1 1 Probabilistic Framework for Onboard Fire Safety Reliability and Effectiveness Models of Passive and Active Fire Safety Systems (D1.3) Philipp Lohrmann (BMT), Apurba Kar (IRS), Antoine Breuillard (BV) BMT - document author - - organisation name - Kostas Spyrou 4.0 - document approved by - - revision number - 13 January 2011 PU - submission date - - distribution level -

Upload: others

Post on 23-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

1

1

Probabilistic Framework for Onboard Fire Safety

Reliability and Effectiveness Models of Passive and Active Fire Safety Systems (D1.3)

Philipp Lohrmann (BMT), Apurba Kar (IRS), Antoine Breuillard (BV) BMT

- document author - - organisation name -

Kostas Spyrou 4.0

- document approved by - - revision number -

13 January 2011 PU

- submission date - - distribution level -

Page 2: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

2

2

Document history

Revision number Date Remarks

1.0 24/07/2009 Skeleton document

2.0 13/10/2010 Final draft for revision by partners

3.0 26/10/2010 Final version

4.0 13/01/2011 Revised version

Page 3: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

3

3

Contents

1 Introduction ............................................................................................................................ 6

1.1 Overview ............................................................................................................................ 6

1.2 Current SOLAS regulations for passenger ships ......................................................... 7

1.2.1 Essential systems in SOLAS Chap II-2 Part C ..................................................... 8

1.2.2 Emergency procedures .......................................................................................10

1.3 Objectives ........................................................................................................................14

2 Analysis of Fire Safety Systems ..........................................................................................15

2.1 Automatic Fire Detection Systems ..............................................................................15

2.1.1 System set-up .........................................................................................................15

2.1.2 Smoke Detector .....................................................................................................19

2.1.3 Heat detector ..........................................................................................................20

2.1.4 Fault tree analysis of a Detector System ............................................................22

2.2 Sprinkler Systems ............................................................................................................27

2.2.1 System set-up .........................................................................................................28

2.2.2 Sprinkler Types and their working principles ....................................................30

2.2.3 Regulatory requirements (Reference FSS code) ................................................34

2.2.4 Fault tree analysis of a Sprinkler System ............................................................36

2.3 Water Mist Systems ........................................................................................................36

2.3.1 System set-up .........................................................................................................36

2.3.2 Fault tree analysis of a Water Mist System/Hi-Fog System ............................40

2.4 CO2 Systems ....................................................................................................................40

2.4.1 System set-up .........................................................................................................40

2.4.2 Fault tree analysis of a CO2 system ....................................................................43

Page 4: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

4

4

2.5 Foam Systems .................................................................................................................43

2.5.1 System set-up .........................................................................................................43

2.5.2 Fault tree analysis of a Foam System ..................................................................48

3 Reliability model of detection and suppression systems ................................................49

3.1 The generic model ..........................................................................................................49

3.2 Propagation of error .......................................................................................................50

3.3 Maintenance intervals ....................................................................................................50

3.4 Application to concrete systems ...................................................................................51

3.4.1 Heat detector ..........................................................................................................51

3.4.2 Photoelectric Smoke Detector ............................................................................52

3.4.3 Ionisation Smoke Detector ..................................................................................54

3.4.4 Detector panel........................................................................................................55

3.4.5 Sprinkler system .....................................................................................................57

3.4.6 Foam System ..........................................................................................................58

3.4.7 Water Mist System .................................................................................................60

3.4.8 Hi-Fog System .......................................................................................................61

3.4.9 CO2 System ............................................................................................................63

4 Conclusions ..........................................................................................................................65

5 References .............................................................................................................................66

Appendix - Fault trees and diagrams used in the failure rate analysis ..................................68

Page 5: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

5

5

Executive summary

A ship fire is a complex scenario that depends on a large range of parameters. While the location and cause of the fire are crucial, the sequence of events immediately after the ignition is of equal importance. In particular, the reaction of the crew and the influence of the fire suppression systems decide whether or not the fire escalates to dangerous proportions. To realistically model a ship fire, it is important to have a quantitative measure for the influence of these factors.

We present a methodology to analyse the reliability of fire suppression systems. For a given (constant) failure rate, we use an exponential curve to describe the reliability as a function of time. The domain of this curve is given by the maintenance interval of the system.

To determine the failure rate of each system, we refer to historical data if possible. In case such data is not available, we perform a detailed fault tree analysis of the system, taking into account redundancies and manual actions. The failure rate derived in this way is then used as input for the exponential model.

For each system, we compute the average and standard deviation of the reliability over the maintenance interval. These figures might be referred to in subsequent scenario analyses carried out later in the project.

Page 6: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

6

6

1 Introduction

1.1 Overview

Although the days of wooden ships are long gone, fire remains one of the most dangerous threats to seafaring vessels. In fact, accident statistics (Figure 1) show that fire is the most frequent incident on cruise ships, outstripping collisions and grounding.

Figure 1- Most frequent hazards on passenger ships (1)

Since 1970, the size of cruise ships has roughly doubled every decade, with the latest generation – the Oasis or Genesis class (2) – carrying over 5,000 passengers. This dramatic increase in size poses new challenges for the avoidance and mitigation of fire risk.

To the present day, fire safety regulations, including SOLAS (3), have been based on prescribed designs and performance based approaches. The weakness of this methodology is twofold: (i) it does not provide a systematic framework for testing fire scenarios and (ii) it might be too rigid to accommodate novel designs.

The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package 1 (WP1) is to systematically generate fire scenarios based on the set up of the vessel, including space type and fire safety systems. Each of these scenarios comes with a probability that determines its weight in the risk analysis. The total fire risk of the ship is then given by

𝑅 = 𝑝𝑖

𝑖∈𝜎

× 𝐶𝑖

Page 7: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

7

7

where 𝜎 denotes the set of all scenarios, 𝑝𝑖 is the probability for scenario 𝑖, and 𝐶𝑖 is a measure of the consequences (or cost) of this scenario (e.g. loss of life). In theory, this sum runs over all possible scenarios. In practice, however, it is impossible to consider all scenarios, and hence one has to preselect. In particular, all scenarios with low probability and low cost would be excluded.

These scenarios constitute the input for the fire and evacuation models developed under work package 2, which in turn will be used for benchmarking in work package 3.

1.2 Current SOLAS regulations for passenger ships

The IMO convention SOLAS Chap II-2 (see (3)) has been one of the first maritime chapters to be rewritten (December 1996 Amendments) in a goal based manner and with support of a Fire Test Procedures code. The goals and functional requirements are given in the first place. Then the sub-sections are given.

The fire safety objectives of SOLAS Chapter II-2 are to:

prevent the occurrence of fire and explosion;

reduce the risk to life caused by fire;

reduce the risk of damage caused by fire to the ship, its cargo and the environment;

contain, control and suppress fire and explosion in the compartment of origin;

provide adequate and readily accessible means of escape for passengers and crew.

In order to achieve the fire safety objectives, the following functional requirements are embodied in the regulations of Chapter II-2 as appropriate

division of the ship into main vertical and horizontal zones by thermal and structural boundaries;

separation of accommodation spaces from the remainder of the ship by thermal and structural boundaries;

restricted use of combustible materials;

detection of any fire in the zone of origin;

containment and extinction of any fire in the space of origin;

protection of means of escape and access for fire fighting;

ready availability of fire-extinguishing appliances; and

minimization of possibility of ignition of flammable cargo vapour

As mentioned above, the fire risk is composed of a frequency of ignition and a consequent severity. The frequency of ignition can be reduced by the prevention of fire ignition and several theoretical possibilities exist (See (4)). The severity is in fact a probabilistic distribution of severity depending on the random nature of activation and efficiency of fire safety systems as well as the random nature of the protection of persons.

Page 8: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

8

8

SOLAS ChapII-2 provides the minimum rules to decrease the frequency of ignition onboard in the second part B (Prevention of fire and explosion), to manage the fire in the third part C (Suppression of fire) and finally to manage the exposed with the fourth part D (Escape). Ro-ro passenger ships have special requirements included in Part G (Special requirements for the protection of vehicles, special category spaces and ro-ro spaces).

In this part, the interest is to exemplify part C with essential systems mandatory onboard passenger ships, including Ro-Pax vessels. The emergency procedures requirements are also presented.

1.2.1 Essential systems in SOLAS Chap II-2 Part C

1.2.1.1 Detection and alarm (Regulation 7)

Smoke detection in service spaces, control stations and accommodation spaces, including corridors, stairways and escape routes within accommodation spaces. Smoke detectors need not be fitted in private bathrooms and galleys and in spaces having little or no fire risk. (regulation 7-5.2)

Manually operated call points throughout the accommodation spaces, service spaces and control stations. (regulation 7-7)

An efficient patrol system shall be maintained so that an outbreak of fire may be promptly detected (Regulation 7-8)

Fire detection alarms for the systems required by paragraph 5.2 centralized in a continuously manned central control station (regulation 7-9)

1.2.1.2 Control of smoke spread (Regulation 8)

Release of smoke from machinery spaces

Draught stops. Air spaces enclosed behind ceilings, panelling or linings shall be divided by close-fitting draught stops spaced not more than 14m apart. In the vertical direction, such enclosed air spaces, including those behind linings of stairways, trunks, etc., shall be closed at each deck. (regulation 8-4)

Atriums equipped with a smoke extraction system. The smoke extraction system shall be activated by the required smoke detection system and be capable of manual control. The fans shall be sized such that the entire volume within the space can be exhausted in 10 min or less.

