product dataair cleaner cleans the air of smoke, dirt, and many pollens commonly found. saves...

16
58DLA/DLX COMFORTt 80 DELUXE 4-WAY MULTIPOISE INDUCED-COMBUSION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh Product Data A04040 THE CARRIER Comfortt 80 GAS FURNACE The 58DLA/DLX 4-way Multipoise Gas Furnaces offer deluxe features not found in other single-stage 80% gas furnaces. Carrier’s QuieTecht noise reduction system makes the Comfortt 80 an incredibly quiet induced-draft gas furnace. The exclusive Carrier Media Cabinet provides an economic way to add high performance air filtration to homes. The gas furnace control system provides a dehumidification mode, a third motor speed selection for continuous fan operation selectable at the thermostat, and fault code storage in the event of power outages. Applications are easy with 4-way multipoise design, through-the-furnace downflow venting, 13 different venting options, and a door designed for easy service access. An inner blower door is provided for tighter sealing in sensitive applications. The 58DLA/DLX furnaces are approved for use with natural or propane gas, and the 58DLX is approved for use in Low NOx Air Quality Management Districts. STANDARD FEATURES QuieTecht noise reduction system SmartEvapt--Humidity control when using a Thermidistat Control Comfort Fant--adjustable constant fan speed from the thermostat High--Efficiency Media Filtration Cabinet included Microprocessor based control center LED diagnostics and self test feature Stores fault codes during power outages Adjustable heating air temperature rise Adjustable cooling airflow Dehumidification selection for summer--time cooling 4--way Multipoise furnace, 13 vent applications Compact design -- only 33--1/3 in. (846 mm) tall Power Heatt Igniter Draft safeguard switch to ensure proper furnace venting Insulated blower compartment Inner door for tighter sealing HYBRID HEATr Dual Fuel System compatible All models are chimney friendly when used with accessory vent kit Twinning in Upflow, Downflow and Horizontal Residential installations eligible for consumer financing through the Retail Credit Program

Upload: others

Post on 09-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

58DLA/DLXCOMFORTt 80 DELUXE 4-WAY MULTIPOISEINDUCED-COMBUSION GAS FURNACEInput Capacities: 45,000 thru 155,000 Btuh

Product Data

A04040

THE CARRIER Comfortt 80 GASFURNACEThe 58DLA/DLX 4-way Multipoise Gas Furnaces offer deluxefeatures not found in other single-stage 80% gas furnaces. Carrier’sQuieTecht noise reduction system makes the Comfortt 80 anincredibly quiet induced-draft gas furnace. The exclusive CarrierMedia Cabinet provides an economic way to add high performanceair filtration to homes. The gas furnace control system provides adehumidification mode, a third motor speed selection forcontinuous fan operation selectable at the thermostat, and faultcode storage in the event of power outages. Applications are easywith 4-way multipoise design, through-the-furnace downflowventing, 13 different venting options, and a door designed for easyservice access. An inner blower door is provided for tighter sealingin sensitive applications. The 58DLA/DLX furnaces are approvedfor use with natural or propane gas, and the 58DLX is approved foruse in Low NOx Air Quality Management Districts.

STANDARD FEATURES— QuieTecht noise reduction system— SmartEvapt--Humidity control when using a

Thermidistat Control— Comfort Fant--adjustable constant fan speed from

the thermostat— High--Efficiency Media Filtration Cabinet included— Microprocessor based control center

LED diagnostics and self test featureStores fault codes during power outagesAdjustable heating air temperature riseAdjustable cooling airflowDehumidification selection for summer--time cooling

— 4--way Multipoise furnace, 13 vent applications— Compact design -- only 33--1/3 in. (846 mm) tall— Power Heatt Igniter— Draft safeguard switch to ensure proper furnace

venting— Insulated blower compartment— Inner door for tighter sealing— HYBRID HEATr Dual Fuel System compatible— All models are chimney friendly when used with

accessory vent kit— Twinning in Upflow, Downflow and Horizontal— Residential installations eligible for consumer

financing through the Retail Credit Program

Page 2: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

2

A02169

HEAT EXCHANGERA02215

CONTROL BOARD

A02170

INDUCER BLOWER

MODEL NUMBER NOMENCLATURE

58DLA 045 100 08

58DLA Deluxe 4--Way Multipoise Nominal Cooling Size58DLX Low NOx version (Airflow at .5 e.s.p.)

