Copyright 2009 Carrier Corporation Form 62D-1PD Carrier’s 62D Series commercial dedi- cated outdoor air units offer: Capacities up to 35 nominal tons Vertical or horizontal configurations • Puron ® environmentally sound refrigerant (R-410A) as standard Double wall construction Optional ARI (Air Conditioning and Refrigeration Institute) listed energy recovery wheel Multiple heating options Forward curve or backward inclined plenum fan options Microprocessor control with keypad and easy to view display Slide-out supply fan tray Remote communication capability Corrosion protection package option Features/Benefits Carrier’s 62D commercial packaged 100% outdoor air unit offers efficiency, application flexibility, quality, reliability and easy maintenance. High efficiency The Carrier dedicated outdoor air unit utilizes highly efficient scroll compres- sors that have been optimally designed for use with Puron refrigerant (R-410A). Operating efficiency of the unit may be increased by adding the optional energy recovery system. The energy recovery system uses an ARI listed energy recovery wheel to transfer sensible and latent heat between the incoming air and the exhaust air, re- ducing energy consumption and im- proving indoor conditions. 62DA,DB,DC,DD07-38 Dedicated Vertical or Horizontal 100% Outdoor Air Unit with Optional Energy Wheel 6 to 35 Nominal Tons Product Data 62D22-38 a62-393 a62-395 62D07-09 62D12-20 a62-394

Upload: others

Post on 23-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

Copyright 2009 Carrier Corporation Form 62D-1PD

Carrier’s 62D Series commercial dedi-cated outdoor air units offer:• Capacities up to 35 nominal tons• Vertical or horizontal configurations• Puron® environmentally sound

refrigerant (R-410A) as standard• Double wall construction• Optional ARI (Air Conditioning and

Refrigeration Institute) listed energy recovery wheel

• Multiple heating options• Forward curve or backward inclined

plenum fan options• Microprocessor control with keypad

and easy to view display• Slide-out supply fan tray• Remote communication capability• Corrosion protection package

option

Features/BenefitsCarrier’s 62D commercial packaged 100% outdoor air unit offers efficiency, application flexibility, quality, reliability and easy maintenance.High efficiencyThe Carrier dedicated outdoor air unit utilizes highly efficient scroll compres-sors that have been optimally designed for use with Puron refrigerant (R-410A). Operating efficiency of the unit may be increased by adding the optional energy recovery system. The energy recovery system uses an ARI listed energy recovery wheel to transfer sensible and latent heat between the incoming air and the exhaust air, re-ducing energy consumption and im-proving indoor conditions.

62DA,DB,DC,DD07-38Dedicated Vertical or Horizontal

100% Outdoor Air Unitwith Optional Energy Wheel

6 to 35 Nominal Tons

ProductData

62D22-38

a62-393

a62-395

62D07-09

62D12-20

a62-394

Page 2: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

2

Flexibility to suit many appli-cationsThe Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties, and special applications. The cus-tomer can choose from vertical or hor-izontal supply configurations and over 6 supply fan motor horsepower rat-ings, with forward curved or backward inclined plenum supply fans. Supply fans may be provided with spring isolation and seismic restraints to address earthquake design requirements. The modulating heating system con-trols 3 sizes of gas heat or a wide range electric heat options. Steam or hydron-ic heating coils are also available. Also available are corrosion protec-tion packages, hot gas reheat, power exhaust, 2 or 4-in. filters, and a motor-ized outdoor air damper. Roof curbs that follow the NRCA (National Roofing Contractors Associa-tion) guidelines are available for vertical applications in 14-in. and 24-in. heights and are installed and weather-proofed by the roofing contractor. Units with horizontal connections may be either curb or slab mounted. All 62DA units bring in 100% out-door air through the outside air intake hood and do not have a return air con-nection. The 62DA units have a verti-cal supply duct opening in the bottom of the unit. All 62DB units bring in 100% out-door air through the outside air intake hood and do not have a return air con-nection. The 62DB units have a hori-zontal supply duct opening in the side of the unit. All 62DC units bring in 100% out-door air through the outside air intake hood. They also have an optional ex-haust and/or energy conservation wheel factory installed. The 62DC units have vertical supply and return duct openings in the bottom of the unit. The return air is not recirculated or mixed with the incoming outdoor air. The return air is used to transfer energy to the incoming air with the en-ergy conservation wheel and is then exhausted.

All 62DD units bring in 100% out-door air through the outside air intake hood. They also have an optional ex-haust and/or energy conservation wheel factory installed. The 62DD units have a horizontal supply duct opening in the side of the unit and a vertical return duct opening in the bot-tom of the unit. The return air is not recirculated or mixed with the incom-ing outdoor air. The return air is used to transfer energy to the incoming air with the energy conservation wheel and is then exhausted.

Durable constructionCabinets are constructed of heavy gage galvanized steel with a pre-painted ex-terior finish to protect the cabinet and preserve the appearance through a long operating life. The cabinet features a double wall design with a galvanized inner liner. The double wall design is insulated with closed-cell foam which adds rigidity to the structure and resists moistureintrusion.

Quality and reliabilityAll units are run tested prior to leaving the factory to help ensure proper oper-ation and enhance life expectancy of key components. Components under-go numerous checks and inspections throughout the manufacturing process to eliminate components that do not meet Carrier’s high quality standards. Reliable, hermetic scroll compres-sors, equipped with crankcase heat-ers, are mounted on rubber isolation mounts for smooth, quiet operation.

Mechanically and electrically inde-pendent dual refrigeration circuits (size 12 and larger) provide redundancy in the event that one circuit should re-quire service. All refrigerant circuits uti-lize a thermostatic expansion valve (TXV) to ensure proper refrigerant me-tering throughout the unit’s broad op-erating envelope. The refrigeration cir-cuits are protected by filter driers spe-cifically designed for Puron® refrigerant (R-410A). Standard warranty coverage provides a one-year parts warranty, 5-year com-pressor warranty, and 5 years on the stainless steel gas heat exchanger.

Easy to install, maintain and serviceMaintaining and servicing a dedicated outdoor air unit is critical in maximiz-ing the life expectancy and efficient operation of the unit. The Carrier unit has been designed for easy access with simple maintenance procedures. Hinged access panels provide easy access to controls, fans, coils and fil-ters. Slide-out supply fan system allows easy maintenance of belts, bearings, blower wheels and motors. A dedicated vertical or horizontal de-sign does not require conversion time during the unit installation. Through the curb power connection minimizes roof penetrations. Power connections are in a protect-ed area, away from harsh environmen-tal conditions. All units feature heavy gage formed galvanized steel base rails with rigging openings to simplify han-dling and lifting at the jobsite.

Features/Benefits (cont)

Table of contentsPage

Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Ratings and Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,6Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-11Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-21Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-45Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49-52

Page 3: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

3

Indoor air qualityThe Carrier dedicated outdoor air unit offers 2 and 4-in. filter tracks that ac-cept a variety of filter types and filter MERV ratings. The condensate drain pan is double sloped to eliminate standing water per ASHRAE (American Society of Heat-ing, Refrigerating, and Air Condition-ing Engineers) Standard 62-1089R. The drain pan is fabricated of heavy gage stainless steel to resist corrosion and is insulated on the bottom with closed cell insulation. The double wall design of the unit with galvanized interior liners allows easy cleaning of the interior surfaces.

Energy recovery The Carrier dedicated outdoor air unit may be optionally equipped with an energy recovery (enthalpy) wheel. The enthalpy wheel meets the requirements of ARI standard 1060 and is certified by ARI. This energy recovery wheel is sized to provide increased energy re-covery and humidity control based on the application requirements. The en-ergy wheel is mounted in a slide-out cassette for simplified maintenance.

Heating systemsCarrier dedicated outdoor air units may be equipped with a variety of heat sys-tem types: gas heat (natural gas or liq-uified petroleum gas), electric, steam, or hot water. Precise leaving air tem-perature control is provided via staged or modulating heat control systems. The gas heating systems are of the induced draft design that draws hot combustion gases through the heat ex-changer at the ideal rate for maximum heat transfer. Induced-draft systems are an inherently safer design than forced draft, positive pressure designs. Induced-draft designs operate the heat exchanger under negative pres-sure, helping to prevent leakage of flue gases into the supply airstream. The gas heat system utilizes a direct-spark ignition and is protected by numerous safety circuits.

Microprocessor controlThe microprocessor-based controller provides complete system control of unit operation. The controller monitors all system sensors and makesoperating decisions based upon the user’s configuration inputs. Local access to the microprocessor control is accomplished via the

BACview handheld keypad/display unit. The BACview handheld or unit-mounted keypad/display features a numeric keypad, direction keys, four programmable function keys, and a backlit LCD (liquid crystal diode) dis-play. The display is a large 4-line by 40-character display that is easy to read, even in low light conditions. In addition, the microprocessor control has the following features:• simple access to set points, time

schedules, status values, and unit configuration parameters

• supports communications with BACnet*, Modbus†, and Lon-Works** building automationprotocols

• alarm conditions are indicated via an alarm LED and an audible signal

• alarm history is recorded and may be accessed via the BACview hand-held keypad/display

• password protection• compressor minimum run time

(3 minutes) and minimum off time (5 minutes) feature

• service run test and a service diag-nostic mode

* Sponsored by ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers).† Registered trademark of Schneider Electric.** Registered trademark of Echelon Corporation.

Page 4: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

4

8

8

FC — Forward CurveHGRH— Hot Gas ReheatOA — Outdoor AirVFD — Variable Frequency

Drive

LEGENDAl — AluminumBI — Backward InclinedCu — CopperEM — Energy Management

* Horizontal units with heat require a BI fan.† Control valves for steam and hot water heat coils are field-supplied.

Model number nomenclature

Page 5: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

5

GAS HEAT CAPACITIES

HYDRONIC HEATING COIL CAPACITIES

ENERGY CONSERVATION WHEEL CAPACITIES

LEGEND

UNITSIZE62D

INPUT(Btuh)

OUTPUT(Btuh)

NO. OFGAS HEATSECTIONS

NO. OFSTAGES

MODULATIONRANGE (%)

MINIMUMENTERINGAIR TEMP

(F)

MAXIMUMENTERINGAIR TEMP

(F)

MINIMUMTEMP

RISE (F)

MAXIMUMTEMP

RISE (F)

MINIMUMLEAVINGAIR TEMP

(F)

MAXIMUMLEAVINGAIR TEMP

(F)

07-09

75,000 60,000 1 2 25-100

-20 75 25 90 50 165

100,000 80,000 1 2 25-100150,000 120,000 1 2 25-100200,000 160,000 1 2 25-100

12-20

150,000 120,000 1 2 25-100200,000 160,000 1 2 25-100250,000 200,000 1 2 25-100300,000 240,000 1 2 25-100

22-38

300,000 240,000 1 2 25-100400,000 320,000 1 2 25-100500,000 400,000 2 4 12.5-100600,000 480,000 2 4 12.5-100

UNITSIZE62D

CFMENTERINGAIR TEMP

(F)

STEAM COIL HOT WATER COILSteam Temp

at 5 psig(F)

TotalBtuh

(1000)

LeavingAir Temp

(F)

EnteringWater Temp

(F)

EnteringWater

Flow (gpm)

TotalBtuh

(1000)

LeavingAir Temp

(F)

LeavingWater Temp

(F)

WaterPressure

Drop (ft wg)

07-09 1,300 70 180 87.7 132.2 180 10.9 106.2 145.3 160.5 1.1 3,000 70 180 200.0 130.1 180 20.1 200.4 131.6 160.1 1.9

12-20 1,300 70 180 87.7 132.2 180 10.9 106.2 145.3 160.5 1.1 3,900 70 180 255.0 130.3 180 26.2 260.6 131.6 160.1 2.1 6,500 70 180 345.2 118.9 180 35.7 346.7 119.2 160.6 3.7

22-38 5,000 70 180 370.3 138.3 180 48.9 475.5 157.6 160.6 1.4 8,000 70 180 493.9 126.9 180 68.0 662.0 146.3 160.5 2.711,000 70 180 590.2 119.5 180 84.4 810.9 137.9 160.8 3.9

UNITSIZE62D

WHEELDIAMETER

(in.)

WHEELTHICKNESS

(in.)

MAXIMUMAIRFLOW

(cfm)

AIRPRESSURE

DROP (in. wg)

HEATINGReturn

Air Temp(db/wb)(F)

EnteringOutdoor Air

Temp (F)

LeavingAir Temp

(F)

SensibleBtuh

07-09 36 4 3000 1.37 70.0/58.0 0.0 42.5 144,892

12-2036 4 2700 1.23 70.0/58.0 0.0 42.5 136,21548 4 4500 1.15 70.0/58.0 0.0 47.3 233,423

22-3842 4 3600 1.20 70.0/58.0 0.0 43.1 183,43248 4 4500 1.15 70.0/58.0 0.0 47.3 233,423

db — Dry Bulb Temperaturewb — Wet Bulb Temperature

Ratings and capacities

Page 6: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

6

ELECTRIC HEAT CAPACITIES

AIRFLOW LIMITS

UNITSIZE62D

ELECTRICHEAT kW

(240,480 / 208)

AMPS MINIMUMENTERINGAIR TEMP

(F)

MAXIMUMENTERINGAIR TEMP

(F)

MINIMUMTEMP

RISE (F)

MAXIMUMTEMP

RISE (F)

MINIMUMLEAVINGAIR TEMP

(F)

MAXIMUMLEAVINGAIR TEMP

(F)240 v 480 v 208 v

07-09

5.0 / 3.8 12.0 6.0 10.4

-20 75 N/A 76 N/A 151

7.5 / 5.6 18.0 9.0 15.6 10.0 / 7.5 24.1 12.0 20.8 15.0 / 11.3 36.1 18.0 31.4 20.0 / 15.0 48.1 24.1 41.6 25.0 / 18.8 60.1 30.1 52.2 30.0 / 22.5 72.2 36.1 62.5 35.0 / 26.3 84.2 42.1 73.0 40.0 / 30.0 96.2 48.1 83.3

12-20

10.0 / 7.5 24.1 12.0 20.8 15.0 / 11.3 36.1 18.0 31.4 20.0 / 15.0 48.1 24.1 41.6 25.0 / 18.8 60.1 30.1 52.2 30.0 / 22.5 72.2 36.1 62.5 35.0 / 26.3 84.2 42.1 73.0 40.0 / 30.0 96.2 48.1 83.3 50.0 / 37.5 120.3 60.1 104.1 60.0 / 45.0 144.3 72.2 124.9

22-38

10.0 / 7.5 24.1 12.0 20.8 15.0 / 11.3 36.1 18.0 31.4 20.0 / 15.0 48.1 24.1 41.6 30.0 / 22.5 72.2 36.1 62.5 40.0 / 30.0 96.2 48.1 83.3 50.0 / 37.5 120.3 60.1 104.1 60.0 / 45.0 144.3 72.2 124.9

UNIT SIZE62D

62DA,DB 62DC,DDMin. CFM Max. CFM Min. CFM Max. CFM

07 390 1,650 520 2,20008 975 4,125 975 4,12509 975 4,125 975 4,12512 1040 4,400 1560 6,60014 1040 4,400 1560 6,60015 1560 6,600 1560 6,60016 1560 6,600 1560 6,60020 1560 6,600 1560 6,60022 1995 8,435 2990 12,65024 1995 8,435 2990 12,65030 2990 12,650 2990 12,65034 2990 12,650 2990 12,65038 2990 12,650 2990 12,650

Ratings and capacities (cont)

Page 7: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

7

LEGEND

UNIT 62DA,DB 07 08 09 12 14 15 16NOMINAL CAPACITY (TONS) 6 7 8 10 12 14 15COMPRESSOR Quantity/Unit … Model 1 … ZP57 1 … ZP67 1 … ZP83 2 … ZP44 2 … ZP57 2 … ZP67 2 … ZP83 Number of Refrigerant Circuits 1 2 Oil Pre-Charged Pre-ChargedREFRIGERANT TYPE R-410A R-410A Operating Charge per circuit (lb-oz) 12-13 15-1 15-3 14-9 14-8 16-8 16-3CONDENSER COIL Rows … Fins/in. 2 … 16 2 … 16 Face Area (sq ft) 12.38 24.75CONDENSER FAN Nominal Cfm (total) 4000 5500 8000 11,000 Quantity … Diameter (in.) 1 ... 24 1 … 26 2 … 24 2 … 26 Motor Hp 1/2 3/4 1/2 3/4HIGH-PRESSURE SWITCH (PSIG) Cutout 640 640 Reset (Manual) 595 595EVAPORATOR COIL Tube Size (in.) 3/8 3/8 Rows … Fins/in. 6 ... 12 6 … 12 Face Area (sq ft) 3.00 7.5 8.0 12.0EVAPORATOR FAN Size (in.) Standard FC 12 x 9 12 x 12 15 x 15 Oversize FC N/A 15 x 15 N/A Optional Backward Inclined (BI) 15.0 15.0 Oversize BI 18.5 18.5 Nominal Cfm 100% OA 1000 1200 1400 1500 1900 2300 2800 Motor Hp Range 1/2 - 5 3/4 - 5 1 - 10OPTIONAL REHEAT COIL 24 x 38 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeOPTIONAL SUBCOOLING COIL 24 x 38 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeLOW-PRESSURE SWITCH (PSIG) Cutout 99 99 Reset (Auto) 135 135CONDENSATE DRAIN CONNECTION (NPT) (in.) 1 1/4 1 1/4

