pro fib us
TRANSCRIPT
Manual
Profibus DP
for NORDAC Frequency Inverters
SK TU1-PBR, -24V, -KL SK CU1-PBR
SK 700E / SK 750E
SK TU2-PBR, -24V trio SK 300E / SK 750E
SK TU3-PBR, -24V SK 500E / SK 520E / SK 530E
Profibus mc vector mc
Illustration of the units with options
BU 0020 GB
Getriebebau NORD GmbH & Co. KG
NORDAC Profibus DP Manual
2 BU 0020 GB
NORDAC Frequency Inverters
Safety and Operating Instructions for Drive Converters
(Compliant: Low voltage directive 73/23/EEC)
1. General information
During operation, drive converters can have, depending on their degree of protection, electrically live, uninsulated and possibly also moving or rotating parts as well as hot surfaces.
Inadmissibly removing the required covers, improper use, and incorrect installation or operation may result in severe damages and injuries.
See the documentation for further information.
Only qualified personnel are to carry out work involving transportation, installation and startup as well as maintenance (observe IEC 364 or CENELEC HD 384 or DIN VDE 0100 and IEC 664 or DIN VDE 0110 and national accident prevention regulations).
Qualified personnel in the context of these basic safety notes are persons familiar with installation, assembly, startup and operation of the product and who possess the necessary qualifications.
2. Proper use
Drive converters are components which are intended to be built into electrical systems or machines.
When being installed into machines, commissioning the drive converters (i.e. initiation of proper operation) is not permitted until it is determined that the machines comply with the provisions of EC directive 89/392/EEC (Machinery Safety Directive); EN 60204 should be observed.
Commissioning (i.e. initiation of proper operation) is only allowed upon compliance with the EMC directive (89/336/EEC).
The drive converters fulfil the requirements of the low voltage directive 73/23/EEC. They are subject to the standardized norms, series prEN 50178/DIN VDE 0160 in conjunction with EN 60439-1/ VDE 0660 part 500 and EN 60146/ VDE 0558.
The technical data and the information on electrical connection conditions are listed on the rating plate as well as in the documentation, and must be observed under all circumstances.
3. Transport, storage
You must observe the instructions on transportation, storage and proper handling.
4. Installation
Installation and cooling of the devices must take place according to the specifications in the relevant documentation.
Protect the drive converters from excessive stress. In particular, no components may be bent or insulating distances altered during transport and handling. Avoid contact with electronic components and contacts.
Drive converters contain electrostatically sensitive components, which are easily damaged through improper handling. Electrical components must not be mechanically damaged or destroyed (potential health risks).
5. Electrical connection
When working on live drive converters, the applicable national accident prevention rules must be complied with (e.g. VBG 4).
Electrical installation shall be carried out according to pertinent regulations (e.g. conductor cross sections, fusing, protective conductor / PE connection). Further instructions are found in the documentation.
You will find notes on EMC-compliant installation, such as shielding, earthing, arrangement of filters and routing of lines, in the documentation for the drive converter. These notes must also always be observed when using CE-marked drive converters. The compliance with limit values required by the EMC legislation is the responsibility of the manufacturer of the machine or system.
6. Operation
If necessary, systems including drive converters must be equipped with additional monitoring and protection devices according to the applicable safety regulations (e.g. law on technical equipment, regulations for the prevention of accidents, etc.). Changes to the drive converters by means of the operating software are allowed.
Immediately after a drive converter has been disconnected from the voltage supply, no live components and power connections should be touched because capacitors can still be charged. Note the respective warning signs on the drive converter.
All protective covers must be kept closed during operation.
7. Maintenance and servicing
Refer to the manufacturer's documentation.
Note: This supplemental operating manual is only valid in conjunction with the product-specific operating manual delivered with each drive converter.
About this document
BU 0020 GB 3
Documentation
Description: BU 0020 GB
Mat. no.: 607 02 02
Unit series: Profibus DP for SK 300E, SK 500/520/530E, SK 700E, SK 750E, vector mc
Version list
Description of previous editions Software Release
Remarks
BU 0020 GB, February 2005 V. 1.0 R0 First edition, pilot series
BU 0020 GB, May 2006 V. 1.1 R0 Correction and initiation of the frequency inverter series SK 500/520E and SK 750E, right-angle plug for SK TU2-PBR-24V not possible (Chap. 2.2)
BU 0020 GB, August 2006
Mat. No. 607 02 02 / 3806
V. 1.1 R0 Parameter adjustment for SK 500/520/530E, correction of the recommended M8/M12 plug, SW2/3 and IW2/3 adjustment, correction P513 = 0,1s
Publisher
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 D-22941 Bargteheide http://www.nord.com/
Telephone +49 (0) 45 32 / 401-0 Fax +49 (0) 45 32 / 401-555
Proper use of the frequency inverter
As a prerequisite to fault-free operation and fulfilment of warranty claims, you must adhere to the information in the operating manual. Therefore, you must first read the operating manualbefore starting work with the unit.
The operating manual contains important service notes. Keep it near the unit.
The Profibus module may only be used with the frequency inverter production series for which it is intended. Only the SK CU1-... modules used with SK 700E and SK 750E or the SK TU2-... with SK 300E and SK 750E may be used with the entire production series. Using this module on other units is not permitted and may lead to their destruction.
The Profibus modules and the associated frequency inverters are units intended for stationary installation in switching cabinets or decentralised assemblies. All specifications referring to the technical data and the permissible conditions where the unit is operated must be observed.
Commissioning (i.e. the initiation of proper use) is not permitted until it has been ensured that the machine complies with the EMC directive 89/336/EEC and that conformity with machine directive 89/392/EEC is established for the finished product (observe EN 60204).
Getriebebau NORD GmbH & Co. KG, 2006
NORDAC Profibus DP Manual
4 BU 0020 GB
Table of contents
BU 0020 GB 5
1 INTRODUCTION........................................................6
1.1 General ............................................................6
1.2 The bus system ...............................................6
1.3 PROFIBUS DP used with NORDAC frequency inverters .........................6
2 SUBASSEMBLIES....................................................7
2.1 NORDAC SK 500E / 520E / 530E...................7
2.1.1 Profibus module SK TU3-PBR...........................8
2.1.2 Profibus module SK TU3-PBR-24V ...................8
2.1.3 Mounting the SK TU3 Technology box ..............9
2.2 NORDAC SK 700E........................................10
2.2.1 SK TU1-PBR ...................................................11
2.2.2 SK TU1-PBR-24V............................................11
2.2.3 Mounting the SK TU1 Technology box ............12
2.2.4 SK CU1-PBR...................................................13
2.2.5 Mounting the SK CU1 customer interface........14
2.3 NORDAC trio SK 300E/ 750E .......................17
2.3.1 SK TU2-PBR ...................................................18
2.3.2 SK TU2-PBR-24V............................................19
2.3.3 SK TU2-PBR-KL..............................................20
2.3.4 Subassembly status messages .......................20
2.3.5 Recommended plug components ....................21
2.3.6 Mounting the SK TU2 Technology box ............24
2.4 NORDAC vector mc ......................................25
2.4.1 Profibus module used with vector mc ..............26
2.4.2 Mounting the Technology box mc....................26
3 THE PROFIBUS PROTOCOL ............................... 27
3.1 Overview........................................................27
3.2 PROFIBUS masters ......................................27
4 BUS ARCHITECTURE........................................... 28
4.1 Laying the bus cables....................................28
4.2 Conductive material.......................................28
4.3 Cable routing and shielding (EMC measures) ...........................................28
4.4 Recommendations from the PROFIBUS Nutzerorganisation e.V. [PROFIBUS User Organisation] ....................29
5 SETTING PARAMETERS ......................................30
5.1 BUS parameter SK 300E/ 700E/ 750E/ vector mc ..................30
5.2 Bus parameters SK 500E/ 520E/ 530E .........35
5.3 Fault monitoring .............................................40
6 DATA TRANSFER..................................................41
6.1 Utility data structure .......................................41
6.2 PPO types......................................................42
6.2.1 PPO types SK 300E/ 700E/ 750E/ vector mc.. 43
6.2.2 PPO types SK 500E/ 520E/ 530E ................... 43
6.3 Process data (PZD) .......................................44
6.3.1 Process data with SK 300E/ 700E/ 750E/ vector mc.................... 44
6.3.2 Process data with SK 500E/520E/530E .......... 44
6.3.3 The control word.............................................. 45
6.3.4 The status word (ZSW) ................................... 46
6.3.5 Setpoint 1 (SW1) ............................................. 47
6.3.6 Second and third setpoint (SW2/3).................. 48
6.3.7 Actual value 1 (IW1) ........................................ 48
6.3.8 Actual value 2 and actual value 3 (IW2/3) ....... 49
6.4 The status machine .......................................49
6.5 Parameter section (PKW)..............................51
6.5.1 Parameter label (PKE) .................................... 51
6.5.2 Subindex (IND)................................................ 54
6.5.3 Parameter value (PWE) .................................. 54
7 SAMPLE TELEGRAMS..........................................55
7.1 Starting disabled Ready to start ................55
7.2 Enable with 50% setpoint value.....................56
7.3 Writing a parameter .......................................57
8 ADDITIONAL INFORMATION ...............................58
8.1 Device master data – GSD file ......................58
8.2 PROFIDRIVE standard parameters ..............58
8.3 Consistent data transfer.................................58
8.4 Repair ............................................................59
9 INDEX ......................................................................60
10 REPRESENTATIVES AND OFFICES .................62
NORDAC Profibus DP Manual
6 We reserve the right to make technical changes BU 0020 GB
1 Introduction
1.1 General
This PROFIBUS DP documentation is only valid for the NORDAC trio SK 300E, SK 500E/ 520E/ 530E, SK 700E, SK 750E and vector mc series.
All basic units are delivered with a blank cover for the Technology box slot. The basic design includes no components for configuration or control.
A Profibus customer interface or a Profibus technology component (depending on the unit series) must be installed in order to establish communication with the Profibus DP.
1.2 The bus system
A multitude of differing automation devices can exchange data using Profibus. PLC, PC, operating and monitoring units are able to communicate via a single bus in serial bit mode. PROFIBUS DP is chiefly used in the area of communication between sensor and actuator, in which quick system reaction times are necessary. PROFIBUS DP is suitable as a replacement for cost-intensive parallel signal transmission using 24V and is suited for the transmission of measured values. This PROFIBUS variant, optimised for speed, is used for applications such as operating frequency inverters connected to automation devices.
In Germany, directives on data exchange have been defined in DIN 19245 parts 1 and 2 as well as in application specific supplements constituting part 3 of this standard. In the course of European field bus standardisation, PROFIBUS will be integrated into the European field bus standard EN 50170.
1.3 PROFIBUS DP used with NORDAC frequency inverters
Features:
Electrically isolated bus interfaces
Standard transfer rate up to 1.5Mbit/s, up to 12Mbit/s possible, depending on design.
Problem-free connection to the inverter using a 9-pin sub-D plug, an M12 round plug, screw terminals
(Technology box) or tension spring clamps (customer interface)
Status display with 2 LEDs (Technology box)
Problem-free programming of all frequency inverter parameters
Controlling the frequency inverter using the Profibus connection
Transmitting setpoint positions for SK 700E/750E with the PosiCon option
Transmitting the current frequency inverter status during operation
Up to 126 frequency inverters can be connected to one bus
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 7
2 Subassemblies
2.1 NORDAC SK 500E / 520E / 530E
By using various modules for display, control and configuration, the NORDAC SK 500E / 520E / 530E may be conveniently adapted to the most diverse requirements.
For simple operation, alpha-numeric display and operating modules may be used. For complex tasks, you may select from various connections to your PC or automation system.
The Technology box (Technology unit, SK TU3-...) is mounted externally on the frequency inverter. This allows easy access and means that it can be exchanged at any time.
As delivered, without the Technology box, 2 LEDs (green/red) are externally visible. These indicate the current unit status.
The green LED indicates that mains voltage is available. During operation, through a flash code that increases in speed, it indicates the degree of overload at the frequency inverter output.
The red LED indicates that faults are present by flashing with a frequency that corresponds with the numerical code of the fault (manual BU 0500, chap. 6).
