NOT TO SCALESITE MAP
VICINITY MAPNOT TO SCALE
N
PACIFIC OCEAN
PACIFIC COAST HWY
PICO BLVDHWY 1B
NIELSON WAY
OCEAN AVE
COLORADO A
VE
CITY OF SANTA MONICACLEAN BEACHES PROJECT FOR PIER AND
PICO/KENTER WATERSHEDSCITY OF SANTA MONICA, COUNTY OF LOS ANGELES,
STATE OF CALIFORNIA
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
PROJECT SITE
CALIFORNIA
STATE R
TE 2
PACIFIC COAST HWY
PACIFIC STN
ITEM AGENCY/UTILITY COMPANY CONTACT PERSON PHONE NO.
OWNER CITY OF SANTA MONICA SELIM EREN, PE (310) 458-8721CIVIL ENGINEER TETRA TECH JASON FUSSEL, P.E. (805) 542-9052EMERGENCY & FIRST RESPONDERS SANTA MONICA POLICE & FIRE DISPATCH 911UNDERGROUND SERVICE ALERT DIGALERT DIGALERT 811UTILITY LOCATOR FOR CITY OF SANTA MONICA SANTA MONICA PUBLIC WORKS GLENN CLAYPOOL (310) 458-5707CITY FACILITIES/SERVICES - AFTER HOURS PHONE NO. SANTA MONICA PUBLIC WORKS ARCADIA WATER TREAT. PLANT (310) 826-6712
NON-EMERGENCY POLICE & FIRE:POLICE SANTA MONICA POLICE FRONT DESK (310) 458-8427FIRE PREVENTION SANTA MONICA FIRE ERIC BINDER (310) 458-2666
CITY OF SANTA MONICA OWNED/MANAGED FACILITIES:STREET LIGHTING ELECTRICAL SYLVESTER MABY (310) 458-4991WATER, SEWER & STORM DRAIN WATER RESOURCES STUART JOSE (310) 458-8535TRASH PICKUP & TRASH ENCLOSURES RESOURCE RECOVERY & RECYCLING DWIGHT LEDUFF (310) 458-2223TRAFFIC SIGNALS TRAFFIC SIGNALS MIKE MORGAN (310) 458-8520TRAFFIC SIGNAGE, STRIPING, LOOPS, CAMERAS & SPEED HUMPS TRANSPORTATION MANAGEMENT HENRY SERVIN (310) 458-8291MUNICIPAL BUS SYSTEM BIG BLUE BUS TIM MCCORMICK (310) 458-5831TREE & ROOT PROTECTION URBAN FORESTER MATTHEW WELLS (310) 458-5182PUBLIC LANDSCAPE OPEN SPACE MANAGEMENT DARRELL BAKER (310) 458-8974NEWSPAPER RACKS PUBLIC WORKS KATHY RUFF (310) 458-8737PARKING ENFORCEMENT POLICE (TRAFFIC SERVICES DIVISION) MARGARITA VERDUZCO (310) 458-2226CITY PARKING FACILITIES PARKING SERVICES JUAN CARRERO (310) 434-8295BEACH FACILITIES BEACH MAINTENANCE PAUL DAVIS (310) 395-9778MUNICIPAL AIRPORT AIRPORT ADMINISTRATION STELIOS MAKRIDES (310) 458-8591MUNICIPAL PIER PIER MAINTENANCE ROD MERL (310) 458-8706MUNICIPAL FIBER NETWORK (MFN) INFORMATION SYSTEMS DIVISION JOSEPH CEVETELLO (310) 458-8381
PRIVATELY OWNED/MANAGED UTILITIES:ELECTRICAL SOUTHERN CALIFORNIA EDISON (SCE) RICHARD PEACOCK (310) 315-3224NATURAL GAS SOUTHERN CALIFORNIA GAS COMPANY (SCG) MIKE GRIMM (310) 605-4180TELEPHONE VERIZON ED GONZALEZ (310) 570-3157CABLE TV TIME WARNER CABLE DOMINIC GASBARRE (818) 466-9998TELECOMMUNICATION/FIBER OPTIC CABLE ABOVE NET KEVIN SULLIVAN (714) 236-8502TELECOMMUNICATION/FIBER OPTIC CABLE METRO ACCESS DESTRY HIPPEN (949) 622-3506TELECOMMUNICATION/FIBER OPTIC CABLE NEXT "G" NETWORKS RAFAEL NUNEZ (909) 593-9700TELECOMMUNICATION/FIBER OPTIC CABLE LEVEL 3 COMMUNICATIONS ROBERT THOMPSON (213) 291-6204TELECOMMUNICATION/FIBER OPTIC CABLE MCI WORLDCOM CRAIG ROBERTSON (714) 591-4614TELECOMMUNICATION/FIBER OPTIC CABLE QWEST COMMUNICATIONS MICHAEL GARRISON
OTHER AGENCIES/DISTRICTS:METROPOLITIAN TRANSPORTATION AUTHORITY (METRO) SPECIAL EVENTS NOTIFICATION (213) 922-4632SANTA MONICA MALIBU UNIFIED SCHOOL DISTRICT (SMMUSD) FACILITIES MANAGEMENT (310) 450-8338SANTA MONICA COLLEGE - ADMINISTRATION SMC ADMINISTRATION (310) 434-4000SANTA MONICA COLLEGE - POLICE SMC CAMPUS POLICE (310) 434-4300CALTRANS - EMERGENCY & PLANNED CLOSURES CALTRANS DISPATCH (323) 259-2352CALTRANS - MAINTENANCE WESTDALE MAINTENANCE STATION (310) 479-0728CALTRANS - INSPECTOR FOR WESTSIDE KEN PAHLEVANI (OR PER CALTRANS PERMIT) (310) 837-8351CITY OF LOS ANGELES TRAFFIC MANAGEMENT BUREAU OF TRAFFIC MANAGEMENT - WESTERN DISTRICT OFFICE (310) 575-8138UNITED STATES POSTAL SERVICE (USPS) SANTA MONICA MAIN OFFICE (310) 576-6786LOS ANGELES COUNTY DEPT. OF PUBLIC WORKS WATERWORKS DIVISION (877) 637-3661
CONTACT LIST
80,000 GALTANK
PS
PS
SMURRF
1.6MG
TANKTO SS
Q = 0-1.2 CFS
Q = 0-1.2 CFS
Q =0-3 CFS
Q > 3 CFSOR TANK IS
FULL
PIC
O K
EN
TER
SD
Q = 0-20 CFS
PRETREATMENT
Q = 0-1.5 CFS
Q > 1.5 CFSOR TANK IS
FULL
PIE
R S
D
1550 LOTDRAINAGE
Q = 0-1.2 CFS
SANTA MONICA BAY(PACIFIC OCEAN)
EXIST.PRETREATMENT
DIVERSION
EXIST.PRE-
TREATMENT
DIVERSION
Q =0-18.5 CFS
PS
EXIST.DIVERSION
EXIST.PUMP STATION
PS
LOW FLOWSUMP PUMP
TO SS
PICO-KENTERPONDING
PS
Q > 18.5 CFS ORTANK IS FULL
EXIST. LOW FLOWSUMP PUMP TO SS
EXIST.DIVERSION
FLOW METER
FLOWCONTROL
FLOW CONTROL
FLOWMETER
ACTUATEDVALVE
ACTUATEDVALVE
GATEVALVE
GATEVALVE
ACTUATEDVALVE
PORTABLEPUMP
EXIST.WET WELL
PROCESS FLOW DIAGRAMNOT TO SCALE
ACTUATEDVALVE
PS
FLOW METER
DEWATERINGSYSTEM
PIER STORM DRAINDIVERSION ANDDEAUVILLE LOT
PICO-KENTER STORMDRAIN DIVERSION
PACIFICOCEAN
CO
LOR
AD
O A
VE
APPIAN WAYPACIFIC COAST HWY
SANTA MONICA URBANRUNOFF RECYCLINGFACILITY (SMURRF)
OCEAN FRONT WALK
SANTA MONICA PIER
PICO-KENTERCHANNEL
CONTROL POINT 1PER SHEET C-3
CONTROL POINT 5PER SHEET C-10
CONTROL POINT 2PER SHEET C-3 CONTROL POINT 3
PER SHEET C-3 CONTROL POINT 4PER SHEET C-10
xxx
x
M
H
M
H
F
/
H
V
M
H M
H
U
/
O
M
H
V
U
/
O
M
H
M
H
M
H
M
H
V
M
M P
B
P
B
V
M
V
P
B
C
O
V
30 STALLS @ 8'-6"
18.5' DEEP (TYP.)
27 STALLS @ 8'-6"
18.5' DEEP (TYP.)
27 STALLS @ 8'-6"
18.5' DEEP (TYP.)
27 STALLS @ 8'-6"
18.5' DEEP (TYP.)
8
.
5
'
T
Y
P
.
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
16.0'
19.7'
16.0'
16.0'
17.0'
16.0'
56
56
56
56
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
8
.
5
'
T
Y
P
.
1
8
.
5
'
T
Y
P
.
22.4'
88
88
88
89
OCEAN FRONT WALK
20.0'
19.7'
19.4'
EXISTING 1550 PARKING LOT
10.8'
12.9'
32'
18'
BEACH MAINTENANCE
APPPIAN WAY
PACIFIC COAST HWY
M
OO
M
AT
AH
IKO
W
AY
54
CONVERT 4 EXISTING
STALLS INTO 2 ADA STALLS
PER DETAIL B, THIS SHEET
92
92
93
91
91 91
91
91
90
90
6
0
°
'
16.00' AISLE
VARIES
PER PLAN
9'-10"
8
'
-
6
"
16.00'
1
8
.
5
'
4" WHITE STRIPE
PER CITY OF SANTA
MONICA PARKING
STANDARDS
1'
V
VAN ACCESSIBLE
SIGN (SEE DETAIL 1,
SHEET C-17)
18'
1'
1' 1'
NOTES:
1. "V" INDICATES 'VAN-ACCESSIBLE' PARKING SPACE
NO
PARKING
3'
9' 8' 9'
3
'
26' 6'
32.00'
NO PARKING ZONE:
4" BLUE LINE DIAGONALS AT
45° AT 3'-0" MAX. CENTERS.
PROVIDE 12" HIGH WHITE
PAINTED LETTERS.
SEE DETAIL 3, SHEET C-17
ACCESSIBLE
SIGN (SEE DETAIL 1,
SHEET C-17)
CONCRETE WHEEL STOP
(TYP.) SEE DETAIL 2,
SHEET C-17
ACCESSIBLE PARKING
SYMBOL (TYP.) SEE DETAIL 4,
SHEET C-17
4" BLUE
STRIPING,
TYP.
4" WHITE STRIPING. MATCH
(E) STRIPING ANGLE.
3475 E. Foothill Blvd.
Pasadena, CA 91107
Phone: (626) 351-4664
Fax: (626) 351-5291
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
3475 E. Foothill Blvd.
Pasadena, CA 91107
Phone: (626) 351-4664
Fax: (626) 351-5291
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
0
SCALE:
10' 20' 40'
1" = 20'
LEGEND:
LIMITS OF WORK
PROPERTY LINE
UNDERGROUND STORAGE
RESERVOIR #1
ACCESSIBLE PARKING STALLSHC
KEY MAP
NTS
TYPICAL PARKING STALLA
_
NTS
54 CONCRETE PAD PER DETAIL 2, SHEET C-13
56 PROVIDE STRIPING FOR STANDARD PARKING STALLS PER
DETAIL A, THIS SHEET (111 STALLS)
88 NO PARKING ZONE. 4" DIAGONALS AT 45° AT 3'-0" ON
CENTER.
89 NO PARKING ZONE. 4" RED STRIPING ALONG THE EDGE OF
PAVEMENT
90 DO NOT ENTER SIGN PER CA MUTCD 2014 REV 1, R5-1. SEE
DETAIL 8, SHEET C-17
91 TYPE I ARROW PER CA MUTCD 2014 REV 1. SEE DETAIL 5,
SHEET C-17
92 TYPE IV ARROW PER CA MUTCD 2014 REV 1. SEE DETAIL 6,
SHEET C-17
93 TYPE III ARROW (B) PER CA MUTCD 2014 REV 1. SEE
DETAIL 7, SHEET C-17
CONSTRUCTION NOTES
ACCESSIBLE PARKING SPACEB
_
NTS
CATCH BASINCB
RADIAL POINT
TOP OF CURB
RP
TC
UNDERGROUND STORAGE RES.
RES
ACCESS MAINTENANCE HOLEMHOL
CONCRETECONC
LIGHT POLE PER
ELECTRICAL PANS
LIGHT
MONITORING WELLWELL
NEW ASPHALT CONCRETEPAVEMENT PER DETAILS 4 & 5,SHEET C-14
48 REPLACE SIDEWALK TO MATCH EXISTING SIDEWALK
50 CONSTRUCT CONCRETE TYPE 'A' CURB PER CITY OFSANTA MONICA STD DWG SM 6. SEE DETAIL 2, SHEET C-18
53 JOIN NEW SIDEWALK TO EXISTING SIDEWALK
54 CONSTRUCT CONCRETE PAD PER DETAIL 2, SHEET C-13
57 CONSTRUCT CONCRETE CURB AND GUTTER PER CITY OFSANTA MONICA STD DWG SM 6. SEE DETAIL 2, SHEET C-18
66 CONNECT PVC TO UNDERGROUND STORAGE RESERVOIRPER DETAIL 3, SHEET C-14
78 CONSTRUCT GRATING CATCH BASIN PER SPPWC 303-3 (V= 7.75', W = 3.0'). INSTALL FILTER INSERT PER DETAIL 6,SHEET C-14
80 CONSTRUCT 6" POLYVINYL CHLORIDE (PVC) PIPE.CONNECT TO CATCH BASIN
CONSTRUCTION NOTES
LEGEND
NEW PORTLAND CEMENTCONCRETE
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
0
SCALE:
10' 20' 40'
1" = 20'
N
NOTES
FINISHED GRADEFG
FINISHED SURFACEFS
1. UNDERGROUND STORAGE RESERVOIR, MAINTENANCE HOLES, ANDSTORM DRAIN SYSTEM PER STORM DRAIN PLANS (SHEETS C-5 THRU C-8).
2. PARKING STRIPING PER SHEET C-3.3. LIGHTING AND FOUNDATION PER ELECTRICAL PLANS
KEY MAPNNTS
PLANTING PER LANDSCAPE PLANS
UNDERGROUND STORAGE RESERVOIRPER STORM DRAIN PLANS
x CONSTRUCTION FENCE
NEW AC PAVEMENT PERDETAIL 4, SHEET C-14
XX
EXISTINGPAVEMENT
(E) FENCE
NEW CURB ANDGUTTER PER CITY
OF SANTA MONICASTD DWG SM 6
EXISTINGBIKE PATH
NEW AC PAVEMENT PERDETAIL 4, SHEET C-14
EXISTINGPROPOSEDEXISTINGPROPOSED
NEW AC PAVEMENT PERDETAIL 4, SHEET C-14
EXISTING PROPOSED
2:1 MAX
(E) SIDEWALK TO BEREMOVED AND REPLACE
SECTION A-AA_
NTS
SECTION B-BB_
NTS
SECTION C-CA_
NTS
NEW TYPE 'A' CURB PERCITY OF SANTA MONICASTD DWG SM 6 EXISTING RETAINING WALL
5.0' CITY SIDEWALK
4"
1"
1"
PROTECT (E) CURBAND GUTTER
6" SUBGRADECOMPACT TO 95%
MAX. DRY DENSITY
6"
xx
MH
MH
F/HV
MH MH
U/O MHV
U/O
MH
MH MH
MH
V
M M PBPB
M
V
PB
CO
UTV UTV UTV UTV UTV UTV UTV UTV UTVSS SS SST T T T T T T T T T T T T T T T T T T T T T T T T T T
JT JT JT JT JT JT JT JT JT JT JT JT JT JT JT
UTV UTV UTV UTV UTV
W W W W W
SS SS SS SS SS SS
UTV
WJT JT JT JT JT JT JT JT JT
UTVJT JT JT U
E
UE UE UE UE UE
UE
UEUEUE
SS SS
SS
SS
SS
SSSS
SS
SS
WW
WW
W W W W
UE
UE
UE
UE UE UE UE UE UE
UTV
UTVUTV
UTVUTV
UTVUTV
UTVUTV
UTVUTV
G G G G G G
GG
G G G
SSSS
SS
STORM DRAIN LINE PERSTORM DRAIN PLANS (TYP.)