(400 CFM per 12,000 Btuh)08---800 CFM12---1200 CFM14---1400 CFM16---1600 CFM

Input Capacity 20---2000 CFM045---44,000 Btuh 110---110,000 Btuh 22---2200 CFM070---66,000 Btuh 135---132,000 Btuh090---88,000 Btuh 155---154,000 Btuh Series Number

58DLA/DLX

Page 3: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

3

FURNACE COMPONENTS

INDUCER MOTOR ASSEMBLY

PRESSURE SWITCH

FLUE COLLECTOR BOX

GAS VALVE

MANUAL RESET LIMIT SWITCHES

HOT SURFACE IGNITOR

CONTROL

RATING PLATE NOT SHOWN (LOCATED ON BLOWER DOOR)

VENT ELBOW

MAIN LIMIT SWITCH (BEHIND GAS VALVE)

DRAFT SAFEGUARD SWITCH

GAS MANIFOLD

GAS BURNER

FLAME SENSOR

BLOWER DOOR SAFETY SWITCH

BLOWER AND MOTOR

*

A09031

*Elbow may be turned to a different position, depending on type of installation.

NOTE: The 58DLA/DLX Furnaces are factory shipped for use with natural gas. These furnaces can be field-convertedfor propane gas with a factory-authorized and listed accessory conversion kit.

58DLA/DLX

Page 4: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

4

CARRIER ACCESSORIES

CONTROLS:THERMOSTATSAND ZONING

Available in programmable andnon-programmable models, Carrierthermostats maintain a constanttemperature level in the home.For the ultimate in home comfort,Carrier’s 2, 4, and 8-zone systemsallow temperature control ofindividual “zones” of the home.This is accomplished through aseries of electronic dampers andremote room sensors. The 4-zonesystem is shown.

A97432

MECHANICALOR ELECTRONICAIR CLEANER

Cleans the air of smoke, dirt, andmany pollens commonly found.Saves decorating and cleaningexpenses by keeping carpets,furniture, and drapes cleaner.Electronic air cleaner is shown.

C04008A01484

MODEL HUMCCLFPHUMIDIFIER

By adding moisture to winter-dryair, a Carrier humidifier can oftenimprove comfort and keepfurniture, rugs, and draperies inbetter condition. Moisturizinghousehold air also helps to retainnormal body heat and providescomfort at lower temperatures.

Accessories

ELECTRONIC AIR CLEANER (EAC) Model EACB

MECHANICAL AIR CLEANER Models EZXCAB, FILCAB

HUMIDIFIER Model HUM

HEAT RECOVERY VENTILATOR Model HRV

ENERGY RECOVERY VENTILATOR Model ERV

UV LIGHTS Model UVL

THERMOSTAT ---NON-PROGRAMMABLE

For use with 1-speed Air Conditioner --- deg. F/C, Auto Changeover --- TP---NAC, TC---NAC

For use with 1-speed Heat Pump --- deg. F/C, Auto Changeover --- TP---NHP, TC---NHP*

For use with 2-speed Air Conditioner --- deg. F/C, Auto Changeover --- TP---NRH*

For use with multi-use / stage configurations --- deg. F/C, Auto Changeover/Temperature and HumidityControl --- TP---PRH{

THERMOSTAT ---PROGRAMMABLE

For use with 1-speed Air Conditioner --- deg. F/C, Auto Changeover, 7-Day Programmable ---TP---PAC

For use with 1-speed Heat Pump --- deg. F/C, Auto Changeover, 7-Day Programmable ---TP---PHP*

For use with 2-speed Air Conditioner --- deg. F/C, Auto Chaongeover, 7-Day Programmable ---TP---PRH*

For use with 1-speed Air Conditioner --- deg. F/C, 5---2 Day Programmable --- TP---PAC

For use with multi-stage applications --- deg. F/C, Auto Changeover, 7-Day Programmable --- TC---PHP}

For multi-use / stage configurations --- deg. F/C, Auto Changeover, 7-Day Programmable/Temperature andHumidity Control ---TP---PRH{

ZONING CONTROL

Comfort™ Series 3-Zone Kit --- ZONECC3ZAC01, ZONECC3ZHP01

2 Performance™ Series ComfortZone™ II Zoning/Temperature and Humidity Control --- ZONECC2KIT01---B

4 Performance™ Series ComfortZone™ II Zoning/Temperature and Humidity Control --- ZONECC4KIT01---B

8 Performance™ Series ComfortZone™ II Zoning/Temperature and Humidity Control --- ZONECC8KIT01---B

* Model HP and 2S thermostat must be field converted to air conditioner operation.† Thermidistat Control can be configured for multiple use and staging, it must be configured for each specific application.

} Dual Fuel thermostat is used with furnace and heat pump application.