1.2.1.3 Containment of fire (Regulation 9)

Main vertical zones bounded by "A-60" class divisions. (regulation 9-2.2.1)

Bulkheads within a main vertical zone required to be "A" class divisions shall be at least "B" class or "C" class divisions as prescribed in the tables in regulation 9- 2.2.3 (regulation 9-2.2.2)

Protection of stairways and lifts in accommodation area as per regulation 9-2.2.5

Penetrations in fire-resisting divisions and prevention of heat transmission as per regulation 9-3

Openings in bulkheads and decks in passenger ships as per regulation 9-4.1

Ventilation systems as per regulation 9-7 Among others, the ventilation fans shall be so disposed that the ducts reaching the various spaces remain within the main

Page 9: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

9

9

vertical zone; and stairway enclosures shall be ventilated and served by an independent fan and duct system which shall not serve any other spaces in the ventilation systems

1.2.1.4 Fire fighting (Regulation 10)

Automatic sprinkler, fire detection and fire alarm system in all control stations, accommodation and service spaces, including corridors and stairways. Alternatively, control stations, where water may cause damage to essential equipment, may be fitted with an approved fixed fire-extinguishing system of another type. Spaces having little or no fire risk such as voids, public toilets, carbon dioxide rooms and similar spaces need not be fitted with an automatic sprinkler system.

Water supply systems, portable fire extinguishers, Fixed fire-extinguishing systems, Fire-fighter's outfits as per regulation 10

1.2.1.5 Structural integrity (Regulation 11)

The hull, superstructures, structural bulkheads, decks and deckhouses shall be constructed of steel or other equivalent material (regulation 11-2)

1.2.1.6 Protection of vehicles, special category and ro-ro spaces (Regulation 20)

Detection should take into account the effect of ventilation of those spaces

Sample extraction smoke detection systems may be used

Special category spaces shall be patrolled

Structural fire protection insulation should be A60 all around the spaces except when spaces of category (5), (9) and (10) are on the other side

sealable ro-ro spaces : CO2 or inert gas or high expansion foam as per resolution A123 (V) MSC.1/ Circ 1272

other : water spraying system as per resolution A123 (V) MSC.1/ Circ 1272

scuppers and possibly drainage/pumping

Portable fire extinguishers

1.2.1.7 Casualty threshold, safe return to port and safe areas (Regulation 21) and Design criteria

for systems to remain operational after a fire casualty (Regulation 22)

For new ships of 120m in length or having three or more fire zones the new regulation II-2 reg. 21 applies:

Definition of casualty threshold defined as the loss of any space of origin of fire up to the nearest A class boundaries being part of the space if fitted with a fixed fire fighting system (sprinklers) or being part of the adjacent spaces otherwise.

Safe return to port if fire breaks out but no casualty threshold is exceeded: a list of systems should remain operational and safe areas should be designed to accommodate the passengers.

Design criteria for systems if fire breaks out and one casualty threshold is exceeded in one MVZ: listed FSSs should be so arranged and segregated as to remain operational during 3 hours in other MVZs and so that the orderly evacuation and abandonment of the ship is possible.

Page 10: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

10

10

1.2.2 Emergency procedures

1.2.2.1 General

Emergency procedures are of primary importance with regards to safety. An effort was undertaken to identify systems required with respect to an emergency situation. In the following, II-2 means SOLAS Chapter II-2; FSS/n Fire Safety Code Chapter n, and LSA/n Life Saving Appliances Code Chapter n.

1.2.2.2 Detection and alarm

Fire detection and fire alarm systems, according to SOLAS Chapter II-2 and FSS Code, rely on fixed fire detection (smoke detection and manual operated call point) and automatic sprinkler. The requirements are mainly encapsulated in:

SOLAS Chapter II-2 Regulation 7 – Detection and alarm

SOLAS Chapter II-2 Regulation 10 – Fire fighting

FSS Code Chapter 8 - Automatic sprinkler, fire detection and fire alarm systems

FSS Code Chapter 9 - Fixed fire detection and fire alarm systems

The following tables summarises main requirements related to fire detection and fire alarm systems. More details, as well as technical implementations, are described in the next chapter.

Smoke Manual Operated Call Point

Sprinkler

Location II-2/7-5.2 In service spaces, control stations and accommodation spaces, including corridors, stairways, escape routes within accommodation spaces and ro-ro spaces (II-2/20.4.1)

II-2/7-7 Throughout the accommodation spaces, service spaces, control stations and ro-ro spaces (II-2/20.4.3.2)

II-2/10-6.1.1 In all control stations, accommodation and service spaces, including corridors and stairways

Section FSS9/2.4.1.1 Grouped into sections

System with individually identifiable fire detectors: a section may serve spaces on both sides of the ship and on several decks, but shall not be situated in more than one main vertical zone.

FSS9/2.4.1.1

Grouped into sections

FSS8/2.4.2.1 Grouped into separate sections.

Each of which shall contain not more than 200 sprinklers. Shall not serve more than two decks and shall not be situated in more than one main vertical zone.

System control: Indication

FSS9-2.5.1.1 Visual and audible fire signal at the control panel and indicating units.

As per smoke

FSS8/2.5.2. Visual and audible alarm signal automatically at one or

Page 11: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

11

11

signal

more indicating units

System control: location

FSS9

/2.5.1.2 The control panel: on the navigation bridge or in the continuously manned central control station.

/2.5.1.3 Indicating unit:

- At least one, be so located that it is easily accessible to responsible members of the crew at all times.

- One be located on the navigation bridge if the control panel is located in the main fire control station.

Ditto FSS8/2.5.2. On the navigation bridge or in the continuously-manned central control station.

In addition, in a position other than on the aforementioned spaces to ensure that the indication of fire is immediately received by the crew.

System control: identification

FSS9/2.5.1.3 Indicating units shall, as a minimum, denote the section.

Ditto FSS8/2.5.2. units shall indicate in which section served by the system a fire has occurred

Table -1: Alarm and indication

In addition, a fire patrol shall be maintained so that an outbreak of fire may be promptly detected (II-2/7-8-1).

1.2.2.3 Control and monitoring of systems

General

Active fire protection systems should be controlled and monitored. On passenger ships, this is mainly centralized in a continuously manned central control station (CMCCS). According to SOLAS Chapter II-2 Regulation 3 ―Definition‖:

Continuously manned central control station is a central control station which is continuously manned by a responsible member of the crew

Central control station is a control station in which the following control and indicator functions are centralized:

1. fixed fire detection and fire alarm systems; 2. automatic sprinkler, fire detection and fire alarm systems; 3. fire door indicator panels; 4. fire door closure; 5. watertight door indicator panels; 6. watertight door closures;

Page 12: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

12

12

7. ventilation fans; 8. general/fire alarms; 9. communication systems including telephones; and 10. microphones to public address systems.

Control stations are those spaces in which the ship's radio or main navigating equipment or the emergency source of power is located or where the fire recording or fire control equipment is centralized. Spaces where the fire recording or fire control equipment is centralized are also considered to be a fire control station.

Additionally, new ChapII-2 reg. 23 imposes New Passenger ships (>1st July 2010) to have one safety centre be part or be close to the navigation bridge and should

1. be ergonomic 2. have communication means with CMCCSs, bridge, storage rooms for FSSs and fire

equipment lockers 3. be capable to control and monitor of functionalities of FSSs:

all powered ventilation systems;

fire doors;

general emergency alarm system;

public address system;

electrically powered evacuation guidance systems;

watertight and semi-watertight doors;

indicators for shell doors, loading doors and other closing appliances;

water leakage of inner/outer bow doors, stern doors and any other shell door;

television surveillance system;

fire detection and alarm system;

fixed fire-fighting local application system(s);

sprinkler and equivalent systems;

water-based systems for machinery spaces;

alarm to summon the crew;

atrium smoke extraction system;

flooding detection systems; and

fire pumps and emergency fire pumps.

Control and monitoring from the continuously manned central control station

In addition to previously discussed requirements on fire detection alarms, according to II-2/9-3 Passenger ships carrying more than 36 passengers shall have the fire detection alarms centralized in a continuously manned central control station. The following table summarises control and monitoring requirements for ventilation fans and fire doors.

Ventilation fan Fire door

Location II-2/9-7.4.2 In general, ducts should remain in the MVZ

MVZ

Stairway enclosure

Page 13: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

13

13

Separated system for stairway enclosures and dangerous areas

Galley boundaries

Ro-ro spaces boundaries

CMCCS Control II-2/7-9.3 Remote shutting down II-2/7-9.3 Remote closing and be capable of reactivation

CMCCS Indicator – Control panel

II-2/7-9.3 closed or off status II-2/7-9.3 & II-2/9-4.1.1.4.6 Open or closed positions

Other requirements

II-2/5-2.1.3 Controls so grouped that that all fans may be stopped from either of two separate positions

II-2/9-4.1.1.4.5 A door closed remotely from the central control station shall be capable of being re-opened from both sides of the door by local control. After such local opening, the door shall automatically close again

Table -2: Control and monitoring: ventilation fans and fire doors

Other Control and monitoring

The following systems could also been controlled and/or monitored from the CMCCS.

Fire damper

II-2/9-4.1.1.8

Smoke extraction system

II2/8-5

Location Where it is necessary that a ventilation duct passes through a main vertical zone division, a fail-safe automatic closing fire damper shall be fitted adjacent to the division

II/9-7.3 Ducts with a free cross-sectional area exceeding 0.075m2 shall be fitted with fire dampers through "A" class bulkheads or decks

Atrium

Control Fail-safe automatic

Be capable of being manually closed from each side of the division

By the required smoke detection system (*)

Be capable of manual control

Indicator Shall be fitted on at least one side of the division with a visible indicator showing whether the damper is in the open position

Table -3: Control and monitoring: Fire damper and smoke extraction system

(*) According to IMO MSC/Circ.1034 (see (5)): ―Guidelines for smoke control and ventilation systems for internal assembly stations and atriums on new passenger ships‖, ―The automatic activation of the smoke extraction system, by means of the smoke detectors, may be delayed for up to 2 min from the activation of the first detector, if not

Page 14: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

14

14

acknowledged. This 2 minute delay is intended to allow for crew verification of the smoke detector alarm‖. This Circular is not a mandatory text but should be brought to the attention of interested parties.