OPTIONAL GAS HEAT FURNACE SECTION Gas Input Sizes (Btuh x 1000) 75, 100, 150, 200 150, 200, 250, 300 Control Type Staged (no. of stages) 2 2 Modulating (% range) 25 - 100 25 - 100 Efficiency (Steady State) (%) 82 82 Supply Line Pressure Range (in. wg) 5.0 min - 13.0 max. 5.0 min - 13.0 max. Rollout Switch Cutout Temp (F) 350 350 Gas Valve Quantity 1 Std - 2 with Modulating Option 1 Std - 2 with Modulating Option Manifold Pressure (in. wg) Natural Gas Std 3.5 3.5 LP Gas Special Order 10.0 10.0OPTIONAL ELECTRIC HEAT Size Range (kW) 5.0,7.5,10.0,15.0,20.0,

25.0,30.0,35.0,40.010.0,15.0,20.0,25.0,30.0,35.0,40.0,50.0,60.0

Control Type Staged (no. of stages) 2 2 SCR (% range) 0 - 100 0 - 100OPTIONAL HOT WATER HEAT COIL 24 x 38 in., 2 Row, 10 FPI, with 1/2-in. Tube SizeOPTIONAL STEAM HEAT COIL 24 x 38 in., 1 Row, 8 FPI, with 5/8-in. Tube SizeOUTDOOR AIR FILTERS Quantity … Size (in.) Standard 2 in. MERV 8 4 ... 20x24 4 ... 20x24 Optional 2 in. Metal Mesh 4 ... 20x24 4 ... 20x24 Optional 4 in. MERV 8 4 ... 20x24 4 ... 20x24 MERV 11 4 ... 20x24 4 ... 20x24 MERV 14 4 ... 20x24 4 ... 20x24

FC — Forward CurvedFPI — Fins per InchLP — Liquid PropaneOA — Outdoor AirSCR — Silicon-Controlled Rectifier

Physical data — 62DA,DB units

Page 8: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

8

LEGEND

UNIT 62DA,DB 20 22 24 30 34 38NOMINAL CAPACITY (TONS) 18 19 20 27 30 35COMPRESSOR Quantity/Unit … Model 2 … ZP90 2 … ZP90 2 … ZP103 2 … ZP137 2 … ZP182 4 … ZPT103 Number of Refrigerant Circuits 2 Oil Pre-ChargedREFRIGERANT TYPE R-410A Operating Charge per circuit (lb-oz) 17-1 25-1 25-5 25-10 26-4 32-1CONDENSER COIL Rows … Fins/in. 2 … 16 2 … 16 3 … 12 Face Area (sq ft) 24.75 42.6CONDENSER FAN Nominal Cfm (total) 11,000 11,000 20,000 Quantity … Diameter (in.) 2 … 26 2 … 26 2 … 30 Motor Hp 3/4 1 1 1/2HIGH-PRESSURE SWITCH (PSIG) Cutout 640 Reset (Manual) 595EVAPORATOR COIL Tube Size (in.) 3/8 Rows … Fins/In. 6 … 12 Face Area (sq ft) 12.0 15.3 23.0EVAPORATOR FAN Size (in.) Standard FC 15 x 15 15 x 15 18 x 18 Oversize FC N/A 18 x 18 N/A Optional Backward Inclined (BI) 15.0 24.5 Oversize BI 18.5 27.0 Nominal Cfm 100% OA 3100 2900 3600 4600 5300 6200 Motor Hp Range 1 1/2 - 10 1 1/2 - 10 1 1/2 - 15 2 - 20OPTIONAL REHEAT COIL 36 x 44 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeOPTIONAL SUBCOOLING COIL 36 x 44 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeLOW-PRESSURE SWITCH (PSIG) Cutout 99 Reset (Auto) 135CONDENSATE DRAIN CONNECTION (NPT) (in.) 1 1/4OPTIONAL GAS HEAT FURNACE SECTION Gas Input Sizes (Btuh x 1000) 150, 200, 250, 300 300, 400, 500, 600 Control Type Staged (no. of stages) 2 2 (Low Heat) / 4 (High Heat) Modulating (% range) 25 - 100 Efficiency (Steady State) (%) 82 Supply Line Pressure Range (in.wg) 5.0 min - 13.0 max. Rollout Switch Cutout Temp (F) 350 Gas Valve Quantity 1 Std - 2 with Modulating Option Manifold Pressure (in. wg) Natural Gas Std 3.5 LP Gas Special Order 10.0OPTIONAL ELECTRIC HEAT Size Range (kW) 10.0,15.0,20.0,25.0,

30.0,35.0,40.0,50.0,60.0

10.0,15.0,20.0,30.0,40.0,50.0,60.0

Control Type Staged (no. of stages) 2 SCR (% range) 0 - 100OPTIONAL HOT WATER HEAT COIL 45 x 38 in., 2 Row, 10 FPI, with 5/8-in. Tube SizeOPTIONAL STEAM HEAT COIL 45 x 38 in., 1 Row, 8 FPI, with 5/8-in. Tube SizeOUTDOOR AIR FILTERS Quantity … Size (in.) Standard 2 in. MERV 8 4 ... 20x24 2 ... 20x24, 2 ... 24x24 Optional 2 in. Metal Mesh 4 ... 20x24 2 ... 20x24, 2 ... 24x24 Optional 4 in. MERV 8 4 ... 20x24 2 ... 20x24, 2 ... 24x24 MERV 11 4 ... 20x24 2 ... 20x24, 2 ... 24x24 MERV 14 4 ... 20x24 2 ... 20x24, 2 ... 24x24

FC — Forward CurvedFPI — Fins per InchLP — Liquid PropaneOA — Outdoor AirSCR — Silicon-Controlled Rectifier

Physical data — 62DA,DB units (cont)

Page 9: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

9

LEGEND* 62DC,DD units without the ECW option use a 6-row evaporator coil.

UNIT 62DC,DD 07 08 09 12 14 15 16 20NOMINAL CAPACITY (TONS) 6 7 8 10 12 14 15 18COMPRESSOR Quantity/Unit … Model 1 … ZP57 1 … ZP67 1 … ZP83 2 … ZP44 2 … ZP57 2 … ZP67 2 … ZP83 2 … ZP90 Number of Refrigerant Circuits 1 2 Oil Pre-Charged Pre-ChargedREFRIGERANT TYPE R-410A R-410A Operating Charge per Circuit (lb-oz) 12-13 15-1 15-3 14-9 14-8 16-8 16-3 17-1CONDENSER COIL Rows … Fins/in. 2 … 16 2 … 16 Face Area (sq ft) 12.38 24.75CONDENSER FAN Nominal Cfm (total) 4000 5500 8000 11,000 Quantity … Diameter (in.) 1 … 24 1 … 26 2 … 24 2 … 26 Motor Hp 1/2 3/4 1/2 3/4HIGH-PRESSURE SWITCH (PSIG) Cutout 640 640 Reset (Manual) 595 595EVAPORATOR COIL* Tube Size (in.) 3/8 3/8 Rows … Fins/in. 4 ... 12 4 … 12 Face Area (sq ft) 4.0 7.5 12.0EVAPORATOR FAN Size (in.) Standard FC 12 x 9 12 x 12 15 x 15 Oversize FC N/A 15 x 15 N/A Optional Backward Inclined (BI) 15.0 15.0 Oversize BI 18.5 18.5 Nominal Cfm 100% OA 1000 1200 1400 1500 1900 2300 2800 3100 Motor Hp Range 1/2 - 5 3/4 - 5 1 - 10 1 1/2 - 10OPTIONAL REHEAT COIL 24 x 38 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeOPTIONAL SUBCOOLING COIL 24 x 38 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeLOW-PRESSURE SWITCH (PSIG) Cutout 99 99 Reset (Auto) 135 135CONDENSATE DRAIN CONNECTION (NPT) (in.) 1 1/4 1 1/4 OPTIONAL GAS HEAT FURNACE SECTION Gas Input Sizes (Btuh x 1000) 75, 100, 150, 200 150, 200, 250, 300 Control Type Staged (no. of stages) 2 2 Modulating (% range) 25 - 100 25 - 100 Efficiency (Steady State) (%) 82 82 Supply Line Pressure Range (in. wg) 5.0 min - 13.0 max. 5.0 min - 13.0 max. Rollout Switch Cutout Temp (F) 350 350 Gas Valve Quantity 1 Std - 2 with Modulating Option 1 Std - 2 with Modulating Option Manifold Pressure (in. wg) Natural Gas Std 3.5 3.5 LP Gas Special Order 10.0 10.0OPTIONAL ELECTRIC HEAT

Size Range (kW) 5.0,7.5,10.0,15.0,20.0, 25.0,30.0,35.0,40.0 10.0,15.0,20.0,25.0,30.0,35.0,40.0,50.0,60.0

Control Type Staged (no. of stages) 2 2 SCR (% range) 0 - 100 0 - 100OPTIONAL HOT WATER HEAT COIL 24 x 38 in., 2 Row, 10 FPI, with 1/2-in. Tube SizeOPTIONAL STEAM HEAT COIL 24 x 38 in., 1 Row, 8 FPI, with 5/8-in. Tube SizeOUTDOOR AIR FILTERS Quantity … Size (in.) Standard 2 in. MERV 8 4 ... 20x24 4 ... 20x24 Optional 2 in. Metal Mesh 4 ... 20x24 4 ... 20x24 Optional 4 in. MERV 8 4 ... 20x24 4 ... 20x24 MERV 11 4 ... 20x24 4 ... 20x24 MERV 14 4 ... 20x24 4 ... 20x24OPTIONAL ECW Type Molecular Sieve Molecular Sieve Size (in.) 36 36 or 48OPTIONAL ECW FILTERS Quantity … Size (in.) with 36 in. ECW 2 ... 20x24, 2 ... 20x20 2 ... 20x24, 2 ... 20x20 with 42 in. ECW N/A N/A with 48 in. ECW N/A 4 ... 20x24, 2 ... 12x24OPTIONAL EXHAUST FAN Size (in.) Standard FC 9 x 7 12 x 12 Oversize FC 12 x 9 15 x 15 Motor Hp Range 1/2 - 5 1/2 - 10

ECW — Energy Conservation WheelFC — Forward CurvedFPI — Fins per InchLP — Liquified PetroleumOA — Outdoor AirSCR — Silicon-Controlled Rectifier

Physical data — 62DC,DD units

Page 10: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

10

Physical data — 62DC,DD units (cont)

LEGEND* 62DC,DD units without the ECW option use a 6-row evaporator coil.

UNIT 62DC,DD 22 24 30 34 38NOMINAL CAPACITY (TONS) 19 20 27 30 35COMPRESSOR Quantity/Unit … Model 2 … ZP90 2 … ZP103 2 … ZP137 2 … ZP182 4 … ZPT206 Number of Refrigerant Circuits 2 Oil Pre-ChargedREFRIGERANT TYPE R-410A Operating Charge per Circuit (lb-oz) 25-1 25-5 25-10 26-4 32-1CONDENSER COIL Rows … Fins/in. 2 … 16 3 … 12 Face Area (sq ft) 42.6CONDENSER FAN Nominal Cfm (total) 11,000 20,000 Quantity … Diameter (in.) 2 … 26 2 … 30 Motor Hp 1 1 1/2HIGH-PRESSURE SWITCH (PSIG) Cutout 640 Reset (Manual) 595EVAPORATOR COIL* Tube Size (in.) 3/8 Rows … Fins/in. 4 … 12 Face Area (sq ft) 23.0EVAPORATOR FAN Size (in.) Standard FC 15 x 15 18 x 18 Oversize FC 18 x 18 N/A Optional Backward Inclined (BI) 24.5 Oversize BI 27.0 Nominal Cfm 100% OA 2900 3600 4600 5300 6200 Motor Hp Range 1 1/2 - 10 1 1/2 - 15 2 - 20OPTIONAL REHEAT COIL 36 x 44 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeOPTIONAL SUBCOOLING COIL 36 x 44 in., 1 Row, 12 FPI, with 3/8-in. Tube SizeLOW-PRESSURE SWITCH (PSIG) Cutout 99 Reset (Auto) 135CONDENSATE DRAIN CONNECTION (NPT) (in.) 1 1/4OPTIONAL GAS HEAT FURNACE SECTION Gas Input Sizes (MBtuh) 300, 400, 500, 600 Control Type Staged (no. of stages) 2 (300 and 400) / 4 (500 and 600) Modulating (% range) 25 - 100 Efficiency (Steady State) (%) 82 Supply Line Pressure Range (in. wg) 5.0 min - 13.0 max. Rollout Switch Cutout Temp (F) 350 Gas Valve Quantity 1 Std - 2 with Modulating Option Manifold Pressure (in. wg) Natural Gas Std 3.5 LP Gas Special Order 10.0OPTIONAL ELECTRIC HEAT Size Range (kW) 10.0,15.0,20.0,30.0,40.0,50.0,60.0 Control Type Staged (no. of stages) 2 SCR (% range) 0 - 100OPTIONAL HOT WATER HEAT COIL 45 x 38 in., 2 Row, 10 FPI, with 5/8-in. Tube SizeOPTIONAL STEAM HEAT COIL 45 x 38 in., 1 Row, 8 FPI, with 5/8-in. Tube SizeOUTDOOR AIR FILTERS Quantity … Size (in.) Standard 2 in. MERV 8 2 ... 20x24, 2 ... 24x24 Optional 2 in. Metal Mesh 2 ... 20x24, 2 ... 24x24 Optional 4 in. MERV 8 2 ... 20x24, 2 ... 24x24 MERV 11 2 ... 20x24, 2 ... 24x24 MERV 14 2 ... 20x24, 2 ... 24x24OPTIONAL ECW Type Molecular Sieve Size (in.) 42 or 48OPTIONAL ECW FILTERS Quantity … Size (in.) with 36 in. ECW N/A with 42 in. ECW 4 ... 20x24, 2 ... 12x24 with 48 in. ECW 6 ... 18x24OPTIONAL EXHAUST FAN Size (in.) Standard FC 15 x 15 Oversize FC 18 x 18 Motor Hp Range 1/2 - 20

ECW — Energy Conservation WheelFC — Forward CurvedFPI — Fins per InchLP — Liquified PetroleumOA — Outdoor AirSCR — Silicon-Controlled Rectifier

Page 11: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

11

UNIT AND COMPONENT WEIGHTS (lb)

COMPONENT62D UNIT SIZE

07 08 09 12 14 15 16 20 22 24 30 34 38Base Unit 1650 1690 1710 1910 1960 2120 2060 2080 3375 3475 3575 3655 4075Hot Gas Reheat 35 35 35 75 75 75 75 75 120 120 120 120 120Liquid Subcooling Coil 25 25 25 55 55 55 55 55 100 100 100 100 100Gas Furnace (Btuh) 75,000 140 140 140 — — — — — — — — — — 100,000 150 150 150 — — — — — — — — — — 150,000 160 160 160 160 160 160 160 160 — — — — — 200,000 170 170 170 170 170 170 170 170 — — — — — 250,000 — — — 210 210 210 210 210 — — — — — 300,000 — — — 250 250 250 250 250 250 250 250 250 250 400,000 — — — — — — — — 275 275 275 275 275 500,000 — — — — — — — — 420 420 420 420 420 600,000 — — — — — — — — 500 500 500 500 500Electric Heater 75 75 75 75 75 75 75 75 100 100 100 100 100Steam Coil 60 60 60 60 60 60 60 60 120 120 120 120 120Hot Water Coil 75 75 75 75 75 75 75 75 150 150 150 150 150Wheel Bypass Dampers 60 60 60 60 60 60 60 60 125 125 125 125 125Energy Conservation Wheel 350 350 350 420 420 420 420 420 470 470 470 470 470Power Exhaust 345 345 345 375 375 375 375 375 525 525 525 525 525Curb 14-in. 275 275 275 275 275 275 275 275 305 305 305 305 305Curb 24-in. 375 375 375 375 375 375 375 375 425 425 425 425 425

Physical data (cont)

Page 12: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

12

Options and accessories

LEGEND

*Factory installed.†Field installed.