58DLA/DLX

Page 5: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

5

CARRIER ACCESSORIES

DESCRIPTION58DLA/DLX

PART NO. 045-08

045-12

070-08

070-12

070-16

090-14

090-16

090-20

110-12

110-16

110-22

135-16

135-22

155-20

Cartridge Media Filter

FILCCCAR0016 X X X X X X X

FILCCCAR0020 X X X X X

FILCCCAR0024 X X

EZ Flex Media Filter with End Caps

EXPXXUNV0016 X X X X X X X

EXPXXUNV0020 X X X X X

EXPXXUNV0024 X X

Replacement EZ Flex Filter Media

EXPXXFIL0016 X X X X X X X

EXPXXFIL0020 X X X X X

EXPXXFIL0024 X X

External Bottom Return Filter Rack

KGAFR0401B14 X X X X

KGAFR0501B17 X X X

KGAFR0601B21 X X X X X

KGAFR0701B24 X X

External Side Return Filter Rack KGAFR0801SRE X X X X X X X X X X X X X X

Unframed Filter 3/4-in. (19 mm)

KGAWF1301UFR† X X X X X X X

KGAWF1401UFR X X X X X

KGAWF1501UFR X X

KGAWF1306UFR† X X X X X X X

KGAWF1406UFR X X X X X

KGAWF1506UFR X X

Flue Extension KGAFE0112UPH X X X X X X X X X X X X X X

Twinning Kit KGATW0601HSI X X X X X X X X X X X X X X

Combustible Floor Base KGASB0201ALL X X X X X X X X X X X X X X

Downflow Vent Guard KGAVG0101DFG X X X X X X X X X X X X X X

Vent Extension Kit KGAVE0101DNH X X X X X X X X X X X X X X

Chimney Adapter KitKGACA02014FC X X X X X X X X X X X

KGACA02015FC X X X

Natural-to-Propane Conversion Kit* KGANP4601ALL X X X X X X X X X X X X X X

Propane-to-Natural Conversion Kit KGAPN3901ALL X X X X X X X X X X X X X X

Label Kit KGALB0101KIT X X X X X X X X X X X X X X

Air Leakage Kit (Qty 10) KGBAC0110DGK X X X X X X X X X X X X X X

Gas Orifice Kit (Qty 50)

KGAHA0150N42

See Installation Instructions for model,altitude, and heat value usages.

KGAHA0250N43(factory supplied)

KGAHA0350N44

KGAHA0450N45

KGAHA0550N46

KGAHA1550N47

KGAHA1650N48

KGAHA0650P54

KGAHA0750P55

KGAHA5750125

KGAHA5750130

KGAHA0850P56

* Factory-authorized and field installed. Fuel conversion kits are AGA/CGA recognized.† Suitable for Side Return Filter Rack (KGAFR0801SRE)X = AccessoryS = Standard

58DLA/DLX

Page 6: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

6

PHYSICAL DATA

UNIT SIZE

045 070 090

08 12 08 12 16 14 16

OUTPUT CAPACITY BTUH*(Nonweatherized ICS) †

58DLX Upflow; all 58DLA 35,000 36,000 53,000 54,000 53,000 71,000 71,000

58DLX Downflow/Horizontal 34,000 34,000 51,000 51,000 51,000 68,000 68,000

INPUT BTUH*58DLX Upflow; all 58DLA 44,000 44,000 66,000 66,000 66,000 88,000 88,000

58DLX Downflow/Horizontal 42,000 42,000 63,000 63,000 63,000 84,000 84,000

AFUE%* Nonweatherized ICS 80.0 80.0 80.0 80.0 80.0 80.0 80.0

SHIPPING WEIGHT --- LB (KG) 104 (47) 107 (49) 111 (50) 115 (52) 126 (57) 127 (58) 140 (64)

CERTIFIED TEMP RISE RANGE --- ° F (° C) 30---60(17---33)

20---50(11---28)

40---70(22---39)

30---60(17---33)

25---55(14---30)

40---70(22---39)

30---60(17---33)

CERTIFIED EXT STATICPRESSURE

Heating 0.10 0.10 0.12 0.12 0.12 0.15 0.15

Cooling 0.50 0.50 0.50 0.50 0.50 0.50 0.50

AIRFLOW CFM‡Heating 920 1250 720 1195 1450 1375 1505

Cooling 845 1160 900 1200 1530 1385 1720

LIMIT CONTROL SPST

HEATING BLOWER CONTROL Solid-State Time Operation

BURNERS (Monoport) 2 2 3 3 3 4 4

GAS CONNECTION SIZE 1/2---in. NPT

GAS VALVE (Redundant) Manufacturer White-Rodgers

Minimum Inlet Pressure (In. wc) 4.5 (Natural Gas)

Maximum Inlet Pressure (In. wc) 13.6 (Natural Gas)

IGNITION DEVICE Hot Surface

* Gas input ratings are certified for elevations to 2000 ft.(610 M) In USA, for elevations above 2000 ft. (610 M), reduce ratings 4 percent for each 1000 ft. (305M) above sea level. In Canada, derate the unit 10 percent for elevations 2000 to 4500 ft. (610 to 1372 M) above sea level. Refer to National Fuel Gas CodeNFPA 54/ANSI Z223.1---2006 Table F.1 (d) or furnace Installation Instructions.

† Capacity in accordance with U.S. Government DOE test procedures.

‡ Airflow shown is for bottom only return ---air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required for eachreturn-air supply.