1.3 Objectives

As stated above, the aim of work package 1 is to create a methodology for the systematic generation of fire scenarios and their incident probabilities. The aim of task 1.3 is to develop a probabilistic model for the reliability and effectiveness of active and passive Fire Safety Systems (FSS). In this context, active FSS are any systems that are activated in the event of a fire and include detection systems (smoke and heat detectors), automatic

suppression systems (sprinklers, 𝐶𝑂2 systems etc) as well as any manual measures. In contrast, passive FSS include structural features like fire walls and fire doors. The analysis done within this task focuses on the reliability of automatic FSS. A methodology is developed that can in principle applied to any system, provided that its setup is known and the failure rates of its components are available. We will analyse the following systems:

Smoke detectors;

Heat detector;

Alarm panel/detector system;

Sprinkler;

Foam system;

Water mist system and Hi-Fog system;

𝐶𝑂2 system. For each system, we perform fault tree analyses as necessary and express the reliability as a function of time over the maintenance interval.

Page 15: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

15

15

2 Analysis of Fire Safety Systems

An important part of this task is the analysis of the Fire Safety Systems used on cruise ships. The reliability and efficiency of these systems are crucial input parameters for any fire simulation model that massively influence the incidence probabilities and consequences of fire scenarios.

In this chapter, we describe in technical detail some typical FSS used on cruise ships. In particular, we give an overview over the functionality of these systems, list its components and briefly describe regulatory requirements. We analyse fault trees of the relevant systems to obtain values for their failure rates.

2.1 Automatic Fire Detection Systems

2.1.1 System set-up

Definition

An Automatic Detection System comprises of detectors, manually operated call points, a control panel displaying the location of the source of a fire and a power supply. Its purpose is to detect a fire at its initial stage and to automatically activate an alarm.

Application as per SOLAS and FP 53/3/1 convention (6):

Table 4 - SOLAS regulation for detection systems

Operation Any required fixed fire detection and fire alarm system with manually operated call points shall be capable of immediate operation at all times (This does not require a back-up control panel). In passenger ships, the fixed fire detection and fire alarm system shall be capable of remotely and individually identifying each detector and manually operated call point. Fire detectors fitted in passenger ship cabins, when activated, shall also be capable of emitting, or cause to be emitted, an audible alarm within the space where they are located.

There shall be not less than two sources of power supply for the

Page 16: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

16

16

Power Supply

electrical equipment used in the operation of the fixed fire detection and fire alarm system, one of which shall be an emergency source of power. Separate feeders reserved shall provide the supply solely for that purpose. Such feeders shall run to an automatic changeover switch situated in or adjacent to the control panel for the fire detection system.

Total operation There shall be sufficient power to permit the continued operation of the system with all detectors activated, but not more than 100 if the total exceeds this figure

Smoke detector

Required in all stairways, corridors and escape routes within accommodation spaces shall be certified to operate before the smoke density exceeds 12.5% obscuration per meter, but not until the smoke density exceeds 2% obscuration per meter. Smoke detectors to be installed in other spaces shall operate within sensitivity limits to the satisfaction of the Administration having regard to the avoidance of detector insensitivity or over sensitivity.

Heat detector

Heat detectors shall be certified to operate before the temperature exceeds 78ºC but not until the temperature exceeds 54ºC, when the temperature is raised to those limits at a rate less than 1ºC per min. At higher rates of temperature rise, the heat detector shall operate within temperature limits to the satisfaction of the Administration having regard to the avoidance of detector insensitivity or over sensitivity.

Operating temperature The operation temperature of heat detectors in drying rooms and similar spaces of a normal high ambient temperature may be up to 130ºC, and up to 140ºC in saunas

Control panel

1.Control and monitor input signals from all connected fire and smoke detectors and manual call points

2. Provide output signals to the navigation bridge, continuously manned central control station or onboard safety centre to notify the crew of fire and fault conditions

3. Monitor power supplies and circuits necessary for the operation of the system for loss of power and fault conditions

4. May be arranged with output signals to other fire safety systems including - paging systems, the fire alarm or public address system, fan stops, fire doors, fire dampers, the sprinkler system, the smoke extraction system, the low-location lighting system, the fixed local application fire-extinguishing system, the CCTV system, other fire safety systems; and fuel system quick closing valves.

Page 17: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

17

17

The maximum spacing of detectors

Table 5 - Spacing of detectors

Type of detector Maximum floor area per detector (m2)

Maximum distance apart between centers (m)

Maximum distance away from

bulkheads (m)

Heat

37

9

4.5

Smoke

74

11

5.5

Regulatory Requirements (FSS code, FP 53/3/1 ):

Fixed fire detection and fire alarm systems with individually identifiable fire detectors shall be so arranged that:

1. means are provided to ensure that any fault (e.g., power break, short circuit, earth, etc.) occurring in the section will not prevent the continued individual identification of the remainder of the connected detectors in the section;

2. all arrangements are made to enable the initial configuration of the system to be restored in the event of failure (e.g., electrical, electronic, informatics, etc.);

3. the first initiated fire alarm will not prevent any other detector from initiating further fire alarms; and

4. no section will pass through a space twice. When this is not practical (e.g., for large public spaces), the part of the section which by necessity passes through the space for a second time shall be installed at the maximum possible distance from the other parts of the section.

Page 18: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

18

18

Cables used in the electrical circuits shall be flame retardant according to standard IEC 60332-1. On passenger ships, cables routed through other main vertical zones that they serve, and cables to control panels in an unattended fire control station shall be fire resisting according to standard IEC 60331, unless duplicated and well separated.

Detectors shall be located for optimum performance. Positions near beams and ventilation ducts, or other positions where patterns of airflow could adversely affect performance, and positions where impact or physical damage is likely, shall be avoided. Detectors shall be located on the overhead at a minimum distance of 0.5 m away from bulkheads, except in corridors, lockers and stairways.

The activation of any detector or manually operated call point shall initiate a visual and audible fire detection alarm signal at the control panel and indicating units. If the signals have not been acknowledged within 2 min, an audible fire alarm shall be automatically sounded throughout the crew accommodation and service spaces, control stations and machinery spaces of category A. This alarm sounding system need not be an integral part of the detection system.

Functionality

A typical detection system has some sensing elements which can sense the presence of smoke or heat caused by a fire in or near to the affected area. Subsequently these sensors send an electrical signal to the fire alarm panel or to specific safety equipment for activation.

When this signal activates the audio-visual alarms on the panel, the concerned crew members are alerted. The panel helps them to quickly identify the fire-affected zone and thus to take appropriate countermeasures like fire extinguishing or evacuation.

The responsible crew member is expected to acknowledge the alarm by pressing a cancel button within two minutes of its activation which silences the hooter/alarm. If this is not done, then the alarm gets activated in all areas/zones.

The control panel has alarms for the following fault situations:

On detection of fire and smoke

Failure of main supply or low voltage of the battery backup system.

Excessive current (fuse gets blown).

Fault in the electrical power cable.

Page 19: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

19

19

Technical details of the Fire Control Panel

Primary Power supply: Commonly a non-switched 120 or 240 V AC source supplied from a commercial power utility. In non-residential applications, a branch circuit is dedicated to the fire alarm system and its constituents. "Dedicated branch circuits" should not be confused with "Individual branch circuits" which supply energy to a single appliance.

Secondary (backup) Power supplies: This component, usually sealed, lead-acid storage batteries or other emergency sources including generators, is used to supply energy in the event of a primary power failure.

Initiating Devices: This component acts as input to the fire alarm control unit and are either manually or automatically activated.

Notification appliances: This component uses energy supplied from the fire alarm system or other stored energy source to inform crew members of the need to take action, usually to evacuate.

Safety Interfaces: This interface allows the fire alarm system to control aspects of the built environment and to prepare the place for fire and to control the spread of smoke fumes and fire by influencing air movement, lighting, process control, human transport and exit.

2.1.2 Smoke Detector

Definition

A smoke detector is a device that monitors the smoke concentration in the surrounding air. Most smoke detectors work either by optical detection (photoelectric) or by physical process (ionisation), while others use both detection methods (hybrid system) to increase sensitivity to smoke. Smoke detectors are usually powered by a central fire alarm system, which in turn is powered by the main power supply system with a battery backup.

Types of Smoke Detectors

Optical – This detector type is based on the fact that smoke particles scatter light. It typically consists of a light source (bulb or infrared LED), a lens to collimate the light into a beam, and

Page 20: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

20

20

a photodiode or other photoelectric sensor at an angle to the beam as a light detector. In the absence of smoke, the light passes in a straight line and misses the detector. When smoke enters the optical chamber across the path of the light beam, some light is scattered by the smoke particles, directing it at the sensor and thus triggering the alarm.

Ionisation – This type of detector is based on the principle that α-radiation is attenuated by smoke particles. A typical source of radiation is a small sample of Americium-241 which has a half-life of over 430 years. The α-particles emitted by the sample pass through the ionisation chamber, an air filled space between two electrodes. The radiation ionises gas molecules within the ionisation chamber, which allows a small electric current to flow between the electrodes. When smoke particles enter the ionisation chamber, they absorb the radiation and hence reduce this current, which triggers the alarm.

While ionisation smoke detectors tend to be cheaper than optical ones, they are also more prone to false alarms.

2.1.3 Heat detector

Definition

A heat detector is a device which responds to the changes in ambient temperature in the vicinity of the detector. A predetermined threshold value is set in the detector system. When the ambient temperature exceeds this threshold value, it sends out an electrical signal to trigger the alarm. In some cases the automatic sprinkler and detection functions are combined in one single device, such that when the temperature exceeds the threshold limit both the fusible bulb of the sprinkler gets fused causing discharge of water and the detector alarm gets activated simultaneously. Heat detectors are generally of three basic types, depending on the physics of operation: ‗rate of rise‘ type, fixed temperature and rate compensation. Yet again, to increase sensitivity any combination of these two types is used.

Types of heat detectors in comparison

Table 6 - Types of detectors

Criterion Rate of rise

detector

Fixed temperature

Detector

Rate compensation detector

Page 21: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

21

21

Combination type heat detectors

This type of detector has multiple sensor elements to respond to the presence of fire and/or smoke. There are many variations in the design of such detectors such as: response from any element, response from a partial combination of all elements or complete response from all elements. Generally, the principle of operation of the first type is to respond to both the rate-of-raise and fixed-temperature scenario. The operation based on rate-of-rise of temperature is very useful and effective in case when fire develops rapidly because it requires much less response time. In contrast, the elements which operate on the principle of fixed-temperature respond slowly to the development of fire because time is required to reach the set temperature, as such this is useful for the case of slowly developing fire. In general, the common features of the construction of a combination detector include a vented air chamber and a flexible diaphragm for sensing the rate-of-rise of temperature. On the other hand, the elements based on the fixed-temperature principle usually consist of a leaf-spring restrained by

Type of detection

Rate-of-rise detectors sense the rate of change in ambient temperature.

