-GY 8 NHR-25X054-GY 8 HTR-25X054-GY 9
2 60.3 61.0 COR-25X060-GY 6 NHR-25X060-GY 6 HTR-25X060-GY 9
2 13/16 3 76.1 2 1/2 76.1 77.0 COR-25X076-GY 5 NHR-25X076-GY 5 HTR-25X076-GY 6
3 88.9 90.0 COR-25X089-GY 4 NHR-25X089-GY 4 HTR-25X089-GY 6
ARMA-CHEK R (Grey) Covering on RollsGrey covering for the insulation materials Class O Armafl ex, NH/Armafl ex HT/Armafl ex
ReferenceThickness
mmWidth mm
Length of rollm m2 / roll
ACH-R20/1-07-GY 1 700 20 14
ACH-R10/2-07-GY 2 700 10 7
ARMA-CHEK R (Grey) Mastic
Reference Description Carton content
ACH-MASTICS Light grey sealing compound for installing Arma-Chek R grey outdoors, 290 ml 12 cartridges
• Allowance length for tubes: ± 1.5%
• For all pre-coated tubes: Delivery quoted on request
• PRE-FABRICATED BENDS, T-PIECES & CAP ENDS! A full range of pre-fabricated Arma-Chek R covers for bends, T-pieces and cap ends is available. For full details see either the separate product range document or call our customer service on 0044 (0)161 287 7100. Prices & delivery are quoted on request.
© Armacell UK Ltd. · Subject to alterations 2008/2009 (1) 55
R
-
The insulation system with extra system security that minimises the risk of Under Insulation Corrosion (UIC) R
ARMA-CHEK R (Black) Pre-coated TubesPrecoated tubes (slit); one butt end of tube with a 50mm overlap of covering material; 50mm selfseal overlap of covering material on seam (longitudinal) of tube; Covering: Black; Length: 1 metre
Copper pipeCu
Iron pipesteel pipe
Fe
Min ID
mm
25 mm Insulation Thickness
Class O Armafl ex NH/Armafl ex HT/Armafl ex
NB inch
Nom OD inch
Nom OD mm
NB inch
Nom OD mm Reference
m / carton Reference
m / carton Reference
m / carton
1/2 5/8 15 16.0 COR-25X015-BK 25 NHR-25X015-BK 25 HTR-25X015-BK 25
18 3/8 17.2 NHR-25X018-BK 25 HTR-25X018-BK 21
5/8 3/4 20.0 COR-25X020-BK 25
3/4 7/8 22 1/2 21.3 22.5 COR-25X022-BK 21 NHR-25X022-BK 21 HTR-25X022-BK 18
1 1 1/8 28 3/4 26.9 29.0 COR-25X028-BK 20 NHR-25X028-BK 20 HTR-25X028-BK 16
1 1/4 1 3/8 35 1 33.7 35.5 COR-25X035-BK 12 NHR-25X035-BK 12 HTR-25X035-BK 12
1 1/2 1 5/8 42 1 1/4 42.4 43.5 COR-25X042-BK 11 NHR-25X042-BK 11 HTR-25X042-BK 12
1 1/2 48.3 49.0 COR-25X048-BK 9 NHR-25X048-BK 9 HTR-25X048-BK 10
2 2 1/8 54 55.0 COR-25X054-BK 8 NHR-25X054-BK 8 HTR-25X054-BK 9
2 60.3 61.0 COR-25X060-BK 6 NHR-25X060-BK 6 HTR-25X060-BK 9
2 13/16 3 76.1 2 1/2 76.1 77.0 COR-25X076-BK 5 NHR-25X076-BK 5 HTR-25X076-BK 6
3 88.9 90.0 COR-25X089-BK 4 NHR-25X089-BK 4 HTR-25X089-BK 6
ARMA-CHEK R (Black) Covering on RollsBlack covering for the insulation materials Class O Armafl ex, NH/Armafl ex HT/Armafl ex
ReferenceThickness
mmWidth mm
Length of rollm m2 / roll
ACH-R20/0,7 1 700 20 14
ARMA-CHEK R (Black) Mastic
Reference Description Carton content
ACH-MASTICD Black sealing compound for installing Arma-Chek R outdoors, 290 ml 12 cartridges
• Allowance length for tubes: ± 1.5%
• For all pre-coated tubes: Delivery quoted on request
• PRE-FABRICATED BENDS, T-PIECES & CAP ENDS! A full range of pre-fabricated Arma-Chek R covers for bends, T-pieces and cap ends is available. For full details see either the separate product range document or call our customer service on 0044 (0)161 287 7100. Prices & delivery are quoted on request.