ICS — Isolated Combustion System

BLOWER PERFORMANCE DATA

UNIT SIZE

045 070 090

08 12 08 12 16 14 16

DIRECT---DRIVE MOTOR Hp (ECM) 1/5 1/3 1/5 1/3 1/2 1/3 1/2

MOTOR FULL LOAD AMPS 2.9 5.2 2.9 5.2 7.9 5.2 7.9

RPM (Nominal) 1075-3 1075-4 1075-3 1075-4 1075-4 1075-4 1075-4

BLOWER WHEEL DIAMETER X WIDTHS --- In. (mm) 10 x 6(254 x 152)

10 x 6(254 x 152)

10 x 6(254 x 152)

10 x 6(254 x 152)

11 x 8(279 x 203)

10 x 8(254 x 203)

10 x 10(254 x 254)

58DLA/DLX

Page 7: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

7

PHYSICAL DATA

UNIT SIZE

090 110 135 155

20 12 16 22 16 22 20

OUTPUT CAPACITY BTUH*(Nonweatherized ICS) †

58DLX Upflow; all 58DLA 71,000 89,000 89,000 89,000 107,000 107,000 125,000

58DLX Downflow/Horizontal 68,000 85,000 85,000 85,000 102,000 102,000 119,000

INPUT BTUH*58DLX Upflow; all 58DLA 88,000 110,000 110,000 110,000 132,000 132,000 154,000

58DLX Downflow/Horizontal 84,000 105,000 105,000 105,000 126,000 126,000 147,000

AFUE%* Nonweatherized ICS 80.0 80.0 80.0 80.0 80.0 80.0 80.0

SHIPPING WEIGHT --- LB (KG) 146 (66) 135 (61) 146 (66) 152 (69) 149 (68) 163 (74) 170 (77)

CERTIFIED TEMP RISE RANGE --- ° F (° C) 25---55(14---30)

50---80(28---44)

40---70(22---39)

30---60(17---33)

50---80(28---44)

40---70(22---39)

45---75(25---42)

CERTIFIED EXTSTATIC PRESSURE

Heating 0.15 0.20 0.20 0.20 0.20 0.20 0.20

Cooling 0.50 0.50 0.50 0.80 0.50 0.50 0.50

AIRFLOW CFM‡Heating High/Low 1990 1335 1515 1900 1525 1850 1790

Cooling 2025 1355 1680 2220 1710 2110 2230

LIMIT CONTROL SPST

HEATING BLOWER CONTROL Solid-State Time Operation

BURNERS (Monoport) 4 5 5 5 6 6 7

GAS CONNECTION SIZE 1/2---in. NPT

GAS VALVE (Redundant) Manufacturer White-Rodgers

Minimum Inlet Pressure (In. wc) 4.5 (Natural Gas)

Maximum Inlet Pressure (In. wc) 13.6 (Natural Gas)

IGNITION DEVICE Hot Surface

* Gas input ratings are certified for elevations to 2000 ft.(610 M) In USA, for elevations above 2000 ft. (610 M), reduce ratings 4 percent for each 1000 ft. (305M) above sea level. In Canada, derate the unit 10 percent for elevations 2000 to 4500 ft. (610 to 1372 M) above sea level. Refer to National Fuel Gas CodeNFPA 54/ANSI Z223.1---2006 Table F.1 (d) or furnace Installation Instructions.

† Capacity in accordance with U.S. Government DOE test procedures.

‡ Airflow shown is for bottom only return ---air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required for eachreturn-air supply.

ICS — Isolated Combustion System

BLOWER PERFORMANCE DATA

UNIT SIZE

090 110 135 155

20 12 16 22 16 22 20

DIRECT-DRIVE MOTOR Hp (PSC) 3/4 1/3 1/2 3/4 1/2 3/4 3/4

MOTOR FULL LOAD AMPS 11.1 5.2 7.9 11.1 7.9 11.1 11.1

RPM (Nominal) ---SPEEDS 1075-4 1075-4 1075-4 1075-4 1075-4 1075-4 1075-4

BLOWER WHEEL DIAMETER x WIDTHS --- In. (mm) 11 x 11(279 x 279)

10 x 8(254 x 203)

10 x 10(254 x 254)

11 x 11(279 x 279)

10 x 10(254 x 254

11 x 11(279 x 279)

11 x 11(279 x 279)

PSC---Permanent Split Capacitor

58DLA/DLX

Page 8: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

8

A02058

SEE NOTES: 1,2,4,7,8,9UPFLOW

SEE NOTES: 1,2,3,4,7,8,9UPFLOW

SEE NOTES: 1,2,4,5,7,8,9DOWNFLOW

A02059 A02061

SEE NOTES:1,2,3,4,5,7,8,9DOWNFLOW

SEE NOTES: 1,2,3,4,5,7,8,9DOWNFLOW

SEE NOTES: 1,2,4,5,6,7,8,9DOWNFLOW

A02060 A02063 A02062

Venting Notes1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel GasCode (NFGC), ANSI Z223.1/NFPA 54. In Canada, latest edition of the National Standards of Canada, Natural Gasand Propane Installation Code (NSCNGPIC), CSA B149.1.