Fixed-temperature heat detectors operate when the temperature of the operating elements reaches a specific point.

This type of detector also activates on sensing the rate of rise of ambient temperature. However, at the lower temperature range it acts as a Fixed temperature type and at the higher range of ambient temperature, in particular close to the set value, it works as rate-of-rise type. Thus it provides more warning time before the temperature actually reaches the set value.

Operating range

Operating range is about 12 to 15˚F (7-8˚C) per min.

Operating temperature is about 135˚F (58˚C)

(up to 5°F per minute)

Areas where it is used

Applied in areas subjected to high ambient temperature, i.e. boiler rooms or places which require detectors that operate only if close to fire.

Used mainly in unattended spaces to detect smoldering fires that increase the temperature of a detector above its design value, usually 135°F to 145°F or 185° to 200°F.

Places where there are low rates of temperature change

Page 22: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

22

22

a eutectic metal which fuses on reaching the temperature at the element to its preset temperature, closing and hence activating the circuit.

2.1.4 Fault tree analysis of a Detector System

We use the fault tree analysis to obtain a value for the failure rate of an Automatic Detector System. To obtain failure rates for individual components, the OREDA handbook (7), (8) has been used. In cases where it didn‘t provide the required information, RIAC data (9) has been referred to. The type of the failure rate distribution for various components has been assumed to be ‗Exponential‘ as indicated in the OREDA handbook. All abbreviations used in the table below are same as those in the OREDA and RIAC data books.

Item Failure Mode

Mean (λ) per

𝟏𝟎𝟔 hrs

Standard Dev.

Mean time to failure (hrs)

Data Source

Remarks

Pump Centrifugal, Sea Water

MD- Critical

56.17

30.45

17803

OREDA This item has been considered for all sea water lifting pumps in the fault tree.

Valve General

Critical 25.97 21.31 38506

OREDA For all valves same value has

been used.

Compressor general

Critical, breakdow

n

6.20 17.26 161290

OREDA -

Pump centrifugal

General

MD- Critical,

breakdown

3.7 11.38 270270

OREDA For pumps other that sea water lift these

values have been used.

Fire and Gas UD-Critical,

0.43 1.13 232558 OREDA

Page 23: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

23

23

detector

General

spurious operation

WB-Critical

PrC-Critical

1.1

3.35

1

909092

-

Table 7 - Failure rates for components from OREDA

The data for the following items has been taken from the RIAC handbook. We have assumed that these items also follow an exponential distribution like those given in OREDA.

Page 24: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

24

24

ITEMS Part Description Quality Level

Application Environment

(λ) per

𝟏𝟎𝟔 hrs

Mean time to failure (hrs)

Data Source

Remarks

Hooter Alarm (annunciator, buzzer)

COM GB 5.379207

185901 RAC

No item in name of Hooter in the RAC, data for Alarm considered

Ventilator Ventilator, air circulator

UNK GM 3.717472

269000 RAC

-

Timer Timer(summary)

- - 0.366406

2729213

RAC

-

Relay switch or other failure in panel

Panel ,fire control system

MIL GM 62.37159

16032.94

RAC

-

Switch Fail

Push Button (Summary)

COM GM 38.2907

26116

RAC

Push button type switch has been considered.

Cable connection

Cable, electrical

UNK GM 25.13005

39793

RAC,

-

Audio visual Device

Alarm (Summary)

- - 0.0431

23201856

RAC

-

Battery DB, BL- Battery

Battery , Rechargable

COM N 0.0064

156250000

RAC -

Page 25: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

25

25

Power Supply

MS-Uninterrupted

COM

GF

4.288808

233165

RAC

For main supply

ES-Diesel Generator (summary)

COM GF 136.11

7347 RAC

For emergency supply

Pressure switch

Switch, Pressure (Summary)

-

-

19.1454

52231.86

RAC

-

Pressure Gauge

Gauge, Pressure

UNK GM 11.08611

90203

RAC

-

Level Indicator

Indicator, liquid level

UNK GM 16.56534

60367

RAC

-

Strainer

Strainer, Water COM GF 3.903612

256173

RAC

-

Nozzle

Nozzle (Summary)

- - 0.2136

4681647

RAC

-

Solenoid Valve

Valve, Solenoid (Summary)

UNK GM 16.94915

59000

RAC

-

Pipe Pipe, water

COM GF 2.9277

341565 RAC -

Page 26: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

26

26

Actuator Pipe(AP)

Pipe UNK GM 0.032

31250000 RAC -

Fiber optic cable

- - - 12.5

80000 Assumed This Item is supposed to be reliable. We have assumed its reliability value as 0.85 over 8000 hrs. of mission time and the MTTF value estimated accordingly.

Table 8 - Component failure rates taken from RIAC

Page 27: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

27

27

In some cases, no data is available. In these cases expert judgement has been used to obtain approximate failure rates. The components in question are given in the table below.

ITEMS for which Static Reliability has been assumed*

Assumed Reliability

Operator fails to take action 0.85

DOOR 0.85

Cylinder 0.85

Battery general

0.85

Table 9 - Static reliabilities

*Static reliability is independent of mission time. It is considered as availability on demand. The fault tree for a Detector System is given in the appendix. We have used the software BlockSim to analyse the tree. We obtain the following failure rate for the whole system:

𝜆 = 0.0029 1

𝑑𝑎𝑦𝑠

2.2 Sprinkler Systems

Definition

A sprinkler system is a fixed installation that discharges water in case of a fire. It is generally used for fighting and suppressing fire in control stations, accommodation and service spaces, as well as corridors and stairways.

Page 28: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

28

28

Precautionary note: In the spaces where water may cause damage to essential equipment, it may be fitted with an alternative approved fixed fire-extinguishing system (SOLAS Regulation 10.6.1.1).

2.2.1 System set-up

A typical sprinkler system consists of three parts: pressure tank, air compressor and sprinkler pump.

A sprinkler system is generally installed for the purpose of fire extinguishing in accommodation areas and service spaces. These are fixed type installations. The system consists of a network of sprinkler heads located in the areas that need to be protected, with an appropriate spacing. Due care needs to be taken for placing the heads so that these do not get damaged by mechanical contacts or impacts. There are different types of sprinkler heads, differing by their mechanism of operation. One very common type is a glass bulb head, used for automatic activation. The glass bulb gets fused at a predetermined temperature in the wide range of 50 °C to 300 °C (10), (11).

Usually the network of sprinkler heads is divided into sections. As per FSS regulations, each of these sections must not have more than 200 sprinkler heads. The sections are equipped with valves which trigger signals for activation of both audible and visual alarms when water flows through them. Thus it is possible to identify which section of the ship has been affected by fire. There is a system fitted in the main control room which automatically keeps track of all the sections of sprinkler heads. Functional diagrams of the system are given below.

Page 29: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

29

29

T o B ilg e

P u m p

P u m p s

F ilte rs

F w d . P u m p R o o m

E n g in e

R o o m

S e a C h e s t

Is o la tio n V a lv e s

C o m p re s s o r

T o B ilg e

P re s s u re

T a n k

P re s s u re S w ic h e s

1 2 3

W a te r

c o n n e c tio n

f ro m s h o re

F re s h w a te r

L e v e l

S w ic thL e v e l

in d ic a to r

T o B ilg e

P re s s u re S w itc h e s

1 : C o m p re s s o r S ta rtin g

P s ta r t :- 0 .7 M P a , P s to p :- 0 .8 M P a

2 : S p r in k le r P u m p S ta rtin g

P s ta r t :- 0 .5 M P a

3 : L o w P re s s u re S ig n a llin g

P s ta r t :- 0 .7 5 M P a

J o c k e y

P u m p

S e a C h e s t

h y d ro p h o re

ta n k

L e v e l

in d ic a to r

F ire p u m p

C o m p re s s e d a ir

to a u to m a tic

s p r in k le r s y s te m

re d u c e r

P

P

P re s s u re C o n tro l

P S ta rt - 0 .5 8 M P a

P S to p - 0 .8 M P a

S a fe ty

V a lv e

F w d . P u m p R o o m

T o S p r in k le r H e a d s

Figure 2 - Functional diagrams of a sprinkler system

Page 30: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

30

30

The regulations demand that each section of sprinklers can be isolated by one stop valve only. The stop valve in each section should be readily accessible in a location outside of the associated section or in cabinets within stairway enclosures.

Additional isolation valves may be fitted for the purpose of servicing, maintenance or for refilling of antifreeze solutions in the sprinkler piping. Audio-visual alarms are provided for these additional isolation valves when fitted.

The quantities of spare nozzles carried on the ships are as follows (FSS Code):

Table 10 - Nozzles

Total number of nozzles Required number of spares

< 300 6

300 to 1000 12

> 1000 24

The number of spare nozzles of any type need not exceed the total number of nozzles installed of that type.

2.2.2 Sprinkler Types and their working principles

As per Resolution A.800(19), the types of Sprinklers Systems are (12):

Wet pipe systems

Dry pipe systems

Deluge systems

Antifreeze systems

Pre-action system

Water-based extinguishing medium

2.2.2.1 Wet pipe systems

This type of sprinkler is the most widely used system. It is the simplest type of sprinkler and also the only type which can be operated automatically. Its active components are an automatic sprinkler head and usually (but not always) an automatic alarm check valve. This simplicity makes the system very reliable as compared to the other types. The pipelines of the

Page 31: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

31

31

water supply system for this type of sprinkler arrangement always remain filled with fresh water (in order to prevent corrosion) under pressure and get activated automatically with the fusing of the sprinkler heads. The sprinkler heads get fused and open for discharge of water only when the temperature reaches a threshold value.