LEDred/green
NORDAC Profibus DP Manual
8 We reserve the right to make technical changes BU 0020 GB
GND
RTS
6
15
9
+5V
A data
B data
SK TU3 Profibus module
The Profibus DP communication assemblies SK TU3-PBR and SK TU3-PBR-24V serve as interface units for drives of the unit series SK 500E/ 520E/ 530E onto higher-level automation systems via Profibus DP.
WARNING
NOTE
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
2.1.1 Profibus module SK TU3-PBR
This Profibus module is supplied internally with power from the frequency inverter. Thus, this Profibus slave is recognised by the master system only when the frequency inverter is connected to the mains supply.
Terminating resistor
The terminating resistor for the final bus slave is the Profibus standard plug.
A transfer rate of up to 1.5Mbit/s may be used.
2.1.2 Profibus module SK TU3-PBR-24V
This Profibus module is supplied with voltage via an external 24V connection. Thus, this Profibus slave is recognised by the master system even when the frequency inverter is not connected to the mains supply. The information required for this is set using a rotary coding switch. This information is transferred when the 24V supply is connected.
A transfer rate of up to 12Mbit/s may be used.
Connecting the power supply
The power supply is 24V DC 25% (terminal 45 = 24V, terminal. 46 = GND, approx. 100mA). The connection is made using screw terminals with a maximum cable cross section of 2.5 mm². When using flexible cables, conductor end sleeves should be used.
The socket assignment is identical to the SK TU3-PBR option.
Terminating resistor
The terminating resistor for the final bus slave is in the Profibus standard plug.
Profibus Status LEDs
BR (green) Bus Ready
BE (red) Bus Error
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 9
Setting the PPO type
The rotary coding switch for the PPO type allows you to choose between the 4 PPO types (chap. 6.2). 1 to 4 means the address range 00 to 99; with +100, you can set addresses from 100 to 127.
When set to PGM, the value from parameter P507 of the frequency inverter is used. In this case, the frequency inverter must be supplied with power.
Setting the Profibus address
The Profibus addresses may be set as decimals (0 to 99) using the rotary coding switches, labelled "x10" and "x1".If the PPO switch is set to PGM, the value from parameter P509 of the frequency inverter is used. In this case, the frequency inverter must be supplied with power.
Notice: The settings made with the rotary coding switches are not transmitted to or saved in the frequency inverter.
NOTEThe cable shield must be connected to the functional ground
1 (normally, the electrically
conductive mounting platform) in order to avoid EMC interference in the unit.
Technology box: In order to achieve this, the Profibus plug should be comprehensively connected with the metal case of the D-sub plug and the functional ground in the cable shield.
2.1.3 Mounting the SK TU3 Technology box
Technology boxes are mounted as follows:
1. Disconnect mains voltage, observe waiting period.
2. Remove or slide the control terminal cover a little to the bottom.
3. Loosen the release on the lower edge of the blank cover and remove the cover with an upwardly turning motion. In some cases, the locking screw next to the latch will need to be removed.
4. Hook the Technology box on the upper edge and click it into place using light pressure. Be sure that the connector strip makes full contact. When needed, fix it into place with the screw (accessories kit).
5. Close the control terminal cover.
1 Electrical operating equipment is generally connected to a functional ground in systems and plants. As a piece of
operating equipment, the functional ground serves to discharge compensation and interference currents, and to secure EMC properties, so that it must be installed and used in terms of these high frequency technologies.
NORDAC Profibus DP Manual
10 We reserve the right to make technical changes BU 0020 GB
2.2 NORDAC SK 700E
By using various modules for display, control and configuration, the NORDAC SK 700E may be conveniently adapted to fulfil the most diverse requirements.
For simple operation, alpha-numeric display and operating modules may be used. For complex tasks, you may select from various connections to your PC or automation system.
The Technology box (Technology unit, SK TU1-...) is mounted externally on the frequency inverter. This makes it easily accessible and means that it can be replaced at any time.
Additionally, other modules (customer interfaces and special options) can be installed within the frequency inverter. These may be used to process digital and analogue signals; they are also suitable for speed control or positioning.
SK TU1 Profibus module
The Profibus DP communication subassemblies SK TU1-PBR and SK TU1-PBR-24V serve as interface units for drives of the unit series SK 700E onto higher-level automation systems through the Profibus DP.
WARNING
NOTE
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 11
GND
RTS
6
15
9
+5V
A data
B data
2.2.1 SK TU1-PBR
This Profibus option is supplied internally with
power from the frequency inverter. Thus, this
Profibus slave is recognised by the master system
only when the frequency inverter is connected to
the mains supply.
Terminating resistor
The terminating resistor for the final bus slave is in the Profibus standard plug.
A transfer rate of up to 1.5Mbit/s may be used.
2.2.2 SK TU1-PBR-24V
This Profibus option is supplied with voltage via an external 24V connection. Thus, this Profibus slave is recognised by the master system even when the frequency inverter is not connected to the mains supply. The information required for this is set using a rotary coding switch. This information is transferred when the 24V supply is connected.
A transfer rate of up to 12Mbit/s may be used.
Connecting the power supply
The power supply is 24V DC 25% (terminal 45 = 24V, terminal. 46 = GND, approx. 100mA). The 24V connection is made via insulation displacement connectors (IDC). The maximum cable cross section is 2.5 mm². When using flexible cables, conductor end sleeves should be used.
The socket assignment for the 9-pin D-Sub socket is identical to the SK TU1-PBR option.
Terminating resistor
The terminating resistor for the final bus slave is in the Profibus standard plug.
Setting the PPO type
The rotary coding switch for the PPO type allows you to choose between the 4 PPO types (chap. 6.2). 1 to 4 means the address range 00 to 99; with +100, you can set addresses from 100 to 127.
When set to PGM, the value from parameter P507 of the frequency inverter is used. In this case, the frequency inverter must be supplied with power.
Setting the Profibus address
The Profibus addresses may be set as decimals (0 to 99) using the rotary coding switches PGM , labelled "x10"and "x1". If the PPO switch is set to PGM, the value from parameter P509 of the frequency inverter is used. In this case, the frequency inverter must be supplied with power.
Note: The settings made with the rotary coding switches are not transmitted into or saved in the frequency inverter. Until the end of 2005, "x16" hex-coding switches were used. This led to a differing determination of the bus address.
NOTEThe cable shield must be connected to the functional ground
2 (normally, the electrically
conductive mounting platform) in order to avoid EMC interference in the unit.
Technology box: In order to achieve this, the Profibus plug should be solidly connected comprehensively with the metal case of the D-sub plug and the functional ground in the cable shield.
2 Electrical operating equipment is generally connected to a functional ground in systems and plants. As a piece of
operating equipment, the functional ground serves to discharge compensation and interference currents, and to secure EMC properties, so that it must be installed and used in terms of these high frequency technologies.
Profibus Status LEDs
BR (green) Bus Ready
BE (red) Bus Error
NORDAC Profibus DP Manual
12 We reserve the right to make technical changes BU 0020 GB
2.2.3 Mounting the SK TU1 Technology box
Technology boxes are mounted as follows:
1. Switch off mains voltage, observe waiting period.
2. Remove the blank cover by pressing on the release on the upper and lower edge.
3. Use light pressure to press the Technology box onto the mounting surface until it audibly clicks into place.
WARNING
NOTE
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
700E
N O R D A C700E
N O R D A C
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 13
Detail: DIP switch
2.2.4 SK CU1-PBR
In addition to the data connections, all bus customer interfaces also have conventional digital inputs and outputs.
The relay contact can transmit a braking control or also a warning to another system.
Various digital functions can be programmed for the input. The digital input is equipped to evaluate a temperature sensor with a switching threshold of 2.5V.
The bus terminating resistor (Rab) can be connected. To do this, both switches must be set at "On". A transfer rate of up to 1.5Mbit/s may be used.
NOTICE: All control voltages refer to a
common reference potential. The AGND /0V and GND /0V are linked within the unit.
Bus system data cable:
Profibus (terminal 81-82, PBR A/B)
SPC output: 2.5 ... 33V
Output relay: max. 2.0A 28V DC /230 V AC
Digital input 1 (P420)
Power supply: 5V, max. 300 mA
Power supply: 15V, max. 300mA
DIP switch for terminating resistor, only at this position with Profibus.
NOTICE:Internal 5V power supply
- do not use -
NOTICE: 83 RTS = ready to send... only required with a few
Profibus modules
X6.1
X6.2
X6.3
01 REL1.1
02 REL1.2
47 PBR +5V
48 PBR 0V
81 PBR A
82 PBR B
40 GND / 0V
41 VO +5V
83 PBR RTS
X6.4
81 PBR A
82 PBR B
90 SHIELD
21 DIG IN 1
42 VO +15V
RTA
RTB
3 Electrical operating equipment is generally connected to a functional ground in systems and plants. As a piece
of operating equipment, the functional ground serves to discharge compensation and interference currents, and to secure EMC properties, so that it must be installed and used in terms of these high frequency technology.
NOTEThe cable shield must be connected to the functional ground
3
(normally, the electrically conductive mounting platform) in order to avoid EMC interference in the unit.
Profibus, SK CU1-PBR
Functions Maximum cross section
X6.1 Output relay 1.5 mm2
X6.2 Digital input 1.5 mm2
X6.3 Data lines 1.5 mm2
X6.4 Data lines, parallel 1.5 mm2
NORDAC Profibus DP Manual
14 We reserve the right to make technical changes BU 0020 GB
Kundenschnittstelle
Sondererweiterung
TechnologieboxVerrieglungsstift
CLOSED
OPEN
Verriegelung geschlossen
Verriegelung geöffnet
Customerinterface
Spezial extension
Technology unit Locking lever
Lock closed
Lock open
2.2.5 Mounting the SK CU1 customer interface
WARNING
NOTE
Only qualified personnel, carefully observing all safety and warning instructions, may install this device.
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
1. Disconnect mains voltage, observe waiting period.
2. Remove the cover grid of the connection area by loosening 2 screws and either pry off (slots) or pull off the housing cover.
3. Move the locking lever to the "open" position.
4. Insert the customer interface into the upper guide rail with light pressure until it clicks into place.
5. Move the locking lever to the "closed" position.
6. Pull out the connection plug by pressing on the release and make the required connections. Next, insert the plug until it clicks into place.
7. Replace all covers.
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 15
Removing the customer interface
1. Disconnect mains voltage, observe waiting period.
2. Remove the cover grid of the connection area by loosening 2 screws and either pry off (slots) or pull off the housing cover
3. Move the locking lever to the "open" position.
4. Using a screwdriver (as shown), detach the customer interface from the locking position and, pull it out completely by hand.
5. Move the locking lever to the "closed" position.
6. Replace all covers.
NOTE
After installing, exchanging or removing modules, message E017, "Change to customer interface", will be displayed after the unit is switched on again.
This message can be immediately reset using the normal measures.
NORDAC Profibus DP Manual
16 We reserve the right to make technical changes BU 0020 GB
Different positions of the customer interface for units 30 kW and larger:
NOTE
WARNING
Only qualified personnel, carefully observing all safety and warning instructions, may install this device.
Never connect or disconnect the customer interface while it is supplied with power.
After installing, exchanging or removing modules, message E017, "Change to customer interface", will be displayed after the unit is switched on again
The procedure is the same as that described on the previous pages, except that there is no locking lever. Click the modules into place by pressing inward on the front edge.
... or different removal procedures for the customer interface for units 30 kW and larger:
Simply pry out, as shown, on the upper edge. If this is too difficult, simply loosen the hooks on the front edge.
NOTE: Be sure to pay attention that the network voltage is shut off and that a sufficient waiting time has elapsed.