2. Immediately increase to 5-in. (127 mm) vent connector outside furnace casing when 5-in. (127 mm) vent connectorrequired, refer to Note 1.

3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace,except when KGAVG0101DFG is used in downflow position.

4. Type B vent where required, refer to Note 1.5. 4--- in. (102 mm) single wall vent must be used inside furnace casing and the KGAVG0101DFG Downflow Vent GuardKit.

6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with bottom ventconfiguration.

7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kit,KGACA02014FC and KGACA02015FC for sizing and complete application details.

8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, space approximately 180°apart.

9. Secure all other single wall vent connector joints with (3) corrosion-resistant screws spaced approximately 120°apart. Secure Type B vent connectors per vent connector manufacturer’s recommendations.

58DLA/DLX

Page 9: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

9

HORIZONTAL RIGHTSEE NOTES 1,2,4,5,7,8,9

A02068

HORIZONTAL RIGHTSEE NOTES 1,2,4,7,8,9

A02069

HORIZONTAL RIGHTSEE NOTES 1,2,4,5,7,8,9

A02070

HORIZONTAL LEFTSEE NOTES 1,2,4,7,8,9

A02064HORIZONTAL LEFT

SEE NOTES 1,2,4,5,7,8,9

A02065

HORIZONTAL LEFTSEE NOTES 1,2,4,5,7,8,9

A02066HORIZONTAL LEFT

SEE NOTES 1,2,4,5,7,8,9

A02067

58DLA/DLX

Page 10: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

10

AIR DELIVERY—CFM (With Filter)*

UNIT SIZERETURN-AIRSUPPLY SPEED

EXTERNAL STATIC PRESSURE (In. wc)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

045-08Bottomor

1 Side(s)

HighMed-HighMed-Low

1085920820

1035875775

975830730

915770680

845710620

770640555

675555470

565440360

390250190

195——

045-12

Bottomor

1 Side(s)

Low

HighMed-HighMed-Low1085

1450136012501055

1375130012101035

1305124011601035

122511751100990

114511151040945

10501040965885

955950885810

845850790715

705725670715

510575520435

070-08Bottomor

1 Side(s)

HighMed-HighMed-Low

1030835725

1010815700

980790675

945760645

900720600

845675555

775610475

680490390

490375300

335265—

070-12Bottomor

1 Side(s)

HighMed-HighMed-LowLow

1425132012001040

1375128011751030

1320124011451010

126512051105985

120011401050945

11251075990895

1035995920845

940905840765

830790725655

655620555505

070-16Bottomor

1 Side(s)

HighMed-HighMed-LowLow

1805163014601275

1740158514201250

1670153013851225

1600147013251195

1530140512801155

1445133012201105

1360125511551050

128011701080980

11801080995910

1075990910835

090-14Bottomor

1 Side(s)

HighMed-HighMed-LowLow

1650151513851205

1600148513601180

1535144013201160

1465138012601120

1385130011951065

1285122011201005

117511151025925

1055990915810

895830710630

645600565510

090-16Bottomor

1 Side(s)

HighMed-HighMed-LowLow

2060179015051225

1985176515051225

1915171514801220

1820164514401195

1720156013751155

1610147013001085

149013451190985

134011951045870

11351010890735

925820740620

090-20

BottomOnly

HighMed-HighMed-LowLow

2405222520201810

2310215519551765

2220208018801715

2130199518051645

2025189517301565

1920178516301480

1790167515351390

1660156514201280

1530142012751145

1350126011351005

Both Sidesor 1

Side & Bottom

HighMed-HighMed-LowLow

2530228519951770

2450221519451740

2365215019001700

2270207518401645

2165198517701575

2065189016851505

1940178016001415

1805166014801325

1670152513501190

1505136011801040

1 Side Only

HighMed-HighMed-LowLow

2475226019501730

2395219019101695

2300211018551650

2200203517951600

2090194017301535

1985184516501470

1865173515551385

1730162014451285

1585147513101165

1425132511501000

110---12Bottomor

1 Side(s)

HighMed-HighMed-LowLow

1625151013601195

1575147013351180

1515141512951155

1445135512501115

1355128511801065

126011851100980

11651070985860

990890810740

785725670605

595530475410

110---16Bottomor

1 Side(s)

HighMed-HighMed-LowLow

2035174515301270

1965171015151265

1880165014701235

1790156014001195

1680145013101130

1495134012151055

136512051095970

12151090990875

1075955830720

875750670600

* A filter is required for each return ---air supply. Airflow performance includes 3/4---in. (19 mm) washable filter media such as contained in factory---authorizedaccessory filter rack. To determine airflow performance without this fitler, assume an additional .1 available external static pressure.

— Indicates unstable operating conditions.