Working Principle: When the sprinkler heads exposed to the threshold temperature, the heat sensitive element (glass bulb or fusible link) is released, allowing water to flow from that sprinkler. The glass bulb or link applies pressure to a cap which acts as a plug preventing water from flowing until the ambient temperature around the sprinkler reaches the design activation temperature of the individual sprinkler. Because each sprinkler activates independently when the predetermined heat level is reached, the number of sprinklers that operate is limited to only those near the fire, thereby maximising the available water pressure over the location of the fire.

2.2.2.2 Dry pipe systems

On vessels operating in areas where the ambient temperature is below the freezing point of water, the wet pipe system is not suitable to use because the static water inside the pipe might freeze, causing blockage of the water flow. In such cases a dry pipe system is a suitable option. In dry pipe systems, the pipes are kept pressurised with air or nitrogen instead of water when the system is in idle state. Water is discharged only after the air/nitrogen is released on fusing of the sprinkler bulb when exposed to the threshold temperature. Hence in the initial stage only air/nitrogen is vented out of the sprinkler head which does not contribute to extinguishing the fire. The actual effect of fire suppression begins when water is discharged through sprinkler nozzles. Due to this delay this system is not as effective as the wet pipe system in the initial stages of a fire.

Working Principle: When the temperature at the sprinkler head reaches the threshold level, it opens out, allowing the air or nitrogen to vent out through the sprinkler head. Thus the pressure in the pipeline drops. This leads to a pressure gradient across the dry pipe valve, allowing water to enter in to the sprinkler piping system. The venting of air or nitrogen from the sprinkler in the initial stage causes the delay in the venting of water from the sprinklers needed to control the fire. Therefore, during the initial stages of fire the dry pipe systems are usually not as effective as wet pipe systems for the suppression of fire.

2.2.2.3 Comparison of Dry Pipe fire Sprinkler systems and Wet Pipe Sprinkler system

Table 11 - Different types of sprinkler systems

Criterion Dry Pipe System Wet Pipe System

Page 32: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

32

32

Complexity Dry pipe systems require additional control equipment and air pressure supply components which increases its complexity.

Wet pipe systems are simple, with the only operating components being the automatic sprinkler heads. Pipes are filled with water under pressure so no extra components are required.

Installation and Maintenance costs

The added complexity impacts the overall dry-pipe installation costs, and increases maintenance expenditure primarily due to added service labour costs.

Its simplicity and wet pipe reduces maintenance and installation costs.

Corrosion potential After operation or testing, the dry-pipe sprinkler system‘s piping is drained, but residual water may collect in low spots, and moisture is also retained in the atmosphere within the piping. This moisture, coupled with the oxygen increases pipe internal wall corrosion rates, possibly leading to leaks.

Wet pipe systems are filled with water all the time, so oxygen exposure is reduced, hence less chance of corrosion or leakage.

Application Dry pipe systems are usually only used in spaces in which the ambient temperature may be cold enough to freeze water.

Wet pipe systems cannot be used in places where the ambient temperature drops below the freezing point of water.

2.2.2.4 Deluge Systems

As per IMO Resolution A.800(19), "Deluge" systems are systems employing open sprinklers attached to a piping system connected to a water supply through a valve that is opened by the detection system installed in the same areas as the sprinklers . In these systems, the sprinklers fitted are of open type (i.e. without any bulb) and the sprinkler network piping system is not filled with liquid or gas under normal condition. This type of system is suitable to rapidly

Page 33: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

33

33

cover large areas affected by fire. Sometimes it is also used to prevent fire from entering from other adjacent locations.

Under normal conditions (i.e. when there is no fire), the ingress of water into the sprinkler network piping is prevented by a deluge valve fitted at the inter-connection of the water supply line with the sprinkler network piping.

Working Principle: On activation of the automatic detector or manual call point the corresponding signal is transmitted to the control panel, which in turn signals the deluge valve to open, allowing water to pass into the sprinkler network piping system and water is instantly discharged through the sprinkler heads.

2.2.2.5 Antifreeze Systems

This type of system is a wet pipe sprinkler system employing automatic sprinklers attached to a piping network containing an antifreeze solution and connected to a water supply (Resolution A.800(19)).

Working principle: When an automatic sprinkler is exposed to sufficient heat, the heat sensitive element (glass bulb or fusible link) is triggered, allowing antifreeze solution to discharge. Immediately after this, water flows from the sprinkler head.

2.2.2.6 Pre-action Systems

This type of sprinkler system employs automatic sprinklers attached to a piping system containing air that may or may not be under pressure, with a supplemental detection system installed in the same area as the sprinklers (Resolution A .800(19)).

Working Principle: Actuation of the detection system opens a valve that permits water to flow into the sprinkler piping system and to be discharged from any sprinklers that may be open.

2.2.2.7 Construction and Working Principle of a Sprinkler Head

Fusible sprinkler heads can be used for both detection and extinguishing of fire. A typical fusible sprinkler head is covered by a semicircular quartzoid bulb, which contains an expandable liquid. A deflector plate is attached at the end of the bulb. This plate serves the purpose of spraying the water over a larger area (Figure 3). When the bulb is exposed to heat, it causes the liquid inside the bulb to expand, leading to breakage of the bulb, and thus allowing the water to flow from the sprinkler head. The water supply system for this sprinkler arrangement features a tank pressurised with compressed air to keep the water in the pipes at a constant pressure. When the bulb fuses and the water flows out, the pressure in the pipe lines drops, which causes a salt water pump to start automatically. This salt water pump provides a continuous supply of water to the sprinkler system. In case of a wet sprinkler system, the piping and heads are initially filled with fresh water under pressure in order to protect the system from corrosion.

Page 34: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

34

34

2.2.3 Regulatory requirements (Reference FSS code)

Table 12 - Regulations on sprinklers

Type of operation -Automatic in operation,

-Capable of both detecting the fire and suppressing the fire.

Pressure Tank capacity

-A pressure tank should have a volume of at least twice that of the charge of fresh water, equivalent to the amount of water which would be discharged in 1 min by the pump.

-Means of replenishing the air under pressure and of replenishing the fresh water charge in the tank

-Provision to prevent passage of sea- water into the tank.

Figure 3 - Sprinkler head

Page 35: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

35

35

Power supply

-Not less than two sources of power for the system.

-Sources of power -Main generator and an emergency source. One supply for the pump should be taken from the main switchboard, and one from the emergency switchboard by separate feeders reserved solely for that purpose.

Water-Supply

Back up

-Provision of a redundant means of pumping.

-The capacity of the redundant means should be sufficient to compensate for the loss of any single supply pump or alternative source. One of the pumps may be the main fire pump connected to the sprinkler system.

Temperature rating

In accommodation and service spaces the sprinklers should have a nominal temperature rating of 57°C to 79°C, except that in locations such as drying rooms, where high ambient temperatures might be expected, the nominal temperature may be increased by not more than 30°C above the maximum deck head temperature.

Pump capacity

Pumps and alternative supply components should be capable of supplying the required flow rate and pressure for the space with the greatest hydraulic demand. For the purposes of this calculation, the design area used to calculate the required flow and pressure should be the deck area of the most hydraulically demanding space, separated from adjacent spaces by A-class

divisions. The design area need not exceed 280 m2.

Sprinkler Piping Should not be used for any other purpose.

Isolation Valves Isolation valves used for service, maintenance or for refilling of antifreeze solutions may be installed in the sprinkler piping in addition to the section stop valves, if provided with a means for giving a visual and audible alarm.

Sprinkler position and Capacity

Sprinklers should be placed in an overhead position and spaced in a pattern to maintain an average application rate of not less than 5 l/m²/min over the nominal area covered by the sprinklers.

System Location

-Sprinkler pump and tank shall be situated in a position reasonably remote from any machinery space of category A and -shall not be situated in space required to be protected by sprinkler system.

Page 36: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

36

36

Testing requirement at the time of installation (Reference FTP Code)

The response time is expressed as a response time index (RTI), which typically has values between 35 and 250 m½s½, where a low value indicates a fast response. Under standard testing procedures (135 °C air at a velocity of 2.5 m/s), a 68 °C sprinkler bulb will break within 7 to 33 seconds, depending on the RTI. The RTI can also be specified in imperial units, where 1 ft½s½ is equivalent to 0.55 m½s½.

2.2.4 Fault tree analysis of a Sprinkler System

Analogously to the previous section, we perform a fault tree analysis of the system. The component failure rates are given in Table 7, Table 8 and Table 9. Once again, we use the software BlockSim to analyse the fault tree diagram given in the appendix. The resulting failure rate is

𝜆 = 0.00036 1

𝑑𝑎𝑦𝑠

2.3 Water Mist Systems

2.3.1 System set-up

Definition

Water mist systems are fixed installations that produce small droplets of water to control and/or extinguish fires.

Working principle

The system works in two ways to control and extinguish fire. The first effect is to remove oxygen from the atmosphere in the vicinity of the fire and the second one is the cooling effect.

High-pressure water mist systems generate very small droplets of water. When exposed to the heat of fire, these droplets evaporate. As this happens, the vapour displaces the oxygen in the vicinity of the flammable material in the area affected by fire. This helps with the extinction and controlling of fire by disruption of the oxygen supply.

Page 37: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

37

37

Water mist systems discharge water at a very high pressure, producing extremely small droplets of water. Unlike the larger drops produced by conventional sprinklers, these smaller particles stay afloat and eventually fill the whole space, creating an atmosphere that impedes fire growth. Moreover, due to their large surface areas, the droplets are very efficient in cooling and hence suppressing the fire.

Typical Schematic Diagram:

Figure 4 - Schematic diagram of a water mist system

Components requirements (FSS Code , MSC/Cir 913):

Nozzle-

An approved type of nozzle with an average distribution of water of at least 5 liters per minute.

Inside Diameter of nozzle at the tip is to be not less than 6 mm.

Corrosion resistant material.

Distribution valves-

To be operated from easily accessible positions outside the spaces to be protected and which will not be readily cut off by an outbreak of fire.

Water Supply Pump-

Page 38: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

38

38

To be sufficient to pressurize the piping system at all times and capable of automatically starting to pump on detecting a pressure drop.

The pump and control equipment are to be provided outside the protected space.