FORCE MAIN PERSTORM DRAIN PLANS (TYP.)
OCEAN FRONT WALK
PACIFIC COAST HWY
(E) 1550 PARKING LOT
(E) PARKING LOT
LIMIT OF WORK
xx
xx
x x x x x x x x x x x x x x x x x x x x x x x x x x xx
xx
xx
xx
xx
xx
xxxxxxxxxxxxxxxxxxxxxxxxx
xx
xx
xx
x
4.95
%
0.50%
(4.3
8%)
0.50%
(18.
31%
)
(1.32%)
(0.03%)
0.01%
2.7:
1
48
50
57
50
APPIAN WAY
(E) 1550 PARKING LOT
BEACHMAINTENANCE
BEGIN
57 END
57
50
50 END
BEGIN
0.01%78
4.09
%
4.41
%
4.79
%
3.60
%
V = 7.75'W = 3.0'
5.00' TAPER0" TO 6" CURB
INV 7.23
INV 3.50
80
66
A
A
C
B
B
C(1
.81%
)
48
53
REPAVE AND CONVERT 4 EXISTING STALLS INTO 2ADA STALLS PER DETAIL B, SHEET C-3FIELD VERIFY EXISTING SLOPES. SLOPES SHALLNOT BE MORE THAN 2% IN ALL DIRECTIONS AFTERREPAVING.
(0.52%)
(2.0
0%)
54
(15.00 FS)
5C-14 LIGHT POLE PER
ELECTRICAL PLANS (TYP.)
1.00
%
78 V = 7.75'W = 3.0'
INV 7.23INV 3.50
80
66
78 INV 7.23
INV 3.50
80
66
V = 7.75'W = 3.0'
xx
M
H
M
H
F
/
H
V
M
H M
H
M
H
V
M
H
M
H
M
H
M
H
V
M
M P
B
P
B
M
V
P
B
C
O
V
PACIFIC COAST HWY
OCEAN FRONT WALK
APPIAN WAY
1550 PARKING LOT
BEACH
MAINTENANCE
15.00'
TYP.5.84'
5.90'
12.87'
8.29'
9.39'
9.99'
11.65'
26.67'
9.94'
10.54'
27.68'
323.93'
20.00'
16.00'
8.82'
PLANTING LEGEND
0
SCALE:
10' 20' 40'
1" = 20'
N
3475 E. Foothill Blvd.
Pasadena, CA 91107
Phone: (626) 351-4664
Fax: (626) 351-5291
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
TREES
SYMBOL BOTANNICAL NAME COMMON NAME SPACING SIZE QUANTITY REMARKS
BRAHEA BRANDEGEEI
SAN JOSE HESPER PALM 15-20 FEET 22
STABILIZED DECOMPOSED GRANITE, 3" DEEP
GROUNDCOVER
12' BTH, MIN.
BRAHEA BRANDEGEEI
SAN JOSE HESPER PALM
24" BOX
3/1/2017 5:17:08 P
M - P
:\01297\135-01297-16014\C
AD
\C
ON
CE
PT
UA
L\E
H-A
RB
-E
LE
VA
TIO
N-1.D
WG
- P
AN
GILIN
AN
, E
LV
A
www.tetratech.com
Bar Measures 1 inch
Copyright: T
etra T
ech
CLEAN BEACHES PROJECT FOR
PIER AND PICO-KENTER WATERSHEDS
DEAUVILLE PARKING LOT
ELEVATION
VIEW FROM OCEAN FRONT WALK
12' B
TH
, M
IN
.
STABILIZED
DECOMPOSED GRANITE
PCH ON-RAMP
APPIAN WAY
PCH
BRAHEA BRANDEGEEI
SAN JOSE HESPER PALM
24" BOX
3/1/2017 5:20:41 P
M - P
:\01297\135-01297-16014\C
AD
\C
ON
CE
PT
UA
L\E
H-A
RB
-E
LE
VA
TIO
N-2.D
WG
- P
AN
GILIN
AN
, E
LV
A
www.tetratech.com
Bar Measures 1 inch
Copyright: T
etra T
ech
CLEAN BEACHES PROJECT FOR
PIER AND PICO-KENTER WATERSHEDS
DEAUVILLE PARKING LOT
ELEVATION
VIEW FROM PACIFIC COAST HIGHWAY
12' B
TH
, M
IN
.
BRAHEA BRANDEGEEI
SAN JOSE HESPER PALM
24" BOX
STABILIZED
DECOMPOSED GRANITE
xx
MH
MH
F/HV
MH MH
MHVMH
MH MH
MH
V
M M PBPB
M
V
PB
CO
V
PACIFIC COAST HWY
OCEAN FRONT WALK
APPIAN WAY
15.00'TYP.
1550 PARKING LOT
BEACHMAINTENANCE
GENERAL LANDSCAPE NOTES
1. FOR ADDITIONAL PLANTING INFORMATION NOT MENTIONED IN THESE GENERAL PLANTING NOTES, REFER TO SPECIFICATIONS.
2. OBTAIN LETTER OF FINAL GRADE CERTIFICATION FROM CITY PRIOR TO BEGINNING PLANTING OPERATIONS CERTIFYING THAT ROUGH GRADES AREWITHIN 1/10TH OF AN INCH FROM SPECIFIED FINISH GRADES. ENSURE THAT FINISH GRADE ELEVATIONS OF PLANTING AREAS ARE SET AT PROPERELEVATIONS RELATIVE TO PAVING FINISH SURFACE ELEVATIONS, UTILITY COVERS AND CURBS.
3. BACKFILL SOIL: SUBSOIL AND TOPSOIL REMOVED FROM EXCAVATIONS MAY BE USED AS BACKFILL SOIL UNLESS OTHERWISE INDICATED. UNLESSTHE EXISTING SOIL CONSISTS OF MORE THAN 6% ORGANIC MATTER IN THE TOP 6", COMPOST SHALL BE APPLIED AT A MINIMUM RATE OF 4 CUBICYARDS PER 1,000 SF OF PERMEABLE AREA TO A DEPTH OF 6" INTO THE SOIL. A POST-INSTALLATION SOIL TEST SHALL BE PERFORMED TO SHOW A6% ORGANIC MATTER CONTENT OR GREATER.
4. IMPORT SOIL: SHOULD IMPORT SOIL BE NEEDED TO BRING THE SITE TO SPECIFIED FINISH GRADES, SOIL SAMPLES SHALL BE TAKEN AT TWO (2)LOCATIONS WITHIN EACH IMPORT SITE. SUBMIT HORTICULTURAL SOIL TEST RESULTS OF IMPORT SOIL AND SOURCE LOCATIONS TO CITY'SAUTHORIZED REPRESENTATIVE FOR APPROVAL PRIOR TO DELIVERING SOIL TO SITE. ENSURE IMPORT SOIL IS OF SANDY LOAM NATURE,CONTAINING NO TOXIC CHEMICALS OR ELEMENTS THAT MIGHT INHIBIT OR RETARD NORMAL PLANT GROWTH.
5. PLANT MATERIAL, I.E., TREES, SHRUBS, AND GROUND COVERS, MUST BE APPROVED BY THE CITY'S AUTHORIZED REPRESENTATIVE PRIOR TOINSTALLATION. PLANT MATERIALS INSTALLED WITHOUT APPROVAL MAY BE SUBJECT TO REMOVAL AND REPLACEMENT WITH RELATED COSTSINCURRED BY THE CONTRACTOR.
6. FINAL LOCATIONS OF PLANT MATERIALS ARE SUBJECT TO THE APPROVAL OF THE CITY'S AUTHORIZED REPRESENTATIVE PRIOR TO INSTALLATION.PERFORM THE FOLLOWING PROCEDURES BEFORE BEGINNING PLANT PIT EXCAVATIONS:
A. TREES - CHALK OR STAKE LOCATIONS BEFORE DIGGING HOLES.
7. NOTIFY THE CITY'S AUTHORIZED REPRESENTATIVE AT LEAST SEVENTY-TWO (72) HOURS IN ADVANCE TO PERFORM A SPECIFIED SITEOBSERVATION TASK. INSUFFICIENT NOTIFICATION TIME GIVEN TO THE CITY'S AUTHORIZED REPRESENTATIVE MAY REQUIRE THE SITE VISIT TO BECANCELED, OR POSSIBLY MAKE THE CONTRACTOR RESPONSIBLE TO COMPENSATE THE CITY FOR OVERTIME.
8. THE CONTRACTOR MUST FURNISH PLANT MATERIAL FREE OF PESTS, POOR CONDITION, OR DISEASE. PLANT MATERIAL MUST BE CERTIFIED PESTAND DISEASE FREE.
9. IF CONFLICTS ARISE BETWEEN THE ACTUAL SIZE OF PLANTING AREAS ON-SITE AND THOSE INDICATED ON DRAWINGS, CONTACT THE CITY'SAUTHORIZED REPRESENTATIVE FOR RESOLUTION. FAILURE TO MAKE SUCH CONFLICTS KNOWN TO THE CITY'S AUTHORIZED REPRESENTATIVE IN ATIMELY MANNER MAY RESULT IN THE CONTRACTOR'S LIABILITY TO RELOCATE PLANT MATERIAL OR INSTALL NEW PLANT MATERIAL AT THECONTRACTOR'S EXPENSE.
10. FILL AREAS WITH STABILIZED DECOMPOSED GRANITE FROM GAIL MATERIAL (CORONA, CA), MINIMUM 3" DEEP. DECOMPOSED GRANITE SHALL NOTBE APPLIED WITHIN 6" OF THE BASE OF TREES.
11. ORGANIC MULCH SHALL BE APPLIED IN A MINIMUM 2' RADIUS AROUND THE TREE BASE.
12. PROVIDE A TREE STAKE AND MOCK-UP ON-SITE FOR THE CITY'S AUTHORIZED REPRESENTATIVE'S REVIEW PRIOR TO PERFORMING TREE STAKING.
13. ENSURE THAT TREES ARE NOT PLANTED TOO DEEP RELATIVE TO FINISH GRADE. TREES PLANTED TOO DEEP WILL BE REPLANTED BY THECONTRACTOR AT NO EXPENSE TO THE CITY - REFER TO SPECIFICATIONS AND DETAILS FOR PROPER GRADE ELEVATIONS. ENSURE THAT NOEXISTING OR NEW PLANT MATERIAL OR ROOTS COME IN CONTACT WITH LIME STABILIZED BACKFILL.
14. INSTALL PLANT MATERIAL WITH ITS BEST SIDE FACING THE PREDOMINANT VIEW OF THE PUBLIC WHERE POSSIBLE.
15. DO NOT PLANT TREES WITHIN 10 FEET OF GAS, WATER OR SEWER LINES. CONTACT CITY IF MEETING THIS REQUIREMENT DIFFERS FROMLOCATIONS INDICATED ON DRAWINGS.
16. REFER TO DRAWING DETAILS FOR REQUIRED PLANTING AND STAKING METHODS.
17. INSTALL LINEAR ROOT BARRIERS ("DEEP ROOT" OR APPROVED EQUAL) FOR ALL TREES WITHIN 5'-0" OF CONCRETE CURB, CONCRETE PAVING PERCITY STANDARDS AND SPECS. REFER TO MANUFACTURER'S INSTALLATION SPECIFICATIONS.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY COORDINATION WITH SUBCONTRACTORS AS REQUIRED TO ACCOMPLISH PLANTINGOPERATIONS.
19. REFER TO THE SPECIFICATIONS FOR PLANTING REQUIREMENTS, MATERIALS AND EXECUTION.
20. ALL TREES SHALL BE TAGGED BY THE LANDSCAPE ARCHITECT AT A NURSERY OR NURSERIES SELECTED BY THE CONTRACTOR OR AT THEDISCRETION OF THE LANDSCAPE ARCHITECT. IF TAGGING IS REQUIRED AT MORE THAN THREE (3) NURSERIES, THE CONTRACTOR IS RESPONSIBLEFOR ADDITIONAL COST FOR THE LANDSCAPE ARCHITECT'S TIME. THE CONTRACTOR SHALL NOTIFY THE LANDSCAPE ARCHITECT AT LEASTSEVENTY-TWO (72) HOURS IN ADVANCE OF THE TREE SELECTION DATE. THE CITY'S AUTHORIZED REPRESENTATIVE MAY ACCOMPANY THEPROJECT LANDSCAPE ARCHITECT FOR THE TREE SELECTION.
21. PRE-SELECTED OR "LANDSCAPE ARCHITECT - TAGGED" PLANT MATERIAL MUST BE INSPECTED BY THE CONTRACTOR AND BE CERTIFIED PEST ANDDISEASE FREE. IT IS THE CONTRACTOR'S OBLIGATION TO WARRANTY ANY AND ALL PLANT MATERIAL PER SPECIFICATIONS.