ITEM OPTION* ACCESSORY†Heat Options Gas Heat X Gas Heat with Override X Electric Heat X Hot Water Heating Coil X Steam Heating Coil X LP Kit XEnergy Conservation Wheel Options Standard Wheel X Optional Wheel X Wheel with VFD Defrost Control X Wheel with Bypass Dampers XControl Options Filter Status Switch X Phase/Voltage Monitor with Energy Management Relay X Firestat X Supply Fan Status Switch X Convenience Outlet X Non-Fused Disconnect Switch XCoil Options Hot Gas Reheat X Liquid Subcooling Coil X Coated Coils XFilter Options 2-in. MERV 8 Filters X X 4-in. MERV 8 Filters X X 4-in. MERV 11 Filters X X 4-in. MERV 13 Filters X 4-in. MERV 14 Filters X 2-in. Metal Mesh Filters XSupply Fan Options Oversize Forward Curved Fan X Backward Inclined Fan X Oversize Backward Inclined Fan XExhaust Fan Options Oversize Forward Curved Fan X Backward Inclined Fan X Oversize Backward Inclined Fan X14-in Factory-Assembled Roof Curb X24-in. Factory-Assembled Roof Curb X14-in Field-Assembled Roof Curb X24-in. Field-Assembled Roof Curb X

VFD — Variable Frequency Drive

Page 13: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

13

SUPPLY

7 20

36

3 1/2

1 TYP.

4

TOP VIEW

FRONT VIEW

SIDE VIEW

38 1/2

57 1/2

82 1/2

38 1/4

39 3/42 1/2

6 1/2

15 1/2

62

8

107 3/425 1/4

FILTER ACCESS

OUTSIDE AIRINTAKE HOOD

CONTROL PANELSUPPLY FAN

CONDENSATE DRAIN PAN

POWER THROUGHTHE CURB

96

(HORIZONTAL SUPPLY)

36

5

520

16 1/2

32

BOTTOM VIEW(VERTICAL SUPPLY)

GASINLET

STANDARD UNIT

a62-448

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

Base unit dimensions — 62DA,DB07-09

Page 14: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

14

Base unit dimensions — 62DC,DD07-09

SUPPLY RETURN

TOP VIEW

FRONT VIEW

BOTTOM VIEW(VERTICAL SUPPLY)

SUPPLY FANFILTER ACCESS

CONTROL PANEL

OUTSIDE AIRINTAKE HOOD

CONDENSATE DRAIN PAN

POWER THROUGHTHE CURB

7 20

15 1/2

3 1/2 3 1/2

36

838 1/4

1TYP.

30 1/4

36

20

38 1/2

57 1/2

96

82 1/2

4

6 1/2

2 1/2 39 3/4

15 1/2

62

107 3/4

9 7/8

25 1/4

SIDE VIEW(HORIZONTAL SUPPLY)

36

5

520

16 1/2

32

EXHAUST

GAS INLET

UNIT WITH OPTIONAL EXHAUST

a62-449

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

Page 15: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

15

S UPPLY FAN

FILTER ACCESS

CONTROL PANEL

SUPPLY RETURN

TOP VIEW

FRONT VIEW

BOTTOM VIEW(VERTICAL SUPPLY)

7 20

15 1/2

3 1/2

36

838 1/4 CONDENSATEDRAIN PAN

3 1/2

38 1/2

57 1/2

104 5/8

30 1/4

36

20

25 1/4

9 7/8

129 7/8

96

EXHAUST

1 TYP

39 3/42 1/2

6 1/2

4

15 1/2

POWER THROUGHTHE CURB

62

3 7/8

SIDE VIEW(HORIZONTAL SUPPLY)

36

5

520

16 1/2

32

ENERGY CONSERVATIONWHEEL ACCESS

OUTSIDE AIRINTAKE HOOD

GAS INLET

UNIT WITH OPTIONAL ENERGY CONSERVATION WHEEL

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-450

Page 16: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

16

Base unit dimensions — 62DA,DB12-20

SUPPLY

TOP VIEW

FRONT VIEW

BOTTOM VIEW(VERTICAL SUPPLY)

38 1/2

57 1/2

82 1/2107 3/4

38 1/4

39 3/42 1/2

6 1/2

15 1/2

1 TYP.

3 1/2

36

7 20

4

62

8

25 1/4

FILTER ACCESS

OUTSIDE AIRINTAKE HOOD

CONTROL PANELSUPPLY FAN

CONDENSATE DRAIN PAN

POWER THROUGHTHE CURB

96

SIDE VIEW(HORIZONTAL SUPPLY)

36

5

520

16 1/2

32

GASINLET

STANDARD UNIT

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-451

Page 17: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

17

S UPP LY FAN FILT E R AC CESS

C ONTR OL PANEL

SU P PLY RETURN

TOP VIEW

FR ONT VIEW

BOTT OM VIEW(VERTICAL SUPPLY)

7 20

15 1/2

36

838 1/4 CONDENSATEDR AIN PAN

1 TYP.

30 1/4

EX HAUST

36

20

38 1/2

57 1/2

96

9 7/8

251/482 1/2

107 3/4

4

6 1/2

2 1/239 3/4

POW E R THR OUGHTHE CURB

15 1/2

3 1/23 1/2

62

SIDE VIEW(HORIZONTAL SUPPLY)

36

5

520

16 1/2

32

GAS INLET

OUTSIDE AIRINTAKE HOOD

UNIT WITH OPTIONAL EXHAUST

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-452

Base unit dimensions — 62DC,DD12-20

Page 18: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

18

Base unit dimensions — 62DC,DD12-20 (cont)

8

62

TOP VIEW

FRONT VIEW

BOTTOM VIEW(VERTICAL SUPPLY)

OUTSIDE AIRINTAKE HOOD

EXHAUST

FILTER ACCESS

CONTROL PANELSUPPLY FAN

POWER THROUGHTHE CURB

38 1/2

57 1/2

4 3/8

38 1/4

39 3/42 1/2

15 1/215 1/26 1/2

4

104 5/8129 7/8

9 7/825 1/4

3 1/2 3 1/2

96

CONDENSATE DRAIN PAN

RETURNSUPPLY

7 3 7/830 1/4

1 TYP.

36 36

20

SIDE VIEW(HORIZONTAL SUPPLY)

36

5

520

16 1/2

32

ENERGY CONSERVATIONWHEEL ACCESS

GAS INLET

UNIT WITH OPTIONAL ENERGY CONSERVATION WHEEL

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-453

Page 19: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

19

17

TOP VIEW

FRONT VIEW

BOTTOM VIEW(VERTICAL SUPPLY)

33 3/4

62 1/4

146 9/16

34112 9/16

59 7/8

83

6 1/2

4

7

40

62 3/8

2 13/161 TYP.

10 7/8 30

FILTER ACCESS

OUTSIDE AIRINTAKE HOOD

CONTROL PANELSUPPLY FAN

CONDENSATE DRAIN PAN

POWER THROUGHTHE CURB

96

SUPPLY

SIDE VIEW(HORIZONTAL SUPPLY)

40 1/2

30 1/218 1/2

4 1/2

43 1/2

4 1/2

GASINLETS

STANDARD UNIT

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-454

Base unit dimensions — 62DA,DB22-38

Page 20: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

20

Base unit dimensions — 62DC,DD22-38

EX HAUST

FILTE R AC CE SS

S U P R YL P ET URN

TOP VIEW

FR ONT VIEW

BOTT OM VIEW(VERTICAL SUPPLY)

OUTS IDE AIRINTAK E HOOD

174 7/8

40

30 42 1/16

50

24

2 7/8

10 7/8

83

C ONDENSATEDR AIN PAN

14 3 /8112 1/2

34 1/4146 3 /4

96

33 3/4

62 1/4

2 1/4

4

6 1/2

P OW E R T H R O U G HT H E C U R B

4 15 /16

S UPP LY FAN CONTR OLPA NEL

59 7/87

1 TYP.

62 3/8

SIDE VIEW(HORIZONTAL SUPPLY)

40 1/2

30 1/218 1/2

4 1/2

43 1/2

4 1/2

GAS INLET

UNIT WITH OPTIONAL EXHAUST

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-455

Page 21: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

21

17

TOP VIEW

FRONT VIEW

BOTTOM VIEW(VERTICAL SUPPLY)

33 3/4

62 1/4

136 5/8

83

59 7/8

63 1/26 1/2

3 1/44 7/8

7

4

40

42 1/16

4 15/162 13/16

1 TYP.

10 7/8 30

50

24

15 3/8

34 3/16

FILTER ACCESS ENERGY CONSERVATIONWHEEL ACCESS

OUTSIDE AIRINTAKE HOOD

CONTROLPANEL

SUPPLY FAN

CONDENSATE DRAIN PAN

POWER THROUGHTHE CURB

EXHAUST

RETURNSUPPLY

170 3/4

96

SIDE VIEW(HORIZONTAL SUPPLY)

40 1/2

30 1/218 1/2

4 1/2

43 1/2

4 1/2

GAS INLET

UNIT WITH OPTIONAL ENERGY CONSERVATION WHEEL

NOTES:1. Carrier recommends a minimum of 24 to

36-in. of service clearance on all sides ofunit except for the control panel side,which should have at least 48-in. clear-ance. Top should be unobstructed.

2. Dimensions are in inches.

a62-456

Page 22: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

22

Accessory dimensions — 62DA,DB,DC,DD07-38

Selection procedureRefer to the RTU Builder software to select unit.

Curb End

UtilityChannel

Curb Side

Equipment Support (Screw 2 parts together)

Supply

Return24 1/2”

36 1/2”20 1/2”

50 1/8”

41 3/4”

74 3/4”

Gasket

NailCounter Flashing(Field Supplied)

Roofing Felt(Field Supplied)

Cant Strip(Field Supplied)

Roofing Material(Field Supplied)

Rigid Insulation(Field Supplied)

Gasket here

Equipment Support(Screw 2 parts together)

Curb SideGasket

NailCounter Flashing(Field Supplied)

Roofing Felt(Field Supplied)

Cant Strip(Field Supplied)

Roofing Material(Field Supplied)

Rigid Insulation(Field Supplied)54 7/8”

37”

104 3/4”

Return

Supply

Gasket here

38 1/2”

24 1/2”

62DA,DB,DC,DD07-20

62DA,DB,DC,DD22-38

a62-457

NOTES:1. Dimensions are in inches.2. Field-assembled curbs are shown. Factory-assembled

curbs are also available.3. Curbs are available in 14-in. and 24-in. heights.

a62-458

NOTES:1. Dimensions are in inches.2. Field-assembled curbs are shown. Factory-assembled

curbs are also available.3. Curbs are available in 14-in. and 24-in. heights.

Page 23: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

23

COOLING CAPACITIES

LEGEND

NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB07 AND 62DC,DD07 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

700TC 55,111 59,173 60,202 61,238 63,239 54,104 58,140 59,162 60,190 62,284SHC 32,796 29,436 28,564 27,694 25,846 36,154 32,851 32,007 31,138 29,366W 3,874 3,920 3,930 3,941 3,954 4,098 4,145 4,156 4,167 4,190

950TC 61,068 65,256 66,325 67,405 69,566 59,832 63,996 65,056 66,127 68,283SHC 37,963 33,311 32,127 30,950 28,517 42,655 38,081 36,932 35,757 33,366W 3,943 3,989 4,001 4,013 4,039 4,167 4,214 4,226 4,239 4,265

1250TC 65,414 69,699 70,787 71,873 74,026 64,034 68,218 69,303 70,381 72,559SHC 43,486 37,447 35,896 34,344 31,194 49,608 43,851 42,329 40,800 37,735W 3,993 4,044 4,057 4,070 4,098 4,217 4,268 4,282 4,296 4,325

1500TC 67,731 72,117 73,181 74,275 76,441 66,347 70,464 71,595 72,661 74,769SHC 47,562 40,692 38,853 37,013 33,313 54,994 48,461 46,676 44,882 41,175W 4,015 4,075 4,089 4,103 4,132 4,237 4,290 4,314 4,328 4,350

62DA,DB07 AND 62DC,DD07 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

700TC 52,000 55,900 56,900 57,900 59,904 50,900 54,600 55,500 56,500 58,598SHC 42,800 39,600 38,800 37,900 36,172 46,000 42,800 42,000 41,200 39,516W 4,593 4,644 4,655 4,666 4,690 4,882 4,910 4,921 4,932 4,968

950TC 57,300 61,200 62,200 63,300 65,314 56,200 59,700 60,700 61,800 63,802SHC 51,700 47,500 46,300 45,200 42,862 5,620 51,800 50,800 49,900 47,579W 4,664 4,711 4,724 4,737 4,754 4,944 4,976 4,988 5,014 5,041

1250TC 61,500 65,100 66,100 67,200 69,133 63,100 63,800 64,600 65,600 67,557SHC 61,500 56,000 54,500 53,200 50,533 63,100 62,100 60,700 59,300 56,437W 4,710 4,753 4,771 4,780 4,814 5,038 5,044 5,056 5,056 5,083

1500TC 65,900 67,400 68,400 69,400 71,364 67,400 67,600 67,500 67,900 69,548SHC 65,900 63,000 61,300 59,600 56,176 67,400 67,600 67,500 66,800 63,387W 4,780 4,786 4,799 4,813 4,841 5,106 5,104 5,102 5,096 5,124

62DC,DD07 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 51,300 60,400 — —SHC 42,100 26,700 — —W 5,115 5,217 — —

950TC 53,200 62,300 — —SHC 46,000 28,200 — —W 5,337 5,465 — —

1250TC 54,500 63,400 60,900 64,100SHC 50,300 29,500 60,900 49,700W 5,607 5,767 5,692 5,752

1500TC 55,400 64,200 — —SHC 54,000 30,900 — —W 5,864 6,050 — —

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Performance data

Page 24: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

24

Performance data (cont)COOLING CAPACITIES (cont)

LEGEND

NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD08 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

800TC 68,400 73,500 74,800 76,100 78,900 67,200 72,200 73,400 74,900 77,500SHC 40,300 36,500 35,500 34,500 32,500 44,100 40,300 39,300 38,300 36,400W 5,414 5,457 5,466 5,474 5,493 5,684 5,718 5,726 5,746 5,765

1150TC 78,300 83,800 85,200 86,700 89,500 76,800 82,200 83,600 85,000 87,900SHC 48,000 42,400 40,900 39,500 36,600 53,600 48,100 46,700 45,200 42,400W 5,496 5,535 5,545 5,556 5,575 5,766 5,708 5,815 5,827 5,848

1450TC 83,800 89,500 91,000 92,400 95,300 82,000 87,600 89,100 90,500 93,400SHC 53,800 46,800 45,000 43,200 39,500 61,000 54,100 52,400 50,600 47,000W 5,538 5,579 5,590 5,600 5,622 5,808 5,850 5,861 5,872 5,895

1800TC 88,200 94,000 95,400 96,900 99,800 86,300 91,900 93,300 94,800 97,700SHC 60,200 51,500 49,300 47,100 42,600 69,400 60,800 58,600 56,400 52,000W 5,562 5,616 5,627 5,638 5,660 5,829 5,873 5,885 5,909 5,920

62DA,DB AND DC,DD08 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

800TC 64,500 69,500 70,800 72,100 74,700 63,100 68,300 69,300 70,500 73,200SHC 51,500 47,800 46,900 45,900 44,000 55,200 51,700 50,600 49,700 47,800W 6,280 6,322 6,331 6,340 6,359 6,605 6,634 6,640 6,649 6,682

1150TC 73,400 78,700 80,000 81,400 84,100 71,800 76,800 78,100 79,400 82,200SHC 64,700 59,300 58,000 56,600 53,800 70,100 64,800 63,500 62,200 59,400W 6,356 6,396 6,406 6,415 6,436 6,679 6,706 6,710 6,719 6,756

1450TC 78,300 83,600 84,900 86,400 89,100 79,700 81,600 82,800 84,200 86,800SHC 75,100 68,600 66,900 65,200 61,600 79,700 75,700 73,900 72,400 68,900W 6,383 6,436 6,432 6,442 6,468 6,741 6,746 6,750 6,774 6,783

1800TC 84,600 87,800 89,000 90,400 93,000 86,800 87,900 86,800 88,100 90,700SHC 84,600 79,200 77,100 74,900 70,600 86,800 87,900 85,800 83,700 79,900W 6,448 6,455 6,465 6,476 6,498 6,803 6,795 6,798 6,791 6,818

62DC,DD08 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 67,900 80,000 71,400 80,600SHC 56,500 36,900 71,400 56,000W 6,667 6,749 6,692 6,754

950TC 70,300 82,300 76,200 82,900SHC 62,700 38,500 76,200 62,000W 6,820 6,918 6,887 6,920

1250TC 72,000 83,700 79,700 84,500SHC 68,600 40,100 79,700 67,800W 6,820 7,080 7,067 7,085

1500TC 73,200 84,700 82,500 85,600SHC 7,320 41,600 82,500 73,300W 7,150 7,239 7,240 7,244

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 25: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

25

COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD09 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

900TC 79,500 85,200 86,700 88,200 91,200 78,100 83,700 85,200 86,800 89,800SHC 46,700 42,300 41,200 40,000 37,700 50,900 46,600 45,400 44,400 42,100W 6,646 6,750 6,778 6,808 6,865 6,967 7,073 7,101 7,150 7,208

1300TC 91,200 97,400 99,000 100,600 103,800 89,300 95,600 97,100 98,700 102,000SHC 55,400 49,000 47,400 45,700 42,400 61,700 55,500 53,900 52,200 48,900W 6,875 6,998 7,027 7,059 7,125 7,192 7,338 7,370 7,404 7,472