Getriebebau NORDGmbH & Co. KG
D-22941 Bargteheide / Germany
Typ/Part-No: SK_XU1_POS 7820055/10C195890
Input: 6 x digital 15V / 24V
Output: 2 x relay 5A 250V~/AC1
Interface: 1 x encoder A,B,N RS422
1 x SSI DAT/CLK RS422
X10.1 X10.2 X10.3
5
DIG
IN
1
6 D
IG IN
2
7 D
IG IN
3
8 D
IG IN
4
11 +
15
V
1
RE
L1
.1
2
RE
L1
.2
3
RE
L2
.1
4
RE
L2
.2
9 D
IG IN
3
10 D
IG IN
4
12
0V
/ G
ND
13 S
SI C
LK
+
14 S
SI C
LK
-
15 S
SI D
AT
+
16 S
SI D
AT
-
17
+5
V
18 0
V /
GN
D
19 S
PU
R A
+
20 S
PU
R A
-
23 S
PU
R N
+
21 S
PU
R B
+
22 S
PU
R B
-
24 S
PU
R N
-
X10.3
Getriebebau NORDGmbH & Co. KG
D-22941 Bargteheide / Germany
Typ/Part-No/ID: SK_CU1_MLT 7820051/10C195890
Input: 2 x analog -10...10V / 0...20mA
6 x digital 15V / 24V
Output: 2 x analog 0...10V
2 x relay 5A 250V~/AC1
X2.1 X2.2 X2.3
11 V
RE
F 1
0V
12
AG
ND
/0V
14
AIN
1 +
16
AIN
2 +
17
AO
UT
1
21 D
IG IN
1
22
DIG
IN
2
23
DIG
IN
3
24
DIG
IN
4
42
VO
+15V
1 R
EL
1.1
2 R
EL
1.2
3 R
EL
2.1
4 R
EL
2.2
25
DIG
IN
5
26
DIG
IN
6
18
AO
UT
2
41
VO
+5V
40
GN
D/0
V
0/4
...2
0m
A (
ON
)
AIN 1
-10/0
...1
0V
(O
FF
)
0/4
...2
0m
A (
ON
)
AIN 2
-10/0
...1
0V
(O
FF
)
Customer interface
Specialextension
Getriebebau NORDGmbH & Co. KG
D-22941 Bargteheide / Germany
Typ/Part-No: SK_XU1_POS 7820055/10C195890
Input: 6 x digital 15V / 24V
Output: 2 x relay 5A 250V~/AC1
Interface: 1 x encoder A,B,N RS422
1 x SSI DAT/CLK RS422
X10.1 X10.2 X10.3
5
DIG
IN
1
6 D
IG IN
2
7 D
IG IN
3
8 D
IG IN
4
11 +
15
V
1
RE
L1
.1
2
RE
L1
.2
3
RE
L2
.1
4
RE
L2
.2
9 D
IG IN
3
10 D
IG IN
4
12
0V
/ G
ND
13 S
SI C
LK
+
14 S
SI C
LK
-
15 S
SI D
AT
+
16 S
SI D
AT
-
17
+5
V
18 0
V /
GN
D
19 S
PU
R A
+
20 S
PU
R A
-
23 S
PU
R N
+
21 S
PU
R B
+
22 S
PU
R B
-
24 S
PU
R N
-
X10.3
Getriebebau NORDGmbH & Co. KG
D-22941 Bargteheide / Germany
Typ/Part-No/ID: SK_CU1_MLT 7820051/10C195890
Input: 2 x analog -10...10V / 0...20mA
6 x digital 15V / 24V
Output: 2 x analog 0...10V
2 x relay 5A 250V~/AC1
X2.1 X2.2 X2.3
11 V
RE
F 1
0V
12
AG
ND
/0V
14
AIN
1 +
16
AIN
2 +
17
AO
UT
1
21 D
IG IN
1
22
DIG
IN
2
23
DIG
IN
3
24
DIG
IN
4
42
VO
+15V
1 R
EL
1.1
2 R
EL
1.2
3 R
EL
2.1
4 R
EL
2.2
25
DIG
IN
5
26
DIG
IN
6
18
AO
UT
2
41
VO
+5V
40
GN
D/0
V
0/4
...2
0m
A (
ON
)
AIN 1
-10/0
...1
0V
(O
FF
)
0/4
...2
0m
A (
ON
)
AIN 2
-10/0
...1
0V
(O
FF
)
Customer interface
Specialextension
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 17
2.3 NORDAC trio SK 300E/ 750E
Technology boxes (Technology Unit) are optional subassemblies which bring increased functionality to the frequency inverter, adapting it to the application requirements. Whichever Technology box is used, the frequency inverter retains its high degree of protection.
SK TU2 Profibus modules
The Profibus DP communication subassemblies SK TU2-PBR, SK TU2-PBR-KL and SK TU2-PBR-24V serve as interface units for drives of the unit series trio SK 300E/750E with higher-level automation systems via the Profibus DP.
Technology box:
SK TU2-... Description Specifications
Profibus module
SK TU2-PBR
This interface enables the NORDAC trio SK 300E/ 750E to be controlled over the serial Profibus port.
2x 5 pin M12 system plug
Transfer rate up to 1.5Mbit/s
Profibus module
SK TU2-PBR-24V
This interface allows for the NORDAC trio SK 300E/ 750E to be controlled over the serial Profibus port.
2x 5 pin M12 system plug
1 power supply 24V/100mA, M8
Transfer rate up to 12Mbit/s
Profibus module
SK TU2-PBR-KL
This interface allows for the NORDAC trio SK 300E/ 750E to be controlled over the serial Profibus port.
8 pin screw terminal / Sub-D9 plug
Transfer rate up to 1.5Mbit/s
WARNING
NOTE
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
A separate earthing wire should be used to earth each module.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
Be sure to check for proper sealing after mounting is completed. (Do not forget the rubber seal).
NORDAC Profibus DP Manual
18 We reserve the right to make technical changes BU 0020 GB
2.3.1 SK TU2-PBR
2x M12, 5-pin plug
No additional power supply
Transfer rate up to 1.5Mbit/s
Terminating resistor
The terminating resistor for the last bus slave can be connected to the output of the last frequency inverter as an end plug.
External M12 bus connection
Special connection accessories are required to connect an SK 300E / 750E with the Profibus option in an existing Profibus network. M12 connectors, which ensure the high IP55/66 type of protection, are used here. The M12 components recommended below are specially designed for Profibus applications. Shielding is provided, and the coding (B-coded) meets Profibus standards. When choosing a connector, be sure not to use the conventional A-coded M12 components.
Standard assignment
M12 pin Signal
1 + 5V
2 A data
3 GND
4 B data
5 Screen
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 19
2.3.2 SK TU2-PBR-24V
This Profibus option is supplied with power via an external 24V connection (M8 round plug). Thus, this Profibus slave is recognised by the master system even when the frequency inverter is not connected to the mains supply. The information required for this is set using a rotary coding switch. This information is transferred when the 24V supply is connected.
A transfer rate of up to 12Mbit/s may be used.
Connection assignments 24V dc
M8 pin Signal
1 24V DC 25%
3 GND
4 n.c.
External M12 Bus connection
Special connection accessories are required to connect an SK 300E / 750E with the Profibus option in an existing Profibus network. M12 connectors, (straight), which ensure the high IP55/66 type of protection, are used here. The M12 components recommended below are specially designed for Profibus applications. Shielding is provided, and the coding (B-coded) meets Profibus standards. When choosing a connector, be sure not to use conventional A-coded M12 components.
Terminating resistor
The terminating resistor for the last bus slave can be connected to the output of the last frequency inverter as an end plug.
Rotary coding switches
The rotary coding switches are located under the corresponding screw covers.
Setting the PPO type
The rotary coding switch for the PPO type allows you to choose between the 4 PPO types (chap. 6.2). 1 to 4 means the address range 00 to 99; with +100, you can set addresses from 100 to 127.
When set to PGM , the value from parameter P507 of the frequency inverter is used. In this case, the frequency inverter must be supplied with power.
Setting the Profibus address
The Profibus addresses may be set as decimals (0 to 99) using the rotary coding switches, labelled "x10" (tens position) and "x1" (ones position); with +100, addresses from 100 to 127 may be set. When set to PGM, the value from parameter P509 of the frequency inverter is used. In this case, the frequency inverter must be supplied with power.
Example: Profibus address = 30dec = x10=3, x1=0
Note: The settings made with the rotary coding switches are not transmitted into or saved in the frequency inverter. Until the end of 2005, "x16" hex-coding switches were used. This led to a differing determination of the bus address.
NOTE
Only commercial straight M12 plugs and sockets may be used with the SK TU2-PBR-24V module. Angled plugs may not be used.
Standard assignments
M12 pin Signal
1 + 5V
2 A Data
3 GND
4 B Data
5 Screen
NORDAC Profibus DP Manual
20 We reserve the right to make technical changes BU 0020 GB
Resistor Network(Profibus)
engaged
not engaged
ON
OFF
2.3.3 SK TU2-PBR-KL
8 x 2.5 mm2 screw terminals
Terminating resistor network (220/390 ) can be connected.
Sub-D9 plug only for finished product testing.
The cable enters through the 2-piece M16 screw connection. There are thus no plug-in contacts outside of the housing. Commercial series terminals are used for this option. The high degree of protection (IP55/66) is effected with the cover/(lid).
The bus and data cables lie parallel to terminals 3 / 6 (A data) and 4 / 7 (B data). In this way, incoming and outgoing cables can be easily distinguished from one another. An additional 24V power supply is not necessary. The frequency inverter supplies the power.
A terminating resistor (220 ) and pull-up / pull-down resistors (390 ) for the last bus slave can be connected with the micro-switch.
SK TU2-PBR-KL terminals Signal
1 + 5V
2 GND
3 A data
4 B data
5 RTS
6 A data
7 B data
8 Screen
2.3.4 Subassembly status messages
To enable quick recognition, the Profibus module's communication status is shown by two LEDs. These indicate various states of the module and communication with colours and flashing cycles.
Further information about the status messages is found in chapter 5.3, "Fault monitoring".
NOTEThe cable shield must be connected to the functional ground
4 (normally, the electrically conductive
mounting platform) in order to avoid EMC interference in the unit.
Technology box with D-sub plug: In order to achieve this, the Profibus plug should be solidly connected with the metal case of the D-sub plug and the functional ground in the cable shield.
4 Electrical operating equipment is generally connected to a functional ground in systems and plants. As a piece
of operating equipment, the functional ground serves to discharge compensation and interference currents, and to secure EMC properties, so that it must be installed and used in terms of high frequency technology.
BR (green) Bus Ready
BE (red) Bus Error
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 21
2.3.5 Recommended plug components
M12 plug
B-coded
Item no. Supplier Description
straight angled
MURR Elektronik Plug M12 straight B-coded 6..8 mm 7000-14001-0000000 ---
LUMBERG Plug M12 straight B-coded 0976 PMC 101 ---
Binder Plug M12 B-coded 99 1437 810 05 ---
plug
NORDAC Profibus DP Manual
22 We reserve the right to make technical changes BU 0020 GB
M12 socket
B-coded
Item no. Supplier Description
straight angled
MURR Elektronik Socket M12 straight B-coded 6..8 mm 7000-14021-0000000 ---
LUMBERG Socket M12 straight B-coded 0976 PFC 101 ---
Binder Socket M12 B-coded 99 1436 810 05 ---
socket
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 23
Terminating resistor
B-coded
Supplier Description Item no.
MURR Elektronik Bus terminating resistor M12 7000-14041-0000000
LUMBERG Profibus terminating resistor M12 0979 PTX 101
Binder --- ---
24V power supply
M8 socket
Supplier Description Item no.
LUMBERG M8 coupling with screw terminals RKMCK 3
Binder Sensor plug connector series 768 (M8x1), screw terminals
99-3400-100-03
Binder Cable socket extruded, screw connection, 3 m 79 3406 42 03
If needed, the manufacturers listed above can also provide pre-assembled Profibus cables.
NOTE / RECOMMENDATION: We recommend that you use pre-assembled M8 cable boxes for the 24V supply to the modules.
plug
socket
NORDAC Profibus DP Manual
24 We reserve the right to make technical changes BU 0020 GB
2.3.6 Mounting the SK TU2 Technology box
WARNING
NOTE
Only qualified personnel, carefully observing all safety and warning instructions, may install this device.
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
Technology boxes are mounted as follows:
1. Switch off mains voltage, observe waiting period.
2. Remove the blank cover by loosening the 6 hexagonal socket screws.
3. Disconnect the PE (earthing) connection and fasten it securely to the Technology box.
4. Make sure that the plug-in contacts and cover seal are properly seated.
5. Place the Technology box into position and fasten screws firmly.
NOTE Pay attention to the earthing wire!
The plug-in earthing wire, which is provided on the metallic cover of the standard unit and on each Technology box, must not be disregarded. Be sure to connect this wire when you install the Technology box to ensure that the device is completely earthed and provides safe operation.