22. PRIOR TO PLANTING, IRRIGATION SYSTEM SHALL BE FULLY OPERATIONAL AND ALL PLANTING AREAS SHALL BE THOROUGHLY WATERED AS PERSPECIFICATIONS.
23. PLANT MATERIAL SHALL BE GROWN AND/OR ACCUMULATED UNDER CLIMATIC CONDITIONS SIMILAR TO THOSE OF THE PROJECT SITE.
24. PLANT MATERIAL MAY BE REJECTED AT ANY TIME BY THE CITY'S AUTHORIZED REPRESENTATIVE DUE TO HEALTH, FORM OR DAMAGE BEFORE ORAFTER PLANTING. WARRANTY ALL PLANT MATERIAL, SMALLER THAN 15 GALLON CONTAINER SIZE, TO BE IN HEALTHY AND FLOURISHING CONDITIONOF ACTIVE GROWTH FOR A PERIOD OF (1) YEAR AFTER DATE OF PROJECT ACCEPTANCE. WARRANTY ALL PLANT MATERIAL, 15 GAL. OR LARGER TOBE IN HEALTHY AND FLOURISHING CONDITION OF ACTIVE GROWTH FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF PROJECT ACCEPTANCE.
25. FERTILIZER TABLETS SHALL BE APPLIED PER THE PROJECT SPECIFICATIONS.
26. PLANT CENTERS SHALL NOT BE PLACED WITHIN EIGHTEEN (18") INCHES OF SPRINKLER HEADS.
27. FORM BERMED WATERING BASIN AROUND ALL TREES INSTALLED IN GROUND COVER AREAS. FILL BASIN WITH MULCH AS SHOWN ON DETAILS ANDAS SPECIFIED.
28. PLANT SPACING SHALL TAKE PRECEDENCE OVER IRRIGATION VALVE BOX, PIPE, AND OTHER EQUIPMENT LOCATIONS. VISIBLE IRRIGATIONEQUIPMENT SHALL BE INSTALLED IN AN ORGANIZED MANNER PERPENDICULAR TO HARDSCAPE ELEMENTS.
29. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING ALL AREAS IN A WEED AND DEBRIS-FREE CONDITION THROUGHOUT THE ESTABLISHMENTPERIOD.
30. QUANTITIES ARE PROVIDED AS A CONVENIENCE TO THE CONTRACTOR. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT A SUFFICIENTNUMBER OF PLANTS ARE PROVIDED TO ACHIEVE SPECIFIED SPACING WITHIN EACH PLANTING AREA.
PLANTING LEGEND
0
SCALE:
10' 20' 40'
1" = 20'
N
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291 Renewal Date
4/30/18Signature
4
Date
N .OC I
O
MAUR
I
E
129ARG
ENT
2/20/17
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
TREES
SYMBOL BOTANNICAL NAME COMMON NAME SPACING SIZE QUANTITY REMARKS
BRAHEA BRANDEGEEI SAN JOSE HESPER PALM 15-20 FEET 22
PLANTING NOTES
1. DRAWING IS DIAGRAMMATIC. VERIFY ALL LOCATIONS AND CONDITIONS ON SITE. COUNT ALL PLANT MATERIAL BEFORE BIDDING.
2. INSPECT ALL EXISTING CONDITIONS ON SITE AND LOCATE ALL EXISTING UTILITIES BEFORE CONSTRUCTION BEGINS. ALL TREE STAKINGLOCATIONS TO BE APPROVED BY THE CITY PRIOR TO ANY DIGGING.
3. CONTRACTOR TO REPAIR AT HIS OWN EXPENSE ALL PROPERTY DAMAGE WHICH OCCURS DURING PROJECT INSTALLATION.
4. ALL PLANT MATERIAL TO BE GUARANTEED FOR 90 DAYS FROM THE DATE OF ACCEPTANCE BY OWNER. CONTRACTOR SHALL STORE PLANTMATERIAL IN SHADE AND PROTECT FORM SUN. ENSURE ON SITE WATERING PRIOR TO PLANTING AND THROUGH THE ESTABLISHMENT PERIOD,SEE SPECIFICATION.
5. FINISH GRADE TO BE 1" BELOW ALL WALKS, CURBS AND PAVING.
6. CONTRACTOR SHALL REMOVE ALL NURSERY STAKES AFTER PLANTING.
STABILIZED DECOMPOSED GRANITE, 3" DEEP
GROUNDCOVER
12' BTH, MIN.
MH
MH
F/HV
MH MH
VMH
MH MH
MH
V
M M PBPB
V
PB
CO
UTV UTV UTV UTV UTV UTV UTVSS SST T T T T T T T T T T T T T T T T T T T
JT JT JT JT JT JT JT JT JT JT JT JT
UTV UTV UTV UTV
W W W WSS SS SS SS
UTV
W JT JT JT JT JT
UTVJT JT JT U
E
UE
UE UE UE
UE
UEUEUE
SS SS
SS
SS
SS
SS
SS
SS
W W
W W
UE UE UE UE UE
UTVUTV
UTVUTV
UTVUTV
UTV
G G G G G
GG
G
SSSS
SSSS
V
PACIFIC COAST HWY
OCEAN FRONT WALK
APPIAN WAY
UNDERGROUND STORAGE RESERVOIR
CONNECT TO EX.10" WATER LINE
B 1"
3/4"
1"
0
SCALE:
10' 20' 40'
1" = 20'
N
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291 Renewal Date
4/30/18Signature
4
Date
N .OC I
O
MAUR
I
E
129ARG
ENT
2/20/17
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
GENERAL IRRIGATION NOTES
1. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROCURE AN ORIGINAL SET OF THESE PRINTED IRRIGATION PLANS FOR BIDDING AND CONSTRUCTION.
2. XEROX COPIES OF THESE PLANS ARE NOT ALLOWED FOR BIDDING AND CONSTRUCTION AS THEY MAY NOT SHOW IRRIGATION SYMBOLS, LINE WEIGHTS, OR LINE TYPESCLEARLY.
3. ALL LOCAL MUNICIPAL AND STATE LAWS, RULES AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS WORK ARE HEREBY INCORPORATED INTO ANDMADE A PART OF THESE SPECIFICATIONS AND THEIR PROVISIONS SHALL BE CARRIED OUT BY THE CONTRACTOR.
4. THE CONTRACTOR SHALL VERIFY SITE CONDITIONS, PROPERTY LINES, DIMENSIONS AND THE LOCATIONS OF ALL EXISTING UTILITIES, STRUCTURES AND SERVICES BEFORECOMMENCING WORK. THE LOCATIONS OF UTILITIES, STRUCTURES AND SERVICES SHOWN IN THESE PLANS ARE APPROXIMATE ONLY. ANY DISCREPANCIES BETWEENTHESE PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED TO THE CITY'S REPRESENTATIVE. CONTRACTOR SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH ALLSITE CONDITIONS PRIOR TO BIDDING AND COMMENCING WORK.
5. THE CONTRACTOR SHALL OBTAIN THE PERTINENT ENGINEERING OR ARCHITECTURAL PLANS BEFORE BEGINNING WORK.
6. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS REQUIRED TO PERFORM THE WORK INDICATED HEREIN BEFORE BEGINNING WORK.
7. THIS DESIGN IS DIAGRAMMATIC. ALL EQUIPMENT SHOWN IN PAVED AREAS IS FOR DESIGN CLARITY ONLY AND IS TO BE INSTALLED WITHIN PLANTING AREAS.
8. THIS DESIGN IS DIAGRAMMATIC. ALL EQUIPMENT SYMBOL SIZES ARE SHOWN FOR DESIGN CLARITY ONLY. CONTRACTOR SHALL MEASURE ALL DISTANCES AND SPACINGFROM CENTER OF SYMBOLS ON THE PLAN AND TRANSFER THOSE DISTANCES TO THE FIELD USING A PROPER MEASURING DEVICE SUCH AS A MEASURE TAPE OR WHEEL.
9. THE CONTRACTOR UNDERSTANDS IT IS THE INTENT OF THESE DRAWINGS TO IRRIGATE ALL NEW PLANT MATERIAL, AND EXISTING PLANT MATERIAL AS REQUIRED, UNLESSSPECIFICALLY NOTATED IN THE DRAWINGS THAT A PLANT MATERIAL IS A NON-IRRIGATED TYPE. WHEN PLANT MATERIAL IS SHOWN IN THESE DRAWINGS TO NOT HAVEIRRIGATION SUBSCRIBED TO IT, THE CONTRACTOR SHALL CONTACT THE CITY'S AUTHORIZED REPRESENTATIVE AND/OR THE LANDSCAPE ARCHITECT THROUGH THEPROJECT 'REQUEST FOR INFORMATION' (R.F.I.) PROCESS FOR CLARIFICATION AND FURTHER DIRECTION. IT IS THE INTENT OF THESE DRAWINGS THAT ALL NEW PLANTMATERIAL RECEIVE A MINIMUM OF 100% IRRIGATION COVERAGE FROM TWO ADJACENT SPRINKLERS WHEN OVERHEAD SYSTEMS ARE USED, AND AT LEAST ONE OR MOREEMITTER POINTS PER PLANT, AS DIRECTED IN THE DRIP EMITTER LEGEND, WHEN IRRIGATION DRIP SYSTEMS ARE USED. IF THE CONTRACTOR FAILS TO NOTIFY THE CITY'SAUTHORIZED REPRESENTATIVE AND/OR THE LANDSCAPE ARCHITECT OF A DISCREPANCY THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR IRRIGATION TO THEPLANT MATERIAL. IRRIGATION SHALL BE OF THE SAME TYPE AS THE SURROUNDING AREA. ULTIMATELY, IT IS RESPONSIBILITY OF THE CONTRACTOR TO PROVIDEIRRIGATION TO EVERY PLANT THAT IS INSTALLED UNDER HIS SUPERVISION.
10. REFER TO SHEET L-3 FOR IDENTIFICATION REQUIREMENTS.
EQUIPMENT / P.O.C. NOTES:
11. VERIFY THE ACTUAL LOCATION AND SIZE OF WATER METER AND BOTH STATIC AND DYNAMIC WATER PRESSURE IN THE FIELD PRIOR TO STARTING WORK. IF ANY OF THEP.O.C INFORMATION SHOWN ON THESE DRAWING IS FOUND TO BE DIFFERENT THAN THE ACTUAL P.O.C. INFORMATION GATHERED IN THE FIELD, IMMEDIATELY NOTIFYLANDSCAPE ARCHITECT. SHOULD THE CONTRACTOR FAIL TO FIELD VERIFY THE P.O.C. INFORMATION AND NOTIFY THE ABOVE, ANY ADDITIONAL COSTS INCURRED BYCHANGES REQUIRED TO BE MADE TO THE IRRIGATION SYSTEM BECAUSE OF LOW OR HIGH PRESSURE OR VOLUME SHALL BE THE SOLE RESPONSIBILITY OF THECONTRACTOR.
12. P.O.C. EQUIPMENT LAYOUT INCLUDING, BUT NOT LIMITED TO, IRRIGATION WATER METER, ELECTRICAL STUB-OUT, BACKFLOW ASSEMBLY, AND MASTER VALVE ISDIAGRAMMATIC DUE TO THE SCALE OF THE DRAWING. LOCATIONS MAY BE SHOWN WITHIN PAVING AND/OR ORIENTED IN A CERTAIN DIRECTION FOR CLARITY ONLY. PLANDOES NOT ACCOUNT FOR EQUIPMENT BY OTHERS WITHIN VICINITY OF P.O.C. CONTRACTOR SHALL VERIFY SPECIFIC LAYOUT ORIENTATION AND ACTUAL EQUIPMENTLOCATIONS WITH CITY'S AUTHORIZED REPRESENTATIVE PRIOR TO INSTALLATION OF EQUIPMENT.
13. ACTUAL LOCATION FOR THE INSTALLATION OF THE BACKFLOW PREVENTION DEVICE AND THE AUTOMATIC CONTROLLER IS TO BE DETERMINED IN THE FIELD BY THE CITY'SAUTHORIZED REPRESENTATIVE. CONTRACTOR SHALL CONTACT REPRESENTATIVE BEFORE COMMENCING WORK.
14. THE CONTRACTOR SHALL NOT WILLFULLY INSTALL ANY EQUIPMENT WHERE SHOWN ON THE PLANS WHEN IT IS OBVIOUS IN THE FIELD THAT CONDITIONS EXIST, WHICH ARENOT INDICATED ON THE PLANS. SUCH CONDITIONS MAY HAVE BEEN UNKNOWN AND NOT EVIDENT AT THE TIME THESE PLANS WERE PREPARED. ANY SUCH CONDITIONSSHALL BE BROUGHT TO THE ATTENTION OF THE LANDSCAPE ARCHITECT AND/OR CITY'S AUTHORIZED REPRESENTATIVE PRIOR TO COMMENCING WORK. SHOULD THECONTRACTOR FAIL TO NOTIFY THE ABOVE, ANY ADDITIONAL COSTS INCURRED BY REQUIRED CHANGES SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY FOR ANY FIELD CHANGES DEEMED NECESSARY BY THE CITY.
15. INSTALL ALL EQUIPMENT AS SHOWN IN THE DETAILS AND SPECIFICATIONS. CONTRACTOR SHALL BE RESPONSIBLE TO COMPLY WITH LOCAL CITY, COUNTY AND STATEREQUIREMENTS FOR BOTH EQUIPMENT AND INSTALLATION.
CONTROLLER / WIRE NOTES:
16. CONTRACTOR SHALL REFER TO IRRIGATION LEGEND FOR CONTROLLER TYPE. FINAL LOCATION OF CONTROLLER AND ELECTRICAL P.O.C. SHALL BE CONFIRMED WITH THECITY'S AUTHORIZED REPRESENTATIVE PRIOR TO COMMENCING WORK.
17. CONTRACTOR SHALL COORDINATE AND VERIFY CONTROLLER PEDESTAL LOCATION IN FIELD WITH ELECTRICIAN FOR CONTROLLER POWER CIRCUIT ROUTING.
18. CONNECTION OF IRRIGATION CONTROLLER TO THE PROVIDED ELECTRICAL STUB-OUT SHALL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR ANDINSTALLATION THEREOF SHALL BE PER LOCAL CODE REQUIREMENTS. CONTRACTOR MAY CHOOSE, IF SO DESIRED, TO SUB THIS WORK TO THE ELECTRICAL CONTRACTOR .