If the pump is fed from the sources of electrical power of the main and emergency generator, the emergency generator is to be capable of automatically starting in the event of failure of the main source of electrical power supply.

Water Storage tank

Should be capable of continuously supplying water-based medium for at least 20 minutes.

Note: Specifications for the following items have not been found in the regulations-

1. Operational requirements

2. Capacity/Quantity requirements

3. Specification for air supply, e.g. quantity, pressure etc.

System Description:

Water Mist Systems consist of a high-pressure pump unit with cylinders, section valves, piping system and nozzle heads. Water is supplied via a pump unit or cylinders depending on the system through a variety of different section valves operated either remotely or manually. For easy operation and monitoring a control panel is installed. Water Mist Systems are an alternative to CO2 systems (see below) and are installed in high-risk areas. Sometimes the system is equipped with glass bulb nozzles, which contain detection bulb glass (see the section on sprinklers) to start the system automatically in the event of fire. For some areas, the system can be activated both automatically and manually [MSC/Cir 913]. For the protection of machinery spaces and local risk areas, the system can be equipped with open nozzles and a detection system to operate manually for total flooding or local protection of high-risk areas.

System Configuration:

The main component of the MIST Fire Extinguishing System and their functions are as follows.

Discharge nozzle -Fire extinguishing head

Section valve -Valve for deluge discharge to the hazardous area

Page 39: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

39

39

Area valve startup solenoid valve -Control valve to drive air-driven area valves

Water pump -High-pressure pump to feed fire extinguishing water under pressure

Control panel -Startup panel for starter to start up the high-pressure pump, Startup device for area discharge by manual operation

Fire detector (for flame and smoke) -Smoke detector and flame detector to judge the fire area

Visible and audible alarms -Lamps and alarms to warn the persons in the area

Figure 5 - Configuration of a water mist system

Applications:

Water mist systems, as an alternative to CO2 system (see below), can generally be used in the similar spaces as the latter. This includes engine rooms, boiler rooms, cargo spaces, galleys, rooms containing electrical and electronic plants and equipment, fuel and lubricating oil tanks and pumps, flammable liquid storages and paint storages. Although the Water Mist system is considered equivalent to CO2 systems, for large ships with engine rooms of larger heights, this

Page 40: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

40

40

system is not as effective as the CO2 system. This system is preferred for installation on small boats, hovercrafts etc. with smaller engine rooms.

2.3.2 Fault tree analysis of a Water Mist System/Hi-Fog System

We have analysed two different systems. The first one is a generic water mist system analysed with the BlockSim software (Figure 28). The resulting failure rate is

𝜆𝑊𝑎𝑡𝑒𝑟𝑀𝑖𝑠𝑡 = 0.0024 1

𝑑𝑎𝑦𝑠

The second system is a Hi-Fog system as used by Carnival Cruise Lines. This system (see Figure 29) was analysed using BV‘s VeriSTAR methodology. The resulting failure rate is

𝜆𝐻𝑖−𝐹𝑜𝑔 = 0.00094 1

𝑑𝑎𝑦𝑠

2.4 CO2 Systems

2.4.1 System set-up

Definition

CO2 systems are fixed installations in an enclosed space that reduce the oxygen content in the atmosphere by the emission of CO2 to an extent where combustion is no longer possible.

Overview

CO2 is well established as an effective medium for fixed fire extinguishing systems. It is widely used in domestic as well industrial houses. On board ships it is used for the machinery spaces and accepted as an alternative to mist and foam fire extinguishing systems (see below). It can be used to fight electrical fire, liquid fire, melted solid fire, solid surface fire, part deep-seated solid fire and gas fire.

The inhalation of CO2 poses a danger to life, and therefore this system is not suitable for spaces occupied by passengers. It can, however, be used in machinery spaces with special precautionary arrangements to ensure complete evacuation before discharging of CO2 in the

Page 41: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

41

41

affected space. In particular, the system should only be activated through manual operation and only on confirmation that the space has no soul left inside.

CO2 cylinders should be stored in well ventilated cabinets or lockers in order to prevent accumulation of gases that might be caused by leakages.

Typical Schematic Diagram of Shipboard CO2 system (13):

Figure 6 - Schematic diagram of a CO2 system

Components and its requirements (As per FSS Code)

Cylinders- Should be kept outside protected space.

Page 42: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

42

42

Pipes, fittings and nozzles-

Constructed of materials having a melting temperature which exceeds 925 ºC.

Corrosion resistant materials.

Actuation and control systems- Back up power requirements.

Distribution valves – Readily accessible, simple to operate and grouped means of control outside protected space which will not be readily cut-off by an outbreak of fire.

Salient features of the applicable rules (FSS Code, SOLAS)

Quantity of CO2-

Cargo Spaces: Sufficient quantity of CO2 shall be available to give a minimum volume of free gas equal to 30% of the gross volume of the largest cargo space to be protected,

Machinery Spaces: Sufficient quantity of CO2 shall be available to give a minimum volume of free gas equal to the larger of the following: 40% of the gross volume of the largest machinery space so protected or 35% of the gross volume of the largest machinery space protected, including the casing.

CO2 discharge time -

85% of the gas shall be discharged into the space within 2 min (for machinery spaces).

Operational precaution-

Automatic release of fire-extinguishing medium shall not be permitted except as permitted by the administration

Alarm -

Opening of release cabinet door shall automatically activate pre -discharge alarm.

It shall operate for the length of time needed to evacuate the space, but not less than 20 s before medium is released.

Page 43: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

43

43

Advantages of CO2 based system

-100% natural, environmentally friendly,

-Does not leave a residue,

-Zero ozone depletion potential.

Disadvantages

-Highly asphyxiating (suffocative),

-Even if discharge CO2 is cold, it has little cooling effect - danger of re-ignition if air is readmitted,

-When discharged, particles of solid carbon dioxide may generate static electricity (CO2 is not an inert medium.

For fault tree diagrams, please refer to the Appendix.

2.4.2 Fault tree analysis of a CO2 system

As in the previous sections, we analyse the fault tree diagram given in the appendix. The resulting failure rate is

𝜆 = 0.0027 1

𝑑𝑎𝑦𝑠

2.5 Foam Systems

2.5.1 System set-up

Definition

Foam systems are fixed installations that produce foam to control and/or extinguish fires.

Page 44: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

44

44

Working principle

Foam is generated by the formation of air bubbles from aqueous solutions. Since foam has a lower density than flammable liquids, it remains floating on the surface and creates a ‗blanket‘ on the liquids, cutting off the oxygen supply and thus suppressing the fire.

Components of a typical Foam system: Foam storage tank Mixing system Control panel Foam liquid Emergency fire pump

Page 45: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

45

45

P U M P

V A L V E

P U M P

T A N KN O N R E T U R N IN G V A L V E

S T R A IN E R R E D U C E R P U M P R E D U C E R

N O N R E T U R N IN G V A L V E

P R O P O R T IO N E R

V A L V E

V A L V E

F O A M M A IN

IS O L A T IO N V A L V E

L E V E L G A U G E

Figure 7 - Schematic diagram of a foam system

Page 46: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

46

46

R e c irc u la tio n L in eF o a m L iq u id

T o F ire M a in

F o a m M a in Is o la tin g V a lv e

F

F ill in g L in e

F o a m T a n k U n it

F o a m M o n ito r V a lv e

D ra inD ra in

F o a m R o o m

ta n k

E

B

CD

L e v e l g a u g e

P re s s u re v a c u u m V a lv e

F lu s h in g L in e

Figure 8 - Configuration of a typical foam system

Regulatory Requirements (FSS Code, SOLAS, FP 53/3/1)

Table 13 - Regulations on foam systems

Quantity of foam Shall be designed to produce foam at the required application rate within 1 min of release.

Quantity of foam -forming liquid

The quantity of foam concentrate available shall be sufficient to produce a volume of foam equal to at least five times the volume of the largest protected space at the nominal expansion ratio, but in any case not less than enough for 30 min of full operation for the largest protected space.

Operation The system shall be capable of manual release, Automatic release of the system shall not be permitted unless appropriate operational measures or interlocks are provided to prevent any local application

Page 47: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

47

47

systems required by regulation II-2/10.5.6 of the Convention from interfering with the effectiveness of the system.

Power supply The system shall be supplied by both main and emergency sources of power. The emergency power supply shall be provided from outside the protected machinery space. All electrical components in connection with the foam generating components shall have at least an IP 54 rating.

Warning Alarms Means shall be provided for automatically giving audible and visual warning of the release of the system. The alarms shall operate for the length of time needed to evacuate the space, but in no case less than 20 s.

Filling rate The design-filling rate for the system shall. be adequate to completely fill the largest protected space in 10 min or less

No. of foam producing units

A minimum of two generators shall be installed in every space containing combustion engines, boilers, purifiers, and similar equipment. Small workshops and similar spaces may be covered with only one foam generator.

Distribution of foam producing units

Foam generators shall be uniformly distributed under the uppermost ceiling in the protected spaces including the engine casing. The number and location of foam generators shall be adequate to ensure all high risk areas are protected in all parts and at all levels of the spaces. Extra foam generators may be required in obstructed locations. The foam generators shall be arranged with at least 1 m free space in front of the foam outlets, unless tested with less clearance.

Operation of a foam system

Open sea suction valve and start firewater pump.

Open fire water supply valve.

Open foam liquid non-return valve

Start foam liquid pump (confirm that the flushing valve is closed)

Open foam liquid proportioner valve.

Open monitor as required to bring fire under control

Page 48: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

48

48

Recent Developments with respect to the FSS Code

A new chapter 6 of FSS (Ref: FP 53/3/1)

Salient Points:

The system and its components shall be suitably designed to withstand ambient temperature changes, vibration, humidity, shock, clogging and corrosion normally encountered on ships, and manufactured and tested to satisfaction of the Administration in accordance with the requirements of new chapter 6 of FSS (From FP 53/3/1)

Piping, fittings and related components inside the protected spaces (except gaskets) shall be designed to withstand 925°C.

System piping, foam concentrate storage tanks, components and pipe fittings in [continuous] contact with the foam concentrate shall be compatible with the foam concentrate and be constructed of corrosion resistant materials such as stainless steel or equivalent. Other system piping and foam generators shall be galvanized steel or equivalent.