Earthing the cover plate
Mounting screws on the Technology box
2 Subassemblies
BU 0020 GB We reserve the right to make technical changes 25
2.4 NORDAC vector mc
The NORDAC vector mc frequency inverter is normally provided without an operating module.
Parameters can only be set via the RS485 interface (control terminals) using USS protocol.
The following my be selected as an option:
o RS232 mc
o CANbus mc
o CANopen mc
o DeviceNet mc
o Profibus mc
o ControlBox mc (parameter setting / control panel)
o ParameterBox (Clear text control panel)
Please observe that there may be additional components or software necessary with the above subassemblies.
NOTEThe necessary parameter settings may be made using, for example, the ControlBox mc (option) or the RS485 customer interface with NORD CON software. The parameter numbers and values are displayed via the 4-digit, 7-segment LED display or the PC monitor.
It is possible to operate the RS485 interface with the Profibus mc module in parallel.
It is not possible to mount a Profibus mc module remote from the frequency inverter; it must be directly attached to the inverter.
NOTE on compatibility Current Profibus mc modules of version 2.1 or higher (see name plate) are only compatible with
NORDAC vector mc frequency inverters with software versions 27.4 and above (see parameter P707).
Older versions are not endorsed for the Profibus mc module and are only executable on older NORDAC vector mc frequency inverters.
NORDAC Profibus DP Manual
26 We reserve the right to make technical changes BU 0020 GB
Tech
nolo
gy
box
mc
2. 3.
1.
GND
RTS
6
15
9
+5V
A data
B data
2.4.1 Profibus module used with vector mc
The Profibus DP communication subassembly "Profibus mc" serves as interface units for drives of the unit series vector mc onto higher-level automation systems through the Profibus DP.
Transfer rate:
The standard design can be operated at a maximum of 1.5Mbit/s.
A 12Mbit/s variant is available upon special order (please note when ordering).
Terminating resistor:
The terminating resistor for the final bus slave is incorporated into the Profibus standard plug (not included in the delivery package).
WARNING
NOTE
Only qualified personnel, carefully observing all safety and warning instructions, may install this device.
Installing or removing the modules should only take place when the power is disconnected. The slots may only be used for the designated modules.
It is not possible to mount a Technology box remote from the frequency inverter; it must be directly attached to the frequency inverter.
2.4.2 Mounting the Technology box mc
The Profibus mc Technology box is mounted as follows:
1. Switch off mains voltage, observe waiting period.
2. Remove the blank cover by simply pressing on the upper edge.
3. First hook the Profibus mc module on the lower end and then on the upper end with light pressure towards the top and click it audibly into place.
In a short time after connection to the mains, the device is ready for operation.
vector mc
- side view -
3 Bus protocol
BU 0020 GB We reserve the right to make technical changes 27
3 The Profibus protocol
3.1 Overview
The second level of the ISO/OSI model defines, among other things, the
- General format of telegrams required for data transfer
- Bus access procedures
- Backup mechanisms
- Times to be ensured
- Possible transfer services
There is little that the user can do to vary the structure of level 2, since almost all services are included in the PROFIBUS-ASICs available so far.
3.2 PROFIBUS masters
PROFIBUS masters are field units which initiate data exchange with field units operating as slaves. Within the bus configuration, a master has sole access rights to the slaves (if there are several devices with master status, when it has been assigned access rights).
Before the system is started up, all of the data that a PROFIBUS master requires to exchange data (e.g. the I/O
range) must be prepared and loaded into the master ( GSD / master file).
The main tasks of a master are to:
- Exchange data with the designated slaves
- Co-ordinate access to the bus
- Undertake fault handling
- Make the data from the slaves available to the user
The following transfer services are defined for the PROFIBUS DP:
- SRD: Send and request data with acknowledgement. In one message cycle, the master transmits output data to a slave and receives input data from the slave as an answer within the same cycle.
- SDN: Send data with no acknowledgement. Allows broadcast telegrams to be transmitted (unacknowledged telegrams).
PROFIBUS DP masters are available as:
- A subassembly within an PLC
- A CPU assembly with an integrated PLC unit
- A standard PC subassembly
- A stand-alone board
NORDAC Profibus DP Manual
28 We reserve the right to make technical changes BU 0020 GB
4 Bus architecture
One bus segment consists of a maximum of 32 slaves. Multiple segments can be joined together using repeaters. In this way, a total of 126 slaves can participate in the application data exchange. Note that reaction times increase as more slaves are added.
The physical requirements for data transfer using a twisted and shielded two-wire conductor, which a serial bus system is supposed to meet, are defined in the specifications of the interference-resistant RS485 interface.
4.1 Laying the bus cables
In an industrial environment, proper installation of the bus system is extremely important to reduce possible interference. The following points are meant to provide some helpful information on how you may avoid interference and other problems right from the start. These cable laying instructions cannot be comprehensive. You must still follow the applicable safety and accident prevention rules.
4.2 Conductive material
The frequency inverter is generally coupled to the PROFIBUS system by a twisted, schielded two-wire cable. This bus cable is specified as conductor type A in the EN 50 170 standard. In order for the guaranteed transfer rates and distances to be actually available and without interference, the specified cable parameters must be observed.
Based on the cable types described above, the following lengths of cable in a bus segment yield these results.
Transfer rate
[kBit/s]9.6 19.2 45.45 93.75 187.5 500 1500 3000 6000 12000
Cable length 1200 1200 1200 1200 1000 400 200 100 100 100
4.3 Cable routing and shielding (EMC measures)
If no measures are taken to ensure electromagnetic compatibility, high-frequency interference, which is mainly caused by switching operations or through lightning strokes, will often disturb the electronic components in devices connected to the bus. Thus, trouble-free operation cannot be guaranteed.
Shielding the bus cable in a technically proficient manner suppresses the electrical interference received from other devices in an industrial area. The measures listed below should help you obtain optimal shielding characteristics:
Keep the cable connection between devices connected to the bus no shorter than 1 m.
Route long connections between devices connected to the bus in the shortest way possible.
The bus cable shielding must be solidly connected to the plug housing on both ends.
Avoid using spur lines to connect field devices to the bus.
Avoid using plug-and-socket connectors to extend bus cables.
A minimum distance of 20 cm should be kept between bus cables and other lines which carry more that 60V. This applies to canlöe routing both inside and outside switching cabinets.
4 Bus architecture
BU 0020 GB We reserve the right to make technical changes 29
Note: With the shielding connected at both ends, a compensating current, liable to damage electronic components, may flow if the earth potentials differ. Potential differences must be reduced by sufficient potential equalisation.
4.4 Recommendations from the PROFIBUS Nutzerorganisation e.V. [PROFIBUS User Organisation]
Please pay special attention to the information given in Profibus "Technical guidelines"
- "Installation Guidelines for PROFIBUS DP/FMS", September 1998, order no. 2.111.
- "Guideline Assembling" version 1.06, order no. 8.021/8.022
- "Guideline Commissioning" version 1.01, order no. 8.031/8.032
- Planning recommendations are being prepared
This technical information is available from the Internet in the download area at www.profibus.com/pb/.The pertinent files are found under "Installation Guide" ... "Handbook PROFIBUS Installation Guideline".
NORDAC Profibus DP Manual
30 We reserve the right to make technical changes BU 0020 GB
5 Setting parameters
In order for the frequency inverter to operate with the Profibus protocol, some settings must be made on the frequency inverter, in addition to the bus connection to the master.
The inverter parameters are mapped in the range 1000 to 1999 in the Profibus protocol. That means that
when configuring via the bus, you must add 1000 to the parameter numbers (e.g. P508 P1508).
5.1 BUS parameter SK 300E/ 700E/ 750E/ vector mc
To address the frequency inverter via Profibus, the Profibus address must be set in P508 and the PPO type in P507 or with the rotary coding switches on SK TU3-PBR-24V, both corresponding to the control configuration.
You can set the parameters for the frequency inverter at any time. The control signal source can be selected with the P509 (control word) parameter and the P510 (setpoint source) parameter. Telegram time-out P513 can be selected according to the bus system involved.
NOTE
Some parameters or parameter settings may be different or limited depending on the frequency inverter type and components involved.
Control terminal parameters
Parameter Setting value / Description / Note Availability with option
P480 ... - 01 ... ... - 10
Function bus I/O in bits Always visible
Bus I/O in bits are seen as digital inputs. Whose function is transmitted over the serial interface. You will find the functions for the bus in bits in the table of functions for the digital inputs P420...P425.
In order to use this function, one of the bus setpoints (P546, P547, P548) should be set at > Digital in bit 0...7 <. The desired function is then assigned to the corresponding bit.
[01] = Bus I/O in bit 0
[02] = Bus I/O in bit 1
[03] = Bus I/O in bit 2
[04] = Bus I/O in bit 3
[05] = Bus I/O in bit 4
[06] = Bus I/O in bit 5
[07] = Bus I/O in bit 6
[08] = Bus I/O in bit 7
[09] = Flag 1
[9] = Flag 2
0 ... 62
[ 12 ]
5 BUS Parameters SK 300E/ 700E/ 750E/ vector mc
BU 0020 GB We reserve the right to make technical changes 31
Parameter Setting value / Description / Note Availability with option
P481 ... - 01 ... ... - 08
Function bus I/O out bits Always visible
Bus I/O out bits are seen as digital outputs. Whose function is transmitted over the serial interface. You will find the functions for the bus out bits in the table of functions for the digital outputs (relay function) P434...P441.
In order to use this function, one of the bus actual values (P543, P544, P545) should be set at > Digital out bit 0...7 <. The desired function is then to assigned to the corresponding bit.
[01] = Bus I/O out bit 0
[02] = Bus I/O out bit 1
[03] = Bus I/O out bit 2
[04] = Bus I/O out bit 3
[05] = Bus I/O out bit 4
[06] = Bus I/O out bit 5
[07] = Bus I/O out bit 6 / Flag 1
[08] = Bus I/O out bit 7 / Flag 2
0 ... 38
[ 10 ]
P482 ... - 01 ... ... - 08
Normalisation: Bus I/O out bits Always visible
-400 … 400%
[ 100 ]
Adjustment of the limit values for the relay functions / bus out bits. With a negative value, the output function is reported negative.
The relay switch closes upon reaching the limit value and with positive setting values. The relay switch closes with negative setting values.
P483 ... - 01 ... ... - 08
Hysteresis: Bus I/O out bits Always visible
1 … 100%
[ 10 ]
The difference between the point in time for starting and stopping in order to avoid an oscillation in the output signal.
Additional parameters
Parameter Setting value / Description / Note Availability with option
P507 PPO type Always visible
1 ... 4
[ 1 ]PPO type used (see chap. 6)
P508 Profibus address Always visible
1 ... 126
[ 1 ]Profibus address
NORDAC Profibus DP Manual
32 We reserve the right to make technical changes BU 0020 GB
Parameter Setting value / Description / Note Availability with option
P509 Interface Always visible
0 ... 21
[ 0 ]
Selection of the interface which is used to control the inverter.
0 = Control terminal or keyboard control using the ControlBox (option), the ParameterBox (option) or the potentiometer option.
1 = Only control terminal. Controlling the frequency inverter is only possible through the 4 digital and the one analogue inputs.
8 = Profibus setpoint. The frequency setpoint is transferred via the Profibus. Control using the digital inputs remains active
9 = Profibus control word. The control signals (Enable, rotational direction,...) are transferred over the Profibus, while the setpoint is transferred via the analogue input or the fixed frequencies.
10 = Profibus. All of the control information is transferred via the Profibus. The analogue input and the digital outputs are inactive (except for some safety functions, see below).
P510 Interface: secondary setpoint Always visible
Selection of the interface which is used to control the inverter. 0 ... 6
[ 0 ]
onlySK 700/750E
0 = Auto: The secondary setpoint is automatically taken from the interface used to transmit the primary setpoint (see P509 >Interface<).
1 = USS
2 = CANbus
3 = Profibus
4 = InterBus
5 = CANopen
6 = DeviceNet
7 = reserved
P513 Telegram time-out Always visible
-0.1 / 0.0 /0.1 ... 100.0 s
[ 0.0 ]
This function monitors whichever bus interface is active. After a valid telegram has been received, the next one must arrive within the period of time set by this parameter. If this is not the case, the inverter signals a fault and disconnects, giving the fault message E010 >Bus time-out<.
