Process cooling with CO2 at Mack`s new brewery in Norway

Upload: buidat

Post on 04-May-2018

219 views

Category:

Documents


2 download

TRANSCRIPT

Process cooling with CO2

at Mack`s new brewery in

Norway

MACK BEER BREWERY - NEW BREWERY 2012

In operation since Dec 2012

Production premises 16800m2

Production of mineral water lemonade and beer

MACK BEER BREWERY – PRODUCTION AND ENERGY

100 000hl/year,

Energy consumption:

11.3GWh/year

200 000hl/year

50% energy sawing!

Energy efficient chillers

Heat recovery

PRODUCTION PROCESS - BEER

Flavour

addition

Wort

evaporation

Wort

cooling Frementation

Fast

cooling

Storing Filtration Pastaurisation Tapping Storing

+ high demand for hot tap water

Heat recovery to

Tap water 70C

Ventilation ~45C

CHOICE OF SYSTEM: NH3 / CO2

Bad experience of prewious NH3 plant:

high NH3 charge, leakage

Re-use existing fermentation tanks

High demand for hot tap water

Brine solution

Transcritical CO2

COOLING PLANT

2 x CO2 transcritical

chillers

Total cooling capacity ~

500Kw

Brine -4/-8C (33%MPG)

Air cooled gas coolers

Heat recovery: tap water

and ventilation

HEAT RECOVERY

Planning/Co-ordination

Grant good functionality for each of the connected systems

Tap water

Ventilation

Gas cooler

Nominal capacity

Tap water

Tap water

Gas cooler

Air

Ventilation

Heating water

Tem

pera

ture

(C

)

PRE-PROJECT STUDY

High peak load

Complex heat recovery

ENOVA Innovasjon

Norge >2.5MNOK

Hours

Cooling demand

winter

Cooling demand

summer

Dail

y p

eak l

oad

(k

w)

Dail

y p

eak l

oad

(k

w)

TECHNICAL ROOM

CHILLERS

EXPERIENCE SO FAR:

COP~3 to 6

«Low» COP cooling= high

COP combined

Gas c

oo

ler

pre

ssu

re (

Bars

)

Time (h)

GC pressure

VARIABLE LOAD F

req

uen

cy (

Hz)

Time (h)

Time (h)

Fre

qu

en

cy (

Hz)

VARIABLE LOAD F

req

uen

cy (

Hz)

Time (h)

Time (h)

~340kW

Fre

qu

en

cy (

Hz)

Time (h)

Te

mp

era

ture

(C

)

Treturn brine

Toutlet brine

Tevap

~340kW

3X5M3 STORAGE TANKS BRINE

EFFECTIVE ACCUMULATION

T retur >30C!

~2C variation

on outlet

26 Days

Set point

change

40C

-10C

HEAT RECOVERY WITH INCREASED PRESSURE

Several factors has impact on high pressure Heat recovery tap water

Heat recovery ventilation

Ambient temperature

Demanding to fulfill all needs!

Tap water

Ventilation

Tem

pera

ture

(C

)

Gas p

ressu

re (

Bar)

Tout Compressor

Tout Tap water

Tout Heating

Gas pressure

Time (h)

RECOVERED HEAT SINCE START

Tap water 170 000 kWh

Ventilation 300 000 kWh

SUMMARY

Operation without any major problems

Low energy consumtion

High energy recovery

Satisfied customer

Satisfied installer