19. CONTROLLER POWER SOURCE SHALL BE SUPPLIED FROM A 'CONTROLLER' DEDICATED CIRCUIT BREAKER.
20. CONTRACTOR SHALL ROUTE THREE ADDITIONAL 'CONTROL' WIRES AND ONE ADDITIONAL 'COMMON' WIRE ALONG ENTIRE MAINLINE ROUTE AND ALONG EACH AND EVERYLEG OF MAINLINE ROUTE. ROUTE WIRES INTO EACH AND EVERY RCV VALVE BOX. WHERE VALVE BOXES ARE GROUPED INTO A MANIFOLD, ROUTE WIRES INTO FIRSTVALVE BOX ON MANIFOLD ONLY. SPARE 'CONTROL' WIRES SHALL BE OF A DIFFERENT COLOR THAN THOSE USED ON THE PROJECT. 'COMMON' WIRE SHALL BE OF ADIFFERENT COLOR THAN THAT USED ON THE PROJECT, OR WHITE WITH A STRIPE.
21. CONTRACTOR SHALL INSTALL METER WIRE/CABLE WITHIN 1" SCH 40 PVC ELECTRICAL CONDUIT.
SYSTEM GROUNDING NOTES:
22. CONTRACTOR SHALL BE RESPONSIBLE FOR GROUNDING CONTROLLER PER MANUFACTURERS REQUIREMENTS. CONTRACTOR SHOULD CONTACT CONTROLLERMANUFACTURER FOR GROUNDING INSTALLATION INFORMATION. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INFORM AND WORK WITH THE ELECTRICALCONTRACTOR SO AS TO PROVIDE ADEQUATE GROUNDING AS DETERMINED BY CONTROLLER MANUFACTURER.
23. CONTRACTOR SHALL USE U.L. APPROVED GROUND ROD AND GROUND PLATE WITH CADWELD 'ONE-SHOT' CONNECTION PROCESS FOR CONNECTING THE #6 AWG GROUNDWIRE FROM THE CONTROLLER GROUND LUG TO THE ROD. MAXIMUM GROUND RESISTANCE SHALL BE PER CONTROLLER MANUFACTURERS SPECIFICATIONS, BUT NOTGREATER THAN 10 OHMS.
24. CONTRACTOR SHALL REFER TO DETAILS 1 AND 2 IN DRAWING L-6 FOR SYSTEM GROUNDING INSTALLATION. ALSO CONTRACTOR MAY CONTACT CONTROLLER ASSEMBLYMANUFACTURER FOR ADDITIONAL CONTROLLER GROUNDING INSTALLATION INFORMATION.
OVERHEAD SPRINKLER / BUBBLER NOTES :
25. ALL HEADS ARE INTENDED TO BE INSTALLED WITH THE NOZZLE, SCREEN AND ARCS SHOWN ON THE PLANS.
26. ALL HEADS ARE REQUIRED TO BE ADJUSTED TO PREVENT OVERSPRAY ONTO ROADWAYS, PATHWAYS, BUILDINGS, WALLS, FENCES, AND HARDSCAPE. THIS INCLUDES, BUTNOT LIMITED TO, ADJUSTMENT OF DIFFUSER PIN OR ADJUSTMENT SCREW, REPLACEMENT OR ADDITION OF PRESSURE COMPENSATING SCREENS, REPLACEMENT OFNOZZLES WITH MORE APPROPRIATE RADIUS UNITS AND THE REPLACEMENT OF NOZZLES WITH ADJUSTABLE ARC UNIT AFTER FIELD REVIEW OF AN AREA DETERMINESSUCH IS REQUIRED.
27. CONTRACTOR SHALL ADJUST ALL HEADS AS REQUIRED TO ACCOMMODATE ANY VERTICAL OBSTRUCTIONS THAT MAY OCCUR, INCLUDING BUT NOT LIMITED TO TREES,LIGHT POLES, BOLLARDS, FIRE HYDRANTS, DRINKING FOUNTAINS, ETC. CONTRACTOR SHALL ADD SPRINKLER HEADS AND/OR REPLACE 'HALF PATTERN' NOZZLES WITHTWO 'QUARTER PATTERN' NOZZLES AS REQUIRED TO ACHIEVE 100% COVERAGE IN ALL AREAS THAT REQUIRE ADJUSTING. ADDITIONAL HEADS SHALL BE INSTALLED AT NOADDITIONAL COSTS TO THE CONTRACT. VERIFY ALL HEAD LAYOUT WITH THE CITY'S AUTHORIZED REPRESENTATIVE PRIOR TO COMMENCING WORK.
RCV / QCV NOTES:
28. REMOTE CONTROL VALVES AND ISOLATION VALVE LOCATIONS ON THIS DRAWING ARE APPROXIMATE. THE LANDSCAPE CONTRACTOR SHALL STAKE OUT EACHELECTRICAL CONTROL VALVE AND ISOLATION VALVE LOCATION FOR REVIEW AND APPROVAL BY THE CITY'S AUTHORIZED REPRESENTATIVE PRIOR TO INSTALLATION OFALL VALVES. FINAL LOCATION AND EXACT POSITIONING FOR ELECTRIC CONTROL VALVES AND ISOLATION VALVES SHALL BE DETERMINED BY THE CITY'S AUTHORIZEDREPRESENTATIVE. MINOR MODIFICATIONS OF REMOTE CONTROL VALVES AND ISOLATION VALVE LOCATIONS AS REQUESTED BY THE CITY'S AUTHORIZEDREPRESENTATIVE SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE PROJECT. FAILURE TO OBTAIN CITY'S APPROVAL PRIOR TO THEINSTALLATION SHALL CAUSE THE CONTRACTOR TO MAKE PROJECT DIRECTED REVISIONS AT NO ADDITIONAL COST TO THE CITY. IN GENERAL, UNLESS OTHERWISEDIRECTED BY THE CITY, ALL VALVES SHALL BE INSTALLED WITHIN THREE FEET FROM EDGE OF HARDSCAPE, WALK OR CURB IN SHRUB PLANTING AREAS.
29. ALL RCV'S AND QCV'S SHALL BE INSTALLED ON A SUB-MAIN MANIFOLD AS SHOWN IN DETAILS 3 AND 4 IN DRAWING L-5. RCV AND QCV SYMBOLS ARE SHOWNDIAGRAMMATICALLY ON TOP OF MAINLINE FOR CLARITY ONLY. PLAN DOES NOT SHOW THE MANIFOLD FOR CLARITY PURPOSES.
30. ALL QUICK COUPLER VALVES SHALL TO BE INSTALLED IN SHRUB OR GROUND COVER AREAS WHERE POSSIBLE. ALL QUICK COUPLER VALVES SHALL BE INSTALLED ASSHOWN IN THE INSTALLATION DETAILS. INSTALL QUICK COUPLERS WITHIN 18 INCHES OF HARDSCAPE. CONTRACTOR SHALL TEE OFF OF MAINLINE WITH 1-1/4 INCHMAINLINE PIPE WHERE APPLICABLE TO LOCATE QUICK COUPLER VALVE WITHIN ADJACENT SHRUB OR GROUNDCOVER AREAS AND/OR 18 INCHES FROM HARDSCAPE.
PIPE / SLEEVE NOTES:
31. MAINLINE LAYOUT IS DIAGRAMMATIC DUE TO THE SCALE OF THE DRAWINGS. ROUTING MAY BE SHOWN WITHIN PAVING FOR CLARITY ONLY, ACTUAL MAINLINE LOCATION TOBE WITHIN PLANTER, A MINIMUM OF 18" OFF ADJACENT HARDSCAPE AND OTHER OBSTACLES TYP. CONTRACTOR SHALL ADJUST MAINLINE ROUTING TO ACCOMMODATE
ANY VERTICAL OBSTRUCTIONS THAT MAY OCCUR, INCLUDING BUT NOT LIMITED TO TREES, LIGHT POLES, BOLLARDS, FIRE HYDRANTS, DRINKING FOUNTAINS, CONCRETEFOOTINGS, ETC.
32. MAINLINE AND/OR LATERAL PIPE ROUTING SHOWN OUTSIDE PROPERTY LINE AND/OR L.O.W. IS DIAGRAMMATIC AND FOR CLARITY ONLY, CONTRACTOR SHALL ROUTEMAINLINE WITHIN PROPERTY LINE AND/OR L.O.W.
33. ALL PIPE MATERIAL AND INSTALLATION LABOR REQUIRED FOR MAINLINE OR LATERAL LINE ADJUSTMENTS DUE TO ACCOMMODATIONS IN THE FIELD SHALL BE INCLUDEDWITHIN CONTRACTED PRICE AND MAY NOT BE SUBMITTED AS A CHANGE ORDER TO THE ORIGINAL BID.
34. NO PVC PIPE MAINLINES SHALL BE ROUTED OR ALLOWED CLOSER THAN 6 FEET FROM ANY TREE TRUNK AT ANY TIME. PIPE ROUTING AS SHOWN ON PLANS IS FORDIAGRAMMATIC PURPOSES ONLY. WHEN PIPE MUST BE ROUTED CLOSER THAN 6 FEET BECAUSE OF HARDSCAPE CONSTRAINTS OR OTHER OBSTACLES CONTRACTORSHALL INSTALL MAINLINE PIPE WITHIN SLEEVE WHERE PIPE IS WITHIN 6 FEET OF THE TRUNK AND SO INDICATE THE PIPE ROUTING AND SLEEVE LOCATIONS ON THEAS-BUILT DRAWINGS.
35. SLEEVES AND THEIR LOCATIONS ARE DIAGRAMMATICALLY SHOWN FOR CLARITY ONLY. ALL IRRIGATION SLEEVES MAY NOT BE SHOWN FOR CLARITY PURPOSES.CONTRACTOR SHALL INSTALL SLEEVES BELOW ALL PAVING, HARDSCAPE, ETC. AND AS DIRECTED BY THE CITY'S AUTHORIZED REPRESENTATIVE. ALL PIPE UNDER PAVEDAREAS SHALL BE INSTALLED IN A SLEEVE, AT MINIMUM TWICE THE DIAMETER OF THE PIPE CARRIED. SEE LEGEND FOR TYPE. ALL SLEEVES TO BE INSTALLED A MINIMUMDEPTH AS SHOWN ON THE PIPE/SLEEVING DETAIL. SLEEVES TO EXTEND AT LEAST 12" PAST THE EDGE OF THE PAVING.
36. ALL SLEEVE ENDS MUST BE SEALED WITH FOAM SEALANT INSIDE PIPE TO MINIMIZE DEBRIS INTRUSION.
37. LATERAL LINES MAY BE SHOWN WITHIN PAVING FOR CLARITY ONLY, ACTUAL LOCATION TO BE WITHIN PLANTER.
38. ALL CONTROL WIRE UNDER PAVED AREAS SHALL BE INSTALLED IN A SLEEVE, SEE LEGEND FOR TYPE. AT MINIMUM SIZE: 2 INCH- FOR UP TO 15 WIRES; 2-1/2 INCH- FOR 16-20WIRES; 3 INCH- FOR 21-55 WIRES. ALL SLEEVES TO BE INSTALLED A MINIMUM DEPTH AS SHOWN ON THE PIPE/SLEEVING DETAIL. SLEEVES TO EXTEND AT LEAST 12" PASTTHE EDGE OF THE PAVING.
DRIP / MICRO-SPRAY SYSTEM NOTES:
39. ALL LATERAL LINES FOR DRIP ZONES SHALL BE PVC SCH 40 PIPE.
40. ALL MAINLINES AND LATERAL LINES SHALL BE THOROUGHLY FLUSHED CLEAN BEFORE DRIP MANIFOLD ASSEMBLIES AND/OR DRIP TUBING CONNECTIONS ARE MADE. ALLDRIP TUBING LINES SHALL BE FLUSHED CLEAN BEFORE BACKFILLING.
41. CONTRACTOR SHALL ALWAYS FOLLOW AND ROUTE, PARALLEL TO GRADE, ANY INLINE DRIP TUBING LAYOUT. ALWAYS LAY DRIPLINES PERPENDICULAR TO SLOPE. DO NOTFOLLOW DIRECTIONAL LAYOUT AS SHOWN IN THE PLANS. HATCH PATTERNS SHOWN IN PLAN'S DRIP AREAS ARE DIAGRAMMATICAL ONLY.
42. FOR ALL INLINE DRIP TUBING AREAS ON SLOPE THE CONTRACTOR SHALL BE HELD ACCOUNTABLE FOR CREATING A TRIANGULAR WETTING PATTERN ACROSS ANY SLOPE.OFFSET THE EMITTERS BY HALF THE EMITTER SPACING WHEN INSTALLING TUBING TO CREATE A TRIANGULAR WETTING PATTERN ACROSS THE SLOPE. DO NOT INSTALLTUBING WHERE THE EMITTERS ARE DIRECTLY IN LINE (PERPENDICULAR) WITH EACH OTHER.
43. FOR TREES: MICRO-SPRAY SPRINKLER UNITS SHALL BE ALIGNED WITH TREES AS SHOWN IN THE DETAILS. CONFIRM ALL PROPOSED LAYOUT IN FIELD WITH OWNER'SAUTHORIZED REPRESENTATIVE PRIOR TO COMMENCING WORK.
44. WHEN DIFFERENT SIZES OR SPECIES OF TREES ARE TIED TO THE SAME ZONE VALVE CONTRACTOR SHALL BE REQUIRED TO MAKE ADJUSTMENTS TO MICRO-SPRAYNOZZLE RADIUS FOR EACH SIZE OR SPECIES OF TREE IN THE ZONE AS NEEDED TO PROVIDE PROPER AND ADEQUATE AMOUNT OF WATER AS REQUIRED BY EACH SPECIES.
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291 Renewal Date
4/30/18Signature
4
Date
N .OC I
O
MAUR
I
E
129ARG
ENT
2/20/17
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
PVC FITTINGS/NIPPLES:1. REQUIRED FOR ALL SOLVENT WELD MAINLINE FITTINGS 2 INCH (2") TO THREE INCH (3"), USE SPEARS PVC CL 315 BLUE 'EVERTUFF' FITTINGS, MODEL 4XX-XXXT,
OR SCH 80 FITTINGS.2. REQUIRED FOR ALL SOLVENT WELD MAINLINE FITTINGS 4 INCH (4") AND LARGER, USE SPEARS PVC CL 315 BLUE 'EVERTUFF' FITTINGS, MODEL 4XX-XXXT ONLY.3. REQUIRED FOR ALL FITTINGS WITH A THREADED MALE AND/OR FEMALE COMPONENT 1 INCH (1") OR LARGER, USE SPEARS PVC CL 315 BLUE 'EVERTUFF' TYPE
OR SCH 80 FITTINGS. FEMALE FITTINGS REQUIRE STAINLESS STEEL REINFORCED COLLAR.4. FOR ALL THREADED PLASTIC NIPPLES USE SCH 80 PVC.