Setting the value at 0 deactivates monitoring.
0.0 = off: Monitoring is switched off.
-0.1 = no error: The FI will continue to operate as programmed even when the communication between BusBox and FI is interrupted (e.g. 24V error, the box having been pulled off, ...).
Hinweis: Depending on the Bus-Master, this setting could be overwritten (inactive).
P543 (P) Bus – Actual value 1 Always visible
When the inverter is bus-controlled, feedback value 1 (IW1) is set by this parameter. 0 ... 12
[ 1 ] 0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current
5 = Status of digital inputs and relays 4
6 = Actual position (only with posicon SK 700/750E)
7 = Setpoint position (only with posicon SK 700/750E)
8 = Setpoint frequency
9 = Fault code
10 = Actual position increment 5
(only with posicon SK 700/750E)
11 = Setpoint position increment 5
(only with posicon SK 700/750E)
12 = BUS I/O out bits 1-7
4 Assignment of the digital inputs for P543/ 544/ 545 = 5 for SK 700/750E
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4
Bit 4 = DigIn 5 Bit 5 = DigIn 6 Bit 6 = DigIn 7 (POS or ENC) Bit 7 = DigIn 8 (POS)
Bit 8 = DigIn 9 (POS) Bit 9 = DigIn 10 (POS) Bit 10 = DigIn 11 (POS) Bit 11 = DigIn 12 (POS)
Bit 12 = Rel 1 Bit 13 = Rel 2 Bit 14 = Rel 3 (POS) Bit 15 = Rel 4 (POS) 5 The set-position or actual-position as for an 8192 line encoder.
5 BUS Parameters SK 300E/ 700E/ 750E/ vector mc
BU 0020 GB We reserve the right to make technical changes 33
Parameter Setting value / Description / Note Availability with option
P544 (P) Bus – Actual value 2 Always visible
When the inverter is bus-controlled, feedback value 2 (IW2) is set by this parameter. 0 ... 12
[ 0 ] This parameter is identical to P543.
PPO 2 or PPO 4 type (P507) is required.
P545 (P) Bus – Actual value 3 Always visible
When the inverter is bus-controlled, feedback value 3 (IW3) is set by this parameter. 0 ... 12
[ 0 ] This parameter is identical to P543.
PPO 2 or PPO 4 type (P507). is required.
P546 (P) Bus – Setpoint value 1 Always visible
0 ... 6
[ 1 ]
When the inverter is bus-controlled, this parameter allocates a function to the transmitted setpoint 1 (SW1).
0 = Off
1 = Setpoint frequency (16 bit)
2 = 16 bit setpoint position (only with posicon, SK 700E/750E option)
3 = 32 bit setpoint position (only with posicon, SK 700E/750E option and when PPO type 2 or 4 is selected).
4 = Control terminal posicon6 (only with posicon, SK 700E/750E, 16 bit option)
5 = Setpoint position (16 bit) increment (only with posicon SK 700E/750E)
6 = Setpoint position (32 bit) increment (only with posicon SK 700E/750E)
P547 (P) Bus – Setpoint value 2 Always visible
When the inverter is bus-controlled, this parameter allocates a function to the transmitted setpoint 2 (SW2).
0 ... 20
[ 0 ]0 = Off
1 = Setpoint frequency
2 = Torque current limit
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit
7 = Maximum frequency
8 = Actual frequency PID-limited
9 = Actual frequency PID-monitored
10 = Torque
11 = Derivative action relating to torque
12 = Control terminal posicon6
(only with posicon using SK 700E/750E)
13 = Multiplication
14 = Process controller actual value
15 = Process controller setpoint
16 = Process controller derivative action
17 = BUS IO in bits 0-7
18 = Curve travel computer (only with posicon usingSK 700E/750E)
19 = Set relays (P541)
20 = Set analogue output (P542)
P548 (P) Bus – Setpoint value 3 Always visible
0 ... 20
[ 0 ]
When the inverter is bus-controlled, this parameter allocates a function to the transmitted setpoint 3
(SW3). This is identical to parameter P547, but it is only available if P546 3 and 6.
6
"Reference point tracking", "Teach-In" and "Reset position" can also be controlled via the additional bits:
Bit 0: Position array/Position increment array Bit 1: Position array/Position increment array Bit 2: Position array/Position increment array
Bit 3: Position array/Position increment array Bit 4: Position array/Position increment array Bit 5: Position array/Position increment array
Bit 6: Reference point tracking Bit 7: Reference point tracking Bit 8: Teach-In
Bit 9: Quit Teach-In Bit 10: Reset position
NORDAC Profibus DP Manual
34 We reserve the right to make technical changes BU 0020 GB
Information parameters
Parameter Setting value / Description / Note Availability with option
P745 Subassemblies version Always visible
0 ... 32767
Software version of the installed subassembly
Array level for SK 700/750E:
[01] Technology box:
[02] Customer interface
[03] Special expansion
P746 Subassembly status Always visible
0000 ... FFFF hex
Status of the installed subassemblies
Array level for SK 700/750E:
[01] Technology box:
[02] Customer interface
[03] Special expansion
NOTEUpon activation, the functions disable voltage, quick stop, remote control and faultacknowledgement are only available on the control terminal (local). To operate the drive, a "high" signal must be applied to the digital inputs which are used prior to the drive being released for operation.
5 Bus Parameters SK 500E/ 520E/ 530E
BU 0020 GB We reserve the right to make technical changes 35
5.2 Bus parameters SK 500E/ 520E/ 530E
To address the frequency inverter via Profibus, the Profibus address must be set in P508 and the PPO type in P507 or with the rotary coding switches on SK TU3-PBR-24V, both corresponding to the control configuration.
You can set the parameters for the frequency inverter at any time. The control signal source can be selected with the P509 (control word) parameter and the P510 (setpoint source) parameters. Telegram time-out P513 can be selected according to the bus system involved.
NOTE
Some parameters or parameter settings may be different or limited depending on the frequency inverter type and components involved.
Control terminal parameters
Parameter Setting value / Description / Note Device Supervisor Parameter set
P480 ... - 01
... ... - 12
Function bus I/O in bits S
Bus I/O-In bits are seen as digital inputs, whose function is transmitted over the serial interface. You will find the functions for the bus in bits in the table of functions for the digital inputs P420...P425.
In order to use this function, one of the bus setpoints (P546, P547, P548) should be set at > Digital in bit 0...7 <. The desired function is then to assigned to the corresponding bit.
0 ... 62
[ 12 ]
[01] = Bus I/O in bit 0
[02] = Bus I/O in bit 1
[03] = Bus I/O in bit 2
[04] = Bus I/O in bit 3
[05] = Bus I/O in bit 4
[06] = Bus I/O in bit 5
[07] = Bus I/O in bit 6
[08] = Bus I/O in bit 7
[09] = Flag 1
[10] = Flag 2
[11] = Bit 8 bus control word
[12] = Bit 9 bus control word
P481 ... - 01
... ... - 10
Function bus I/O out bits S
Bus I/O-Out bits are seen as digital outputs, whose function is transmitted over the serial interface. You will find the functions for the bus out bits in the table of functions for the digital outputs (relay function) P434...P441.
In order to use this function, one of the bus actual values (P543, P544, P545) should be set at > digital out bit 0...7 <. The desired function is then to assigned to the corresponding bit.
0 ... 38
[ 10 ]
[01] = Bus I/O out bit 0
[02] = Bus I/O out bit 1
[03] = Bus I/O out bit 2
[04] = Bus I/O out bit 3
[05] = Bus I/O out bit 4
[06] = Bus I/O out bit 5
[07] = Bus I/O out bit 6 / Flag 1
[08] = Bus I/O out bit 7 / Flag 2
[09] = Bit 10 bus status word
[10] = Bit 13 bus status word
NORDAC Profibus DP Manual
36 We reserve the right to make technical changes BU 0020 GB
Parameter Setting value / Description / Note Device Supervisor Parameter set
P482 ... - 01
... ... - 08
Normalisation: Bus I/O out bits S
-400 … 400%
[ 100 ]
Adjustment of the limit values for the relay functions / bus out bits. With a negative value, the output function is reported negative.
With positive setting values, the relay switch closes upon reaching the limit value. The relay switch opens with negative setting values.
P483 ... - 01
... ... - 08
Hysteresis: Bus I/O out bits S
1 … 100%
[ 10 ] The difference between the point in time for starting and stopping in order to avoid an oscillation in the output signal.
Additional parameters
Parameter Setting value / Description / Note Device Supervisor Parameter set
P507 PPO type
1 ... 4
[ 1 ]PPO type used (see chap. 6)
P508 Profibus address
1 ... 126
[ 1 ]Profibus address
P509 Source: Control word
0 ... 9
[ 0 ]
Selection of the interface which is used to control the frequency inverter (FI).
0 = Control terminal or keyboard control ** using the ControlBox (if P510=0), the ParameterBox (not ext. p-box) or using bus I/O bits.
1 = Only control terminal.* Controlling the FI is only possible through the digital and analogue inputs or through bus. I/O bits.
2 = USS control word.* The control signals (enable, rotational direction,...) are transferred over the RS485 interface, while the setpoint is transferred via the analogue input or the fixed frequencies.
3 = CAN control word *
4 = Profibus control word *
5 = Interbus control word *
6 = CANopen control word *
7 = DeviceNet control word *
8 = reserved
9 = CAN Broadcast *
*) Keyboard control (ControlBox, ParameterBox) is disabled,parameters can still be set.
**) If communication is interrupted with the keyboard during control (time-out 0.5 sec.),the FI blocks without an error message.
5 Bus Parameters SK 500E/ 520E/ 530E
BU 0020 GB We reserve the right to make technical changes 37
Parameter Setting value / Description / Note Device Supervisor Parameter set
P510 ... - 01
... - 02Source: Setpoint value S
Choosing the setpoint source to be configured:
[01] = Source: Main setpoint value [02] = Source: Secondary setpoint value
Selection of the interface which provides the FI with its setpoint value.
0 ... 8
[ 0 ]
0 = Auto: The source of the main and secondary set-point values is automatically derived from the para-meter setting P509 >Interface<.
1 = Control terminal: Digital and analogue inputs control the frequency, including the fixed frequencies.
2 = USS
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = reserved
P513 Telegram time-out S
-0.1 / 0.0 /0.1 ... 100.0 s
[ 0.0 ]
This function monitors whichever bus interface is active. After a valid telegram has been received, the next one must arrive within the period of time set by this parameter. If this is not the case, the inverter signals a fault and disconnects, giving the fault message E010 >Bus time-out<.
Setting the value at 0 deactivates monitoring.
0.0 = off: Monitoring is switched off.
-0.1 = no error: The FI will continue to operate as programmed even when the communication between BusBox and FI is interrupted (e.g. 24V error, the box having been pulled off, ...).
Hinweis: Depending on the Bus-Master, this setting could be overwritten (inactive).
P543 Bus – Actual value 1 S P
When the inverter is bus-controlled, feedback value 1 is set by this parameter. 0 ... 21
[ 1 ]
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs 5
6 = ... 7 reserved
8 = Setpoint frequency
9 = Fault code
10 = ... 11 reserved
12 = Bus I/O out bits 0...7
13 = ... 16 reserved
17 = Analogue input value 1 (P400)
18 = Analogue input value 2 (P405)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency acc. to ramp master value
21 = Actual frequency without slip master value
P544 Bus – Actual value 2 S P
0 ... 21
[ 0 ] This parameter is identical to P543.
PPO 2 or PPO 4 type (P507) is required.
5 Assignment of digital inputs for P543/ 544/ 545 = 5
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4 Bit 4 = DigIn 5 Bit 5 = DigIn 6 Bit 6 = DigIn 7 Bit 7 = reserved Bit 8 = reserved Bit 9 = reserved Bit 10 = reserved Bit 11 = reserved Bit 12 = Out 1 Bit 13 = Out 2 Bit 14 = Out 3 Bit 15 = Out 4
NORDAC Profibus DP Manual
38 We reserve the right to make technical changes BU 0020 GB
Parameter Setting value / Description / Note Device Supervisor Parameter set
P545 Bus – Actual value 3 S P
0 ... 21
[ 0 ] This parameter is identical to P543.
PPO 2 or PPO 4 type (P507) is required.