58DLA/DLX

Page 11: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

11

AIR DELIVERY—CFM (With Filter)* continued

UNIT SIZERETURN-AIRSUPPLY SPEED

EXTERNAL STATIC PRESSURE (In. wc)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

110-22

BottomOnly

HighMed-HighMed-LowLow

2530223019201640

2470220519001650

2400216518801635

2320211018451510

2220203517951575

2115195017301520

2000185516501455

1865174015551375

1730161514601285

1590148513401170

Both Sidesor 1

Side & Bottom

HighMed-High

—2235

—2200

24152155

23502100

22502040

21451955

20151850

18751740

17151595

15601470

1 Side Only

HighMed-HighMed-LowLow

2540212517901515

2495212017951535

2430210517901535

2355206017651520

2265201017201490

2175194016501445

2065184015851390

1935173015001315

1785161513901225

1650148512801120

135-16Bottomor

Side(s)

HighMed-HighMed-LowLow

2090179015451325

2010175515251320

1930170515001295

1835164014501265

1710155013801210

1590146513151150

147013601215995

133512101005865

1025945855745

835785670540

135-22

BottomOnly

HighMed-HighMed-LowLow

2485219518801640

2400215018501635

2310209018201615

2215200017801585

2110192017151530

2000182516351465

1880172015401370

1725156514151255

1535140512901150

1355125511601040

Both Sidesor 1

Side & Bottom

HighMed-HighMed-LowLow

—218018801640

—214518501635

2385206018201615

2305201017801585

2195194517151530

2085186516351465

1960176515401370

1825166014151255

1670151512901150

1465132511601040

1 Side Only

HighMed-HighMed-LowLow

2320212518451640

2250206518251620

2155199517651580

2055191017101540

1970181516501485

1855171015701410

1725161014751330

1600149013701220

1450134012401080

128011751100960

155-20

BottomOnly

HighMed-HighMed-LowLow

2465211518001570

2430210517901565

2375207517701551

2305203017351525

2230198016951495

2110191016401445

2000183015701370

1865172514651270

1725159013451175

1545142512251070

Both Sidesor 1

Side & Bottom

HighMed-High

—2155

—2135

23752095

22852040

22001975

21051895

19951790

18701685

17301550

15701400

1 Side Only HighMed-High

—2140

—2095

22602040

21801975

20851890

19751810

18651705

17401595

16051480

14551325

* A filter is required for each return ---air supply. Airflow performance includes 3/4 in. (19 mm) washable filter media such as contained in factory---authorizedaccessory filter rack. To determine airflow performance without this fitler, assume an additional .1 available external static pressure.

— Indicates unstable operating conditions.

58DLA/DLX

Page 12: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

12

DIMENSIONS

2-7/16"

1-1/8"

28-7/8" (733mm)

25-1/4"

22-9/16"

JUNCTION BOX LOCATION

7/8" DI A ACCESSORY 1/2" (13 mm) DIA.

THERMOSTAT WIRE ENTRY

3-15/16" (84mm)

LEFT HAND GAS ENTRY

33-5/16" 24-7/8"

5-1/2"

7/8" (22mm) DIA.ACCESSORY

11/16"

21-5/8" BOTTOM INLE T

1-11/16"

13/16"

11/16"

4-13/16"

AIRFLOW

19"

OUTLE T

13/16"

11/16" 8-9/16"

VENT OUTLE T 5 PLACES (TYP)

3-3/4"

1-3/4" DIA.RIGHT HAND GAS ENTRY

7/8" DIA. K.O. WIRE ENTRY

SIDE INLE T

14-7/8"

7/8" DIA. ACCESSORY

1-1/4"

1" 22-1/16"

A D

F

E

(FLUE COLLAR)

5-15/16"(135mm)

24" CASING

1-5/16"

1/2" DIA. K.O.THERMOSTAT WIRE ENTRY

ALTERNAT E JUNCTION BOX

LOCATIONS (TYP)

26-1/8"

1-1/2"

7-3/4" 9-5/8"

11-1/2"

5-1/2"

(664mm)

(641mm)

(573mm)

(22mm)

(846mm)

(17mm) (549mm)

(610mm)

(43mm)

(140mm)

(632mm)

(17mm)

(140mm)

(95mm)

(21mm) (122mm)

(217mm)

(62mm)

(33mm)

(29mm) (483mm)

(13mm)

(44mm)

(22mm)

(22mm)

(38mm) (560mm)

(25mm)

(32mm)

(378mm)

(17mm) (197mm) (244mm)

(292mm)

(21mm)

A04037

NOTES:1. Two additional 7/8---in. (22 mm) diameter holes are located in the top plate.2. Minimum return ---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.a. For 800 CFM---16---in. (406 mm) round or 14 1/2 x 12---in. (368 x 305 mm) rectangle.b. For 1200 CFM---20---in. (508 mm) round or 14 1/2 x 19 1/2---in. (368 x 495 mm) rectangle.c. For 1600 CFM---22---in. (559 mm) round or 14 1/2 x 22 1/16---in. (368 x 560mm) rectangle.d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, acombination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.