56 2008/2009 (1) © Armacell UK Ltd. · Subject to alterations
R
-
The First Sound Control Systems to Minimise the Risk of Under Insulation Corrosion
INDUSTRIAL SYSTEMS
-
The First Sound Control Systems to Minimise the Risk of Under Insulation CorrosionIndustrial Systems
Combining thermal and noise absorption, ArmaSound Industrial Systems are the latest development for Marine, Offshore and Industrial environments. A sandwich system with different layers of Armafl ex insulation, Arma-Chek R coverings and ArmaSound 240 insulation provides signifi cant noise reduction for all pipe work typically used by these industries.
» Combined thermal and acoustic properties
» The “built-in water-vapour-barrier” provides continuous long-term thermal effi ciency
» Prevents condensation by using closed cell technology
» No galvanic corrosion
» Non-metal cladding system - reduces Health and Safety risks
» Signifi cantly reduced insulation thickness and overall system weight
» Resists UV, oil, chemical and weather attacks
» Considerable reduction in maintenance costs
» Meets ISO 15665 Class A to Class C, Class D acc. to Shell DEP Spec. No. 31
» Meets NORSOK standard R-004 Class 6, 7 and 8
» Meets ASTM E 1222
What is ISO 15665:AcousticISO 15665 is an international standard setting classes for acoustic pipework insulation systems. Insulation systems are classifi ed by their insertion loss performance and the diameter of pipe onto which they are applied.
The standard allows noise control engineers to select the correct insulation system during the design stage in order to ensure that specifi ed noise targets are met.
Table: Minimum insertion loss required for each class acc. ISO 15665:2003
Class
Nominal pipe diameter D mm
Octave band centre frequency, Hz125 250 500 1 000 2 000 4 000 8 000
lower limit upper limit Minimum insertion loss, dB
A1 < 300 - 4 - 4 2 9 16 22 29
A2 ≥ 300 < 650 - 4 - 4 2 9 16 22 29
A3 ≥ 650 < 1 000 - 4 2 7 13 19 24 30
B1 < 300 - 9 - 3 3 11 19 27 35
B2 ≥ 300 < 650 - 9 - 3 6 15 24 33 42
B3 ≥ 650 < 1 000 - 7 2 11 20 29 36 42
C1 < 300 - 5 - 1 11 23 34 38 42
C2 ≥ 300 < 650 - 7 4 14 24 34 38 42
C3 ≥ 650 < 1 000 1 9 17 26 34 38 42
-
Application Areas_pipe work in
Gas & Oil Facilities_
Industrial Applications_
INDUSTRIAL SYSTEMS
Cryogenic Applications_
1
2
3
3 Arma-Chek R 2 mm
2 Armafl ex 25 mm
1 Armafl ex 25 mm
ArmaSound Industrial System A (EL)
ArmaSound Industrial Systems acc. to ISO 15665
For more information and assistance on understanding ISO 15665, including a full calculation tool, see www.armacell.com/uk.