Means shall be provided for the crew to safely check the quantity of foam concentrate and take periodic control samples for foam quality.

Means for testing the operation of the system and assuring the required pressure and flow shall be provided by pressure gauges at both inlets (water and foam liquid supply) and at the outlet of the foam proportioner. A test valve should be installed on the distribution piping downstream of the foam proportioner, along with orifices, which reflect the calculated pressure drop of the system. All sections of piping shall be provided with connections for flushing, draining and purging with air.

2.5.2 Fault tree analysis of a Foam System

As above, we analyse the tree diagram given in the appendix. The resulting failure rate is:

𝜆 = 0.0096 1

𝑑𝑎𝑦𝑠

Page 49: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

49

49

3 Reliability model of detection and suppression systems

3.1 The generic model

Following the literature, we define the reliability 𝑅 of a system as the probability that the system will function on demand. In this section, we derive the reliability as a function of

time. We assume that 𝑅 is influenced by two factors:

The system‘s intrinsic failure rate, denoted throughout this report by λ,

The intervals in which the system is checked (and repaired or replaced if necessary).

In general, λ itself is time-dependent. In particular, one would expect to see the well-documented ‗burn-in‘ and ‗wear-out‘ effects, resulting in the familiar ‗bathtub‘ curve. However, as we have no information about the time-dependence of the failure rate, we will assume it to be constant. This is an acceptable approximation for most of the system‘s life span.

We assume that each system is checked after a maximum time 𝑇𝑚𝑎𝑥 . Let 𝐼 = [0, 𝑇𝑚𝑎𝑥 ) denote the maintenance interval of the given system. The reliability of the system at time t is then given by

𝑅(𝜆, 𝑡) = 𝑒−𝜆𝑡 , 𝑡 𝜖 𝐼, ( 1 )

where λ is measured in 1 𝑑𝑎𝑦𝑠 and t in days. A fire can occur at any time during the maintenance interval; hence all values in the range of R are equally likely to occur. We therefore compute the expectation value of R over the maintenance interval and use this number as the system‘s reliability:

𝑅 = 1

𝑇𝑀𝑎𝑥

𝑒−𝜆𝑡𝑑𝑡 = 1

𝑇𝑀𝑎𝑥𝜆 1 − 𝑒−𝜆𝑇𝑀𝑎𝑥

𝑇𝑀𝑎𝑥

0

( 2 )

The variance of R can be computed as usual:

𝑣𝑎𝑟 𝑅 = 𝑅2 − 𝑅 2 = 1

2𝜆𝑇𝑀𝑎𝑥 1 − 𝑒−2𝜆𝑇𝑀𝑎 𝑥 − 𝑅 2

( 3 )

Page 50: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

50

50

3.2 Propagation of error

In general, the failure rate λ is not known exactly; often the literature provides error margins on λ. This uncertainty of λ propagates to an uncertainty of the reliability R. Let Δλ denote the error (i.e. standard deviation) of the failure rate λ. The uncertainty of R due to the uncertainty of λ can be computed using Taylor‘s expansion:

Δ𝑅(𝜆, 𝑡) = Δ𝜆𝑘

𝑘!

𝜕𝑘𝑅(𝜆, 𝑡)

𝜕𝜆𝑘

𝑘=1

With R as given in equation ( 1 ), this takes the form

Δ𝑅(𝜆, 𝑡) = Δ𝜆𝑘

𝑘!(−1)𝑘

𝑘=1

𝑡𝑘𝑒−𝜆𝑡

For small values of Δλ we only use the linear term, and hence we obtain

𝛥𝑅 𝜆, 𝑡 ≈ 𝛥𝜆 𝑡𝑒−𝜆𝑡 ( 4 )

3.3 Maintenance intervals

The intervals in which fire detection and suppression systems are tested differ between systems and between ship operators. The testing intervals are regulated by IMO MSC/Circ.850 (14) and are currently under revision (15). In the new version, each system may be the subject to different intervals for different tests. For example, a variety of tests are to be performed on sprinkler systems with intervals ranging between monthly (―verify all control and section valves are in the proper open or closed position, and all pressure gauges are in the proper range‖ etc) and 10-yearly (―perform a hydrostatic test and internal examination of 10% of the system‘s compressed gas cylinders. If one or more cylinders fail, a total of 50% of the onboard cylinders should be tested. If further cylinders fail, all cylinders should be tested‖).

Page 51: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

51

51

3.4 Application to concrete systems

We use the above model to obtain reliability curves for the systems considered in Chapter 2. In each case, we plot the reliability against time and if possible give an estimate for the error of each data point. We will use two different maintenance intervals of one month and one year. This will serve to highlight the effect maintenance intervals have on the reliability of the system.

3.4.1 Heat detector

According to the OREDA data (8), the mean critical failure for heat detectors is given by

𝜆𝐻𝑒𝑎𝑡 = 6.4 ± 3.8 ∙ 10−5 1

𝑑𝑎𝑦

We use a maintenance interval of one year. Plugging this into equations ( 1 ) and ( 4 ), we obtain the following reliability data:

Figure 9 - Reliability of Heat detector – yearly maintenance

96.00

96.50

97.00

97.50

98.00

98.50

99.00

99.50

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Heat Detector -yearly maintenance

Page 52: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

52

52

Figure 10 - Reliability of Heat detector - monthly maintenance

Finally, we use equation ( 2 ) and ( 3 ) to obtain the average reliability and standard deviation:

𝑅𝐻𝑒𝑎𝑡 𝑦𝑒𝑎𝑟𝑙𝑦 = 98.8% ± 0.7%

𝑅𝐻𝑒𝑎𝑡 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 99.90% ± 0.06%

3.4.2 Photoelectric Smoke Detector

Analogously to the previous section we use the failure rate given in the OREDA handbook:

𝜆𝑃ℎ𝑜𝑡𝑜 = 4.5 ± 2.7 ∙ 10−5 1

𝑑𝑎𝑦

Using a maintenance interval of one year, we obtain the following reliability data:

99.65

99.70

99.75

99.80

99.85

99.90

99.95

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Heat Detector -monthly maintenance

Page 53: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

53

53

Figure 11 - Reliability of Photoelectric Smoke detector – yearly maintenance

Figure 12 - Reliability of Photoelectric Smoke detector – monthly maintenance

97.00

97.50

98.00

98.50

99.00

99.50

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Photoelectric Smoke Detector -yearly maintenance

99.75

99.80

99.85

99.90

99.95

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Photoelectric Smoke Detector -monthly maintenance

Page 54: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

54

54

Averaging over the maintenance intervals, we obtain:

𝑅𝑃ℎ𝑜𝑡𝑜 𝑦𝑒𝑎𝑟𝑙𝑦 = 99.2% ± 0.5%

𝑅𝑃ℎ𝑜𝑡𝑜 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 99.93% ± 0.04%

3.4.3 Ionisation Smoke Detector

The OREDA failure rate is

𝜆𝐼𝑜𝑛 = 1.0 ± 0.7 ∙ 10−4 1

𝑑𝑎𝑦

This yields the following data:

Figure 13 - Reliability of Ionisation Smoke Detector - yearly maintenance

93.00

94.00

95.00

96.00

97.00

98.00

99.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Ionisation Smoke Detector -yearly maintenance

Page 55: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

55

55

Figure 14 - Reliability of Ionisation Smoke Detector - monthly maintenance

The mean reliability over the maintenance intervals is

𝑅𝐼𝑜𝑛 𝑦𝑒𝑎𝑟𝑙𝑦 = 98.2% ± 1.1%

𝑅𝐼𝑜𝑛 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 99.85% ± 0.09%

3.4.4 Detector panel

This is the system described in section 2.1.4. As there is no historical data available, we will use the failure rate derived by fault tree analysis:

𝜆 = 0.00288 1

𝑑𝑎𝑦𝑠

99.40

99.50

99.60

99.70

99.80

99.90

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Ionisation Smoke Detector -monthly maintenance

Page 56: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

56

56

Mind that no errorbars were derived from the fault trees. With this failure rate, we obtain the following reliability data:

Figure 15 - Reliability of Detector Panel - yearly maintenance

Figure 16 - Reliability of Detector Panel - monthly maintenance

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Detector Panel -yearly maintenance

91.00

92.00

93.00

94.00

95.00

96.00

97.00

98.00

99.00

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Detector Panel -monthly maintenance

Page 57: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

57

57

Taking the average over the maintenance intervals, we obtain the following reliability:

𝑅𝑃𝑎𝑛𝑒𝑙 𝑦𝑒𝑎𝑟𝑙𝑦 = 62% ± 19%

𝑅𝑃𝑎𝑛𝑒𝑙 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 95.8% ± 2.4%

3.4.5 Sprinkler system

As there is no historical data available for this system, we will use the value for λ as derived by fault tree analysis in chapter 2. The value is

𝜆 = 0.00036 1

𝑑𝑎𝑦𝑠

With this failure rate, we obtain the following reliability data:

Figure 17 - Reliability of Sprinkler - yearly maintenance

86.00

88.00

90.00

92.00

94.00

96.00

98.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Sprinkler -yearly maintenance

Page 58: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

58

58

Figure 18 - Reliability of Sprinkler - monthly maintenance

Taking the average as above, we obtain the reliability:

𝑅𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟 𝑦𝑒𝑎𝑟𝑙𝑦 = 93.7% ± 3.6%

𝑅𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 99.5% ± 0.3%

3.4.6 Foam System

Analogously to the sprinkler system, we use the value for λ derived in chapter 2,

𝜆 = 0.0072 1

𝑑𝑎𝑦𝑠

98.80

99.00

99.20

99.40

99.60

99.80

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Sprinkler -monthly maintenance

Page 59: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

59

59

This yields the following reliability data:

Figure 19 - Reliability of Foam system - yearly maintenance

Figure 20 - Reliability of Foam system - monthly maintenance

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Foam System -yearly maintenance

75.00

80.00

85.00

90.00

95.00

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Foam System -monthly maintenance