P546 Function Bus setpoint value 1 S P
When the inverter is bus-controlled, this parameter allocates a function to the transmitted setpoint 1.
0 ... 24
[ 1 ]
0 = Off
1 = Setpoint frequency (16 bit)
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (P536)
7 = Maximum frequency (P105)
8 = Actual frequency PID-limited
9 = Actual frequency PID-monitored
10 = Torque, servomode (P300)
11 = Derivative action relating to torque (P214)
12 = reserved
13 = Multiplication
14 = PI process controller actual value
15 = PI process controller setpoint
16 = PI process controller derivative action
17 = Digital in bits 0...7
18 = reserved
19 = Output state(P434/441/450/455 = 38)
20 = Analogue output value (P418 = 31)
21 = ... 24 reserved
P547 Function Bus setpoint value 2 S P
0 ... 24
[ 0 ] This parameter is identical to P546.
P548 Function Bus setpoint value 3 S P
0 ... 24
[ 0 ] This parameter is identical to P546.
5 Bus Parameters SK 500E/ 520E/ 530E
BU 0020 GB We reserve the right to make technical changes 39
Information parameters
Parameter Setting value / Description / Note Device Supervisor Parameter set
P745 Subassemblies version
0.0 ... 999.9 Execution state for the subassemblies installed, but only when they have their own processor.
P746 Subassembly status
0000 ... FFFF (hex) Status of the installed subassemblies (when active).
NOTEWhen activated, the functions disable voltage, quick stop, remote control and fault acknowledgement are only available on the control terminal (local). To operate the drive, a "high" signal must be applied to the digital inputs which are used prior to the drive being released for operation.
NORDAC Profibus DP Manual
40 We reserve the right to make technical changes BU 0020 GB
5.3 Fault monitoring
The PROFIBUS module monitors the following functions:
Connection to the master: Faults, for example when the bus cable is pulled out.
Baud rate recognition
Process data reception from the PROFIBUS: After a valid telegram has been received, the next one must arrive within the period of time set by the frequency inverter parameter "USS time-out".
Process data reception from the inverter: If the connection to the frequency inverter is broken, a fault message (2 bytes: 0x02 0x04) is logged in the PROFIBUS telegram in the expanded diagnosis.
The state of the PROFIBUS subassembly can be read out in parameter P746. If you have a customer interface, this can be done using a Technology box or ControlBox. When using a Technology box, the parameter must be read out using an additional bus subassembly with a USS or CAN interface. With the Technology box, there are also 2 LEDs available for diagnosis (see below).
Parameter P746 is a subindex parameter. Subindex 0 shows the status of the PROFIBUS Technology box; Subindex 1 shows the status of the PROFIBUS customer interface.
The parameter contains binary-coded information, which is displayed in hexadecimals:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Subassembly ID PROFIBUS=6 Subassembly ready
Connection to the master
Initialisation is active
Reserved (0)
Subassembly error
Time-out error
Reserved (0)
Reserved (0)
Technology box LED display:
The status of the PROFIBUS Technology box is indicated by the two built-in LEDs.
Green LED
BR Bus Ready
Red LED
BE Bus Error
Meaning
... flashing slowly = 1 Hz (1 sec. cycle), flashing quickly = 2 Hz (0.5 sec. cycle)
ON OFF Operation normal, data is transferred at cyclic intervals via the PROFIBUS.
flashing slowly OFF No process data has been received since initialisation
e.g. No connection to the master
flashing slowly brief illuminated PROFIBUS module initialisation (upon initialisation or change of a Profibus parameter on the frequency inverter).
flashing slowly ON Time-out in process data reception. The watchdog time configured by the Profibus master has expired. No new process data has been received for a maximum of 3 sec. (e.g. baud rate not recognised, cable interruption).
flashing slowly flashing slowly Time-out in process data reception: The time set in P513 has expired. No new process data has been received.
flashing slowly flashing quickly Software version 3.3 R0 and above
ON flashing slowly Up to software version 3.2 R0
Communication between the inverter and the PROFIBUS subassembly is inter-rupted
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 41
6 Data transfer
6.1 Utility data structure
This section describes the cyclic data traffic between the master and the inverter.
The utility data is divided into two categories:
PKW category (Configuration; Parameter- Kennung- Wert/"Parameter Label Value")
PZD category (Process data)
The PKW category of utility data allows for parameter values to be read and written. All tasks which are transferred using the PKW interface are generally tasks regarding configuration, monitoring and diagnosis.
The PZD (process data) category is used for controlling the frequency inverter. Control words, status words as well as setpoint and actual values are transferred in process data.
An access operation always consists of a task telegram and a reply telegram. Utility data is transferred from the master to the slave in the task telegram. Utility data is transferred from the slave to the master in the task telegram. The structure of both telegrams is the same.
MASTER SLAVE
parameter task control word + setpoint
parameter reply status wort + actual value
PKW section PZD section
task telegram
reply telegram
processing
Illustration: Telegram traffic / Utility data section structure
The process data is immediately processed in the frequency inverter (high priority) to enable quick responses to control commands or to notify the master of status changes without delay.
In contrast, a lower priority is assigned to the processing speed of PKW data. Therefore, it can take considerably longer to process them.
NORDAC Profibus DP Manual
42 We reserve the right to make technical changes BU 0020 GB
6.2 PPO types
The parameter process data object (PPO) is defined for cyclic data traffic. Using PPOs, both process data (PZD) and parameters (PKW) can be transferred from the master to the inverter. The frequency inverter can process PPO types 1, 2, 3 or 4.
Type Task
PPO1 Extended parameter telegram with 32 bits of parameter value and process data
PPO2Telegram with extended process data (main setpoint and two secondary setpoints) and 32 bits of parameter value
PPO3 Process data telegram with main setpoint, without parameter data
PPO4Telegram with extended process data with main setpoint and secondary setpoints, without parameter data.
PPO3 and PPO4 are pure process data objects for uses where no cyclic parameter processing is necessary.
Abbreviations used:
PPO Parameter process data object STW Control word
PKW Parameter label value ZSW Status word
PZD Process data SW1..3 Setpoint value 1-3
PKE Parameter label IW1..3 Actual value 1-3
IND Index
PWE Parameter value
Note: Usually, the only way for a stored program controller (PLC) to consistently transmit double words is to access I/O memory. Whenever longer data formats are to be transmitted (with PKW channels, always; with PZD data, when PPO2 or PPO4 types are involved) system functions must be used (e.g. SFC14, read consistent data; SFC15, write consistent data).
NOTE
Protocol definition requires that 6 words each be reserved for the process data (PZD) address range for PPO types 2 and 4. The last two words are not used for the process data telegrams; they are reserved for other uses.
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 43
6.2.1 PPO types SK 300E/ 700E/ 750E/ vector mc
The following table provides an overview of the PPO types that are supported.
PKW PZD
PKE IND PWE PWE PZD1 PZD2 PZD3 PZD4
STW SW1 SW3 SW2
ZSW IW1 IW3 IW2
1st word 2
nd word 3
rd word 4
th word 5
th word 6
th word 7
th word 8
th word
PPO 1
PPO 2
1st word 2
nd word 3
rd word 4
th word
PPO3
PPO4
6.2.2 PPO types SK 500E/ 520E/ 530E
The following table provides an overview of the PPO types that are supported. Please note the arrangement of SW2/SW3 and IW2/IW3.
PKW PZD
PKE IND PWE PWE PZD1 PZD2 PZD3 PZD4
STW SW1 SW2 SW3
ZSW IW1 IW2 IW3
1st word 2
nd word 3
rd word 4
th word 5
th word 6
th word 7
th word 8
th word
PPO 1
PPO 2
1st word 2
nd word 3
rd word 4
th word
PPO3
PPO4
NORDAC Profibus DP Manual
44 We reserve the right to make technical changes BU 0020 GB
6.3 Process data (PZD)
In the PZD process data section, control words and setpoint values are transferred from the master to the inverter, and, in response, the inverter sends status words and actual values to the master. The structure of the PZD range remains the same as far as the order of its elements (words) is the concerned. However, different terms are used
depending on the direction of data transfer (master inverter or inverter master.
The process data section of the utility data has the following structure:
- STW: Control word;length 16 bit, task telegram contains control bits (e.g. enable, quick stop, fault acknowledgement
- ZSW: Status word; length 16 bit, reply telegram contains status bits (e.g. FI working, fault)
- SW1...3: Setpoint values; maximum 3 possible, 16 or 32 bit, task telegram e.g. frequency setpoint, position setpoint, torque setpoint
- IW1...3: Actual values; maximum 3 possible, 16 or 32 bit, reply telegram e.g. actual frequency value, actual position value, actual torque value
6.3.1 Process data with SK 300E/ 700E/ 750E/ vector mc
1st word 2
nd word 3
rd word 4
th word
PZD section with 1x16 bit setpoint
STWZSW
SW1IW1
PP0 types 1.3
PZD section with up to 3 16 bit setpoints
STWZSW
SW1IW1
SW3IW3
SW2IW2
PP0 types 2.4
PZD section with 1x 32 bit setpoint and 1x 16 bit
STWZSW
SW1IW1
SW2IW2
PP0 types 2.4
6.3.2 Process data with SK 500E/520E/530E
1st word 2
nd word 3
rd word 4
th word
PZD section with 1x16 bit setpoint
STWZSW
SW1IW1
PP0 types 1.3
PZD section with up to 3 16 bit setpoints
STWZSW
SW1IW1
SW2IW2
SW3IW3
PP0 types 2.4
Note: 32 bit setpoints are composed of a high and a low word (each 16 bit).
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 45
6.3.3 The control word
In task telegrams, the control word (STW) is the first word transferred to the frequency inverter in the process data section.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2/3 SW2/3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Meaning of the individual bits:
Bit Value Meaning Remarks
0 0 OFF 1 Reverse with the brake ramp, with disconnection from supply at f=0Hz
1 ON Ready for operation
1 0 OFF 2 Cut off voltage; the inverter output voltage is switched off; the FI enters a state where switching on is disabled.
1 Operating condition OFF 2 is cancelled
2 0 OFF 3 Quick stop with programmed quick stop time; with disconnection from supply at f=0Hz; the FI switches to starting disabled condition.
1 Operating condition OFF 3 is cancelled
3 0 Disable operation Cut off voltage; the inverter output voltage is switched off; the FI enters a state where switching on is enabled.
1 Enable operation The output voltage is enabled; ramp to the setpoint applied
4 0 Lock ramp generator Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains in the operation enabled state.
1 Operating condition Enable ramp generator
5 0 Stop ramp generator The setpoint currently provided by the ramp generator is "frozen" (frequency is maintained).
1 Enable ramp generator Enable setpoint on ramp generator
6 0 Disable setpoint Selected setpoint value is set to zero on the ramp generator.
1 Enable setpoint Selected ramp generator setpoint is activated.
7 0
1 Acknowledge A change of value from 0 to 1 begins acknowledgement of faults which are no longer active.
Notice: When a digital input has been programmed for the "ack.fault" function, this bit must not permanently be set to 1 via the bus (otherwise, edge evaluation would be prevented).
8 0/1 Reserved
9 0/1 Reserved
10 0 PZD invalid The transmitted process data is invalid
1 PZD valid Valid process data is being transferred from the master
Notice: If only setpoints are being transferred from the bus (setting: interface), this bit must be set in order for the transferred setpoint to become valid.
11 0
1 Rotational direction: right
Rotational direction right – ON
12 0
1 Rotational direction: left
Rotational direction left – ON
13 0/1 Reserved
14 0/1 Bit 0 to switch parameter set
15 0/1 Bit 1 to switch parameter set
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
NORDAC Profibus DP Manual
46 We reserve the right to make technical changes BU 0020 GB
6.3.4 The status word (ZSW)
In inverter reply telegrams, the status word (ZSW) is the first word transferred to the frequency inverter in the process data section.