1600TC 96,900 103,200 104,900 106,500 109,800 94,800 101,200 102,800 104,400 107,700SHC 61,300 53,400 51,400 49,400 45,300 63,200 61,500 59,500 57,500 53,500W 6,992 7,122 7,155 7,189 7,259 7,327 7,459 7,494 7,528 7,599

2100TC 103,200 109,600 111,300 112,900 116,100 101,000 107,300 109,000 110,600 113,900SHC 70,300 60,100 57,500 54,900 49,700 81,100 71,000 68,400 65,800 60,700W 7,123 7,259 7,294 7,330 7,383 7,458 7,573 7,628 7,647 7,739

62DA,DB AND 62DC,DD09 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

900TC 75,200 80,700 82,200 83,600 86,600 73,500 79,200 80,400 82,000 84,900SHC 59,200 55,000 54,000 52,900 50,700 63,500 59,200 58,100 57,000 54,900W 7,713 7,824 7,872 7,904 7,968 8,126 8,232 8,270 8,323 8,388

1300TC 85,600 91,600 93,100 94,600 97,800 83,800 89,400 90,900 92,500 95,600SHC 74,400 68,200 66,600 65,000 61,800 80,500 74,300 72,900 71,300 68,200W 7,958 8,085 8,121 8,155 8,225 8,377 8,478 8,504 8,572 8,642

1600TC 90,900 96,700 98,300 99,900 109,100 90,400 94,500 95,900 97,500 100,600SHC 84,900 77,500 75,500 73,600 69,700 90,400 85,300 83,400 81,600 77,700W 8,075 8,206 8,239 8,274 8,320 8,537 8,601 8,629 8,693 8,735

2100TC 98,600 102,600 104,200 105,800 108,900 101,400 103,200 102,000 103,200 106,400SHC 98,600 92,100 90,000 87,500 82,500 101,400 104,300 100,400 97,700 93,300W 8,258 8,326 8,362 8,390 8,456 8,805 8,811 8,810 8,813 8,888

62DC,DD09 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 79,900 93,500 83,607 94,200SHC 66,000 43,200 83,600 65,100W 8,222 8,515 8,299 8,531

950TC 82,600 96,000 89,000 96,700SHC 73,000 44,800 89,000 72,000W 8,450 8,748 8,590 8,737

1250TC 84,400 97,700 93,200 98,600SHC 79,900 46,800 93,200 78,700W 8,688 8,984 8,881 9,005

1500TC 85,800 98,700 96,100 99,800SHC 85,300 48,400 96,100 85,000W 8,894 9,184 9,124 9,192

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 26: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

26

Performance data (cont)COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD12 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1100TC 90,500 97,300 99,100 100,800 104,500 88,900 95,600 97,300 99,100 102,700SHC 53,500 48,300 47,000 45,600 42,900 58,800 53,600 52,300 50,900 48,200W 6,462 6,486 6,486 6,488 6,488 6,834 6,866 6,868 6,874 6,882

1500TC 101,600 108,800 110,700 112,600 116,400 99,500 106,700 108,500 110,300 114,100SHC 62,300 55,100 53,200 51,300 47,500 69,600 62,500 60,600 58,800 55,100W 6,502 6,504 6,502 6,500 6,492 6,886 6,902 6,904 6,906 6,906

1800TC 107,200 114,600 116,500 118,400 122,300 104,834 112,200 114,000 115,900 119,700SHC 68,200 59,500 57,300 55,000 50,500 77,100 68,500 66,300 64,100 59,700W 6,482 6,498 6,494 6,490 6,476 6,884 6,886 6,884 6,908 6,904

2200TC 112,500 120,200 122,100 124,000 127,800 110,000 117,400 119,300 121,100 124,900SHC 75,400 65,000 62,300 59,500 54,100 86,500 76,200 73,500 70,800 65,500W 6,484 6,460 6,452 6,472 6,454 6,888 6,888 6,884 6,882 6,874

62DA,DB AND 62DC,DD12 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1100TC 85,300 91,700 93,600 95,300 98,800 83,600 89,700 91,400 93,100 96,600SHC 69,200 64,000 62,800 61,456 58,800 74,400 69,100 67,800 66,600 64,000W 7,630 7,664 7,692 7,696 7,720 8,060 8,110 8,118 8,128 8,166

1500TC 95,000 101,800 103,600 105,400 108,900 92,800 99,300 101,000 102,700 106,300SHC 84,000 77,000 75,300 73,500 69,800 90,900 84,100 82,504 80,700 77,200W 7,704 7,720 7,726 7,732 7,748 8,148 8,172 8,180 8,188 8,202

1800TC 100,000 106,800 108,600 110,400 114,014 100,600 104,000 105,700 107,500 110,900SHC 94,400 86,300 84,200 82,000 77,700 100,600 94,800 92,600 90,900 86,600W 7,714 7,744 7,748 7,754 7,762 8,202 8,198 8,208 8,210 8,230

2200TC 106,500 111,500 113,400 115,200 118,800 109,100 109,100 110,300 111,900 115,600SHC 106,500 97,700 95,800 93,200 88,000 109,100 109,100 105,900 103,400 99,100W 7,768 7,766 7,764 7,766 7,772 8,250 8,238 8,232 8,238 8,242

62DC,DD12 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 87,200 103,400 90,700 104,000SHC 71,200 47,400 90,700 70,500W 8,028 8,120 8,064 8,102

950TC 90,000 106,300 96,200 106,900SHC 77,500 49,100 96,200 76,600W 8,192 8,276 8,238 8,256

1250TC 92,900 109,200 102,400 109,900SHC 86,700 51,700 102,400 85,700W 8,428 8,502 8,486 8,480

1500TC 94,800 110,700 106,400 111,600SHC 93,800 53,600 106,400 92,900W 8,620 8,688 8,682 8,668

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 27: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

27

COOLING CAPACITIES (cont)

LEGEND

NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD14 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1350TC 109,000 117,100 119,200 121,300 125,500 107,000 115,000 117,000 119,200 123,400SHC 64,700 58,200 56,500 54,900 51,400 71,100 64,700 63,100 61,400 58,000W 7,722 7,812 7,834 7,854 7,898 8,168 8,260 8,282 8,304 8,348

1900TC 122,900 131,400 133,500 135,700 133,200 120,300 128,800 130,900 133,100 130,700SHC 76,300 67,000 64,600 62,300 54,300 85,600 76,500 74,200 71,800 62,300W 7,880 7,972 7,996 8,022 7,986 8,326 8,420 8,446 8,472 8,438

2400TC 130,700 139,400 141,600 143,800 148,200 127,900 136,400 138,600 140,800 145,200SHC 85,600 74,000 71,100 68,100 62,000 97,700 86,300 83,300 80,400 74,400W 7,970 8,072 8,098 8,126 8,182 8,416 8,520 8,548 8,576 8,634

2900TC 136,100 144,900 147,100 149,300 153,700 133,100 141,600 143,800 146,000 150,400SHC 94,600 80,600 77,100 73,512 66,300 109,000 95,600 92,100 88,600 81,500W 8,018 8,144 8,172 8,200 8,258 8,460 8,570 8,620 8,648 8,692

62DA,DB AND 62DC,DD14 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1350TC 102,700 110,500 112,500 114,500 118,700 100,600 108,000 110,000 111,900 116,100SHC 84,000 77,500 76,000 74,400 71,100 90,000 83,830 822,300 80,700 77,500W 9,156 9,256 9,278 9,300 9,350 9,734 9,788 9,810 9,832 9,902

1900TC 115,000 123,000 125,100 127,200 125,400 113,000 120,000 122,000 124,100 122,500SHC 103,800 95,200 92,900 90,700 78,100 113,000 104,200 102,200 100,000 85,800W 9,316 9,412 9,440 9,464 9,436 9,878 9,940 9,966 9,988 9,988

2400TC 122,200 123,000 132,000 134,100 138,400 125,000 127,000 128,790 130,900 135,000SHC 120,800 95,200 107,000 104,600 98,900 125,000 121,700 118,800 116,300 111,100W 9,388 9,412 9,520 9,550 9,598 10,182 10,062 10,064 10,086 10,144

2900TC 131,200 130,100 136,800 138,800 143,200 134,300 134,500 134,400 135,800 139,400SHC 131,200 124,000 120,700 117,344 111,600 134,300 134,500 134,400 132,100 125,100W 9,532 9,564 9,592 9,620 9,672 10,182 10,176 10,172 10,194 10,228

62DC,DD14 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 105,700 124,500 111,700 125,600SHC 89,000 57,244 111,700 88,100W 9,756 9,964 9,824 9,996

950TC 108,600 127,500 117,500 128,300SHC 96,700 59,600 117,500 95,200W 9,976 10,212 10,082 10,210

1250TC 111,000 129,800 122,900 130,700SHC 105,400 61,900 122,900 103,900W 10,232 10,472 10,380 10,468

1500TC 113,200 131,300 127,100 132,500SHC 107,500 64,200 127,100 112,600W 10,464 10,722 10,666 10,718

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 28: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

28

Performance data (cont)COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD15 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1700TC 140,600 151,000 153,700 156,400 161,900 138,000 148,300 151,100 153,700 159,200SHC 83,100 75,000 72,900 70,700 66,500 91,200 83,100 81,100 79,008 74,800W 10,836 10,920 10,940 10,964 10,996 11,378 11,444 11,484 11,504 11,542

2300TC 157,100 168,100 170,900 173,700 179,500 154,000 164,900 167,700 170,500 176,200SHC 96,100 84,900 82,100 79,200 73,300 107,400 96,400 93,500 90,700 85,000W 10,974 11,050 11,070 11,090 11,130 11,514 11,594 11,614 11,634 11,676

3000TC 169,400 180,700 183,600 186,400 192,200 165,700 177,000 179,800 182,700 188,500SHC 109,600 95,000 91,300 87,500 85,200 124,600 110,300 106,600 102,900 95,500W 11,066 11,148 11,168 11,190 11,232 11,606 11,690 11,712 11,734 11,778

3600TC 176,400 187,900 190,800 193,700 199,400 172,600 183,800 186,700 189,600 183,300SHC 120,300 103,000 98,600 94,200 85,200 138,400 121,600 117,300 112,900 104,100W 11,100 11,206 5,614 11,248 11,292 11,636 11,748 11,770 11,792 11,814

62DA,DB AND 62DC,DD15 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1700TC 132,600 142,800 145,400 148,000 153,400 129,900 139,600 142,200 144,800 150,100SHC 107,300 99,300 97,300 95,300 91,200 114,900 107,200 105,300 103,300 99,200W 12,564 12,652 12,670 12,688 12,726 13,212 13,272 13,288 13,306 13,340

2300TC 147,300 157,800 160,600 163,400 168,800 144,000 154,100 156,800 159,500 165,000SHC 129,400 118,800 116,200 113,400 107,800 140,300 129,700 127,300 124,600 119,100W 12,694 12,744 12,792 12,812 12,828 13,340 13,386 13,406 13,424 13,490

3000TC 158,500 169,000 171,600 174,300 179,800 161,300 164,800 167,300 170,000 175,700SHC 153,800 140,500 136,800 133,200 126,000 161,300 154,500 150,900 147,500 141,200W 12,782 12,832 12,862 12,884 12,928 13,476 13,468 13,490 13,516 13,548

3600TC 169,000 175,500 178,200 180,600 186,200 173,100 173,300 173,900 176,600 181,400SHC 169,000 157,500 153,400 148,800 141,300 173,100 173,300 170,900 167,200 158,400W 12,870 12,888 12,908 12,940 12,984 13,576 13,570 13,548 13,560 13,612

62DC,DD15 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 134,900 158,700 141,900 159,700SHC 112,200 72,800 141,900 110,700W 13,280 13,500 13,368 13,478

950TC 138,900 162,500 150,000 163,600SHC 122,700 75,800 150,000 120,800W 13,574 13,762 13,696 13,774

1250TC 142,900 165,900 158,500 167,600SHC 136,500 79,500 158,500 135,100W 13,978 14,166 14,140 14,174

1500TC 144,500 167,100 161,800 169,700SHC 142,900 81,400 161,800 141,300W 14,174 14,362 14,354 14,380

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 29: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

29

COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD16 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1100TC 166,500 178,300 181,600 184,700 190,900 163,700 175,300 178,400 181,400 187,900SHC 98,400 88,500 86,100 83,500 78,400 107,900 98,200 98,700 93,200 88,200W 13,376 13,594 13,684 13,742 13,864 14,050 14,272 14,332 14,390 14,552

1500TC 187,500 200,000 203,200 206,500 213,000 183,800 196,300 199,500 202,700 209,200SHC 115,200 101,400 97,900 94,300 84,114 129,000 115,400 112,000 108,500 101,400W 13,814 14,062 14,128 14,194 14,326 14,488 14,742 14,808 14,876 15,014

1800TC 272,400 272,300 272,300 272,600 226,400 280,800 280,900 280,900 280,900 222,200SHC 272,400 272,300 272,300 272,600 94,400 280,800 280,900 280,900 280,900 113,200W 15,744 15,736 15,714 15,748 14,622 16,838 16,792 16,788 16,786 15,306

2200TC 209,000 222,100 225,300 228,600 235,100 204,700 217,400 220,700 223,900 230,500SHC 144,600 123,200 117,700 112,200 101,300 166,300 146,000 140,600 135,300 124,500W 14,264 14,538 14,608 14,678 14,822 14,936 15,210 15,282 15,356 15,466

62DA,DB AND 62DC,DD16 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

1100TC 157,400 169,000 172,000 175,000 181,100 154,000 165,400 168,300 171,300 177,400SHC 126,900 117,300 114,900 112,500 107,600 135,800 126,642 124,300 121,900 117,100W 15,542 15,814 15,874 15,938 16,100 16,370 16,598 16,660 16,720 16,908

1500TC 176,000 188,100 191,300 194,400 200,800 172,300 183,900 186,900 190,000 196,300SHC 156,000 143,000 139,700 136,300 129,400 169,200 156,500 153,402 150,100 143,300W 15,980 16,240 16,310 16,380 16,522 16,816 17,022 17,090 17,154 17,358

1800TC 188,000 199,900 203,200 206,100 212,400 191,300 195,600 198,300 201,400 207,500SHC 183,300 167,000 163,200 158,700 150,000 191,300 184,600 180,300 176,200 108,300W 16,250 16,516 16,532 16,620 16,772 17,264 17,350 17,420 17,492 17,598

2200TC 201,600 207,700 211,100 213,900 220,600 206,500 206,700 206,800 209,700 215,100SHC 201,600 189,300 184,900 179,200 170,400 206,500 206,700 206,400 201,800 191,000W 16,568 16,672 16,724 16,814 16,900 17,642 17,630 17,632 17,630 17,794

62DC,DD16 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 159,700 186,600 168,400 187,900SHC 133,800 85,900 168,400 132,000W 16,490 17,062 16,676 17,092

950TC 163,200 190,000 176,100 191,400SHC 143,800 88,600 176,100 142,200W 16,836 17,414 17,106 17,398

1250TC 165,900 192,400 182,000 194,100SHC 153,300 91,200 182,000 151,700W 17,166 17,742 17,510 17,732

1500TC 168,100 194,100 186,800 196,200SHC 162,400 93,700 186,800 160,900W 17,486 18,056 18,945 18,050

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 30: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

30

Performance data (cont)COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD20 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

2400TC 215,300 215,300 217,900 221,000 213,800 210,300 219,900 223,500 226,400 210,100SHC 215,300 215,300 210,700 205,600 87,300 210,300 194,300 189,500 183,800 99,200W 19,142 19,126 19,178 19,174 15,438 18,026 18,208 18,206 18,284 16,186

3100TC 186,100 198,700 202,000 205,200 231,300 190,600 203,600 206,900 210,300 227,000SHC 184,800 171,300 167,900 164,100 94,700 190,600 156,400 152,800 149,000 110,400W 18,576 18,774 18,772 18,904 15,750 8,810 17,874 17,938 18,004 16,498

3700TC 201,400 207,200 210,300 213,500 241,700 199,700 212,400 215,800 219,100 236,800SHC 201,400 192,000 187,800 184,200 100,200 199,700 174,300 170,300 165,800 119,300W 18,846 18,956 19,024 19,080 15,930 17,810 18,056 18,118 18,122 16,676

4400TC 215,300 215,300 217,800 220,800 250,300 210,300 219,800 223,500 226,400 245,000SHC 215,300 215,300 210,400 205,400 106,400 210,300 194,000 189,500 183,772 131,300W 19,142 19,126 19,124 19,184 16,078 18,026 18,162 18,206 18,286 16,824

62DA,DB AND 62DC,DD20 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

2400TC 186,300 100,000 203,300 206,800 201,900 183,000 196,200 199,800 203,200 197,400SHC 111,100 99,500 96,600 93,500 122,600 122,700 111,200 108,400 105,400 134,100W 14,926 15,200 15,260 15,318 17,824 15,658 15,898 16,000 16,062 18,728