SPECIFICATION GRADE IRRIGATION VALVE BOXES FOR IRRIGATION EQUIPMENT: PRO SERIES.
WIRE SPLICE CONNECTOR, MODEL DBR/Y-6 FOR RCV CONNECTIONS AND SPLICES.3M
NDS
SPEARS
IRRIGATION WIRE #12 AWG UF DIRECT BURIAL (U.L. APPROVED) FOR RCV 'CONTROL' WIRES, MODEL P7072-REV 14.IRRIGATION WIRE #12 AWG UF DIRECT BURIAL (U.L. APPROVED) FOR RCV 'COMMON' WIRES, MODEL P7072-REV 14.
MAINLINE ISOLATION FULL PORT BRONZE BALL VALVE, WITH STAINLESS STEEL HANDLE AND NUT OPTION, MODEL B-58570-SSHN, UPC# 039923680426. INSTALLED WITH HANDLE ONSIDE. LINE SIZE UP TO 2 INCH, 2" SIZE UP TO 3 INCH PIPE.
NIBCO
DRIP ZONE ASSEMBLY, SIZE PER PLAN: MODEL XCZ-###-PRB-COM WITH PRB-QKCHK-200M PRESSURE REGULATING BASKET FILTER(S). INSTALL BALL VALVE ON UPSTREAM SIDEOF VALVE FOR ISOLATION.
1 1/2" DRIP ZONE ASSEMBLY: MODEL XCZ-150-PRB-COM. USE ON ZONES UP TO FORTY (40) GPM FLOW. WITH PRB-QKCHK-200M PRESSURE REGULATING BASKET FILTER ANDINCLUDED 1 1/2" BALL VALVE. INSTALL BALL VALVE ON UPSTREAM SIDE OF VALVE FOR ISOLATION.
RAIN BIRD
RAIN BIRD
1 1/2" MASTER CONTROL VALVE: NORMALLY CLOSED M/V, MODEL 3200. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.SUPERIOR
MANIFOLD ISOLATION VALVE: SLO-CLOSE FULL BLOCK TRUE UNION 'SOCKET' PVC BALL VALVE WITH EPDM O-RINGS, MODEL VXX101N-SC. CONTRACTOR SHALL INSTALL ALLRCV'S/QCV'S ON MANIFOLDS. VALVE TO MATCH MANIFOLD SIZE. VALVE MANIFOLDS WITH ISOLATION VALVE ARE NOT SHOWN ON PLANS FOR CLARITY.
LASCO
PAIGE ELECTRIC
NEW 1 1/2" POTABLE WATER METER WITH 1 1/2" SERVICE LINE PER CITY OF SANTA MONICA STANDARD DRAWINGS SMW-5 AND SMW-9. CONTRACTOR SHALL SUPPLY ALLHARDWARE AND FITTINGS REQUIRED TO CONNECT IRRIGATION MAINLINE IMMEDIATELY DOWNSTREAM OF METER OUTLET, BEFORE ANY EXISTING EQUIPMENT. CONTRACTORSHALL VERIFY METER LOCATION, SIZE, SERVICE LINE SIZE, AND STATIC WATER PRESSURE BEFORE COMMENCING WORK.
P.O.C.
ALL REMOTE CONTROL VALVES SHALL BE OUTFITTED WITH A PURPLE ID TAG INDICATING THE CONTROLLER AND VALVE NUMBER.CHRISTY'S
NO SYMBOL
NO SYMBOL
NO SYMBOL
NO SYMBOL
NO SYMBOL
NO SYMBOL
6" WIDE METALLIC DETECTABLE MARKER TAPE, MODEL TA-DT-6-BI. TAPE SHALL BE INSTALLED 12" ABOVE ALL IRRIGATION MAINLINES AND SLEEVES.CHRISTY'SNO SYMBOL
CONTRACTOR SHALL COORDINATE ALL CONDUITS, SLEEVES, AND WIRE ROUTING WITH GENERAL CONTRACTOR AND ANY AFFECTED ON-SITE TRADES AS REQUIREDTHROUGHOUT PROJECT.
N/ANO SYMBOL
IRRIGATION UTILITIES
SYMBOL MFR. MODEL NO. / DESCRIPTION
IRRIGATION PIPE/SLEEVE
PVC PIPE, SCH 40, 3/4" - 2", AS LATERAL LINES. 12" BELOW GRADE. SEE PLAN FOR SIZES
PVC PIPE, SCH 40, SIZE AS REQUIRED, FOR RCV/QCV MANIFOLDS, 18" BELOW GRADE. MANIFOLDS AND PIPE ARE NOT SHOWN ON PLAN FOR CLARITY. MANIFOLD PIPE SIZE SHALLBE SAME AS LARGEST LATERAL SIZE IN MANIFOLD. USE 1-1/4" FOR QCV MANIFOLD.
PIPE AND WIRE SLEEVES, ASTM D3034 PVC GRAVITY SEWER PIPE, MINIMUM TWICE THE DIAMETER OF PIPE CARRIED AND MINIMUM 1-1/2" PIPE FOR WIRE CARRIED. PLACE BELOWALL PAVING, HARDSCAPE, ETC, AND AS DIRECTED BY OWNER'S AUTHORIZED REPRESENTATIVE.
AS APRVD
AS APRVD
PVC PIPE, CL 315, AS MAINLINES, 24"-36" BELOW GRADE. SEE PLAN FOR SIZES. INSTALL WITH T. CHRISTY 6" WIDE METALLIC DETECTABLE MARKER TAPE, MODEL TA-DT-6-BL.AS APRVD
NO SYMBOL AS APRVD
GPM PSI
0.25 30
1 1/2" REDUCED PRESSURE BACKFLOW PREVENTION ASSEMBLY, MODEL 825YA, WITH WYE STRAINER #650A. INSTALL CENTERED ON A 30"X36"X4" POURED-IN-PLACE CONCRETEPAD. UNIT TO BE INSTALLED WITHIN V.I.T. STAINLESS STEEL ENCLOSURE. CONTRACTOR SHALL DETERMINE EXACT LOCATION WITH THE OWNER'S AUTHORIZED REPRESENTATIVEBEFORE INSTALLATION.
FEBCO
BACKFLOW ASSEMBLY ENCLOSURE, MODEL SBBC-22SS. INSTALL ON CONCRETE PAD WITH BF ASSEMBLY CENTERED. CONCRETE PAD TO EXTEND 6" BEYOND OUTSIDEDIMENSIONS OF ENCLOSURE. REFER TO MANUFACTURER'S INSTALLATION DETAIL AND SPECIFICATIONS FOR ADDITIONAL INSTALLATION INFORMATION.
NO SYMBOL V.I.T.
IRRIGATION MISCELLANEOUS
SYMBOL MFR. MODEL NO. / DESCRIPTION
2" ELECTRICAL CONDUIT. ROUTE CONDUIT ALONG MAINLINE WHERE SHOWN ON PLANS.AS APRVD
IRRIGATION P.O.C.
CONNECTION TO EXISTING IRRIGATION MAINLINE. CONTRACTOR SHALL SUPPLY ALL HARDWARE AND FITTINGS REQUIRED TO CONNECT PROPOSED IRRIGATION MAINLINE TOEXISTING MAINLINE. CONTRACTOR SHALL VERIFY MAINLINE LOCATION, SIZE, AND STATIC WATER PRESSURE BEFORE COMMENCING WORK.
N/A
IRRIGATION CONTROLLER
117 VOLT ELECTRICAL POWER, PROVIDED BY ELECTRICIAN. CONTRACTOR SHALL COORDINATE AND VERIFY CONTROLLER PEDESTAL LOCATION IN FIELD WITH ELECTRICIAN.ELECTRICIAN SHALL ROUTE AND INSTALL ALL CONDUIT AND CONDUCTORS TO WITHIN THE CONTROLLER PEDESTAL LOCATION. IRRIGATION CONTRACTOR SHALL CONNECTIRRIGATION CONTROLLER TO ELECTRICAL STUB-OUT. CONTROLLER CIRCUIT SHALL BE SUPPLIED FROM A DEDICATED BREAKER FROM THE POWER SOURCE.
N/A
CONTROLLER GROUNDING EQUIPMENT KIT. CONTRACTOR SHALL GROUND CONTROLLER PER MANUFACTURER'S SPECIFICATIONS, BUT NOT LESS THAN PER LOCAL ANDNATIONAL ELECTRICAL CODE. GRD. WIRE / GRD. ROD / GRD. PLATE CONNECTIONS SHALL BE BY CADWELD PROCESS ONLY. MAXIMUM RESISTANCE SHALL BE NO MORE THAN 10OHMS. CONTRACTOR SHALL PROVIDE PROOF OF MEASURED RESISTANCE TO CITY'S AUTHORIZED REPRESENTATIVE BEFORE MAINTENANCE PERIOD BEGINS AND INCLUDEDOCUMENT WITHIN SUBMITTED MAINTENANCE MANUAL.
AS APRVD
WEATHER-BASED SMART IRRIGATION CONTROLLER, CS3-8-S1/CS3-GR/GR-STUBBY/COMM-5YRCALSENSE
NO SYMBOL
TREE IRRIGATION
TREE BUBBLER: RWS-B-C-1401, ROOT WATERING SYSTEM WITH 36" TUBE, 0.25 GPM BUBBLER & CHECK VALVE ON RISER, 4" GRATE, VERSATILESWING ASSEMBLY WITH 1/2" M NPT INLET, EACH SYMBOL REPRESENTS (AT MINIMUM) TWO UNITS, PLACE SPRAY HEADS ON OPPOSITE CORNERS,6” FROM EDGE OF ROOTBALL. ADJUST LOCATION PER ROOTBALL SIZE.
RAIN BIRD
A
B
GALLONS PER MINUTETOTAL LENGTH OF DRIP TUBING
VALVE NUMBER
VALVE SIZE
LATERAL PIPE SIZEDIAMETER (IN.) FLOW RATE (GPM)
3/4 8
1 13
1 1/4 23
1 1/2 32
2 53
NOTE:
ALL END RUNS OF LATERAL PIPE SHALL BE A MINIMUM OF 3/4" SIZE PIPE.
IDENTIFICATION REQUIREMENTS
ALL PROPOSED WATER LINES (PRESSURE/NON-PRESSURE), VALVE BOXES, HYDRANTS AND APPURTENANCES SHALL BE IDENTIFIED WITH CONTINUOUS PIPELINE IDENTIFICATION TAPE ATTACHED TOTHE PIPE AND SECURED EVERY 5 FEET TO CLEARLY DISTINGUISH BETWEEN RECYCLED WATER, NON-POTABLE AND POTABLE WATER SYSTEMS. IN ADDITION TO PIPE IDENTIFICATION, ALL WATERVALVES SHALL BE LABELED WITH APPROVED IDENTIFICATION TAGS DISTINGUISHING BETWEEN POTABLE WATER, NON-POTABLE STORMWATER, ON-SITE TREATED STORMWATER, AND NON-POTABLEWATER.
• RECYCLED WATER - ALL BURIED RECYCLED WATER LINES (PRESSURE/NON-PRESSURE) SHALL BE PURPLE COLORED PIPE WITH CONTINUOUS WORDING "CAUTION: NON-POTABLE RECLAIMED(RECYCLED) WATER, DO NOT DRINK" IN BLACK LETTERS PRINTED ON OPPOSITE SIDES OF THE PIPE.
• PROJECTS UTILIZING EXTENSIVE PIPELINE INSTALLATION SHALL USE PURPLE PIPE PROPERLY STENCILED/LABELED. FOR LIMITED APPLICATION, THE USE OF CONTINUOUS LETTERING ONTHREE INCH (3") MINIMUM WIDTH PURPLE TAPE WITH ONE INCH BLACK OR WHITE CONTRASTING LETTERING BEARING THE CONTINUOUS WORDING "CAUTION RECYCLED WATER"PERMANENTLY AFFIXED AT FIVE FOOT INTERVALS ATOP ALL HORIZONTAL PIPING, LATERALS AND MAINS IS AN ACCEPTABLE ALTERNATIVE TO PURPLE PIPE, IF PURPLE PIPE IS UNAVAILABLE INTHE SIZE REQUIRED BY THE PROJECT DESIGN. IDENTIFICATION TAPE SHALL EXTEND TO ALL VALVE BOXES AND/OR VAULTS, EXPOSED PIPING, HYDRANTS AND QUICK COUPLERS.
• POTABLE WATER - ALL POTABLE WATER LINES SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA PLUMBING CODE AND ALL OTHER GOVERNING CODES, RULES AND REGULATIONS.BURIED POTABLE WATER LINES SHALL BE IDENTIFIED BY CONTINUOUS LETTERING ON THREE INCH (3") MINIMUM WIDTH BLUE OR GREEN TAPE WITH ONE INCH WHITE LETTERING BEARING THECONTINUOUS WORDING "POTABLE WATER" PERMANENTLY AFFIXED AT FIVE FOOT INTERVALS ATOP ALL HORIZONTAL PIPING, LATERALS AND MAINS. IDENTIFICATION TAPE SHALL EXTEND TOALL VALVE BOXES AND/OR VAULTS, EXPOSED PIPING AND HYDRANTS.
• IDENTIFICATION TAPE IS NOT NECESSARY FOR EXTRUDED COLORED PVC WITH CONTINUOUS WORDING "POTABLE WATER" PRINTED IN CONTRASTING LETTERING ON OPPOSITE SIDES OF THEPIPE.
• NON-POTABLE WATER - ALL NON-POTABLE IRRIGATION/INDUSTRIAL WATER LINES (PRESSURE/NON-PRESSURE) SHALL BE IDENTIFIED BY CONTINUOUS LETTERING ON THREE INCH (3") MINIMUMWIDTH YELLOW TAPE WITH ONE INCH BLACK LETTERING BEARING THE CONTINUOUS WORDING "CAUTION: NON-POTABLE WATER, DO NOT DRINK" PERMANENTLY AFFIXED AT FIVE FOOTINTERVALS ATOP ALL HORIZONTAL PIPING, LATERALS AND MAINS. IDENTIFICATION TAPE SHALL EXTEND TO ALL VALVE BOXES AND/OR VAULTS, EXPOSED PIPING, HYDRANTS AND QUICKCOUPLERS. NON-POTABLE WATER IS WATER SUPPLIED FROM THE POTABLE WATER SYSTEM THROUGH AN APPROPRIATE BACKFLOW PREVENTER.