Test Results Class A2 nom. pipe-Ø: ≥ 300mm to < 650mm
Octave band centre frequency, Hz
125 250 500 1 000 2 000 4 000 8 000
Insertion loss, dB -3.9 -1.3 6.4 13.6 24.7 34.8 41.1
3 Arma-Chek R 2 mm
2 ArmaSound 240 25 mm
1 Armafl ex 25 mm
1
2
3
ArmaSound Industrial System B (EL)
Test Results Class B2 nom. pipe-Ø: ≥ 300mm to < 650mm
Octave band centre frequency, Hz
125 250 500 1 000 2 000 4 000 8 000
Insertion loss, dB -3.3 2.0 13.3 20.9 27.4 39.7 45.0
ArmaSound Industrial System C (EL)
Test Results Class C2 nom. pipe-Ø: ≥ 300mm to < 650mm
Octave band centre frequency, Hz
125 250 500 1 000 2 000 4 000 8 000
Insertion loss, dB -1.2 11.8 16.3 24.3 36.0 49.8 47.6
5 Arma-Chek R 2 mm
4 ArmaSound Barrier E 2 mm
3 ArmaSound Barrier E 3 mm
2 ArmaSound 240 25 mm
1 Armafl ex 25 mm
ArmaSound Industrial Systems acc. to ISO 15665
1
23
5
4
-
Armacell UK LimitedMars Street Oldham, Lancs. OL9 6LYTel 0161 287 7100 · Fax 0161 633 2685www.armacell.com · [email protected]
All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specifi c use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.
© Armacell UK Ltd. · Subject to alterations · Printed in UK 038-001-1007-EN (UK,ROI)
The First Sound Control Systems to Minimise the Risk of Under Insulation Corrosion
ARMAFLEXArmafl ex is the worlds leading fl exible elastomeric insulation material. Combining an excel-lent thermal conductivity with a closed cell structure, Armafl ex is renowned for its built-in water vapour barrier, its resistance to water ingress and its long term durability. Unlike other insulation materials Armafl ex requires no external vapour barrier and will maintain its thermal properties over a long period of time.As a dust and fi bre free material Armafl ex has the ideal combination of properties that make it the thermal insulation material of choice for many large scale industrial and offshore projects.
ARMASOUND 240Delivering optimal performance at lower thicknesses than traditional materials, ArmaSound 240 is a uniquely advanced open cell acoustic insulation material. With a peak absorption frequency determined by the insulation thickness and the material density ArmaSound 240 can be engineered to target specifi c problem noise frequencies. Thanks to a density much greater than traditional acoustic absorption materials, ArmaSound 240 is also suitable for some applications that may also call for an acoustic airborne noise barrier.ArmaSound 240 provides a dust and fi bre free solution that is suitable for use in a range of demanding environments.
ARMASOUND Barrier EVinyl sound barrier mat loaded with naturally occurring minerals. The product is free of lead, unrefi ned aromatic oils and bitumen. It is excellent at reducing the transmission of airborne sound and in enhancing the insertion loss performance of pipe insulation.
ARMA-CHEK RArmaChek R is a particularly resilient, non metallic, covering system. Markedly reducing the corrosion and installation issues associated with metallic covering systems ArmaChek R has been designed to work in harmony with Armafl ex insulation, expanding and contracting as required. It is also used to enhance the insertion loss performance of our acoustic insulation systems.
INDUSTRIAL SYSTEMS
6 Arma-Chek R 2 mm
5 Armafl ex 25 mm
4 ArmaSound Barrier E 4 mm
3 ArmaSound 240 25 mm
2 ArmaSound 240 25 mm
1 Armafl ex 25 mm1
2
3
ArmaSound Industrial System D (EL)
4
6
5
Test Results Class D2 nom. pipe-Ø: ≥ 300mm to < 650mm
Octave band centre frequency, Hz
125 250 500 1 000 2 000 4 000 8 000
Insertion loss, dB -3.3 5.1 15.6 37.2 48.8 49.7 45.6
ArmaSound Industrial Systems acc. to SHELL DEP Spec No. 31
Components of ArmaSound Industrial Systems
-
ArmaSound BARRIERHigh performance sound barrier for a quieter environment
High performance sound barrier for a quieter environment
ArmaSound BARRIER
ArmaSound Barrier E: Vinyl sound barrier mat loaded with naturally occurring minerals
ArmaSound Barrier T: Bitumen based, lead free, sound barrier mat ideal for use with metal claddings.