3100TC 203,300 217,100 220,600 224,200 37,000 199,200 212,900 216,400 219,900 211,700SHC 125,600 110,442 106,600 102,700 141,300 141,000 125,900 122,100 118,300 156,500W 15,274 15,512 15,572 15,632 181,900 16,006 16,252 16,314 16,376 19,032

3700TC 213,300 227,400 230,900 234,500 226,000 208,800 222,700 226,200 229,700 220,300SHC 137,000 119,000 114,400 109,700 156,800 155,600 137,700 133,200 128,600 175,300W 15,456 15,696 15,754 15,814 18,242 16,188 16,434 16,496 16,556 19,136

4400TC 211,900 236,100 239,600 243,100 233,300 217,100 230,900 234,400 237,900 226,900SHC 149,700 128,300 122,800 117,400 174,500 171,500 150,900 145,500 140,100 195,100W 15,612 15,848 15,906 15,964 18,418 16,344 16,584 16,602 16,662 19,298

62DC,DD20 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 173,900 204,500 180,800 205,900SHC 141,800 93,800 180,800 140,100W 18,058 18,668 18,196 18,696

950TC 178,600 209,200 189,900 210,800SHC 152,800 96,800 189,900 151,100W 18,426 18,988 18,650 19,008

1250TC 182,200 212,800 197,400 214,300SHC 163,400 99,600 197,400 161,000W 18,770 19,374 19,072 19,404

1500TC 185,000 215,300 203,600 217,100SHC 173,600 102,300 203,600 171,600W 19,098 19,694 19,466 19,698

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 31: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

31

COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD22 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

2100TC 178,100 191,300 194,700 198,200 205,200 175,000 188,000 191,300 194,800 201,900SHC 105,100 94,900 92,300 89,700 84,400 115,000 105,000 102,400 99,900 94,700W 14,536 14,772 14,822 14,874 14,976 15,258 15,458 15,510 15,562 15,714

2900TC 201,100 215,300 218,900 222,600 230,000 197,200 211,200 214,800 218,400 225,700SHC 122,600 108,600 104,900 101,300 92,900 136,800 122,900 119,300 115,700 108,500W 14,938 15,144 15,196 15,244 15,348 15,664 15,876 15,930 15,982 16,088

3600TC 214,600 229,200 232,900 236,600 244,100 210,100 224,400 228,100 231,800 239,200SHC 136,400 118,900 114,500 110,000 100,800 154,300 137,100 132,700 128,200 119,200W 15,146 15,352 15,404 15,454 15,554 15,872 16,084 16,136 16,188 16,292

4400TC 225,500 240,300 244,000 247,700 255,200 220,300 234,800 238,500 242,200 249,700SHC 151,100 129,900 124,400 119,000 108,000 173,300 152,400 147,000 141,600 130,900W 15,310 15,514 15,564 15,614 15,710 16,036 16,244 16,242 16,294 16,446

62DA,DB AND 62DC,DD22 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

2100TC 168,400 181,200 184,500 187,800 194,500 164,900 177,300 180,500 183,900 190,500SHC 134,600 125,000 122,500 120,000 114,900 144,400 134,600 132,200 129,800 124,700W 16,854 17,116 17,174 17,228 17,338 17,736 17,958 18,000 18,126 18,238

2900TC 188,700 202,100 205,500 209,000 216,000 184,700 197,300 200,500 203,900 210,700SHC 164,664 151,100 147,600 144,200 137,100 178,400 165,100 161,600 146,200 151,200W 17,266 17,486 17,540 17,602 17,706 18,160 18,308 18,364 18,482 18,600

3600TC 200,800 213,900 217,400 220,900 228,100 201,300 208,500 211,900 215,200 222,300SHC 189,200 172,800 168,500 164,100 155,500 201,300 189,900 185,800 181,900 173,400W 17,487 17,690 17,684 17,798 17,838 18,468 18,596 18,568 18,692 18,720

4400TC 212,900 223,200 227,100 230,600 237,100 218,400 218,500 221,300 224,300 231,300SHC 212,900 195,800 191,800 186,500 175,800 218,400 218,500 213,000 207,300 198,300W 17,686 17,798 17,830 17,882 18,004 18,770 18,684 18,740 18,792 18,870

62DC,DD22 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 176,100 207,900 182,700 209,400SHC 143,100 95,200 182,700 141,700W 17,828 18,358 17,940 18,382

950TC 181,200 213,100 192,300 214,600SHC 154,200 98,400 192,300 152,500W 18,184 18,712 18,372 18,736

1250TC 185,000 216,800 200,100 218,400SHC 165,000 101,400 200,100 163,000W 18,470 19,040 18,772 19,000

1500TC 187,800 219,600 206,700 221,100SHC 175,100 104,200 206,700 172,400W 18,788 19,306 19,148 19,338

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 32: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

32

Performance data (cont)COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD24 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

2400TC 202,100 217,000 220,800 224,700 232,500 198,500 213,100 216,900 220,700 228,600SHC 119,200 107,704 104,700 101,700 95,500 130,600 119,142 116,200 113,200 107,300W 16,584 16,916 16,988 17,062 17,210 17,498 17,770 17,844 17,918 18,140

3600TC 233,100 248,900 252,900 256,900 265,000 228,300 243,900 247,800 251,800 259,900SHC 144,600 126,900 122,400 117,900 108,600 162,334 144,900 140,400 136,000 126,900W 17,264 17,584 17,668 17,754 17,930 18,108 18,500 18,586 18,674 18,852

4800TC 251,000 266,500 270,600 274,500 282,500 245,000 260,600 264,600 268,600 276,700SHC 166,900 143,400 137,400 131,300 119,200 191,000 167,900 162,000 156,100 144,200W 17,572 17,990 18,080 18,102 18,288 18,550 18,896 18,988 19,256 19,272

6000TC 261,300 277,200 281,300 285,300 293,200 255,000 270,100 275,000 278,900 286,800SHC 187,800 157,800 151,500 144,200 129,100 216,300 190,100 182,800 175,600 160,800W 17,888 18,250 18,260 18,356 18,562 18,920 19,100 19,154 19,256 19,500

62DA,DB AND 62DC,DD24 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

2400TC 190,900 205,200 208,800 215,500 220,000 186,800 200,600 204,200 207,900 215,300SHC 153,000 141,900 139,000 136,200 130,300 164,200 153,000 150,100 147,400 141,500W 19,520 19,882 19,960 20,036 20,192 20,652 20,940 21,014 21,180 21,338

3600TC 218,300 233,000 236,700 240,600 248,300 214,000 227,500 231,100 234,600 242,100SHC 197,100 180,300 176,000 171,600 162,700 214,200 197,900 193,600 189,200 180,400W 20,198 20,524 20,608 20,696 20,878 21,252 21,550 21,640 21,832 22,010

4800TC 235,800 248,400 252,100 255,800 263,100 241,800 243,100 246,300 249,800 257,000SHC 235,800 215,800 210,700 204,900 193,300 241,800 239,300 233,800 228,000 217,900W 20,618 20,918 20,918 21,012 21,420 22,052 22,064 22,166 22,142 22,284

6000TC 256,200 259,200 262,300 266,200 272,600 261,500 261,600 261,600 261,800 266,900SHC 256,200 249,900 242,600 236,400 223,300 261,500 261,600 261,600 261,800 252,600W 21,132 21,188 21,192 21,258 21,456 22,600 22,574 22,564 22,558 22,566

62DC,DD24 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 206,000 241,100 219,700 242,800SHC 177,600 111,700 219,700 175,200W 21,090 21,888 21,390 21,930

950TC 210,700 245,500 229,800 247,400SHC 192,500 115,800 229,800 189,800W 21,582 22,392 22,017 22,438

1250TC 214,200 248,600 237,700 250,700SHC 206,300 119,500 237,700 203,600W 21,986 22,866 22,596 22,838

1500TC 217,800 250,700 244,000 253,200SHC 217,800 123,200 244,000 217,900W 22,524 23,314 23,148 23,288

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 33: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

33

COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD30 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

3400TC 277,800 298,000 303,100 308,200 318,800 272,600 292,400 297,400 302,800 313,300SHC 164,500 148,000 143,700 139,400 130,600 180,600 164,300 160,000 155,900 147,300W 22,754 23,200 23,244 23,332 23,514 23,870 24,200 24,292 24,460 24,648

4600TC 309,100 330,100 335,400 340,900 351,600 302,800 323,500 328,700 334,100 344,900SHC 189,900 167,300 161,400 155,600 143,800 212,342 190,100 184,300 178,700 167,000W 23,372 23,740 23,836 23,942 24,132 24,486 24,872 24,958 25,060 25,262

5800TC 329,600 351,000 356,500 361,900 372,800 322,400 343,500 348,800 354,300 365,100SHC 212,800 184,400 177,100 169,800 155,000 241,700 213,800 206,600 199,400 184,900W 23,748 24,138 24,238 24,340 24,548 24,856 25,256 25,358 25,464 25,676

7000TC 343,700 365,300 370,700 376,200 387,100 335,700 357,200 362,500 367,800 378,700SHC 234,300 200,300 191,700 183,000 165,500 268,900 236,400 227,800 219,200 202,000W 23,938 24,418 24,522 24,626 24,838 25,050 25,438 25,546 25,746 25,964

62DA,DB AND 62DC,DD30 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

3400TC 261,700 281,100 286,000 291,000 301,100 256,600 274,700 279,500 284,400 294,600SHC 212,900 196,600 192,500 188,400 180,000 228,200 212,300 208,300 204,300 196,000W 26,332 26,764 26,856 26,950 27,142 27,700 28,030 28,120 28,214 28,520

4600TC 289,400 309,100 314,200 319,400 329,900 281,900 301,700 306,500 311,600 321,700SHC 256,500 235,000 229,500 224,000 212,600 277,500 257,300 251,800 246,300 235,100W 26,944 27,330 27,432 27,534 27,744 28,492 28,588 28,688 28,782 29,114

5800TC 307,600 327,200 332,600 337,900 347,800 316,800 319,400 324,116 328,800 339,400SHC 297,400 271,700 264,800 257,900 243,600 316,800 299,500 292,900 286,600 272,900W 27,230 27,712 27,762 27,806 28,062 29,028 29,094 29,104 29,288 29,376

7000TC 327,900 340,200 345,300 350,400 360,000 340,300 335,200 341,300 341,300 351,300SHC 327,900 306,200 299,400 291,000 274,000 340,300 335,200 33,600 324,700 310,000W 27,738 27,902 27,974 28,100 28,338 29,560 29,440 29,434 29,484 29,706

62DC,DD30 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 265,100 310,300 277,900 311,900SHC 219,700 143,400 277,900 215,600W 27,698 28,552 28,100 28,614

950TC 272,800 317,300 293,600 319,600SHC 240,400 148,100 293,600 236,300W 28,390 29,300 28,922 29,298

1250TC 277,600 321,600 304,100 324,400SHC 257,400 152,600 304,100 253,100W 28,942 29,812 29,604 29,858

1500TC 282,000 325,100 313,900 328,400SHC 275,900 157,600 313,900 272,300W 29,570 30,430 30,188 30,474

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 34: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

34

Performance data (cont)COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD34 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

4000TC 336,800 361,300 367,700 374,200 387,300 330,700 354,900 361,200 367,500 370,800SHC 198,800 179,300 174,400 169,400 159,200 217,600 198,500 193,600 188,600 178,700W 29,918 30,446 30,600 30,700 31,034 31,310 31,844 31,986 32,132 32,580

5300TC 373,600 399,500 406,200 413,000 426,600 366,200 391,900 398,400 405,100 418,600SHC 226,900 201,000 194,300 187,600 174,100 252,700 227,200 220,600 214,000 200,700W 30,760 31,374 31,538 31,708 32,058 32,140 32,904 33,070 33,240 33,596

6700TC 399,900 426,600 433,300 440,100 453,800 391,500 417,736 424,400 431,200 444,800SHC 254,100 221,300 213,000 204,500 187,400 287,400 255,100 246,900 238,600 221,700W 31,414 32,094 32,274 32,458 32,836 32,788 33,608 33,790 33,796 34,360

8000TC 416,900 443,800 450,600 457,300 471,000 407,800 434,000 441,050 447,600 461,200SHC 277,600 238,800 228,800 218,800 198,700 318,100 279,700 270,000 260,100 240,400W 31,864 32,582 32,770 32,960 33,358 33,368 34,082 34,116 34,468 34,872

62DA,DB AND 62DC,DD34 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

4000TC 318,000 341,500 347,600 353,900 366,500 311,200 334,000 340,000 346,100 358,500SHC 254,900 236,300 231,500 226,800 217,000 273,500 254,800 250,100 245,400 235,700W 34,678 35,248 35,398 35,720 36,048 36,562 37,164 37,320 37,476 38,008

5300TC 350,600 375,000 381,400 387,800 400,900 343,600 366,100 372,600 378,300 391,000SHC 303,700 278,600 272,200 265,800 252,900 328,700 304,000 297,800 291,400 278,500W 35,526 36,300 36,502 36,678 37,046 37,428 38,278 38,298 38,630 39,006

6700TC 375,100 398,700 405,000 411,400 424,300 373,200 389,800 396,400 401,000 413,600SHC 352,400 321,900 313,800 305,600 289,200 373,200 354,000 347,400 338,800 322,600W 36,364 37,026 37,208 37,394 37,784 38,514 39,010 39,076 39,358 39,754

8000TC 405,500 415,800 421,300 427,600 439,600 403,200 405,900 410,900 416,900 430,000SHC 360,600 361,500 351,600 342,000 322,500 403,200 398,800 389,200 380,200 363,700W 35,737 37,370 37,470 37,525 38,106 39,468 39,528 39,698 39,890 40,046

62DC,DD34 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 320,600 376,800 331,900 379,600SHC 259,100 172,600 331,900 256,000W 35,964 37,534 36,224 37,616

950TC 329,800 385,900 350,200 388,800SHC 279,400 178,000 350,200 276,600W 36,876 38,348 37,444 38,272

1250TC 334,200 390,200 360,300 393,300SHC 292,000 181,400 360,300 289,500W 37,344 38,832 38,002 38,744

1500TC 341,000 396,100 374,800 400,000SHC 314,700 187,700 374,800 312,300W 38,188 39,684 39,070 39,612

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 35: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

35

COOLING CAPACITIES (cont)

LEGENDNOTES:

1. Direct interpolation is permissible. Do not extrapolate.2. Cooling capacities are gross and do not include deduction for

indoor fan motor heat.

62DA,DB AND 62DC,DD38 WITHOUT ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

4800TC 392,300 420,200 427,400 434,700 449,500 384,900 412,500 419,600 426,700 441,600SHC 232,300 208,700 202,600 196,500 184,200 255,000 231,800 225,800 219,800 207,600W 34,926 35,556 35,722 35,890 36,236 36,660 37,302 37,468 37,640 38,148

6200TC 428,700 457,700 465,100 472,600 487,700 420,100 448,700 456,000 463,300 478,300SHC 261,500 230,900 223,000 215,100 199,200 291,700 261,600 253,800 246,000 230,300W 35,806 36,496 36,678 36,862 37,238 37,532 38,388 38,572 38,760 39,146

7600TC 453,600 482,900 490,400 497,900 513,000 444,000 472,800 480,100 487,500 502,400SHC 288,200 250,700 241,200 231,500 211,900 326,000 289,000 279,600 270,000 250,800W 36,438 37,166 37,354 37,546 37,942 38,160 39,048 39,242 39,438 39,840

9000TC 459,300 488,700 496,100 503,600 530,600 449,400 478,200 485,500 492,900 519,200SHC 295,500 256,100 246,000 235,900 223,800 335,500 296,600 286,600 276,600 270,600W 36,584 37,320 37,512 37,706 38,452 38,304 39,200 39,394 39,594 40,342

62DA,DB AND 62DC,DD38 WITHOUT ECW (cont)

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)100 105

Entering Air — Ewb (F)70 74 75 76 78 70 74 75 76 78

4800TC 369,500 396,300 403,200 410,200 424,260 361,600 387,800 394,500 400,900 414,700SHC 299,800 277,200 271,500 265,700 253,700 322,200 299,700 294,100 288,100 276,300W 40,792 41,460 41,632 41,994 42,362 43,110 43,738 43,916 44,146 44,726

6200TC 401,900 428,800 435,900 443,000 457,400 394,400 418,800 425,800 432,200 445,800SHC 351,100 321,800 314,300 306,800 291,400 380,500 351,700 344,200 336,800 321,400W 41,844 42,554 42,746 42,938 43,336 44,292 44,912 45,100 45,288 45,678

7600TC 425,600 451,200 458,000 464,900 479,600 423,000 441,400 448,900 455,200 466,900SHC 399,500 364,700 355,400 346,000 327,500 423,000 400,900 393,800 384,400 365,200W 42,510 43,210 43,404 43,598 43,788 45,074 45,602 45,642 45,948 46,356

9000TC 443,800 468,200 476,100 481,600 495,600 453,600 458,300 464,400 470,000 484,400SHC 446,200 404,900 396,300 384,900 363,100 453,600 448,800 438,800 427,700 409,300W 42,440 43,724 43,742 43,860 44,246 46,022 46,128 46,294 46,488 46,600

62DC,DD38 WITH ECW

Entering Air Quantity (Cfm)

Temp (F) Air Entering (Edb)85 90

Entering Air — Ewb (F)60 70 60 70

700TC 371,000 435,300 381,600 437,800SHC 298,500 198,700 381,600 294,100W 42,020 43,874 42,266 43,950

950TC 378,700 442,800 396,800 445,200SHC 314,500 204,600 396,800 309,300W 42,604 44,486 43,222 44,564

1250TC 386,100 448,700 409,100 452,100SHC 331,100 207,400 409,100 326,000W 43,312 45,058 43,946 44,944

1500TC 390,500 453,500 421,200 457,400SHC 344,400 211,500 421,200 340,900W 43,866 45,598 44,670 45,480

ECW — Energy Conservation WheelEdb — Entering Dry BulbEwb — Entering Wet BulbW — Compressor Motor Power Input (W)SHC — Sensible Heat Capacity (Btuh)TC — Total Capacity (Btuh) Gross

Page 36: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

36

Performance data (cont)

00.