PZD1 PZD2 PZD3 PZD4
ZSW IW1 IW2/3 IW2/3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Meaning of the individual bits:
Bit Value Meaning Remarks
0 0 Not ready to start
1 Ready to start Initialisation completed, charging relay ON, output voltage disabled
1 0 Not ready for operation Causes: No command has been activated, fault is signalled, OFF2 or OFF3 activated, starting disabled state activated
1 Ready for operation ON command activated, no faults present. The inverter can be started with the command ENABLE OPERATION
2 0 Operation disabled
1 Operation enabled The output voltage is enabled; ramp to the existing setpoint
3 0 No fault
1 Fault Drive fault resulting in stoppage; this state is changed to starting disabled after the fault has been successfully acknowledged
4 0 OFF2 OFF2 command applied
1 No OFF2
5 0 AUS3 OFF3 command applied
1 No OFF3
6 0 Starting not disabled
1 Starting disabled Switches first to OFF1, then to ready-to-start status
7 0 No warning
1 Warning Drive operation continues, no acknowledgement necessary
8 0 Actual value not o.k. Actual value does not match setpoint (with posicon: failure to reach setpoint position)
1 Actual value o.k. Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached
9 0 Local guidance Guidance on local device has been activated
1 Guidance requested The master has been requested to assume guidance.
10 0 Actual MFR 1 value below reference value
Programmed function of MFR 1 has not been executed or actual value < programmed reference value
1 MFR 1 value has been equalled
Programmed function of MFR 1 has been executed
or actual value > programmed reference value
11 0
1 Rotational direction: right
Inverter output voltage is turning right
12 0
1 Rotational direction: left
Inverter output voltage is turning left
13 0 Actual MFR 4 value below reference value
Only with SK 700E/750E with posicon extension Status MFR 4 = 0
1 MFR 4 value has been equalled
Only with SK 700E/750E with posicon extension Status MFR 4 = 1
14 0/1 Currently active parameter set 0
15 0/1 Currently active parameter set 1
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 47
6.3.5 Setpoint 1 (SW1)
The function of the 1st setpoint is selected in parameter P546. The following options are available:
Setpoint frequency (16 bit)
In setpoint 1, the setpoint frequency is always transferred as a 16 bit value. In a task telegram, setpoint 1 is transferred as the second word to the frequency inverter in the process data section.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2/3 SW2/3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The setpoint is transferred as an integral number corresponding to the value range from -32768 to 32767 (8000 hex to 7FFF hex). The value 16384 (4000 hex) is equivalent to 100%. The value C000 hex is equivalent to -100%. A 100% setpoint is equal to the maximum frequency set in the same parameter set (parameter P105).
Setpoint position (16 or 32 bits)
When the SK 700E has been fitted with the posicon special extension, the absolute setpoint position can be transferred in setpoint 1. The position can be transferred as either a 16 or 32 bit value with a resolution amounting to 1=0.001 revolutions. Alternatively, the information applied to the control terminals (with a posicon control bits setting) can be transferred in binary form.
16 bit setpoint position setting
The 16 bit value may have a value range from +32767 (= 32.767 revolutions) to -32768 (= -32.768 revolutions). The 16 bit setpoint position is transferred as the second word in the process data section (like the setpoint frequency, see above).
32 bit setpoint position setting
For a 32 bit value, the full position range of +/- 50000.000 revolutions is available. The 32 bit setpoint position is transferred as the second and third words in the process data section.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2
Posicon control bits setting:
A 16 bit value is transferred, representing the information applied to the posicon special extension control terminals. The setpoint position results from the position array or the position increment, respectively, as defined in the P610 setpoint mode.
The transferred bits have the following meaning (cf. BU 0710 operating instructions):
Bit 0-5 Bit0-bit5 position array / pos. increment
Bit 6 Reference point tracking
Bit 7 Reference point
Bit 8 Teach-in
Bit 9 Quit teach-in
Bit 10 Reset position
NORDAC Profibus DP Manual
48 We reserve the right to make technical changes BU 0020 GB
6.3.6 Second and third setpoint (SW2/3)
When PPO types 2 or 4 are used, in addition to setpoint 1, a 2nd
setpoint can be transmitted with the word PZD4, and a 3
rd with the word PZD3.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2/3 SW2/3
A third setpoint can only be transmitted if the first setpoint does not transfer a 32 bit setpoint.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2
The second and third setpoints are always 16 bits wide. The function of the second and third setpoints can be set in the inverter in parameter P547 "Function setpoint 2" or in P548 "Function setpoint 3".
Both setpoints are transferred as an integral number in the range from -32768 to 32767. The value 16384 (4000 hex) is equivalent to 100%. The value C000 hex is equivalent to -100%; hence, setpoints in the range from -200% to +200% can be transferred. A setpoint of 100% is equivalent to the respective nominal value.
Setting 100% corresponds to the:
Off
Setpoint frequency, PID actual frequency, PID actual frequency limited, PID actual frequency monitored, frequency addition, frequency subtraction, maximum frequency
Maximum frequency
Torque current limit Torque current limit (P112)
Current limit Inverter nominal current
Torque, servomode Nominal torque
Derivative action relating to torque Derivative action relating to torque (P214)
The posicon control bits can also be transferred here (cf. setpoint 1)
6.3.7 Actual value 1 (IW1)
The system provides for the actual frequency, which is the effective output frequency of the frequency inverter, to be transferred as the actual value 1, with a 16 bit value. In the inverter reply telegram, the actual value 1 is transferred to the master as the second word in the process data section.
PZD1 PZD2 PZD3 PZD4
ZSW IW1 IW2/3 IW2/3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The actual value 1 is transferred as an integral number in the range from -32768 to 32767. In addition to the actual frequency, other current inverter values may also be transferred. The setting is made in P543 "Function actual value 1".
The "actual frequency", "actual speed", "current", and "torque current" settings are transferred as a percentage value of the respective rated quantity. The value 16384 (4000 hex) is equivalent to 100%. The value C000 hex is equivalent to -100%. Actual values in the range from -200% to +200% may be transferred.
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 49
The "Digital I/O status" setting can be used to transfer the status of the control terminals and the relays (MFR).
Bit Status
Bits 0-5 Digital input 1-6
Bits 6-11 with posicon special extension Digital input 7-12
Bits 6-11 with encoder special extension Digital input 13
Bits 12-15 Multi-function relays 1-4
The "actual position" and the "setpoint position" settings transfer the current absolute position. The resolution is 1=0.001 revolutions. If the value "setpoint position 32 bits" is set in parameter P546 "function setpoint 1", then the value of the setpoint position or actual position, respectively, is transferred as a 32 bit value in PZD2 and PZD3 as well.
PZD1 PZD2 PZD3 PZD4
ZSW IW1 IW2
6.3.8 Actual value 2 and actual value 3 (IW2/3)
If PPO types 2 or 4 are used for transfer, it is possible to transfer additional actual values to the control.
The actual value 2 (IW2) is transferred in PZD4. The value to be transferred can be selected in P544 (bus actual value 2). When the actual value 1 is not a 32 bit value, the actual value 3 (IW3) can be transferred in PZD3. The value to be transferred can be selected in P545 (bus actual value 3). The scaling is the same as that of actual value 1 (see above).
6.4 The status machine
The frequency inverter runs through a status machine. The transition between various statuses is triggered by related control commands in the process data control word. The current status is reported in the process data status word.
After the inverter is switched on, it is in the "starting disabled" status. This status can only be cleared by sending the command "Shutdown (off 1)".
The reply to a master telegram does not normally yet includes a response to the control command which was sent. The controller must further check the slave's replies to see if the control command was carried out.
The following bits indicate the frequency inverter's status:
Status Bit6
Starting disabled
Bit5
Quick stop
Bit4
Disable voltage
Bit3
Fault
Bit2
Operation enabled
Bit1
Ready for operation
Bit0
Ready to start
Not ready to start 0 X X 0 0 0 0
Starting disabled 1 X X 0 0 0 0
Ready to start 0 1 1 0 0 0 1
Switched on 0 1 1 0 0 1 1
Operation enabled 0 1 1 0 1 1 1
Fault 0 X X 1 0 0 0
Fault active 0 X X 1 1 1 1
Quick stop active 0 0 1 0 1 1 1
NORDAC Profibus DP Manual
50 We reserve the right to make technical changes BU 0020 GB
disable starting
ready to start
started
operation enabled
quick stop active
reaction to fault
active
fault
from any device status
3 4 5 6 8
4 5
5
not ready to start
inverter sw itch on
charging relay pulled in
fault
reaction to fault completed
Bit0 = 0: stop
& Bit1 = 1: enable voltage
& Bit2 = 1: enable pulses
(xxxx x1xx xxxx x110)
Bit 3 = 0: disable operation Bit0 = 1: start
Bit3 = 1: enable operation
Bit2 = 0: quick stop
Bit1 = 0: disable voltage
v Bit2 = 0: quick stop
priority of control commands:
1. disable voltage
2. quick stop
3. stop
4. enable operation
5. start
6. disable operation
7. reset fault
coding of states:
1: bit 0 = 0
2: bit 6 = 1
3: bit 0 = 1
4: bit 1 = 1
5: bit 2 = 1
6: bit 5 = 0
7: bit 2 & bit 3 = 1
8: bit 3 = 1
3
5
2 3
3 64
2
2
1
2
3 7
8
f=0 equalled
(quick stop completed)
Bit7 0 1
fault acknow ledgement
control bits:
0. ready to start / stop
1. enable / disable voltage
2. enable pulses / quick stop
3. enable / disable operation
4. operation condition / disable
ramp generator (RG)
5. enable / stop RG
6. enable / disable setpoint
7. fault acknow ledgement (0 1)
10. control data valid / invalid
11. positive phase sequence
12. negative phase sequence
14. parameter set bit 0
15. parameter set bit 1
4
5
6
Bit4 = 0: ramp dow n to quick stop and remain
in 'operation enable' condition
Bit5 = 0: keep frequency constant
Bit6 = 0: setpoint = 0%
Bit0 = 0: stop
5
Bit3 = 1: enable operation
& Bit0 = 1: start
2
Sequence of inverter states
2
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 51
6.5 Parameter section (PKW)
Parameter processing in cyclic data traffic can be accomplished using the PKW mechanism. To do this, the master formulates a task and the inverter formulates the answer. The parameter section is only used when PPO type 1 and PPO type 2 are used for the transfer.
The parameter section basically consists of a parameter label in which the type of task (write, read, etc.) and the related parameter are defined. Using the index, individual parameter sets or array elements may be addressed. The parameter value contains the word to be written or read.
Note: A parameter task must be repeated until the frequency inverter answers with the relevant reply telegram.
6.5.1 Parameter label (PKE)
Tasks or answers and the relevant parameters are encoded in the parameter label (PKE).
1 2 3 4
PKE IND PWE1 PWE2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
AK PNU
SP
M
The parameter label (PKE) is always a 16 bit value.
PNU: Bits 0 to 16 contain the required parameter number (PNU) or, in the frequency inverter reply telegram, the number of the current parameter.
Note: You will find the parameter number (PNU) for each frequency inverter series in the relevant operating manual.
The frequency inverter parameters are mapped in the range 1000 to 1999 in the Profibus protocol. That means that when setting parameters via the bus, you must add 1000 to the parameter numbers (e.g. P508
PNU=1508).
SPM: Bit 11 is the toggle bit for spontaneous messages. This function is not supported.
AK: Bits 12 to 15 contain the task label or the reply label.
NORDAC Profibus DP Manual
52 We reserve the right to make technical changes BU 0020 GB
The following table shows all tasks that can be transferred from the master to the frequency inverter. The right column contains the reply that is normally sent ("AK" reply label=positive). Depending on the task label, only certain reply labels are possible. In case of a fault (AK=negative), the frequency inverter always sends the master a value of 7 in the reply label (AK).
AK Function Reply label positive
0 No task 0
1 Request parameter value 1 / 2
2 Change parameter value (word) 1
3 Change parameter value (double word) 2
4 Reserved (request description element) -
5 Reserved (change description element) -
6 Request parameter value (array) 4 / 5
7 Change parameter value (array word) 4
8 Change parameter value (array double word) 5
9 Request number of array elements 6
10 Reserved -
11 Change parameter value (array double word)
Without writing in EEPROM
5
12 Change parameter value (array word)
Without writing in EEPROM
4
13 Change parameter value (double word)
Without writing in EEPROM
2
14 Change parameter value (word)
Without writing in EEPROM
1
6 Data transfer
BU 0020 GB We reserve the right to make technical changes 53
Meaning of the values sent in the reply label:
AK Function
0 No answer
1 Transfer parameter value (word)
2 Transfer parameter value (double word) *
4 Transfer parameter value (array word)
5 Transfer parameter value (array double word) *
7 Task not executable (with error number in PWE2)
* Only with PPO type 2 and PPO type 4
As long as a task has not been executed, the inverter delivers the reply from the previous task. You must always check in the master whether the reply received matches the task sent. The following may be used in the plausibility check: The value in the reply label (AK), the received parameter number (PNU) with the corresponding index (IND) as well as the current parameter value (PWE) for writing parameters.