• STORMWATER - ALL STORMWATER LINES SHALL BE IDENTIFIED BY CONTINUOUS LETTERING ON THREE INCH (3") MINIMUM WIDTH PURPLE TAPE WITH ONE INCH YELLOW LETTERING BEARINGTHE CONTINUOUS WORDING "CAUTION: UNTREATED STORMWATER, DO NOT DRINK, SUBSURFACE IRRIGATION" OR "CAUTION: UNTREATED STORMWATER, DO NOT DRINK" OR "CAUTION:NON-POTABLE STORMWATER, DO NOT DRINK" OR "CAUTION: ON-SITE TREATED STORMWATER, NON-POTABLE WATER, DO NOT DRINK" PERMANENTLY AFFIXED AT FIVE FOOT INTERVALS ATOPALL HORIZONTAL PIPING, LATERALS AND MAINS. IDENTIFICATION TAPE SHALL EXTEND TO ALL VALVE BOXES AND/OR VAULTS, EXPOSED PIPING AND HYDRANTS.
• EXPOSED PIPING, VALVE BOXES, VAULTS, CONTROL VALVES, QUICK COUPLING VALVES, OUTLETS AND RELATED APPURTENANCES SHALL BE COLOR CODED AND LABELED OR TAGGED TODIFFERENTIATE BETWEEN RECYCLED WATER, POTABLE WATER AND NON-POTABLE WATER SYSTEMS, I.E.,
a. "CAUTION: RECYCLED WATER DO NOT DRINK" IN BLACK OR WHITE CONTRASTING LETTERING ON A PURPLE BACKGROUND.b. "POTABLE WATER" IN BLACK LETTERING ON A BLUE OR GREEN BACKGROUND.c. "CAUTION: NON-POTABLE WATER - DO NOT DRINK" YELLOW WITH BLACK LETTERING.d. "CAUTION: NON-POTABLE STORMWATER" OR "CAUTION: ON-SITE TREATED STORMWATER, DO NOT DRINK" PURPLE BACKGROUND WITH YELLOW LETTERING.
• TAGS SHALL BE IDENTIFIED WITH THE APPROPRIATE WORDING ON BOTH SIDES. TAGS IDENTIFYING RECYCLED WATER SHALL HAVE THE APPROPRIATE WORDING ON ONE SIDE AND SYMBOLON THE OPPOSITE SIDE.
1" FLOW METER: FM-1B. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.CALSENSE
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291 Renewal Date
4/30/18Signature
4
Date
N .OC I
O
MAUR
I
E
129ARG
ENT
2/20/17
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
ROOT BARRIER2_
SCALE: NTS
FINISH GRADE
24" DEEP LINEARPOLYETHYLENE ROOTBARRIER
ROOT BALL
AMENDED BACKFILL MIX
NOTES:FOR PLANTING, REFER TOTREE PLANTING DETAIL.
24" M
IN.
3" SCH 40 PVCPERFORATED AERATIONPIPE WRAPPED WITHFILTER CLOTH ANDCAPPED. (2 EACH)
WATER BASIN - EXCEPTIN LAWN AREAS.
FINISH GRADE
PALM TRUNK TO BEPLUMB (VERTICAL),AND SKINNED(UNLESS OTHERWISENOTED IN SPECS.)
PALM ROOTBALL. PLANT 6" MIN.BELOW ORIGINAL GRADE. PRUNE -CLEAN CUT ALL ROOT ENDS.
BACKFILL: 100% WASHED #16SIEVED SAND (UNLESSOTHERWISE NOTED IN SPECS.)
8" DIA. AUGERED HOLE TOPERMEABLE LAYER (10' MAX.)BACKFILL W/ #16 SIEVED SAND.
TIE (2) SISSAL ORORGANIC TWINE TOSTABILIZE THE FRONDS &PROTECT THE HEARTTIED PRIOR TO DELIVERY.TRIM 1/3 OF FRONDS.
NOTE:-PALM IS TO BE TRIMMED, SKINNED ANDTIED BACK AT IT'S ORIGINAL LOCATIONPRIOR TO DELIVERY.
-WATER & FERTILIZE PER MAINTENANCESPECS.
-SEE SPECS FOR PERCOLATION TEST INFO.
BA
RE
TR
UN
K H
EIG
HT
(SE
E P
LAN
FO
R S
KIN
NE
D R
EQ
UIR
EM
EN
TS.)
6"R
OO
TBA
LL12
"A
UG
ER
TO
PE
RM
EA
BLE
LAY
ER
(10'
MA
X.)
3"
12" (TYPICALALL SIDES
OF SQUAREPIT.)
EQ. EQ.
PALM TREE PLANTING3_
SCALE: NTS
MANIFOLD LAYOUT5_
SCALE: NTS
LEGEND1. IRRIGATION MAINLINE
2. MAINLINE TEE FITTING, MAINLINE x MANIFOLD SIZE
3. MANIFOLD ISOLATION VALVE. REFER TO LEGEND FORTYPE. MANIFOLD SIZE
4. ALL VALVE BOXES TO HAVE A MINIMUM 12" SEPARATIONBETWEEN BOXES
5. IRRIGATION MANIFOLD "SUB-MAINLINE" PIPE. SIZE PERLARGEST LATERAL PIPE
6. REMOTE CONTROL VALVE
7. RECTANGULAR SPECIFICATION GRADE VALVE BOX.REFER TO LEGEND FOR TYPE
8. PVC SCH 80 UNION. ONE OR TWO REQUIRED. SEE RCVINSTALLATION DETAILS
9. LATERAL LINE TO SPRINKLERS
10. SIDEWALK / HARDSCAPE EDGE, INSTALL BOXES 12"-18"FROM EDGE
11. QUICK COUPLER VALVE
12. MAINLINE TEE FITTING, MAINLINE x 1-1/2" SIZE
13. QCV MANIFOLD ISOLATION BALL VALVE. REFER TOLEGEND FOR TYPE
14. QUICK COUPLER SWING JOINT
15. 10" ROUND SPECIFICATION GRADE VALVE BOX. REFER TOLEGEND FOR TYPE
FLOW METER INSTALLATION4_
SCALE: NTS
CONTROLLER ENCLOSURE1_
SCALE: NTS
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291 Renewal Date
4/30/18Signature
4
Date
N .OC I
O
MAUR
I
E
129ARG
ENT
2/20/17
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
SECTION/ELEVATIONNOTES:A. USE TEFLON TAPE ON ALL MALE THREADS WITHIN ASSEMBLY.B. USE PVC SCH 80 45 DEGREE ELLS TO TRANSITION TO MAINLINE DEPTH.C. SET TOP OF VALVE BOX 1/2" ABOVE FINISHED GRADE IN TURF AREAS.D. IN SHRUB AREAS INSTALL VALVE BOX 2" ABOVE SOIL LEVEL OR 1" ABOVE MULCH LAYER, WHICHEVER IS
HIGHER.
LEGEND1. PVC MAINLINE PIPE TO FLOW SENSOR
AS REQUIRED
2. PVC SCH 80 SLIP COUPLER, ASREQUIRED
3. 3/4" CRUSHED GRAVEL, MINIMUM 6"DEPTH
4. LANDSCAPE FABRIC
5. PVC SCH 80 UNION (2 REQ.)
6. PVC SCH 80 NIPPLE, MIN. LENGTH 3",VALVE SIZE (4 REQ.)
7. PVC SCH 80 REDUCER SLIPxTHRDBUSHING, SF, MAINLINE SIZE x VALVESIZE (2 REQ.)
8. NOMINAL SIZE SOLID BRICK (4 REQ.)
9. PVC MAINLINE PIPE FROM BACKFLOWPREVENTION DEVICE
10. FINISH GRADE
11. USE PVC SCH 80 45 DEGREE ELLS TOTRANSITION TO MAINLINE DEPTH
12. 12" RECTANGULAR SPECIFICATIONGRADE VALVE BOX WITH "T" COVER.HEAT BRAND 'MV' ON LID
13. MASTER CONTROL VALVE. REFER TOLEGEND FOR SPECIFICATION
14. CONTROL WIRES WITH WATER TIGHTSPLICES PROVIDE 24" COIL OF WIRE ATVALVE
1/2"
B
B B
B
B
PP
SECTION/ELEVATION
NOTE:A. USE TEFLON TAPE ON ALL MALE THREADS WITHIN ASSEMBLY.B. CONCRETE SLAB SHALL BE MINIMUM 4" THICK AND EXTEND A MINIMUM 6" PAST
THE BACKFLOW ASSEMBLY PIPING AND/OR ENCLOSURE ON ALL SIDES.
6" MIN.
12" MIN.
B
LEGEND1. BACKFLOW DEVICE, REFER TO LEGEND FOR
SPECIFICATION
2. BACKFLOW ENCLOSURE, REFER TO LEGEND FORSPECIFICATION
3. BRASS BALL VALVE
4. WYE STRAINER, REFER TO LEGEND FOR SPECIFICATION
5. BRASS NIPPLE, MAX. LEN. 3" (4 REQ.)
6. BRASS RISER, LEN. AS REQUIRED, (2 REQ.)
7. CONCRETE SLAB
8. IRRIGATION SERVICE LINE FROM METER
9. PVC SCH 80 SS COUPLER, SVC LINE SIZE
10. PVC SCH 80 NIPPLE, LENGTH BEYOND THRUST BLOCK,(2 REQ.)
11. CONCRETE THRUST BLOCK, 1 CU. FT.
12. PVC SCH 80 REDUCING ADAPTER, SF, COUPLER SIZE (2REQ.)
13. PVC SCH 80 SS COUPLER, MAINLINE SIZE
14. BRASS ELBOW
15. IRRIGATION MAINLINE
16. BRASS UNION (2 REQ.)
17. PRESSURE REGULATOR, IF SPECIFIED. REFER TOLEGEND FOR SPECIFICATION - IF NOT SPECIFIED,INSTALL ONE BRASS NIPPLE IN PLACE OF TWO 3"NIPPLES AND REGULATOR
SECTION/ELEVATION
LEGEND1. PVC LATERAL LINE PIPE TO ZONE
2. PVC SCH 40 SLIP COUPLER, AS REQUIRED
3. 3/4" CRUSHED GRAVEL, MIN. 5" -6" DEPTH
4. PVC SCH 80 TT UNION, SIZE PER RCV
5. REMOTE CONTROL VALVE, REFER TO LEGEND FOR SPECIFICATION
6. LANDSCAPE FABRIC
7. PVC SCH 80 MAINLINE TEE/ELL FITTING
8. PVC MANIFOLD BACKBONE MAINLINE, DEPTH PER SPECS
9. SOLID BRICK, NOMINAL SIZE (MIN. 4 REQ.)
10. PVC PIPE, MINIMUM PRESSURE RATING-315 PSI, SIZE PERIMMEDIATE DOWNSTREAM RCV LATERAL SIZE
11. PVC SCH 80 SS EL, SIZE PER #10
12. FINISH GRADE
13. RECTANGULAR SPECIFICATION GRADE VALVE BOX WITH BOLTDOWN 'T' COVER. HEAT BRAND "RCV" AND ZONE # ON LID
14. PVC SCH 80 REDUCER BUSHING, SPGxFIPT, SIZE AS REQUIRED
15. PVC SCH 80 PVC NIPPLE, RCV SIZE, MIN. LENGTH 4" (2 REQ.)
16. RCV ID TAG
17. CONTROL WIRES WITH WATER TIGHT SPLICES PROVIDE 24" COILOF WIRE AT VALVE
18. SCH 40 PVC MALE ADAPTER MIPTxSLIP, SIZE PER RCV
19. SCH 40 PVC REDUCER BUSHING, SS, SIZE AS REQUIRED
NOTES:A. USE TEFLON TAPE ON ALL MALE THREADS WITHIN ASSEMBLY.B. SET TOP OF VALVE BOX 1/2" ABOVE FINISHED GRADE IN TURF AREAS.C. IN SHRUB AREAS INSTALL VALVE BOX 2" ABOVE SOIL LEVEL OR 1" ABOVE
MULCH LAYER, WHICHEVER IS HIGHER.
6" MAX2" MIN
2"
SECTION/ELEVATION
LEGEND1. PVC SCH 80 45 DEGREE ELL
2. LANDSCAPE FABRIC
3. 3/4" CRUSHED GRAVEL, MIN. 5" -6" DEPTH
4. SOLID BRICK, NOMINAL SIZE (MIN. 4 REQ. )
5. IRRIGATION MAINLINE
6. FINISH GRADE
7. PVC SCH 80 COUPLER, SS, MAINLINE SIZE
8. PVC SCH 80 REDUCING BUSHING, SF, MAINLINE SIZE xVALVE SIZE
9. PVC SCH 80 NIPPLE, 3" LENGTH (2 REQ.)
10. BALL VALVE, REFER TO LEGEND FOR TYPE. INSTALLSHUTOFF HANDLE PERPENDICULAR TO BOX LID
11. PVC SCH 80 TT UNION, SIZE PER VALVE
12. PVC SCH 80 MALE ADAPTER
13. RECTANGULAR SPECIFICATION GRADE VALVE BOX WITH 'T'COVER. HEAT BRAND 'BV' ON LID
1/2"
NOTES:A. USE TEFLON TAPE ON ALL MALE THREADS WITHIN ASSEMBLY.B. USE 45 DEGREE ELLS TO TRANSITION TO MAINLINE DEPTH.C. INSTALL VALVE CENTERED IN BOX.D. REDUCING BUSHINGS ONLY REQUIRED WHEN VALVE IS SIZED SMALLER THAN MAINLINE.E. SET TOP OF VALVE BOX 1/2" ABOVE FINISHED GRADE IN TURF AREAS.F. IN SHRUB AREAS INSTALL VALVE BOX 2" ABOVE SOIL LEVEL OR 1" ABOVE MULCH LAYER, WHICHEVER IS
HIGHER.