05.

00.1

05.1

00.2

05.2

00.3

05.3

00.4

0483634323038262422202816141210186420

Syste

mC

urv

e(s

)

1/6HP

1/41/3

1/2

3/4

1

1-1

/2

2

3

5

600 RPM700

800900

1000

1100

1200

31 00

1400

1500

1600

1700

1800

1900

2000

VOLUME (CFM IN 100s)

ST

AT

IC P

RE

SS

UR

E (

in. w

g)

EXHAUST BLOWER PERFORMANCE

FORWARD CURVED FAN (9 x 7 in.)a62-407

Page 37: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

37

00.

05.

00.1

05.1

00.2

05.2

00.3

05.3

00.4

27864606652584440463238242026121840

Syste

mC

urv

e(s

)

1/3HP

1/2

3/4

1

1-1

/2

2

3

5

7-1

/2

10

MPR005

600

700

08 0

900

1000

1100

1200

1300

1400

1500

1600

VOLUME (CFM IN 100s)

ST

AT

IC P

RE

SS

UR

E (

in. w

g)

EXHAUST BLOWER PERFORMANCE (cont)

FORWARD CURVED FAN (12 x 9 in.)

00.

05.

00.1

05.1

00.2

05.2

00.3

05.3

00.4

27864606652584440463238242026121840

Syste

mC

urv

e(s

)

1/3HP

1/2

3/4

1

1-1

/2

2

3

5

7-1

/2

10

MPR 005

600

700

08 0

900

1 000

1100

1200

1300

1 400

1 500

1 600

VOLUME (CFM IN 100s)

ST

AT

IC P

RE

SS

UR

E (

IN. W

G)

0

0

FORWARD CURVED FAN (12 x 12 in.)

a62-408

a62-409

Page 38: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

38

Performance data (cont)

00.

05.

00.1

05.1

00.2

05.2

00.3

05.3

00.4

02816141210186420

Syste

mC

urv

e(s

)

1HP

1-1/22

3

5

7-1

/2

10

15

20

300 RPM

400

500

600

07 0

800

900

1000

1100

VOLUME (CFM IN 100s)

ST

AT

IC P

RE

SS

UR

E (

IN. W

G)

EXHAUST BLOWER PERFORMANCE (cont)

FORWARD CURVED FAN (15 x 15 in.)

00.

05.

00.1

05.1

00.2

05.2

00.3

05.3

00.4

11019876543210

Syste

mC

urv

e(s

)

1/3HP

1/2

3/4

1

1-1

/2

2

3

5

7-1

/2

10

400 RPM

500

600

700

800

900

1000

1100

1200

1300

VOLUME (CFM IN 1000s)

ST

AT

IC P

RE

SS

UR

E (

in. w

g)

FORWARD CURVED FAN (18 x 18 in.)

a62-410

a62-411VOLUME (CFM IN 1000s)

Page 39: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

39

ST

AT

IC P

RE

SS

UR

E (

in. w

g)

BR

AK

E H

OR

SE

PO

WE

R

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

0.4

0.8

1.2

1.6

2.0

2.4

2.8

3.2

5 10 15 20 25 30 35 40

2000RPM

1800RPM

1600RPM

1400RPM

1200RPM

1000RPM

VOLUME (CFM IN 100s)

2000RPM

1800RPM

1600RPM

1400RPM

1200RPM1000

RPM

BHP@RPM

BHP@RPM

SP@RPM

SP@RPM

SUPPLY BLOWER PERFORMANCE

BACKWARD INCLINED PLENUM FAN (15-in.)

ST

AT

IC P

RE

SS

UR

E (

in. w

g)

BR

AK

E H

OR

SE

PO

WE

R

1

2

3

4

6

5

1 2 4 5 6 7 8 93

1

2

3

4

5

6

2000 RPM SP@RPM

1800 RPM

1600 RPM

1400 RPM

1200 RPM

1000 RPM1000 RPM

1200 RPM

1400 RPM

1600 RPM

1800 RPM

2000 RPM

VOLUME (CFM IN 100s)

BHP@RPM

BHP@RPM

SP@RPM

BACKWARD INCLINED PLENUM FAN (18.5-in.)

a62-412

a62-413VOLUME (CFM IN 1000s)

Page 40: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

40

VOLUME (CFM IN 100S)

BR

AK

E H

OR

SE

PO

WE

R

ST

AT

IC P

RE

SS

UR

E (

IN. W

G)

168

7

6

1800 RPM

SP@ RPM

1600 RPM

SYSTEMCURVE

600RPM

800RPM

1000RPM

1200RPM

1400RPM

1600RPM

1800RPM

BHP@RPM

BHP@RPM

SP@RPM

1400 RPM

1200 RPM

800RPM

600RPM

1000 RPM

5

3

2

1

2 4 6 8 10 12 14 16

14

12

10

8

6

4

2

SUPPLY BLOWER PERFORMANCE (cont)

BACKWARD INCLINED PLENUM FAN (24.5-in.)

VOLUME (CFM IN 100s)

ST

AT

IC P

RE

SS

UR

E (

IN. W

G)

BR

AK

E H

OR

SE

PO

WE

R

1800 RPM

1600 RPM

1400 RPM

1200 RPM

SYSTEMCURVE

1000 RPM

800RPM

600RPM

600RPM

800RPM

1000 RPM

1200 RPM

1600 RPM

1800 RPM

1400RPM

BHP@RPM

SP@ RPM

8

7

6

5

4

3

2

1

4 8 12 16 20 24

4

8

12

16

20

24

28

32

SP@RPM

BHP@RPM

BACKWARD INCLINED PLENUM FAN (27-in.)

a62-414

a62-415

VOLUME (CFM IN 1000s)

VOLUME (CFM IN 1000s)

Performance data (cont)

Page 41: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

41

COMPONENT PRESSURE DROPS (in. wg)UNITS 62DA,DB,DC,DD07-09

COMPONENT PRESSURE DROPS (in. wg)UNITS 62DA,DB,DC,DD12-20

COMPONENTSUPPLY AIR CFM

500 900 1300 1700 2100 2500 2900 3300 3500Cabinet Loss .03 .04 .06 .09 .12 .16 .20 .25 .272-in. Cleanable Filters .01 .01 .01 .02 .03 .03 .04 .05 .052-in. Pleated MERV 8 Filters .03 .04 .05 .08 .10 .11 .11 .12 .134-in. Pleated MERV 8 Filters .03 .04 .05 .06 .08 .08 .09 .09 .104-in. Pleated MERV 11 Filters .04 .06 .07 .10 .12 .11 .14 .15 .164-in. Pleated MERV 14 Filters .07 .10 .15 .18 .22 .23 .24 .26 .27Evaporator Coil .06 .10 .14 .18 .22 .26 .30 .35 —Hot Gas Reheat Coil .01 .01 .02 .02 .03 .04 .05 .06 .07Liquid Subcooling Coil .01 .01 .02 .02 .03 .04 .05 .06 .07Electric Heat .01 .01 .01 .02 .03 .04 .05 .07 .07Gas Heat 75,000 Btuh Input .01 .02 .03 .05 .06 .07 .09 .10 .12Gas Heat 100,000 Btuh Input .01 .02 .04 .05 .07 .08 .10 .12 .13Gas Heat 150,000 Btuh Input .01 .03 .05 .06 .08 .09 .11 .13 .15Gas Heat 200,000 Btuh Input .01 .03 .06 .07 .09 .10 .12 .14 .16Hot Water Coil .01 .01 .01 .02 .02 .03 .05 .06 .06Steam Coil .01 .01 .01 .01 .01 .02 .02 .03 .03Energy Wheel .26 .47 .66 .88 1.09 1.29 1.50 1.70 —

COMPONENTSUPPLY AIR CFM

1300 1950 2600 3250 3900 4550 5200 5850 6500Cabinet Loss .06 .11 .16 .26 .34 .50 .67 .85 1.042-in. Cleanable Filters .01 .02 .03 .05 .06 .07 .08 .09 .102-in. Pleated MERV 8 Filters .05 .07 .10 .12 .15 .18 .22 .26 .304-in. Pleated MERV 8 Filters .05 .06 .08 .09 .11 .14 .17 .20 .244-in. Pleated MERV 11 Filters .07 .10 .12 .15 .17 .21 .26 .30 .354-in. Pleated MERV 14 Filters .15 .18 .22 .26 .30 .37 .45 .53 .60Evaporator Coil .10 .16 .18 .27 .32 .36 — — —Hot Gas Reheat Coil .04 .05 .06 .07 .08 .10 .11 .13 .15Liquid Subcooling Coil .04 .05 .06 .07 .08 .10 .11 .13 .15Electric Heat .01 .02 .04 .06 .08 .12 .15 .19 .24Gas Heat 150,000 Btuh Input .01 .03 .04 .07 .11 .15 .20 .25 .31Gas Heat 200,000 Btuh Input .01 .03 .05 .08 .12 .17 .22 .27 .34Gas Heat 250,000 Btuh Input .01 .03 .06 .09 .13 .18 .24 .30 .37Gas Heat 300,000 Btuh Input .02 .04 .07 .10 .15 .20 .26 .33 .40Hot Water Coil .01 .02 .03 .05 .07 .10 .13 .16 .20Steam Coil .01 .01 .02 .03 .04 .05 .06 .08 .10Standard Energy Wheel .66 .99 1.33 1.61 — — — — —Optional Energy Wheel .37 .56 .74 .93 1.11 1.30 1.48 — —

Page 42: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

42

Performance data (cont)COMPONENT PRESSURE DROPS (in. wg)

UNITS 62DA,DB,DC,DD22-38

COMPONENTSUPPLY AIR CFM

2800 3400 4000 4400 5000 7000 8500 10000 12000Cabinet Loss .07 .16 .25 .34 .43 .48 .58 .71 .842-in. Cleanable Filters .01 .01 .02 .02 .04 .06 .08 .10 .122-in. Pleated MERV 8 Filters .04 .05 .07 .09 .10 .17 .25 .32 .384-in. Pleated MERV 8 Filters .02 .03 .05 .06 .08 .15 .21 .27 .324-in. Pleated MERV 11 Filters .05 .06 .08 .10 .12 .20 .29 .36 .444-in. Pleated MERV 14 Filters .08 .10 .12 .14 .18 .30 .40 .50 .60Evaporator Coil .18 .20 .22 .24 .28 .34 .40 .55 —Hot Gas Reheat Coil .04 .04 .05 .06 .07 .08 .10 .13 .25Liquid Subcooling Coil .04 .04 .05 .06 .07 .08 .10 .13 .25Electric Heat .10 .11 .12 .13 .14 .16 .18 .20 .22Gas Heat 300,000 Btuh input .07 .10 .13 .17 .23 .40 .52 — —Gas Heat 400,000 Btuh input — .15 .21 .28 .36 .48 .57 .68 —Gas Heat 500,000 Btuh input — — .19 .25 .32 .40 .48 .54 .71Gas Heat 600,000 Btuh input — — — — .30 .38 .45 .52 .67Hot Water Coil .06 .08 .10 .12 .14 .16 .20 .26 .50Steam Coil .04 .04 .05 .06 .07 .08 .10 .13 .25Standard Energy Wheel 1.04 1.27 1.49 1.64 — — — — —Optional Energy Wheel .80 .97 1.14 1.25 1.42 1.99 — — —

Page 43: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

43

ENERGY CONSERVATION WHEEL PERFORMANCE

STANDARD WHEEL — SIZES 07-20

LEGEND

COOLING MODE HEATING MODE Return Air = 75 db / 63 wb Return Air = 70 db / 58 wb

db 95 90 -10 0 10 20 30 wb 63 67 71 75 78 80 63 67 71 75 78 80 -11 -1 9 19 29

900 CFM Total MBH -0.1 10.3 21.9 34.5 44.9 52.2 -0.1 10.4 21.9 34.6 45.0 52.3 95.3 85.6 75.3 63.9 50.8 Sens. MBH 16.9 16.9 16.9 16.9 16.9 16.9 12.7 12.7 12.7 12.7 12.7 12.7 67.8 59.3 50.8 42.4 33.9 Lvg. DB 77.6 77.6 77.6 77.6 77.6 77.6 76.9 76.9 76.9 76.9 76.9 76.9 59.8 61.0 62.3 63.6 64.9 Lvg. WB 63.0 63.6 64.2 64.9 65.5 65.9 63.0 63.6 64.3 65.0 65.5 65.9 52.1 52.7 53.4 54.1 55.0

1200 CFM Total MBH 0.0 13.2 27.8 43.9 57.0 66.2 0.0 13.3 27.9 43.9 57.0 66.3 121.1 108.9 95.8 81.3 64.6 Sens. MBH 21.6 21.6 21.6 21.6 21.6 21.6 16.2 16.2 16.2 16.2 16.2 16.2 86.4 75.6 64.8 54.0 43.2 Lvg. DB 78.3 78.3 78.3 78.3 78.3 78.3 77.5 77.5 77.5 77.5 77.5 77.5 56.7 58.4 60.0 61.7 63.3 Lvg. WB 63.0 63.7 64.6 65.6 66.2 66.7 63.0 63.8 64.6 65.5 66.2 66.8 50.1 51.0 51.9 52.9 54.0

1500 CFM Total MBH 0.2 16.9 35.2 55.3 67.8 83.4 0.1 16.9 35.2 55.3 67.8 83.5 144.4 129.8 114.2 96.9 77.1 Sens. MBH 27.3 27.3 27.3 27.3 27.3 27.3 20.5 20.5 20.5 20.5 20.5 20.5 103.3 90.3 77.4 64.5 51.6 Lvg. DB 78.1 78.1 78.1 78.1 78.1 78.1 77.3 77.3 77.3 77.3 77.3 77.3 53.8 55.8 57.8 59.9 61.9 Lvg. WB 62.9 63.7 64.5 65.4 66.0 66.6 63.0 63.7 64.5 65.4 66.0 66.6 48.2 49.3 50.4 51.6 53.0

1800 CFM Total MBH 0.4 18.3 38.1 59.8 77.5 89.9 0.3 18.3 38.0 59.7 77.4 89.9 165.3 148.6 130.7 110.9 88.2 Sens. MBH 29.6 29.6 29.6 29.6 29.6 29.6 22.2 22.2 22.2 22.2 22.2 22.2 118.5 103.7 88.9 74.0 59.2 Lvg. DB 79.8 79.8 79.8 79.8 79.8 79.8 78.6 78.6 78.6 78.6 78.6 78.6 51.0 53.3 55.7 58.1 60.5 Lvg. WB 62.9 64.0 65.2 66.5 67.5 68.2 63.0 64.1 65.3 66.5 67.5 68.2 46.3 47.6 49.0 50.4 52.1

2100 CFM Total MBH 0.6 20.6 42.4 66.5 86.0 99.9 0.5 20.4 42.3 66.3 85.9 99.8 184.0 165.4 145.4 124.4 98.2 Sens. MBH 33.0 33.0 33.0 33.0 33.0 33.0 24.5 24.5 24.5 24.5 24.5 24.5 132.2 115.7 99.2 82.6 66.1 Lvg. DB 80.4 80.4 80.4 80.4 80.4 80.4 79.1 79.1 79.1 79.1 79.1 79.1 48.3 51.0 53.7 56.4 59.2 Lvg. WB 62.9 64.2 65.5 66.9 68.0 68.8 63.0 64.2 65.5 67.0 68.1 68.9 44.5 46.0 47.6 49.3 51.2

2400 CFM Total MBH 0.9 22.6 46.3 72.4 93.7 108.7 0.7 22.4 46.1 72.2 93.5 108.6 200.7 180.4 158.6 134.6 107.1 Sens. MBH 36.1 36.1 36.1 36.1 36.1 36.1 27.1 27.1 27.1 27.1 27.1 27.1 144.6 126.5 108.5 90.3 72.3 Lvg. DB 81.1 81.1 81.1 81.1 81.1 81.1 79.5 79.5 79.5 79.5 79.5 79.5 45.8 48.8 51.8 54.9 57.9 Lvg. DB 62.8 64.3 65.8 67.3 68.6 69.4 62.9 64.3 65.8 67.4 68.6 69.5 42.6 44.4 46.2 48.2 50.4