Page 60: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

60

60

The average reliability is found to be

𝑅𝐹𝑜𝑎𝑚 𝑦𝑒𝑎𝑟𝑙𝑦 = 35% ± 25%

𝑅𝐹𝑜𝑎𝑚 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 89.9% ± 5.6%

3.4.7 Water Mist System

Analogously to the previous sections, we use the failure rate derived by fault tree analysis:

𝜆 = 0.0022 1

𝑑𝑎𝑦𝑠

Thus we obtain for the reliability:

Figure 21- Reliability of Water Mist system - yearly maintenance

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Water Mist System -yearly maintenance

Page 61: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

61

61

Figure 22 - Reliability of Water Mist System - monthly maintenance

We obtain for the average reliability:

𝑅𝑀𝑖𝑠𝑡 𝑦𝑒𝑎𝑟𝑙𝑦 = 69% ± 16%

𝑅𝑀𝑖𝑠𝑡 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 96.8% ± 1.8%

3.4.8 Hi-Fog System

We use the failure rate derived by the VeriSTAR analysis:

𝜆 = 0.00094 1

𝑑𝑎𝑦𝑠

We obtain the following reliability data:

93.00

94.00

95.00

96.00

97.00

98.00

99.00

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Water Mist System -monthly maintenance

Page 62: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

62

62

Figure 23- Reliability of Hi-Fog System - yearly maintenance

Figure 24- Reliability of Hi-Fog System - monthly maintenance

65.00

70.00

75.00

80.00

85.00

90.00

95.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Hi-Fog System -yearly maintenance

97.00

97.50

98.00

98.50

99.00

99.50

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

Hi-Fog System -monthly maintenance

Page 63: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

63

63

Thus we obtain for the average reliability:

𝑅𝐻𝑖−𝐹𝑜𝑔 𝑦𝑒𝑎𝑟𝑙𝑦 = 84.7% ± 8.3%

𝑅𝐻𝑖−𝐹𝑜𝑔 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 98.6% ± 0.8%

3.4.9 CO2 System

In chapter 2, we derived the following failure rate:

𝜆 = 0.00271

𝑑𝑎𝑦𝑠

Thus we obtain the following reliability data:

Figure 25- Reliability of CO2 system - yearly maintenance

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

CO2 System -yearly maintenance

Page 64: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

64

64

Figure 26- Reliability of CO2 system - monthly maintenance

This gives the average reliability:

𝑅𝐶𝑂2 𝑦𝑒𝑎𝑟𝑙𝑦 = 63% ± 18%

𝑅𝐶𝑂2 𝑚𝑜𝑛𝑡 ℎ𝑙𝑦 = 96.0% ± 2.3%

91.00

92.00

93.00

94.00

95.00

96.00

97.00

98.00

99.00

100.00

0 5 10 15 20 25 30

Re

liab

ility

/%

Time / Days

CO2 System -monthly maintenance

Page 65: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

65

65

4 Conclusions

We have developed a methodology to determine the reliability of fire detection and suppression systems as a function of time, taking into account the effects of regular system checks. The only input required for this method is the failure rate of the system (λ). For several devices, historical data is available and can be used to deduce the failure rate. If such data is not available (as is generally the case for more complex system, like an alarm panel), fault tree analysis can be used to determine the system‘s failure rate. We have demonstrated this in Chapter 2, where we analysed detector, sprinkler, foam, water mist and CO2 systems. The results show a range of reliabilities for these systems. Sprinkler systems show a particularly high reliability. This is apparently due to the presence of potential manual backups for the automatic action of the components in the system. The reliability of detector, CO2 and Water Mist systems is generally in the same order of magnitude. However, CO2 systems are relatively more reliable owing to the existence of some static blocks through AND gates in the fault tree structure. These static blocks represent manual action and have been indicated by blue blocks in the fault trees. Foam system, in contrast, have a significantly lower reliability caused by the presence of large numbers of OR gates in the fault tree structure. Figure 33 in the appendix compares the reliabilities of the five systems analysed by fault trees. The strength of the fault tree method is that it can in principle be used for any system, regardless of its complexity. The disadvantage of this method is the fact that it does not take into account interactions between components and knock-on effects. In other words, the failure probabilities of different components of the same system are not necessarily independent; damage to one component may affect the failure probability of other (neighbouring) components. For this reason, a failure rate derived with the fault tree method is only an approximation of the system‘s actual failure rate. It appears that some of the failure rates derived for this report are unrealistically high (in particular for the foam system) and should be treated with caution. A refined analysis might be required to obtain more reliable results. Nonetheless, the methodology can yield useful results when no other sources of data are available. It is advisable to compare the results of any fault tree analysis with experimental or historical data whenever possible to verify the predictions of the model.

Page 66: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

66

5 References

1. Nilsen, O.V. Risk Analysis for Cruise Ships (SAFEDOR, Deliverable 4.1.2). s.l. : DNV, 2007.

2. NRI. Worldcruise Network. [Online] 2010. http://www.worldcruise-network.com/projects/genesis/.

3. MCA. Maritime and Coast Guard Agency. [Online] 2010. http://www.mcga.gov.uk/c4mca/mcga-guidance-regulation/mcga-gr-solas_ii-2.htm.

4. National Fire Protection Association. NFPA 550: Guide to the Fire Safety Concepts Tree. 2007.

5. International Maritime Organization. Guidelines for Smoke Control and Ventilation Systems for Internal Assembly Stations and Atriums on New Passenger Ships. 2002. http://www.imo.org/includes/blastDataOnly.asp/data_id%3D5334/1034.pdf.

6. IMO Sub Committee on Fire Protection. Report to the Maritime Safety Committee. s.l. : International Maritime Organization, 2009. http://www.uscg.mil/imo/fp/docs/fp53-report.pdf.

7. SINTEF Industrial Management. Offshore Reliability Data Handbook. s.l. : OREDA participants, 2002.

8. —. Offshore Reliability Data Handbook. s.l. : OREDA participants, 2009.

9. The Reliability Information Analysis Center. Nonelectronic Parts Reliability Data. 1995.

10. Maritime Training Advisory Board. Marine Fire Prevention, Fire Fighting and Fire Safety. s.l. : Dept. of Commerce, Maritime Administration, 1979.

11. Cote, Arthur E. Operation of Fire Protection Systems. s.l. : NFPA, 2003.

12. IMO Assembly. Revised Guidelines for Approval of Sprinkler Systems. s.l. : International Maritime Organization, 1995. http://www.imo.org/includes/blastDataOnly.asp/data_id%3D22567/A800.pdf.

13. Indian Registry of Shipping Archive.

14. International Maritime Organization. MSC/Circ. 850. 1998. http://www.mpa.gov.sg/sites/circulars_and_notices/pdfs/shipping_circulars/mc00-07a.pdf.

15. Private correspondence with IMO.

Page 67: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

67

16. Estimates of the Operational Reliability of Fire Protection Systems. Bukowski R.W., Budnick E.K. and Schemel C.F. s.l. : Fire Protection Strategies for 21st Century Building and Fire Codes Symposium, 1999.

17. J.R., Hall. U.S. Experience with Sprinklers and Other Automatic Fire Extinguishing Equipment. s.l. : National Fire Protection Association, 2010.

18. NTUA. Probabilistic Framework for Onboard Fire Safety - Comprehensive Fire Accidents Database. s.l. : FIREPROOF Deliverable 1.1, 2010.

19. VTT Technical Research Centre of Finland. Survivability for Ships in Case of Fire. s.l. : Final Report of SURSHIP-FIRE project, 2009.

20. NTUA, SSRC. Probabilistic Framework for Onboard Fire Safety - Fire Ignition Model Specification. s.l. : FIREPROOF Deliverable 1.2, 2010.

21. International Maritime Organisation. MSC/Circ. 850. 1998. http://www.mpa.gov.sg/sites/circulars_and_notices/pdfs/shipping_circulars/mc00-07a.pdf.

Page 68: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

68

Appendix - Fault trees and diagrams used in the

failure rate analysis

Figure 27 - Foam System on Reliasoft BlockSim

Page 69: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

69

Figure 28 - Water Mist System on Reliasoft BlockSim

OR

Water mist fails to suppress fire

SV

Solenoid valve failure

OR

Improper Water Supply

N

Nozzzle Failure

P

Piping damage

OR

Pump failure

V

Pre pump valve failure/ mistakenly closed

MD

Mechanical damage

MS

Main supply failure

ES

Emergency supply failure

AND

Power supply failure

V

Section valve failure/ mistakenly closed

PF

Fail to operate pump

Page 70: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

70

Figure 29 - Set-up of the Hi-Fog system

Page 71: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

71

Figure 30 - Sprinkler System on Reliasoft BlockSim

Top

No Discharge

O R

A utomatic

Sprinkler Sy stem

Fail to start

O R

Sprinkler Pump

Fail to start

A ND

Pressure

Tank Failure

PG

Pressure

Gauge Failure

E

Jocky pump

Failure

A ND

No Power

Supply

MStF

O perator Fail to start

A ND

No Power

Supply

MS

Main Supply

Failure

ES

Emergency Supply

Failure

ES

Emergency Supply

Failure

MS

Main Supply

Failure

C

C ompressor

Damage

MD

Mechanical

Damage

D

Detection

Failure

PS

Pressure sw itch

Failure

MD

Mechanical

Damage

MD

Mechanical Damage

ES

Emergency Supply

Failure

A ND

No Power

Supply

MS

Main Supply

Failure

RV

V alv e Failure

O R

Emergency Pump

Fail to start on demand

O R

F ire Main Fail to start on demand

MStF

O perator fails

to start

MD

Mechanical Damage

Page 72: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

72

Figure 31 - CO2 System on Reliasoft BlockSim

Page 73: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

73

Figure 32 - Detector System on Reliasoft BlockSim

Page 74: Probabilistic Framework for Onboard Fire Safety...The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based approach to fire safety. The aim of work package

74

Figure 33- Reliabilities of systems analysed by fault trees over one year

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 50 100 150 200 250 300 350

Re

liab

ility

/%

Time / Days

Sprinkler System

Foam System

Mist System

CO2 System

Detector System

Hi-Fog System