FURNACESIZE

ACABINETWIDTH

DSUPPLY---AIRWIDTHIN. (MM)

ERETURN---AIRWIDTHIN. (MM)

FCENTER LINETOP AND

BOTTOM FLUECOLLARIN. (MM)

FLUECOLLAR*IN. (MM)

SHIP WTLB (KG)

FILTERMEDIACABINETSIZEIN. (MM)

045---08 14---3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 114 (52) 16 (406)

045---12 14---3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 117 (53) 16 (406)

070---08 14---3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 121 (55) 16 (406)

070---12 14---3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 125 (57) 16 (406)

070---16 17---1/2 (445) 15---7/8 (403) 16---1/8 (410) 11---9/16 (294) 4 (102) 136 (62) 16 (406)

090---14 17---1/2 (445) 15---7/8 (403) 16---1/8 (410) 11---9/16 (294) 4 (102) 135 (61) 16 (406)

090---16 21 (533) 19---3/8 (492) 19---1/2 (495) 13---5/16 (338) 4 (102) 150 (68) 20 (508)

090---20 21 (533) 19---3/8 (492) 19---1/2 (495) 13---5/16 (338) 4 (102) 156 (71) 20 (508)

110---12 17---1/2 (445) 15---7/8 (403) 16---1/8 (410) 11---9/16 (294) 4 (102) 143 (65) 16 (406)

110---16 21 (533) 19---3/8 (492) 19---1/2 (495) 13---5/16 (338) 4 (102) 156 (71) 20 (508)

110---22 21 (533) 19---3/8 (492) 19---1/2 (495) 13---5/16 (338) 4 (102) 162 (73) 20 (508)

135---16 21 (533) 19---3/8 (492) 19---1/2 (495) 13---5/16 (338) 4 (102){ 159 (72) 20 (508)

135---22 24---1/2 (622) 22---7/8 (581) 23 (584) 15---1/16 (383) 4 (102){ 173 (78) 24 (610)

155---20 24---1/2 (622) 22---7/8 (581) 23 (584) 15---1/16 (383) 4 (102){ 180 (82) 24 (610)

* 5 in. or 6 in. (127 or 152 mm) vent connector may be required in some cases.

{ 135 and 155 size furnaces require 5---in. (127 mm) vents. Use a 4---5 in. (102---127 mm) vent adapter between furnace and vent stack.

58DLA/DLX

Page 13: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

13

A

Media/Filter Cabinet A B C

16" (406 mm) 17" (432) 16 1/4"(413) 15" (381)

20" (508 mm) 21" (533) 20 1/4"(514) 19" (483)

24" (610 mm) 25" (635) 24 1/4"(616) 23" (584)

23 5/8"

23 3/8"

Furnace Side

23 3/4"

Centerline Screw Slots

25 5/8"

Duct Side

24 1/2"

With Flanges Bent Out23 1/8"

Opening

5 3/4"

C O

peningw

ith Flanges B

ent In

B

(600 mm)

(594 mm)

(603 mm)

(146 mm)

(651 mm)

(622 mm)

(587 mm)

A00444

A08471

EFFICIENCYRATINGCERTIFIED

MEETS DOE RESIDENTIAL CONSERVATIONSERVICES PROGRAM STANDARDS.

Before purchasing this appliance, read importantenergy cost and efficiency information availablefrom your retailer.

58DLA/DLX

Page 14: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

14

TYPICAL WIRING SCHEMATIC

A99440

ELECTRICAL DATA

FURNACESIZE

VOLTS---HERTZ---PHASE

OPERATING VOLTAGERANGE MAXIMUM

UNIT AMPSUNIT

AMPACITY#

MAXIMUMWIRE

LENGTH FT.(M)‡

MAXIMUMFUSE ORCKT BKRAMPS†

MINIMUMWIREGAUGE

MAXIMUM* MINIMUM*

045---08 115---60---1 127 104 5.4 7.54 49 (15) 15 14

045---12 115---60---1 127 104 7.0 9.50 39 (12) 15 14

070---08 115---60---1 127 104 5.0 7.06 52 (16) 15 14

070---12 115---60---1 127 104 6.8 9.22 40 (12) 15 14

070---16 115---60---1 127 104 9.5 12.60 29 (9) 15 14

090---14 115---60---1 127 104 8.2 10.83 34 (10) 15 14

090---16 115---60---1 127 104 10.0 13.13 28 (9) 15 14

090---20 115---60---1 127 104 13.6 17.61 32 (8) 20 12

110---12 115---60---1 127 104 8.2 10.75 34 (10) 15 14

110---16 115---60---1 127 104 10.1 13.12 28 (9) 15 14

110---22 115---60---1 127 104 14.8 18.99 30 (9) 20 12

135---16 115---60---1 127 104 10.2 13.27 27 (8) 15 14

135---22 115---60---1 127 104 14.4 18.55 30 (9) 20 12

155---20 115---60---1 127 104 15.0 19.33 29 (9) 20 12* Permissible limits of the voltage range at which the unit operates satisfactorily.# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,etc.) full load amps.