2700 CFM Total MBH 1.3 24.4 49.8 77.7 100.4 117 1.0 24.1 49.5 77.4 100.2 116.3 215.6 193.7 170.3 144.5 115.0 Sens. MBH 38.9 38.9 38.9 38.9 38.9 38.9 29.2 29.2 29.2 29.2 29.2 29.2 155.6 136.2 116.7 97.3 77.8 Lvg. DB 81.7 81.7 81.7 81.7 81.7 81.7 80.0 80.0 80.0 80.0 80.0 80.0 43.4 46.7 50.0 53.4 56.7 Lvg. WB 62.8 64.4 66.0 67.7 69.1 70.0 62.9 64.5 66.1 67.8 69.1 70.1 40.9 42.8 44.9 47.1 49.6

3000 CFM Total MBH 1.6 26.1 52.9 82.4 106.4 123.4 1.2 25.7 52.6 82.0 106.0 123.1 228.8 205.6 180.7 153.4 122.0 Sens. MBH 41.4 41.4 41.4 41.4 41.4 41.4 31.0 31.0 31.0 31.0 31.0 31.0 165.6 144.9 124.2 103.5 82.8 Lvg. DB 82.2 82.2 82.2 82.2 82.2 82.2 80.4 80.4 80.40 80.4 80.4 80.4 41.1 44.7 48.3 51.9 55.6 Lvg. WB 62.8 64.5 66.3 68.1 69.5 70.5 62.9 64.6 66.3 68.2 69.6 70.6 39.1 41.3 43.6 46.1 48.8

DB — Dry Bulb Temperature (F)Lvg. — LeavingMBH — Btuh x 1000Sens. — SensibleWB — Wet Bulb Temperature (F)

Page 44: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

44

Performance data (cont)ENERGY CONSERVATION WHEEL PERFORMANCE (cont)

STANDARD WHEEL — SIZES 22-38

LEGEND

COOLING MODE HEATING MODE Return Air = 75 db / 63 wb Return Air = 70 db / 58 wb

db 95 90 -10 0 10 20 30 wb 63 67 71 75 78 80 63 67 71 75 78 80 -11 -1 9 19 29

1200 CFM Total MBH -0.2 13.9 29.3 46.2 60.1 69.9 -0.1 13.9 29.4 46.3 60.2 70.0 127.5 114.7 100.9 85.6 52.8 Sens. MBH 22.7 22.7 22.7 22.7 22.7 22.7 17.0 17.0 17.0 17.0 17.0 17.0 90.7 79.4 68.0 56.7 35.1 Lvg. DB 77.5 77.5 77.5 77.5 77.5 77.5 76.9 76.9 76.9 76.9 76.9 76.9 60.0 61.3 62.5 63.8 66.2 Lvg. WB 63.0 63.6 64.2 64.9 65.5 65.8 63.0 63.6 64.2 64.9 65.5 65.9 52.2 52.8 53.5 54.2 55.8

1600 CFM Total MBH -0.1 17.7 37.3 58.8 76.4 88.8 0.0 17.8 37.4 58.9 76.5 88.9 162.3 145.9 128.4 108.9 86.6 Sens. MBH 28.9 28.9 28.9 28.9 28.9 28.9 21.7 21.7 21.7 21.7 21.7 21.7 114.9 101.3 86.8 72.3 57.9 Lvg. DB 78.2 78.2 78.2 78.2 78.2 78.2 77.4 77.4 77.4 77.4 77.4 77.4 57.0 58.6 60.3 61.9 63.5 Lvg. WB 63.0 63.7 64.5 65.4 66.1 66.6 63.0 63.8 64.6 65.6 66.2 66.7 50.3 51.1 52.0 53.0 54.1

2000 CFM Total MBH 0.1 21.3 44.6 70.1 91.0 105.7 0.1 21.3 44.6 70.1 91.0 105.8 193.7 174.2 153.2 130.0 103.4 Sens. MBH 34.6 34.6 34.6 34.6 34.6 34.6 25.9 25.9 25.9 25.9 25.9 25.9 138.5 121.2 103.9 86.5 69.3 Lvg. DB 79.0 79.0 79.0 79.0 79.0 79.0 78.0 78.0 78.0 78.0 78.0 78.0 54.1 56.1 58.1 60.1 62.1 Lvg. WB 62.9 63.9 64.9 65.9 66.8 67.4 63.0 63.9 64.9 66.0 66.8 67.4 48.4 49.5 50.6 51.8 53.2

2400 CFM Total MBH 0.5 24.6 51.1 80.3 104.0 120.9 0.3 24.5 51.1 80.2 104.0 120.9 222.0 199.6 175.5 148.9 118.5 Sens. MBH 39.8 39.8 39.8 39.8 39.8 39.8 29.8 29.8 29.8 29.8 29.8 29.8 159.1 139.2 119.4 66.4 79.5 Lvg. DB 79.7 79.7 79.7 79.7 79.7 79.7 78.5 78.5 78.5 78.5 78.5 78.5 51.4 53.7 56.0 58.4 60.7 Lvg. WB 62.9 64.0 65.2 66.4 67.4 68.1 63.0 64.0 65.2 66.4 67.4 68.1 46.6 47.8 49.2 50.6 52.3

2800 CFM Total MBH 0.8 27.6 57.0 89.3 115.7 134.4 0.6 27.5 56.9 89.2 115.6 134.3 274.4 222.4 195.5 165.9 132.0 Sens. MBH 44.4 44.4 44.4 44.4 44.4 44.4 33.3 33.3 33.3 33.3 33.3 33.3 177.7 155.5 133.3 111.1 88.9 Lvg. DB 80.3 80.3 80.3 80.3 80.3 80.3 79.0 79.0 79.0 79.0 79.0 79.0 48.8 51.4 54.1 56.7 59.4 Lvg. WB 62.9 64.1 65.4 66.8 67.9 68.7 63.0 64.2 65.5 66.9 68.0 68.8 44.8 46.3 47.8 49.5 51.4

3200 CFM Total MBH 2.2 30.3 61.2 95.2 126.1 142.5 1.2 32.5 66.7 104.4 125.6 156.8 270.1 242.8 213.5 181.1 144.1 Sens. MBH 47.9 47.9 47.9 47.9 47.9 47.9 39.3 39.3 39.3 39.3 39.3 39.3 194.5 170.2 145.9 121.6 97.2 Lvg. DB 81.1 81.1 81.1 81.1 81.1 81.1 79.9 79.9 79.9 79.9 79.9 79.9 46.3 49.3 50.4 55.2 58.1 Lvg. WB 62.8 64.3 65.8 67.5 68.5 69.6 62.9 64.4 66.0 67.7 68.5 69.7 43.0 44.7 45.2 48.4 50.6

3600 CFM Total MBH 2.8 32.8 65.8 101.9 135.4 152.3 2.1 32.2 65.1 101.3 135.1 156.8 290.5 261.0 229.5 194.7 154.9 Sens. MBH 51.6 51.6 51.6 51.6 51.6 51.6 38.7 38.7 38.7 38.7 38.7 38.7 209.6 183.4 157.2 131.0 104.8 Lvg. DB 81.7 81.7 81.7 81.7 81.7 81.7 80.0 80.0 80.0 80.0 80.0 80.0 43.9 47.2 50.4 53.7 57.0 Lvg. WB 62.7 64.3 66.1 67.9 69.0 70.2 62.8 64.5 66.1 67.9 69.0 69.9 43.0 43.2 45.2 47.3 49.7

4000 CFM Total MBH 2.1 35.1 71.3 111.1 143.6 166.5 1.6 34.7 70.9 110.7 143.2 166.1 308.6 277.3 243.8 206.8 164.6 Sens. MBH 55.8 55.8 55.8 55.8 55.8 55.8 41.8 41.8 41.8 41.8 41.8 41.8 223.2 195.3 167.4 139.5 111.6 Lvg. DB 82.1 82.1 82.1 82.1 82.1 82.1 80.3 80.3 80.3 80.3 80.3 80.3 41.7 45.2 48.8 52.3 55.8 Lvg. WB 62.8 64.4 66.2 68.0 69.4 70.4 62.9 64.5 66.3 68.1 69.5 70.5 39.6 41.7 43.9 46.3 49.0

DB — Dry Bulb Temperature (F)Lvg. — LeavingMBH — Btuh x 1000Sens. — SensibleWB — Wet Bulb Temperature (F)

Page 45: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

45

ENERGY CONSERVATION WHEEL PERFORMANCE (cont)

OPTIONAL WHEEL — SIZES 12-38

LEGEND

COOLING MODE HEATING MODE Return Air = 75 db / 63 wb Return Air = 70 db / 58 wb

db 95 90 -10 0 10 20 30 wb 63 67 71 75 78 80 63 67 71 75 78 80 -11 -1 9 19 29

1500 CFM Total MBH 0.1 17.4 36.8 58.2 75.6 87.9 0.2 17.5 36.9 58.3 75.8 88.1 159.1 144.3 126.9 107.7 85.6 Sens. MBH 28.5 28.5 28.5 28.5 28.5 28.5 21.4 21.4 21.4 21.4 21.4 21.4 114.1 99.8 85.6 71.3 57.0 Lvg. DB 77.4 77.4 77.4 77.4 77.4 77.4 76.8 76.8 76.8 76.8 76.8 76.8 60.5 61.6 62.8 64.0 65.2 Lvg. WB 63.0 63.6 64.2 64.8 65.4 65.7 63.0 63.6 64.2 64.9 65.4 65.8 52.6 53.1 53.7 54.4 55.2

2000 CFM Total MBH 0.1 22.3 47.0 74.2 96.3 112.0 0.1 22.4 47.1 74.3 96.4 112.1 204.6 184.0 161.9 137.4 109.2 Sens. MBH 36.5 36.5 36.5 36.5 36.5 36.5 27.4 27.4 27.4 27.4 27.4 27.4 145.9 127.6 109.4 91.2 72.9 Lvg. DB 78.1 78.1 78.1 78.1 78.1 78.1 77.3 77.3 77.3 77.3 77.3 77.3 57.6 59.1 60.7 62.2 63.8 Lvg. WB 63.0 63.7 64.5 65.3 66.0 66.5 63.0 63.7 64.5 65.4 66.1 66.5 50.7 51.5 52.3 53.2 54.3

2500 CFM Total MBH 0.1 26.9 56.3 88.6 115.0 133.6 0.1 26.9 56.3 88.7 115.0 133.7 244.8 220.1 193.6 164.2 130.6 Sens. MBH 43.7 43.7 43.7 43.7 43.7 43.7 31.8 32.8 32.8 32.8 32.8 32.8 174.9 153.0 131.2 109.3 87.4 Lvg. DB 78.8 78.8 78.8 78.7 78.7 78.8 77.9 77.9 77.9 77.9 77.9 77.8 54.8 56.7 58.6 60.5 62.4 Lvg. WB 63.0 63.8 64.8 65.8 66.6 67.2 63.0 63.9 64.8 65.9 66.7 67.3 48.9 49.9 50.9 52.1 53.4

3000 CFM Total MBH 0.5 31.1 64.7 101.7 131.8 153.1 0.4 31.0 64.7 101.7 131.8 153.1 281.1 252.7 222.2 188.6 150.0 Sens. MBH 50.3 50.3 50.3 50.3 50.3 50.3 37.7 37.7 37.7 37.7 37.7 37.7 201.3 176.1 151.0 125.8 100.6 Lvg. DB 79.5 79.5 79.5 79.5 79.5 79.5 78.3 78.3 78.3 78.3 78.3 78.3 52.1 54.4 56.6 58.8 61.1 Lvg. WB 62.9 64.0 65.1 66.3 67.2 67.9 63.0 64.0 65.1 66.3 67.3 67.9 47.1 48.3 49.6 50.9 52.5

3500 CFM Total MBH 0.9 35.0 72.3 113.4 146.9 170.6 0.7 34.8 72.2 113.3 146.8 170.6 313.9 282.1 248.1 210.5 167.5 Sens. MBH 56.3 56.3 56.3 56.3 56.3 56.3 42.2 42.2 42.2 42.2 42.2 42.2 225.3 197.1 168.9 140.8 112.6 Lvg. DB 80.1 80.1 80.1 80.1 80.1 80.1 78.8 78.8 78.8 78.8 78.8 78.8 49.6 52.2 54.7 57.3 59.8 Lvg. WB 62.9 64.1 65.3 66.7 67.8 68.5 63.0 64.1 65.4 66.7 67.8 68.6 45.4 46.8 48.3 49.9 51.7

4000 CFM Total MBH 1.4 38.5 79.2 123.9 160.4 186.3 1.1 38.2 78.9 123.7 160.2 186.1 343.4 308.7 271.4 230.3 183.2 Sens. MBH 61.7 61.7 61.7 61.7 61.7 61.7 46.3 46.3 46.3 46.3 46.3 46.3 247.0 126.1 185.3 154.4 123.5 Lvg. DB 80.7 80.7 80.7 80.7 80.7 80.7 79.3 79.3 79.3 79.3 79.3 79.3 47.2 50.0 52.9 55.7 58.6 Lvg. WB 62.8 64.2 65.6 67.1 68.3 69.1 62.9 64.3 65.7 67.2 68.3 69.2 43.7 45.3 47.0 48.8 50.9

4500 CFM Total MBH 1.9 41.7 85.4 133.4 166.0 200.3 1.5 41.3 85.0 133.0 165.7 199.9 370.0 332.5 292.3 248.0 197.3 Sens. MBH 66.6 66.6 66.6 66.6 66.6 66.6 50.0 50.0 50.0 50.0 50.0 50.0 266.7 233.4 200.0 166.7 133.3 Lvg. DB 81.3 81.3 81.3 81.3 81.3 81.3 79.7 79.7 79.7 79.7 79.7 79.7 44.9 48.0 51.2 54.3 57.4 Lvg. WB 62.8 64.3 65.9 67.5 69.2 69.6 62.9 64.4 65.9 67.5 69.2 69.7 42.0 43.8 45.7 47.8 50.1

5000 CFM Total MBH 2.5 44.7 91.0 144.9 183.3 212.7 1.9 44.1 90.5 141.4 182.8 212.2 393.8 353.9 311.1 263.9 210.0 Sens. MBH 71.1 71.1 71.1 71.1 71.1 71.1 50.0 50.0 50.0 50.0 50.0 53.3 284.5 248.9 213.4 177.8 142.3 Lvg. DB 81.8 81.8 81.8 81.8 81.8 81.8 79.7 79.7 79.7 79.7 79.7 80.1 42.7 46.1 49.5 52.9 56.3 Lvg. WB 62.8 64.4 66.1 67.8 69.2 70.2 62.9 64.5 66.1 67.9 69.3 70.2 40.3 42.4 44.5 46.8 49.3

DB — Dry Bulb Temperature (F)Lvg. — LeavingMBH — Btuh x 1000Sens. — SensibleWB — Wet Bulb Temperature (F)

Page 46: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

46

Electrical dataCOMPRESSOR ELECTRICAL DATA

CONDENSER FAN MOTOR ELECTRICAL DATA

SUPPLY AND EXHAUST FAN MOTOR ELECTRICAL DATA

ENERGY CONSERVATION WHEEL ELECTRICAL DATA

VOLTAGEUNIT SIZE 62D

07 08 09 12 14 15 16 20 22 24 30 34 38Number of Compressors 1 1 1 2 2 2 2 2 2 2 2 2 4

208/230-3-60RLA (each) 20.6 22.5 25.0 16.1 20.5 22.5 25.0 29.5 29.5 31.5 48.1 53.1 31.5LRA 155 149 164 91 155 149 164 195 195 225 245 425 225

460-3-60RLA (each) 9.7 10.6 12.2 7.1 9.6 10.6 12.2 14.8 14.8 16.7 22.5 23.8 16.7LRA 75 75 100 46 75 75 100 95 95 114 125 187 114

VOLTAGEUNIT SIZE 62D

07 08 09 12 14 15 16 20 22 24 30 34 38Number of Fans 1 1 1 2 2 2 2 2 2 2 2 2 2208/230-3-60 FLA 3.0 4.0 4.0 2.3 2.3 4.0 4.0 4.0 4.0 4.0 6.0 6.0 6.0460-3-60 FLA 1.5 2.0 2.0 1.2 1.2 2.0 2.0 2.0 2.0 2.0 3.0 3.0 3.0

VOLTAGEMOTOR HP

3/4 1 1 1/2 2 3 5 7.5 10 15 20208/230-3-60 FLA 3.4 3.2 4.8 6.3 9.8 15.7 22.3 29.0 43.4 57.0460-3-60 FLA 1.7 1.5 2.0 2.9 4.1 6.8 10.0 12.9 18.9 24.5

VOLTAGEWHEEL SIZE (in.)