8" MAX2" MIN
BACKFLOW ASSEMBLY 1_
SCALE: NTS
MAINLINE ISOLATION VALVE2_
SCALE: NTS
NOT USED3_
SCALE: NTS
RCV ASSEMBLY4_
SCALE: NTS
MASTER VALVE ASSEMBLY5_
SCALE: NTS
NOT USED6_
SCALE: NTS
3475 E. Foothill Blvd.Pasadena, CA 91107Phone: (626) 351-4664Fax: (626) 351-5291 Renewal Date
4/30/18Signature
4
Date
N .OC I
O
MAUR
I
E
129ARG
ENT
2/20/17
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
CONTROLLER GROUNDING INSTALLATION 1_
SCALE: NTS
WIRE CONNECTION3_
SCALE: NTS
PIPE/WIRE/SLEEVE INSTALLATION4_
SCALE: NTS
VALVE BOX LOCATION 5_
SCALE: NTS
C
TOP VIEW
LEGEND1. CONTROLLER ASSEMBLY
PEDESTAL
2. #6 AWG SOLID BARE COPPER WIRE
3. U.L. APPROVED 5/8"x8' COPPERGROUND ROD WITH CADWELD'ONE-SHOT' CONNECTION
4. 10" ROUND SPECIFICATION GRADEVALVE BOX
5. 4"x96" COPPER GROUND PLATE,U.L. APPROVED
PLAN VIEW
LEGEND1. 'RCV' HEAT BRANDED ON TO VALVE BOX LID
2. APPROPRIATE STATION NUMBER HEAT BRANDEDON TO VALVE BOX LID
3. RECTANGULAR SPECIFICATION GRADE VALVEBOX, TYP.
4. QUICK COUPLER VALVE BOX, TYP.
5. 'QCV' HEAT BRANDED ON TO VALVE BOX LID
PLAN VIEW
NOTES:A. CENTER VALVE BOX OVER REMOTE CONTROL
VALVE TO FACILITATE SERVICING VALVE.B. SET RCV AND VALVE BOX ASSEMBLY IN
GROUND-COVER/SHRUB AREA WHEREPOSSIBLE.
C. SET BOXES PARALLEL TO EACH OTHER ANDPERPENDICULAR TO EDGE.
D. AVOID HEAVILY COMPACTING SOIL AROUNDVALVE BOXES TO PREVENT COLLAPSE ANDDEFORMATION OF VALVE BOXES.
EDGE OFPAVING
SECTION/ELEVATION
DEPTH CHART
WIRING
6" & LARGER
3" & 4"
21/2" & SMALLER
18"
12"
- -
18"
24"
36"
BESIDE
18"
24"
36"
A B C D
36"
30"
24"
-
36"
E F
36"
36" 36"
30"30"
-MAIN MAIN
BESIDE
F
D
E
C
B
A
NOTES:A. SLEEVE UNDER PEDESTRIAN WALKWAYS
SHALL EQUAL DEPTHS INDICATED INCOLUMNS A, B, & C.
B. LINES MUST HAVE MIN. CLEARANCE OF 4"FROM EACH OTHER & 12" FROM OTHERTRADES.
C. RUN WIRING BESIDE MAINLINE ATLOCATION SHOWN, TAPE & BUNDLE @ 10'O.C.
D. TIE A 24" LOOP IN ALL WIRING ATCHANGES IN DIRECTION.
E. ALL SLEEVES MUST BE 2X THE DIAMETEROF THE PIPE WITHIN.
F. ALL SLEEVE ENDS MUST BE SEALEDWITH FOAM SEALANT INSIDE PIPE TOMINIMIZE DEBRIS INTRUSION.
G. ALL SLEEVES MUST EXTEND 12" MIN.DISTANCE PAST EDGE OF ROADWAY,CURB, OR SIDEWALK.
H. CONTRACTOR MUST ADJUST MAINLINEAROUND ALL STREET LIGHT LOCATIONS,LIGHT BOLLARDS, TREE ROOT BALLS,(MIN. 5' CLEARANCE), AND OTHEROBSTACLES.
LEGEND1. ON-GRADE LATERAL PIPE
2. UNDISTURBED SOIL
3. COMPACTED BACKFILL
4. LATERAL LINE
5. CONTROL WIRES
6. MAINLINE TRACER TAPE OR AWG#6 BARE COPPER TRACER WIRE,REFER TO LEGEND FORSPECIFICATION
7. MAINLINE, REFER TO LEGEND FORSPECIFICATION
8. ROADWAY / PAVING
9. SAND BACKFILL
10. LATERAL LINE SLEEVE
11. MAINLINE SLEEVE
12. CONTROL WIRE SLEEVE
-
CL
LEGEND1. PVC MAINLINE OR MANIFOLD SUBMAIN /
BACKBONE PIPE. SEE LEGEND FOR DEPTHAS PER SPECIFICATION
2. LANDSCAPE FABRIC, MINIMUM 4.5 OZ.MATERIAL. SEE SPECIFICATIONS FORAPPROVED TYPE
3. PVC SCH 80 SLO-CLOSE BALL VALVE,INSTALL VALVE CENTERED IN BOX. REFERTO LEGEND FOR SPECIFICATION
4. 8" PVC CL 160 PIPE OR NON-PERF DRAINPIPE, LENGTH AS REQUIRED. FIT PIPEOUTSIDE UNION. USE FABRIC TO FILLIRREGULARITIES
5. 3/4" CRUSHED GRAVEL, FILL TO 2" BELOWTOP OF SLEEVE AND 5" BELOW BALL VALVEFOR SUPPORT
6. SUPPORT BRICKS, (3 REQ.)
7. SITE SOIL
8. FINISH GRADE
9. 10" ROUND SPECIFICATION GRADE VALVEBOX WITH BOLT DOWN 'T' COVER. HEATBRAND "BV" ONTO LID.
NOTES:A. USE TEFLON TAPE ON ALL MALE THREADS WITHIN ASSEMBLY.B. SET TOP OF VALVE BOX 1/2" ABOVE FINISHED GRADE IN TURF AREAS.C. IN SHRUB AREAS INSTALL VALVE BOX 2" ABOVE SOIL LEVEL OR 1/2" ABOVE MULCH LAYER,
WHICHEVER IS HIGHER.D. CONTRACTOR TO PROVIDE ONE STANDARD 30 INCH SPRINKLER KEY WRENCH FOR THE
OPERATION OF BALL VALVES.
SECTION/ELEVATION
SECTION/ELEVATION
LEGEND1. CONTROLLER ASSEMBLY
PEDESTAL. REFER TO LEGENDFOR SPECIFICATION
2. PVC ELECTRICAL SWEEP ELL(1-½" OR LARGER)
3. #6 AWG SOLID BARE COPPERWIRE
4. U.L. APPROVED 4"x96"COPPER GROUND PLATE
5. GROUNDING ENHANCEMENTEARTH CONTACT MATERIAL.SEE NATIONAL ELECTRICCODE FOR SPECIFICATION
6. 5/8"x8' COPPER CLAD GROUNDROD, U.L. APPROVED
7. CADWELD 'ONE-SHOT'CONNECTION
8. 10" ROUND SPECIFICATIONGRADE VALVE BOX
NOTE:A. INSTALL 10" ROUND SPECIFICATION
GRADE VALVE BOX OVER RODWITH TOP OF GROUND RODEXPOSED WITH CADWELD'ONE-SHOT' CONNECTION
SIDE VIEW
SECTION/ELEVATION
LEGEND1. LOW VOLTAGE WIRES
2. POLY TUBE PRE-FILLED WITHWATERPROOF GEL
3. WIRE CONNECTOR. WIRES SHALLBE PRE-STRIPPED OF 1/2" OF THEINSULATION PRIOR TO INSERTIONINTO THE CONNECTOR. TWISTCONNECTOR ONTO WIRES TOSEAT FIRMLY.
CONTROLLER GROUNDING INSTALLATION2_
SCALE: NTS
MANIFOLD ISOLATION VALVE6_
SCALE: NTS
3475 E. Foothill Blvd.
Pasadena, CA 91107
Phone: (626) 351-4664
Fax: (626) 351-5291
ARB SUBMITTAL 3/20/2017
S a n t a M o n i c aCity of
N
0
SCALE:
10' 20' 40'
1" = 20'
BEACH
MAINTENANCE
EXTERIOR LIGHTING
(TYP).
PACIFIC COAST WAY
XSP Series Area
LED AREA
XSP1™ Area XSP2™ Area
BENEFITS
• Improved illumination performance • Significant energy and maintenance savings • Eliminate the relamping cycle • Field Adjustable Output option for increased flexibility • 10-year limited warranty
FEATURES
• Minimum 70 CRI (4000K & 5700K); 80 CRI (3000K) • CCT: 3000K (+/-300K), 4000K (+/-300K), 5700K (+/-500K) • NanoOptic® Precision Delivery Grid™ optic • Exclusive Colorfast DeltaGuard® Finish
APPLICATIONS
• Airport, auto dealership, corporate & office, education, government, healthcare, industrial & warehouse, municipal, parking, pedestrian, petroleum & convenience stores, recreation & public venues, restaurants & hospitality, retail & grocery
MAKING THE SWITCH TO LED LIGHTING IS AN EASY DECISION.Designed to replace up to 400W metal halide pole-mounted area lights, the Cree XSP Series Area light provides an excellent alternative to traditional HID lighting with superior optical control to put the light exactly where it needs to go. The XSP Area leverages Cree’s innovative technology, developed for the industry-leading XSP Series street lights, offering customers a premier area lighting solution covered by a 10-year limited warranty.
122 www.cree.com/lighting T (800) 236-6800 F (262) 504-5415
XSP Series Area
LED AREA
OSQ SERIES AREA Low-Profile Area Lighting Solutions
XSP SERIES WALL PACK Affordable Site Lighting Solutions
DPT SERIES POST-TOP LUMINAIRE Easily Convert Decorative Street Lights to LED
You May Also Be Interested In:
Poles & Tenon Options
POLE SPECIFICATION HORIZONTAL TENON OPTIONS
Dimensions
XSP1™ (SINGLE-MODULE)
XSP2™ (DOUBLE-MODULE)
23.7"(601mm)
5.1"(129mm)
9.3"(237mm)
23.7"
(601m
m)
5.1"
(129
mm)
9.3"
(237
mm)
PS Crown-Weld® Square Straight Steel Poles
PS5R Round Steel Poles
PSRV Round Tapered Steel Poles
Accessory Information
BIRD SPIKE OPTIONS* BACKLIGHT CONTROL SHIELD OPTIONS FOUR POINT MOUNTING KIT
XA-SP1BRDSPK (single-module)XA-SP2BRDSPK (double-module)
Provides 1/2 Mounting Height CutoffXA-SP1BLS (for use with single-module)XA-SP2BLS (for use with double-module)
XA-XSP4PTMNT Includes large bracket for mounting to 2" (51mm) IP, 2.375" (60mm) O.D. tenon, small bracket for mounting to 1.25" (32mm) IP, 1.66" (42mm) O.D. tenon and mounting bolts
26.2"(665mm)
4.6"(117mm)
14.5"(368mm)
26
.2"
(665m
m)
4.6"
(117mm)
14.5"
(368mm)
* Specify mounting configuration
PD-*H4 Square Internal Mount Mounts to 4" (102mm) square aluminum or steel poles
PT-*H Round External MountMounts to 2-3/8 – 3" (60 – 76mm) round aluminum or steel poles
WM-2L Wall Mount
XA-TMDA8 Direct Arm Pole Adaptor BracketMounts to 3 – 6" (76 – 152mm) round or square aluminum or steel poles
23.7"(601mm)
5.1"(129mm)
9.3"(237mm)
26.2"(665mm)
4.6"(117mm)
14.5"(368mm)
Ordering Information Example: BXSP-B-HT-2ME-A-40K-UL-SV
PRODUCT VERSION MOUNTING OPTIC INPUT POWER DESIGNATOR CCT VOLTAGE COLOR OPTIONS OPTIONS
BXSP BC
HTHorizontal Tenon
2ME*Type II Medium2LG*Type II Long3ME*Type III Medium4ME*Type IV Medium5METype V Medium5SH Type V Short
A 53W (XSP1, B)B 101W (XSP2, B)E 101W (XSP1, C)F 139W (XSP2, C)
30K3000K40K4000K57K5700K
ULUniversal120–277VUH Universal 347-480V
BK Black BZ Bronze SV Silver
MLMulti-Level N Utility Label and NEMA® Photocell ReceptacleQ9 Field Adjustable OutputRNEMA® Photocell Receptacle
123www.cree.com/lighting T (800) 236-6800 F (262) 504-5415
T (800) 236-6800 F (262) 504-5415US: lighting.cree.com/lighting
† See http://lighting.cree.com/warranty for warranty terms
T (800) 473-1234 F (800) 890-7507Canada: www.cree.com/canada
Rev. Date: V6 08/24/2016
Product DescriptionDesigned from the ground up as a totally optimized LED street and area lighting system, the XSP Series delivers incredible efficiency without sacrificing application performance. Beyond substantial energy savings and reduced maintenance, Cree achieves greater optical control with our NanoOptic® Precision Delivery Grid™ optic when compared to traditional cobra head luminaires. The XSP Series is the better alternative for traditional street and area lighting with quick payback and improved performance.Applications: Roadway, parking lots, walkways and general area spaces
Accessories
Field-Installed
Backlight Control ShieldXA-SP2BLS- Provides 1/2 mounting height cutoff
Bird SpikesXA-SP2BRDSPK
NanoOptic® Precision Delivery Grid™ optic
Made in the U.S.A. of U.S. and imported parts
CRI: Minimum 70 CRI
CCT: 3000K (+/- 300K); 4000K (+/- 300K); 5700K (+/- 500K)
Limited Warranty†: 10 years on luminaire/10 years on Colorfast DeltaGuard® finish
Performance Summary
XSP SeriesXSP2™ LED Street/Area Luminaire – Double Module – Version C
Ordering InformationExample: BXSP-C-HT-2ME-F-30K-UL-SV
BXSP C HT F
Product Version Mounting OpticInput Power Designator
CCT VoltageColor Options
Options
BXSP C HTHorizontal Tenon
2ME*Type II Medium2LG*Type II Long3ME*Type III Medium4ME*Type IV Medium
F139W
30K3000K40K4000K57K5700K
ULUniversal120-277VUHUniversal 347-480V
BKBlack BZBronze SVSilver
N-Q9 Utility Label and NEMA® Photocell Receptacle - External wattage label per ANSI C136.15 - 7-pin receptacle per ANSI C136.41 - Factory connected 0-10V dim leads - Photocell and shorting cap by others - Includes Q9 option - Refer to Field Adjustable Output spec sheet for details
Q9 Field Adjustable Output - Refer to Field Adjustable Output spec sheet for details
R NEMA® Photocell Receptacle - 7-pin receptacle per ANSI C136.41 - Factory connected 0-10V dim leads - Photocell and shorting cap by others
* Available with Backlight Shield when ordered with field-installed accessory (see table above)NOTE: Price adder may apply depending on configuration
26.2"(665mm)
4.6"(117mm)
14.5"(368mm)
Weight
24 lbs. (11kg)
T (800) 236-6800 F (262) 504-5415US: lighting.cree.com/lighting T (800) 473-1234 F (800) 890-7507Canada: www.cree.com/canada
Product Specifications
CONSTRUCTION & MATERIALS• Die cast aluminum housing
• Tool-less entry
• Mounts on 1.25" (32mm) IP, 1.66" (42mm) O.D. or 2" (51mm) IP, 2.375" (60mm) O.D. horizontal tenon (minimum 8" [203mm] in length) and is adjustable +/- 5˚ to allow for fixture leveling (includes two axis T-level to aid in leveling)
• Luminaire secures with two mounting bolts
• Exclusive Colorfast DeltaGuard® finish features an E-Coat epoxy primer with an ultra-durable powder topcoat, providing excellent resistance to corrosion, ultraviolet degradation and abrasion. Black, bronze and silver are available
• Weight: 24 lbs. (11kg)
ELECTRICAL SYSTEM• Input Voltage: 120-277V or 347-480V, 50/60Hz
• Power Factor : > 0.9 at full load
• Total Harmonic Distortion: < 20% at full load
• Class 1 driver
• Integral 10kV surge suppression protection standard
• When code dictates fusing, a slow blow fuse or type C/D breaker should be used to address inrush current