{ Time---delay type is recommended.} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.

58DLA/DLX

Page 15: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

15

TYPICAL INSTALLATION

CONDENSINGUNIT

AIRFLOW

ELECTRONICAIR CLEANER

GAS-FIREDWATER HEATER

HUMIDIFIER

A02184

58DLA/DLX

Page 16: Product DataAIR CLEANER Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner. Electronic

16

GUIDE SPECIFICATIONSGas Furnace58DLA/DLXGeneralSYSTEM DESCRIPTIONFurnish a _________________ fixed capacity gas--fired

furnace for use with natural gas or propane (factoryauthorized conversion kit required for propane); furnishcold air return plenum; furnish external medial cabinet foruse with accessory media filter or standard filter.QUALITY ASSURANCEUnit will be designed, tested and constructed to the

current ANSI Z 21.47/CSA 2.3 design standard forgas--fired central furnaces.Unit will be 3rd party certified by CSA to the current

ANSI Z 21.47/CSA 2.3 design standard for gas--firedcentral furnaces.Unit will carry the CSA Blue StarR and Blue FlameR

labels.Unit efficiency testing will be performed per the current

DOE test procedure as listed in the Federal Register.Unit will be certified for capacity and efficiency and

listed in the latest GAMA Consumer’s Directory ofCertified Efficiency Ratings.Unit shall carry the current Federal Trade Commission

Energy Guide efficiency label.DELIVERY, STORAGE AND HANDLINGUnit shall be shipped as single package only and is

stored and handled per unit manufacturer’srecommendations.WARRANTY (for inclusion by specifying engineer)U.S. and Canada only. Warranty certificate available

upon request.ProductsEQUIPMENTComponents shall include: slow-opening gas valve to

reduce ignition noise, regulate gas flow, with electricswitch gas shut--off; flame proving sensor, hot surfaceigniter, pressure switch assembly, flame rollout switch,blower and inducer assembly, 40va transformer;low--voltage (heating) (heating/cooling) thermostat.Blower Wheel and Blower MotorGalvanized blower wheel shall be centrifugal type,

statically and dynamically balanced. Blower motor of PSCtype shall be permanently lubricated with sealed bearings,of _______hp, and shall be multiple--speed direct drive.Blower motor shall be soft mounted to the blower scroll toreduce vibration transmission.FiltersFurnace may have reusable--type filters. Filter shall be

_______ (x) _______in. (mm). An accessory highefficiency Media Filter is available as an option._______________ Media Filter.CasingCasing shall be of .030 (.76 mm) in. thickness

minimum, pre--painted galvanized steel.Inducer MotorInducer motor shall be soft mounted to reduce vibration

transmission.Draft Safeguard SwitchDraft Safeguard Switch (blocked vent safeguard) shall

be factory installed to reduce the possibility of vent gasinfiltration due to a blocked or restricted vent pipe.

Heat ExchangersHeat exchangers shall be a 4-Pass 20 gage aluminized

steel of fold--and--crimp sectional design when appliedoperating under negative pressure.ControlsControl shall include a micro--processor based

integrated electronic control board with at least 11 servicetroubleshooting codes displayed via diagnostic flashingLED light on the control, a self--test feature that checks allmajor functions of the furnace within one minute, and areplaceable automotive--type circuit protection fuse.Multiple operational settings available including, separateblower speeds for heating, cooling, and continuous fan.Continuous fan speed may be adjusted from thethermostat. Cooling airflow will be selectable between 350or 400 CFM per ton of air conditioning. Features will alsoinclude temporary reduced airflow in the cooling mode forimproved dehumidification when a ThermidistatR isselected as the thermostat.OPERATING CHARACTERISTICSHeating Capacity shall be ________ Btuh input;

________ Btuh output capacity.Fuel Gas Efficiency shall be 80% AFUE. Air delivery

shall be ___________ cfm minimum at 0.50 in. wcexternal static pressure.Dimensions shall be: depth __________ in. (mm);

width _________ in (mm); height_________in. (mm)(casing only). Height shall be_________in.(mm) with A/Ccoil and _____________in. (mm) overall with plenum.ELECTRICAL REQUIREMENTSElectrical supply shall be 115 volts, 60 Hz,

single--phase (nominal). Minimum wire size shallbe_________AWG; maximum fuse size or circuit breakershall be __________Amps.SPECIAL FEATURESRefer to section of the product data sheet identifying

accessories and descriptions for specific features andavailable enhancements.

Copyright 2009 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 2/09

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 58DL-6PD

Replaces: 58DL-5PD

58DLA/DLX