36 42 48208/230-3-60 FLA 2.5 2.5 2.5460-3-60 FLA 1.3 1.3 1.3

Page 47: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

47

Control componentsThe 62D Series of dedicated outdoor air units use a micro-processor controller that has been specifically designed forCarrier commercial equipment. The controller monitorsthe operating conditions in the outdoor air unit and con-trols the compressors, fans, heating systems, and optionaldevices. The controller has the capability of communicat-ing with all major building automation protocols includingBACnet, Modbus, and LonWorks protocols.

Sequence of operationOperation of the dedicated outdoor air unit is based uponthe occupancy schedule that the installer or user programsinto the controller. When the building is in the Occupiedmode, the supply fan starts and the mode of operation ofthe unit is based on the outdoor-air temperature (OAT). Ifthe OAT is between 56 F and 59 F, only the supply fan willoperate, which will provide cool outdoor air to the space.

If the OAT is 60 F or greater, then the unit will operatein Cooling mode. When the OAT is between 60 F and74 F, only the first stage cooling will be energized. Whenthe OAT is greater than 74 F, then all stages of cooling willbe in operation. If the unit is equipped with hot gas reheat,then the leaving-air temperature (LAT) will be controlled to72 F. An OAT of 55 F or less will cause the unit to operate ina heating mode. When the OAT is between 55 F and 46 F,the first stage heating is energized. When the OAT is lessthan 46 F, all stages of heating will be in operation. If theunit is equipped with modulating gas heat, SCR (silicon-controlled rectifier) electric heat, hot water heat, or steamheat, the leaving-air temperature will be controlled to 72 F. The unit is also equipped with a low temperature protec-tion system. If the LAT is sensed at 40 F or less, the unitwill be turned off to protect the space from potential freez-ing conditions.

Controls

Page 48: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

48

Typical wiring schematic (gas unit shown)

LEGENDAPS — Air Pressure SwitchCR — Control RelayFR — Fan RelayHR — Hi-Fire RelayIC — Ignition ControllerPS — Pressure SwitchSR — Start RelayTD — Time Delay

Page 49: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

49

Packaged Rooftop Cooling Unit and Packaged Rooftop Cooling Unit with HeatHVAC Guide Specifications —Section 62DA,DB,DC,DDSize Range: 6 to 35 Tons Nominal (Cooling)Carrier Model Number: 62DA,DB,DC,DD

Part 1 — General1.01 SYSTEM DESCRIPTION:

Outdoor roof curb or slab mounted, electronicallycontrolled, cooling or cooling/heating unit utilizinghermetic scroll compressors with crankcase heatersfor cooling duty and gas combustion or electric forheating duty. Units shall discharge supply air verti-cally or horizontally as shown on contract drawings.

1.02 QUALITY ASSURANCEA. Unit shall be designed to conform to ANSI/

ASHRAE 15 (latest edition), ASHRAE 62, and ULStandard 1995.

B. Unit shall be listed by ETL and ETL, Canada as atotal package.

C. Gas heat equipped units shall be designed to con-form with ANSI Standard Z21.47 (U.S.A.) / CSAStandard 2.3 (Canada), Gas-Fired Central Furnaces.

D. Roof curb shall be designed to NRCA criteria perBulletin B-1986.

E. Insulation and adhesive shall meet NFPA 90Arequirements for flame spread and smokegeneration.

1.03 DELIVERY, STORAGE AND HANDLINGUnit shall be stored and handled per manufacturer’srecommendations.

Part 2 — Products2.01 EQUIPMENT

A. General:Factory-assembled, single-piece heating and coolingunit. Contained within the unit enclosure shall be allfactory wiring, piping, refrigerant charge (R-410A),operating oil charge, single refrigerant circuit (sizes07–09) or dual refrigerant circuits (sizes 12–38),microprocessor based control system and associatedhardware, and all special features required prior tofield start-up.

B. Unit Cabinet:1. Double wall design, constructed of G-90 galva-

nized steel, bonderized and pre-coated with abaked enamel finish.a. Top cover shall be 18-gage sheet metal with

1.0-in. thick, 4.0-lb density, closed cell insu-lation with a 24-gage sheet metal interiorliner.

b. Access panels and doors shall be 20-gagesheet metal with 1.0-in. thick, 4.0-lb density,closed cell insulation with a 24-gage sheetmetal interior liner. Access doors shall be

equipped with stainless steel hinges andquarter turn, adjustable, cam-action latches.

c. Corner and center posts shall be 16-gagegalvanized steel.

d. Base pans shall be 16-gage galvanized steel.All openings through the base pan shall haveupturned flanges at least 0.5 inches inheight.

e. Basepans shall be insulated with 0.375-in.thick closed cell foam insulation.

f. Compressor rail shall be 12-gage galvanizedsteel.

g. Condensate pan shall be 16-gage stainlesssteel insulated with closed cell neopreneinsulation.

h. Base rail shall be 14-gage galvanized steel.i. Fan deck (indoor and outdoor section) shall

be 16-gage galvanized steel.j. Roof sections shall be sloped for proper

drainage.2. Unit casing shall be capable of withstanding

500-hour salt spray exposure per ASTM B117(scribed specimen).

3. Unit shall have insulated hinged access doorsfor easy access to the control box and otherareas requiring servicing. Each door shall sealagainst a rubber gasket to help prevent air andwater leakage and be equipped to permit easeand safety during servicing.

4. Interior cabinet surfaces shall be lined with24 gage galvanized steel.

5. Unit shall have a factory-installed sloped con-densate drain connection fabricated of stainlesssteel.

6. Unit shall be equipped with rigging openings inframe rails to facilitate overhead rigging.

7. Filters shall be accessible through a hingedaccess panel.

8. Unit shall have vinyl coated security grille toprotect the condenser and compressor section.

9. The outdoor air opening shall have a factory-installed hood with bird screen.

C. Fans:1. Indoor Evaporator Fans:

a. Double-width/double-inlet, centrifugal, beltdriven, forward-curved type with single out-let discharge.

b. Fan shaft bearings shall be of the pillowblock type with positive locking collar andare permanently lubricated.

c. Fans shall be statically and dynamicallybalanced.

d. Evaporator fan shaft bearings shall have aminimum L10 life of 30,000 hours.

Guide specifications

Page 50: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

50

Guide specifications (cont)e. The fan assembly shall be mounted in rubber

vibration isolators.f. Fan assembly shall be on a slide-out deck

that is removable for maintenance and service.

2. Condenser Fans:a. Fans shall be direct-driven propeller type

only, with corrosion-resistant blades rivetedto corrosion-resistant steel supports.

b. Fans shall discharge air vertically upwardand be protected by PVC coated steel wiresafety guards.

c. Fans shall be statically and dynamicallybalanced.

D. Compressors:1. Fully hermetic, scroll type compressors with

overload protection and short cycle protectionwith minimum on and off timers.

2. Factory rubber-in-shear mounted for vibrationisolation.

3. Reverse rotation protection capability.4. Crankcase heaters shall only be activated during

compressor off mode.E. Coils:

1. Standard evaporator coil shall have enhancedsurface aluminum plate fins mechanicallybonded to six rows of seamless internallygrooved copper tubes with all joints brazed.

2. Standard condenser coil shall have enhancedsurface aluminum plate fins mechanicallybonded to seamless internally grooved coppertubes with all joints brazed.

3. Coils shall be pressure tested at 650 psig priorto unit assembly; leak tested at 150 psig andundergo final testing at 475 psig.

4. Optional coil coatings for corrosion protectionshall be available.

F. Refrigerant Components:1. Unit shall be equipped with single refrigerant

circuit (sizes 07–09) or dual refrigerant circuits(sizes 12–38), with each circuit containing:a. Solid core filter drier.b. Adjustable thermostatic expansion valve.c. Minimum load valved. Gage connection ports

2. Unit shall be equipped with fan cycling lowambient head pressure control to allow opera-tion down to 35 F.

G. Filter Section:Standard filter section shall be supplied with 2-in.thick MERV-8 fiberglass filters.

H. Controls and Safeties:1. Microprocessor Controls:

a. Local access to the microprocessor controlshall be via a handheld keypad/display unit.The keypad/display unit shall have anumeric keypad, direction keys, and pro-grammable function keys. The display shallbe a 4 line by 40 character backlit LCD display.

b. BACnet, Modbus, and LonWorks protocolcapable.

c. Shall provide a 5° F temperature differencebetween cooling and heating set points tomeet ASHRAE 90.1, energy standard.

d. Shall provide an alarm indicator and an audi-ble alarm signal.

e. Shall provide and display a current alarm listand an alarm history list.

f. Compressor minimum run time (3 minutes)and minimum off time (5 minutes) shall beprovided.

g. Shall have service run test capabilityh. Shall have a service diagnostic mode.i. Minimum of 2 capacity stages (single circuit)

or 3 capacity stages (dual circuit) of mechan-ical capacity control (excluding hot gasbypass) controlled with logic to maintainsupply-air temperature set point.

j. Unit shall be complete with self-containedlow voltage control circuit.

2. Safeties:a. Unit shall incorporate a solid-state compres-

sor lockout which provides optional resetcapability at the space thermostat shouldany of the following safety devices trip andshut off compressor:1) Compressor lockout protection provided

for either internal or external overload.2) Low-pressure protection.3) Freeze protection (evaporator coil).4) High-pressure protection.5) Loss of charge protection.

b. Supply-air sensor shall be located in the unitand shall be used for compressor stagecontrol.

c. Induced draft heating section shall be pro-vided with the following minimumprotections:1) High-temperature limit switch.2) Differential pressure switch to prove

induced draft.3) Flame rollout switch.4) Flame proving controls.5) Redundant style gas valve.

Page 51: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

51

I. Operating Characteristics:1. Unit shall be capable of starting and running at

115 F ambient outdoor temperature per maxi-mum load criteria of ARI Standard 340/360.

2. Unit with standard controls will operate in cool-ing down to an outdoor ambient temperature of35 F.

3. Unit shall be equipped with a motorized twoposition outdoor air (OA) damper for 100% OAoperation.

4. Unit shall be provided with fan time delay toprevent cold air delivery (gas heat only).

J. Electrical Requirements:All unit power wiring shall enter unit cabinet at a sin-gle location.

K. Motors:1. Compressor motors shall be cooled by refriger-

ant gas passing through motor windings andshall have either internal line break thermal andcurrent overload protection or external currentoverload modules with compressor temperaturesensors.

2. All condenser-fan motors shall be open dripproof with permanently lubricated ball bearings,class F insulation and manual reset overloadprotection.

3. All indoor-fan motors 5 hp and larger shallmeet the minimum efficiency requirements asestablished by the Energy Policy Act of 1992(EPACT), effective October 24, 1997.

L. Special Features:Certain features are not applicable when the fea-tures designated * are specified. For assistance inamending the specifications, contact your localCarrier Sales Office.

1. Hot Gas Reheat:A factory-installed hot gas reheat (HGRH) coilshall be available. The HGRH coil shall be avail-able on the lead circuit only or on both refriger-ant circuits. Units with HGRH will have variablespeed low ambient head pressure control.

2. Energy Recovery:a. The factory-installed enthalpy wheel shall be

certified to meet the requirements of ARIStandard 1060 and shall be ARI listed.

b. The enthalpy wheel shall be constructed ofcorrugated synthetic fibrous media with adesiccant intimately bound and uniformlyand permanently dispersed throughout thematrix structure of the media.

c. The desiccant material shall be molecularsieve, 4 angstrom or smaller.

d. The rotor shall be constructed of alternatinglayer of flat and corrugated media.

e. Wheel construction shall be fluted or formedhoneycomb geometry so as to eliminateinternal wheel bypass.

f. The wheel frames shall be evenly spacedsteel spokes with a galvanized steel outerband and rigid center hub.

g. The wheel seals shall be full contact nylonbrush type.

h. The wheel shall slide out of the cabinet sidefor service.

i. Wheel cassettes shall be constructed of gal-vanized steel. Cassettes shall have integralpurge section.

j. The wheel bearings shall be inboardmounted, permanently sealed roller bearingsor externally flanged bearings.

k. The wheel shall be driven by a fractionalhorsepower AC motor via multilink drivebelts.

l. Energy wheel defrost control and air bypassshall be available.

3. Gas Heating:a. Gas heat shall be induced-draft combustion

type with energy saving direct spark ignitionsystems and redundant main gas valves.

b. The heat exchanger shall be of the tubularsection type constructed of a minimum of20-gage stainless steel.

c. Burners shall be of the in-shot type con-structed of aluminum coated steel.

d. All gas piping shall enter the unit cabinet at asingle location.

e. Induced-Draft Fans:1) Shall be direct-driven, single inlet, for-

ward-curved centrifugal type.2) Shall be statically and dynamically bal-

anced.3) Shall be made from steel with a corro-

sion-resistant finish.f. High-corrosion areas such as flue gas collec-

tion and exhaust areas shall be lined withcorrosion resistant material.

g. The unit shall have factory-installed gas heatwith 2-stage heat control or modulating con-trol providing 25% to 100% burnermodulation.

4. Electric Heat:a. Electric resistance heaters shall be factory-

installed, nichrome element type, open wirecoils with 0.375 in. inside diameter, insu-lated with ceramic bushings, and includeoperating and safety controls. Coil ends shallbe staked and welded to terminal screwslots.

b. Factory-installed electric heat shall havestaged heat control (1, 2, 3, or 4 stages) or

Page 52: Product 62DA,DB,DC,DD07-38 Data Dedicated Vertical or ... · The Carrier 62D units are designed to meet customer’s requirements for new construction, replacement opportuni-ties,

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 52 Catalog No. 04-52620004-01 Printed in U.S.A. Form 62D-1PD

Replaces: 62D-1APDSection 8Tab 8d

Carrier Corporation • Syracuse, New York 13221 7-09

Guide specifications (cont)SCR (silicon controlled rectifier) controlproviding infinite capacity adjustment.

5. Hot Water Heat:Unit shall have a 2-row hot water coil, alumi-num construction, with air vents installeddownstream of the evaporator coil. Coil con-nection stubs will be located inside the unitcabinet. Hydronic control valves shall be fieldfurnished.

6. Steam Heat:Unit shall have 1-row, steam distributing type,aluminum fin coil installed downstream of theevaporator coil. Coil connection stubs will belocated inside the unit cabinet. Control valvesto be field furnished.

7. Backward Inclined Plenum Supply Fan:A factory-installed backward inclined plenumfan shall be mounted on rubber isolation andinstalled on a slide-out deck that is removablefor maintenance and service.

8. Liquid Subcooling Coil:The shall be equipped with a factory-installedliquid subcooling coil on all circuits.

9. Exhaust Fan:Package shall include an exhaust fan (centrifu-gal style) fan mounted on rubber vibration iso-lation with gravity relief damper. The shaftmounted fan shall be mounted in sealed ballbearings and driven via an adjustable sheavebelt drive.

10. Modulating Exhaust Fan:Package shall include an exhaust fan (centrifu-gal style) fan mounted on rubber vibration iso-lation with gravity relief damper. The shaftmounted fan is mounted in sealed ball bear-ings and driven via an adjustable sheave beltdrive. Control shall be based on building pressure.

11. Oversize Fan Motors:Oversize fan motors shall be available for bothoptional supply and exhaust fan motors.

12. Liquefied Propane Conversion Kit:Kit shall contain all the necessary hardwareand instructions to convert a standard naturalgas unit for use with liquefied propane gas.

13. Convenience Outlet:Shall be factory-installed and internallymounted with an externally accessible 115-v,15 amp GFI, female receptacle with hingedcover. The outlet shall require field-supplied115-v power supply wiring.

14. Non-Fused Disconnect Switch:Shall be factory-installed, internally mounted,and UL approved. Non-fused switch shallprovide unit power shutoff. Shall be accessiblefrom outside the unit and shall provide poweroff lockout capability.

15. Firestat:A factory-installed, manual-reset firestat shallbe mounted in the return air opening of theunit. The firestat shall be set to open at 135 F.

16. Dirty Filter Status Switch:The manual reset filter status switch shall be apressure differential switch and will indicate adirty filter. The switch shall be factoryinstalled.

17. Fan Status Switch:The unit shall be equipped with a field-adjust-able differential air pressure switch installedacross the filters or supply fan to provideproof of airflow.

18. Phase/Voltage Monitor:A factory-installed under-voltage and phaseloss sensor shall stop the unit whenever volt-age is too low, phases are out of sequence, ora phase is dropped. The unit will restart auto-matically within five minutes after the correctpower is supplied.

19. Spring Fan Isolation:Supply fan and power exhaust fan (ifequipped) shall be mounted in spring type iso-lation with seismic restraints.

20. 4-Inch Filters:Optional filter section shall be supplied with4-in. thick MERV-8, 11, or 14 pleated fiber-glass filters.

21. Filter Kits:Accessory filter kits shall be available withMERV-8, 11, or 13 type filters.

22. Full Perimeter Roof Curb:Curb shall be formed of 14-gage galvanizedsteel with wood nailer strip and shall be capa-ble of supporting entire unit weight.