• Designed with 0-10V dimming capabilities. Controls by others
• 10V Source Current: 0.15mA
REGULATORY & VOLUNTARY QUALIFICATIONS• cULus Listed• Suitable for wet locations• Certified to ANSI C136.31-2001, 3G bridge and overpass vibration
standards• Meets CALTrans 611 Vibration testing• 10kV surge suppression protection tested in accordance with IEEE/ANSI
C62.41.2• Meets FCC Part 15, Subpart B, Class A standards for conducted and
radiated emissions • Luminaire and finish endurance tested to withstand 5,000 hours of
elevated ambient salt fog conditions as defined in ASTM Standard B 117• Meets Buy American requirements within ARRA• DLC qualified. Exceptions apply when N-Q9 or Q9 (select adjustments)
options are ordered. Please refer to www.designlights.org/QPL for most current information
• RoHS compliant. Consult factory for additional details• Dark Sky Friendly, IDA Approved when ordered with 30K CCT. Please
refer to http://darksky.org/fsa/fsa-products/ for most current information
XSP2™ LED Street/Area Luminaire – Double Module – Version C
Recommended XSP Series Version C Luminaire Lumen Maintenance Factors (LMF)1
AmbientInput Power Designator
InitialLMF
25K hrProjected2
LMF
50K hrProjected2
LMF
75K hrCalculated3
LMF
100K hrCalculated3
LMF
5˚C(41˚F) F 1.04 0.97 0.91 0.85 0.80
10˚C(50˚F) F 1.03 0.96 0.90 0.84 0.79
15˚C(59˚F) F 1.02 0.95 0.89 0.83 0.78
20˚C(68˚F) F 1.01 0.94 0.88 0.82 0.77
25˚C(77˚F) F 1.00 0.93 0.87 0.81 0.76
1 Lumen maintenance values at 4000K and 25˚C (77˚F) are calculated per TM-21 based on LM-80 data and in-situ luminaire testing2 In accordance with IESNA TM-21-11, Projected Values represent interpolated value based on time durations that are within six times (6X) the IESNA LM-80-08 total test duration (in hours) for the device under testing ((DUT) i.e. the packaged LED chip)3 In accordance with IESNA TM-21-11, Calculated Values represent time durations that exceed six times (6X) the IESNA LM-80-08 total test duration (in hours) for the device under testing ((DUT) i.e. the packaged LED chip)
Electrical Data*
Input PowerDesignator
System Watts120-277V
System Watts347-480V
Total Current (A)
120V 208V 240V 277V 347V 480V
F 139 135 1.22 0.68 0.59 0.52 0.40 0.29
* Electrical data at 25˚C (77˚F). Actual wattage may differ by +/- 10% when operating between 120-480V +/- 10%
T (800) 236-6800 F (262) 504-5415US: lighting.cree.com/lighting T (800) 473-1234 F (800) 890-7507Canada: www.cree.com/canada
PhotometryAll published luminaire photometric testing performed to IESNA LM-79-08 standards by a NVLAP accredited laboratory. To obtain an IES file specific to your project consult: http://lighting.cree.com/products/outdoor/street-and-roadway/xsp-series-1
XSP2™ LED Street/Area Luminaire – Double Module – Version C
2LG
BXSP-C-**-2LG-F-30K-ULMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 11,134Initial FC at grade
80' 80'
20'
20'
40'
0m
6.1
6.1
12.2
12.2
40' 40'60' 60'20' 20'0'
12.218.3 6.1 0m 6.1 12.2 18.324.4 24.4
0'
40'
30.5 30.5 36.636.642.7 42.7
100' 100'120' 120'140' 140'
18.3
18.3
60'
24.4
24.4
80'
80'
60'
Position of vertical planeof maximum candlepower.
1
CURB LINE
.5
80˚
.2.1 2
BXSP-C-**-2ME-F-30K-UL w/XA-SP2BLSMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 9,543Initial FC at grade
.5.1 .2 21
60˚80'
20'
20'
40'
6.1
0m
6.1
12.2
40'60' 20' 0' 20' 40' 60'
12.218.3 6.1 0m 6.1 12.2 18.3
80'
24.4 24.4
0'
40' 12.2
30.5 30.5
100' 100'18.360'
Position of vertical planeof maximum candlepower.
18.360'
CURB LINE
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type II Medium w/BLS Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 9,543 B1 U0 G2 11,643 B2 U0 G2 12,215 B2 U0 G2
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type II Medium Distribution
Input PowerDesignator
3000K 4000K 5700K
Initial Delivered Lumens*
BUGRatings** Per TM-15-11
Initial Delivered Lumens*
BUGRatings** Per TM-15-11
Initial Delivered Lumens*
BUG Ratings** Per TM-15-11
F 11,256 B2 U0 G2 13,732 B2 U0 G2 14,408 B3 U0-G2
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type II Long w/BLS Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 8,197 B1 U0 G2 10,001 B2 U0 G2 10,493 B2 U0 G2
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type II Long Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 11,134 B2 U0 G2 13,583 B3 U0 G3 14,251 B3 U0 G3
CESTL Test Report #: PL04154-001BXSP-C-**-2LG-E-30K-ULInitial Delivered Lumens: 6,944
2580
5161
7741
10322150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
RESTL Test Report #: PL06675-002BXSP-C-**-2ME-E-40K-UL w/XA-SP1BLSInitial Delivered Lumens: 7,078
1921
3843
5764
7686150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
BXSP-C-**-2ME-F-30K-ULMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 11,256Initial FC at grade
.5.1 .2 21
60˚80'
20'
20'
40'
6.1
0m
6.1
12.2
40'60' 20' 0' 20' 40' 60'
12.218.3 6.1 0m 6.1 12.2 18.3
80'
24.4 24.4
0'
40' 12.2
30.5 30.5
100' 100'18.360'
Position of vertical planeof maximum candlepower.
18.360'
CURB LINE
CESTL Test Report #: PL04155-001BXSP-C-**-2LG-E-30K-UL w/XA-SP1BLSInitial Delivered Lumens: 5,302
2556
5111
7667
10233150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
BXSP-C-**-2LG-F-30K-UL w/XA-SP2BLSMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 8,197Initial FC at grade
80' 80'
20'
20'
40'
0m
6.1
6.1
12.2
12.2
40' 40'60' 60'20' 20'0'
12.218.3 6.1 0m 6.1 12.2 18.324.4 24.4
0'
40'
30.5 30.5 36.636.642.7 42.7
100' 100'120' 120'140' 140'
18.3
18.3
60'
24.4
24.4
80'
80'
60'
Position of vertical planeof maximum candlepower.
1
CURB LINE
.5
80˚
.2.1 2
2ME
RESTL Test Report #: PL06675-001BXSP-C-**-2ME-E-40K-ULInitial Delivered Lumens: 8,850
1951
3902
5852
7803150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
T (800) 236-6800 F (262) 504-5415US: lighting.cree.com/lighting T (800) 473-1234 F (800) 890-7507Canada: www.cree.com/canada
PhotometryAll published luminaire photometric testing performed to IESNA LM-79-08 standards by a NVLAP accredited laboratory. To obtain an IES file specific to your project consult: http://lighting.cree.com/products/outdoor/street-and-roadway/xsp-series-1
XSP2™ LED Street/Area Luminaire – Double Module – Version C
3ME
BXSP-C-**-3ME-F-30K-ULMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 11,011Initial FC at grade
.5
.1 .2
2
1
45˚
80'80'
20'
20'
40'
6.1
0m
6.1
12.2
40'60' 20' 0' 20' 40' 60'
12.218.3 6.1 0m 6.1 12.2 18.3
80'
24.4 24.4
24.4
0'
40' 12.230.5 30.5
100' 100'
18.360'
Position of vertical planeof maximum candlepower.
CURB LINE
4ME
BXSP-C-**-4ME-F-30K-ULMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 11,134Initial FC at grade
0m6.1 18.312.2
30.5
18.3
18.3
24.4
24.4
0m0'
6.120'
6.120'
60'
80'
100'
12.240'
12.240'
60'
40'
18.3
60' 20'
12.2
40'
6.1
20'0' 60'
24.4
80'
24.4
80'
Position of vertical planeof maximum candlepower.
80'
100'30.5 30.5
30.5
100'100'
.1
.2
45˚
.5
1
2
CURB LINE
CESTL Test Report #: PL04094-001BXSP-C-**-3ME-F-30K-UL w/XA-SP2BLSInitial Delivered Lumens: 9,009
1644
3289
4933
6577150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
BXSP-C-**-3ME-F-30K-UL w/XA-SP2BLSMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 9,176Initial FC at grade
.5.1
.22
1
45˚
80'80'
20'
20'
40'
6.1
0m
6.1
12.2
40'60' 20' 0' 20' 40' 60'
12.218.3 6.1 0m 6.1 12.2 18.3
80'
24.4 24.4
24.4
0'
40' 12.230.5 30.5
100' 100'
18.360'
Position of vertical planeof maximum candlepower.
CURB LINE
CESTL Test Report #: PL04092-001BXSP-C-**-4ME-E-30K-UL w/XA-SP1BLSInitial Delivered Lumens: 5,530
1364
2728
4092
5456150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
BXSP-C-**-4ME-F-30K-UL w/XA-SP2BLSMounting Height: 25' (7.6m) A.F.G.Initial Delivered Lumens: 8,687Initial FC at grade
0m6.1 18.312.218.3
18.3
0m0'
6.120'
6.120'
60'
24.480'
12.240'
12.240'
60'
40'
18.3
60' 20'
12.2
40'
6.1
20'0' 60'
24.4
80'
24.4
80'
.2.1
Position of vertical planeof maximum candlepower.
45˚
1
.5
30.5100'
CURB LINE
2
CESTL Test Report #: PL04093-001BXSP-C-**-3ME-F-30K-ULInitial Delivered Lumens: 10,671
1676
3352
5029
6705150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type III Medium w/BLS Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings**
Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 9,176 B2 U0 G2 11,195 B2 U0 G2 11,746 B2 U0 G2
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type III Medium Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 11,011 B2 U0 G2 13,434 B3 U0 G2 14,095 B3 U0 G2
CESTL Test Report #: PL04091-001BXSP-C-**-4ME-E-30K-ULInitial Delivered Lumens: 6,923
1390
2780
4171
5561150˚
120˚ 120˚
60˚
90˚ 90˚
60˚
30˚
150˚
Candlepower Trace: Vertical plane throughhorizontal angle of maximum candlepower.
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type IV Medium w/BLS Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings**
Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 8,687 B1 U0 G2 10,598 B2 U0 G2 11,119 B2 U0 G2
* Initial delivered lumens at 25˚C (77˚F). Actual production yield may vary between -10 and +10% of initial delivered lumens** For more information on the IES BUG (Backlight-Uplight-Glare) Rating visit: www.ies.org/PDF/Erratas/TM-15-11BugRatingsAddendum.pdf. Valid with no tilt
Type IV Medium Distribution
Input PowerDesignator
3000K 4000K 5700K
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
InitialDeliveredLumens*
BUGRatings** Per TM-15-11
F 11,134 B2 U0 G2 13,583 B3 U0 G3 14,251 B3 U0 G3
T (800) 236-6800 F (262) 504-5415US: lighting.cree.com/lighting
© 2016 Cree, Inc. and/or one of its subsidiaries. All rights reserved. For informational purposes only. Content is subject to change. Patent www.cree.com/patents. Cree®, NanoOptic®, and Colorfast DeltaGuard® are registered trademarks, and the Cree logo, Precision Delivery Grid™ and XSP2™ are trademarks of Cree, Inc. The UL logo is a registered trademark of UL LLC. NEMA® is a registered trademark of the National Electrical Manufacturers Association. The DLC QPL logo is a registered trademark of Northeast Energy Efficiency Partnerships, Inc.
T (800) 473-1234 F (800) 890-7507Canada: www.cree.com/canada
XSP2™ LED Street/Area Luminaire – Double Module – Version C
Luminaire EPA
Horizontal Tenon Mount – Weight: 24 lbs. (11kg)
Single 2 @ 90˚ 2 @ 180˚ 3 @ 90˚ 4 @ 90˚
Tenon Configuration If used with Cree tenons, please add tenon EPA with luminaire EPA
PD-1H4; PT-1H PD-2H4(90); PT-2H(90) PD-2H4(180); PT-2H(180) PD-3H4(90); PT-3H(90) PD-4H4(90); PT-4H(90)
0.69 1.14 1.38 1.83 2.28
Tenons and Brackets‡ (must specify color)
Square Internal Mount Horizontal Tenons (Aluminum)- Mounts to 4" (102mm) square aluminum or steel polesPD-1H4 – Single PD-3H4(90) – 90˚ TriplePD-2H4(90) – 90˚ Twin PD-4H4(90) – 90˚ QuadPD-2H4(180) – 180˚ Twin
Wall Mount Brackets- Mounts to wall or roofWM-2L – Extended Horizontal
Round External Mount Horizontal Tenons (Aluminum)- Mounts to 2.375"-3" (60-76mm) O.D. round aluminum or steel poles or tenons- Mounts to 3" (76mm), 5" (127mm), or 6" (152mm) square pole with PB-1A* tenonPT-1H – Single PT-3H(90) – 90˚ TriplePT-2H(90) – 90˚ Twin PT-4H(90) – 90˚ QuadPT-2H(180) – 180˚ Twin
Direct Arm Pole Adaptor Bracket - Mounts to 3-6" (76-152mm) round or square aluminum or steel polesXA-TMDA8
Tenon EPA
Part Number EPA
PD Series Tenons 0.09
PT Series Tenons 0.10
WM-2L 0.13
XA-TMDA8 0.19
‡ Refer to the Bracket and Tenons spec sheet for more details* Specify pole size: 3 (3"), 5 (5"), or 6 (6") for single, double or triple luminaire orientation or 5 (5") or 6 (6") for quad luminaire orientation