-
High performance sound barrier for a quieter environmentArmaSound BARRIER
50
40
30
20
10
0
100 1000 10000
Frequency (Hz)
Tran
smis
sio
n L
oss
(dB
)
ArmaSound Barrier EVinyl sound barrier mat loaded with naturally occur-ring minerals. The product is free of lead, unrefined aromatic oils and bitumen. It is excellent at reducing the transmission of airborne sound and in enhancing the insertion loss performance of pipe insulation by providing a barrier to noise.
ArmaSound Barrier TBitumen based, lead free, sound barrier mat ideal for use with metal claddings. It is excellent at reducing the transmission of airborne sound and in enhancing the insertion loss performance of pipe insulation by provid-ing a barrier to noise.
Efficient and weight saving anti-drumming of thin wall sheet metal
Excellent adhesion on stainless steel, sheet metal and plastics
Technical DataArmaSound Barrier E ArmaSound Barrier T
Mean Sound Reduction Index RW 28 dB (result valid for 4mm)
Loss factor (@ 20°C, 200 Hz, 1mm steel) ≥ 0.15
Max. Service Temperature * +65° C +80° C
Min. Service Temperature * -30° C -30° C
Application Temperature * > +5° C > +18° C
Thickness 2 mm 3 mm 4 mm 2.3 mm ± 0.2 mm
Weight 5 kg/m2 7.5 kg/m2 10 kg/m2 2 kg/m2 (approx.)
Tensile Strength 2.6 MPa 150 N/20 mm (acc. to DIN 53 112)
Elongation at Break 90%
Hardness Shore A 90
Adhesion on ono-corrosive sheet steel ≥ 7 N/cm
Colour black grey
Health Aspects free of lead free of lead
Storage Temperature +10° C to +25° C
Shelf life approx. 12 months approx. 12 months
Outdoor applications: - ArmaSound Barrier should be covered with Arma-Chek R or Arma-Chek D.
Transmission Loss Curve acc. to ISO 140 Part 3 *
* The results above are based on 4mm ArmaSound Barrier E.
Armacell UK LimitedMars Street Oldham, Lancs. OL9 6LYTel +44 (0)161 287 7100 · Fax +44 (0)161 633 2685www.armacell.com/uk · [email protected]
All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropri-ate for the specific use intended by the recipient. For updates to this document please refer to our website www.armacell.com/uk.
© Armacell UK Ltd. · Subject to alterations · Printed in UK ASoundB-028-0309-EN (UK,ROI,ZA)
-
Armacell GmbHMünster - GERMANY
for the type of product
SURFACE MATERIALS AND FLOOR COVERINGS WITH LOW FLAME-SPREADCHARACTERISTICS: PIPE INSULATION COVERS
ARMAFLEX AC
Regulations and standards :SOLAS 74 Convention, as amended, Regs. II-2/3.29, II-2/3.40.5, II-2/5.3.2.4, II-2/6.2 - IMO Resolution MSC.97(73)(2000 HSCCode) 7.4.3.4, 7.4.3.5, 7.4.3.6 - IMO Resolution A.653(16) - IMO Resolution MSC.61(67), Annex 1 Parts 2 & 5, and Annex 2 -ISO 1716(1973) - IMO MSC/Circ.916, as amended by IMO MSC/Circ.1008 - IMO MSC/Circ.1004.
This certificate is issued under the French Maritime Authority to attest that BUREAU VERITAS did undertake the relevant type-examinationprocedures for the product identified above which was found to comply with the relevant requirements of the Council Directive 96/98/EC of 20December 1996 as amended
This certificate is valid until : 07 Jun 2011
Page 1 / 2
MARINE DIVISION
17 bis Place des Reflets - La Défense 292400 Courbevoie - France
Tel. 33 1 42 91 52 91Fax. 33 1 42 91 28 94
www.veristar.com
Certificate number: 10826/B0 EC
File number : ACI 1360/001/006
Annex A1 Item number : A.1/3.18d
This certificate is not valid when presented without thefull attached schedule composed of 7 sections
EC TYPE EXAMINATION CERTIFICATEas per Module B of European Union Council Directive 96/98/EC on marine equipment
as last amended by Commission Directive 2002/75/EC of 2 September 2002
This certificate is issued to
At Paris la Défense, on : 07 Jun 2006
For BUREAU VERITAS, Notified Body N°0062By order of the Secretary
Approval office Local office : BV HAMBURG
Surveyor : U. Storm
This certificate does not allow to issue the Declaration of Conformity and to affix the mark of conformity (wheelmark) to the products corresponding tothis type. To this end, the production-control phase module (D, E or F) of Annex B of the Directive is to be complied with and controlled by a writteninspection agreement with a notified body.This certificate remains valid until the date stated above, unless cancelled or revoked, provided the conditions indicated in the subsequent page(s) are compliedwith and the product remains satisfactory in service. This certificate will not be valid if the applicant makes any changes or modifications to the approved product,which have not been notified to, and agreed in writing with BUREAU VERITAS. Should the specified regulations or standards be amended during the validity ofthis certificate, the product(s) is/are to be re-approved prior to it/they being placed on board vessels to which the amended regulations or standards apply.BUREAU VERITAS S.A. is designated by the French Maritime Authority as a "notified body" under the terms of the French Regulations Division 140 Chapter140-2. This certificate is issued within the scope of the General Conditions of BUREAU VERITAS Marine Division. Any Person not a party to the contract pursuantto which this document is delivered may not assert a claim against BUREAU VERITAS for any liability arising out of errors or omissions which may be contained insaid document, or for errors of judgement, fault or negligence committed by personnel of the Society or of its Agents in establishment or issuance of this document,and in connection with any activities for which it may provide.
BV mod. Ad.E 536 August 2005 This certificate consists of 2 pages
-
THE SCHEDULE OF APPROVAL
1. PRODUCT DESCRIPTION :
"ARMAFLEX AC" - Insulation material for piping
Insulating sheets and pipes made up of elastomeric foam based on synthetic rubber.
Approx. weight: 1960 g/m².Thickness: from 6 to 32 mm.
2. DOCUMENTS AND DRAWINGS :
As per documentation filed under ACI 1360/001/006.
3. TEST REPORTS :
Test report n° SN97.42.3 dated September 30, 1997 as per IMO FTP Code, Annex 1, Part 5 [testing standard: IMO ResolutionA.653(16)] from TÜV Nord, Germany.
4. APPLICATION / LIMITATION :
• "ARMAFLEX AC" complies with the Smoke and Toxicity requirements as per IMO FTP Code, Annex 2, Paragraph 2.2.• Calorific value to be less than 45 MJ/m² as per ISO 1716(1973).• Insulation material for cold service piping (less than 15°C) and approved for use as a low flame spread surface material.• Approval valid for ships having to comply with SOLAS 74 Convention, as amended, and for units having to comply with
IMO Resolution A649 (The "MODU Code").
On board installation & Maintenance requirements:• The Manufacturer's instruction manual should be kept on board.• The fitting aboard to be the same as used for the test.
5. PRODUCTION SURVEY REQUIREMENTS :
5.1 - The production conformity assessment module shall either be "D, Production-Quality Assurance" or "E, Product-QualityAssurance" or " F, Product Verification".
5.2 - Each equipment or batch of equipment is to be supplied with its manual (or instruction) for installation, use andmaintenance in the language required by the Ship's Flag Administration.
6. MARKING OF PRODUCT :
- ¤ conformity mark and number of the Notified Body undertaking surveillance module (where BV, 0062).- Last two digits of year mark affixed.
7. OTHERS :
7.1 - This approval is given on the understanding that the Manufacturer will accept full responsibility for informing shipbuildersor their sub-contractors of the proper methods of fitting and general maintenance of the approved equipment and the conditionsof this approval.
7.2 - This certificate supersedes EC Type Examination Certificate N° 10826/A0 EC, issued on 07/03/2001 by the Society.
*** END OF CERTIFICATE ***
Page 2 / 2
Certificate number : 10826/B0 EC