Error messages when the task is not executable
When the reply label is "Task not executable" (AK=7), an error message is added to the inverter reply parameter value (PWE2). You can find the meaning of the transferred values in the following table.
No. Information
0 Invalid parameter number
1 Parameter value cannot be changed
2 Lower or upper value limit exceeded
3 Faulty subindex
4 No array
5 Invalid data type (currently only with SK 700E)
6 Can only be reset (only 0 may be written)
7 Description element cannot be changed
9 Description element not available
201 Invalid task element in the previously received task
202 Internal reply label cannot be displayed
NORDAC Profibus DP Manual
54 We reserve the right to make technical changes BU 0020 GB
6.5.2 Subindex (IND)
1 2 3 4
PKE IND PWE1 PWE2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
P1-P4 No information/all 0
Array 1-64 P1-P4
Subindex
The structure and function of the parameter index (IND) depends on the type of parameter being transferred. With values that are dependent on the parameter set, bits 8 and 9 of the index (IND) can be used to select the parameter set (0=parameter set 1, 1=parameter set 2, ...).
If you are working with parameters which are outside of an array parameter (e.g. a position array when using the posicon option), then you are also able to use bit 10 to bit 15 within the subindex of the required parameter (0=array element 1, 1=array element 2, ...) to call:
Array element Parameter set Index
5 (000101 BIN) 2 (01BIN) 15HEX = 0001 0101 BIN
21 (010101 BIN) 4 (11 BIN) 57HEX = 0101 0111 BIN
If a parameter is not dependent on a parameter set, then bits 8-15 are used for the subindex.
You can find the structure of the individual parameter and the values that may be called using the subindex in the operating manual.
When using the subindex, you must use task labels no. 6, 7, 8, or 11 and 12 (cf. chap. 6.5.1) in order for the subindex to be operative.
6.5.3 Parameter value (PWE)
The transfer of the parameter value (PWE) always happens as a word (16 bit) or a double word (32 bit), depending on the PPO type or the parameter. Each telegram can transfer only one parameter.
A 32 bit parameter value set consists of PWE1 (high-order word) and PWE2 (low-order word, 4th word). A 16 bit
parameter value is transferred in PWE2 with PPO1 and PPO2. With negative values, the high-order word must be set to FFFF hex.
Notice: 32 bit parameter values are only used with the posicon option). All of the relevant parameters are described in the posicon supplemental manual.
The parameter value is transferred as an integral value. When using parameters with a resolution of 0.1 or 0.01, multiply the parameter value with the resolution's reciprocal value.
Example: To set a ramp time of 99.99 seconds:
99.99s 99.99 * 1 / 0.01 = 99.99 * 100 = 9999 Thus, the value 9999 dec = 270F hex must be transferred.
7 Sample telegrams
BU 0020 GB We reserve the right to make technical changes 55
7 Sample telegrams
The following presents some typical telegrams, which should illustrate the control and configuration of the frequency inverter using the Profibus.
7.1 Starting disabled Ready to start
A frequency inverter is to be changed from the "starting disabled" state (STW bit 0=0), which is active after the device is initialised, to the "ready to start" state (STW bit 0=1). Parameter set 1 is valid. Only the PZD channel is considered.
Procedure:
Check the last status word (ZSW 0B 70)
Generate the control word (STW 04 7E)
Check the reply telegram (ZSW 0B 31)
Details: Frequency inverter status word Frequency inverter is in starting disabled status
9 10 11 12
ZSW ZSW IW1 IW1
0B 70 00 00
Bit Value Value HEX Meaning
15 0 Parameter set bit 1 off
14 0 Parameter set bit 0 off
13 0 Reserved
12 0
0
Rotational direction left -- OFF
11 1 Rotational direction right -- ON
10 0 Below reference value
9 1 Bus control
8 1
B
Setpoint=actual value
7 0 No warning
6 1 Starting disabled
5 1 No quick stop
4 1
7
Voltage disabled
3 0 No fault
2 0 Operation disabled
1 0 Not ready for operation
0 0
0
Not ready to start
In order to change the inverter status to ready to start, the following telegram must be sent:
9 10 11 12
STW STW SW1 SW1
04 7E 00 00
Abbreviations:
PKW Parameter label value
PZD Process data
PKE Parameter label
IND Index
PWE Parameter value
STW Control word 1
ZSW Status word 1
SW1..3 Setpoint value
IW1..3 Actual value
NORDAC Profibus DP Manual
56 We reserve the right to make technical changes BU 0020 GB
When the inverter status has been changed to ready to start, it reports the follow reply telegram:
9 10 11 12
ZSW ZSW IW1 IW1
0B 31 00 00
Notice: The control telegram must be sent cyclically because the inverter may not change to the required status within the telegram reply time.
7.2 Enable with 50% setpoint value
A frequency inverter in "ready to start" status must be enabled for clockwise rotation with 50% of the setpoint value. The controller received the previous reply telegram as follows.
Procedure:
Check the last status word (ZSW 0A 31)
Generate the control word (STW 04 7F)
Check the reply telegram (ZSW 0F 37)
Details: Output condition (frequency inverter status word)
9 10 11 12
ZSW ZSW IW1 IW1
0B 31 00 00
The following telegram must be sent to the frequency inverter
9 10 11 12
STW STW SW1 SW1
04 7F 20 00
The inverter accelerates the motor on the ramp. When the frequency inverter reaches 50% of the setpoint value, it replies with the following telegram.
9 10 11 12
ZSW ZSW IW1 IW1
0F 37 20 00
Notice: The status of MFR 1 is reported in bit 10 of the reply telegram. Depending on the programmed function and status, the status word may contain a change.
7 Sample telegrams
BU 0020 GB We reserve the right to make technical changes 57
7.3 Writing a parameter
When transferring parameter tasks, note that the slave does not immediately reply to the task in the master telegram parameter channel. Instead, a positive reply may be delayed by one or more communication cycles. The master must thus repeat the required task for as long as it takes to receive the corresponding slave reply.
The ramp-up time parameter (PNU = 102dec/66hex) for a frequency inverter must be set to 10 sec in parameter set 3. Only the PKW channel is considered.
Because the ramp-up time has an inverter-internal resolution of 0.01 sec, a parameter value of 10/0.01=1000 (3E8hex) must be transferred for 2 sec.
Procedure:
Select the parameter (P 102dec+1000=P 1102=P 44Ehex)
Select parameter set 3 (IND=02)
Set the parameter value (1000dec/3E8hex)
Check the reply telegram
Written in hexadecimals, the telegram consists of the following:
3 4 5 6 7 8 9 10
PKE PKE IND IND PWE PWE PWE PWE
24 4E 02 00 00 00 03 E8
When the inverter completes the task, it replies with
3 4 5 6 7 8 9 10
PKE PKE IND IND PWE PWE PWE PWE
14 4E 02 00 00 00 03 E8
NORDAC Profibus DP Manual
58 We reserve the right to make technical changes BU 0020 GB
8 Additional information
8.1 Device master data – GSD file
All of the characteristics of NORDAC PROFIBUS modules are summarised in a device master file (GDS file). The structure, content and coding of these device master data sets (GSD) is standardised. This enables convenient project planning using the NORDAC inverter with project devices from various manufacturers. The GSD file is available from Getriebebau Nord (www.nord.com).
There is one GSD file available for standard components up to 1.5 Mbaud and another available for special designs up to 12 Mbaud.
up to 1.5 Mbaud: NORD7531.GSD (module without 24V supply)
up to 12 Mbaud: NORD12M.GSD (module with 24V supply)
The PROFIBUS User Organisation e.V. archives this information for all manufacturers and makes it available on the Internet; download at (http:// www.profibus.com).
8.2 PROFIDRIVE standard parameters
The following parameters, which have been defined in the PROFIDRIVE profile, have been implemented in the PROFIBUS module:
PNU Comment
918 Address of user device
927 PKW operating priority (always 1, i.e. the PROFIBUS interface)
947 Fault number
The current fault number is stored in this parameter.
965 Profile number (3.0)
967 Control word
968 Status word
970 Load data set
When the parameter is set to 1, the factory settings are restored, and all bits used to effect a change are set to 0.
971 Save to non-volatile memory
(always occurs automatically)
These parameter numbers are not mapped.
8.3 Consistent data transfer
Usually, a stored program controller (PLC) can only transmit double words consistently by accessing I/O memory. Whenever longer data formats are to be transmitted (with PKW channels, always; with PZD data, when PPO2 or PPO4 types are involved) system functions must be used (e.g. SFC14, read consistent data; SFC15, write consistent data).
8 Additional information
BU 0020 GB 59
8.4 Repair
In case a repair is necessary, send the device to our local subsidiary or direct to the following address:
NORD Electronic DRIVESYSTEMS GmbH
Tjüchkampstr. 37
26605 Aurich, Germany
In case you have question about are repair, please contact:
Getriebebau NORD GmbH & Co. KG
Telephone: 49 (0)4532 / 401-437 or -518
Telefax: 49 (0)4532 / 401-555
When a frequency inverter or any of its accessories is sent in for repair, we cannot accept any responsibility for any parts which may be attached, such as line cables, potentiometers, external displays, etc.
Please remove all non-original parts from the frequency inverter.
NOTE
If possible, please state your reason for returning the part/device. Also, please provide the name of at least one contact person for any questions we may have.
This is important so that we may make repairs as quickly and efficiently as possible.
NORDAC Profibus DP Manual
60 BU 0020 GB
9 Index
2
24V connection ....................................................8, 11
24V Connection .......................................................19
A
Abbreviations ...........................................................43
Actual value .............................................................48
B
Bus architecture .......................................................28
Bus cables ...............................................................28
BUS Error.................................................................20
BUS Ready ..............................................................20
C
Conductive material .................................................28
Control word.............................................................45
D
Data transfer ............................................................41
Device master data ..................................................58
Display and operation ................................................7
E
E017.................................................................. 15, 16
F
Fault monitoring .......................................................40
Functional ground ......................................................9
G
GSD file....................................................................58
Guidelines ................................................................29
L
LED display............................................................. 40
LEDs ....................................................................... 20
Low voltage directive .................................................2
M
M12 Connectors................................................ 18, 19
M12-Stecker- Komponenten................................... 21
M8-Stecker- Komponenten..................................... 21
P
Parameter section................................................... 51
PGM.................................................................. 11, 19
PKW........................................................................ 41
PPO type....................................................... 9, 11, 19
PPO types............................................................... 42
Process data ........................................................... 44
PROFIBUS Master.................................................. 27
Profibus mc ............................................................. 26
Profibus module ...................................................... 17
Profibus protocol ..................................................... 27
PZD......................................................................... 41
R
Repair...................................................................... 59
Rotary coding switches ................................. 9, 11, 19
9 Index
BU 0020 GB 61
S
Sample telegrams....................................................55
Setpoint....................................................................47
Setting parameters ..................................................30
Shielding ..................................................................28
SK 300E...................................................................17
SK 500E / 520E / 530E..............................................7
SK 700E...................................................................10
SK 750E...................................................................17
SK CU1-PBR ...........................................................13
SK TU1-PBR............................................................11
SK TU1-PBR-24V....................................................11
SK TU2-PBR......................................................17, 18
SK TU2-PBR-24V..............................................17, 19
SK TU2-PBR-KL ................................................17, 20
SK TU3-PBR..............................................................8
SK TU3-PBR-24V......................................................8
Status machine ........................................................49
Status messages .....................................................20
Status word..............................................................46
Stecker- Komponenten............................................21
Subindex..................................................................54
T
Technology boxes....................................................17
Terminating resistor M12.........................................23
trio SK 300E.............................................................17
U
Utility data structure .................................................41
V
vector mc .................................................................25
NORDAC Profibus DP Manual
62 BU 0020 GB
10 Representatives and offices
N O R D Worldwide Subsidiaries:
Brasil
NORD Motoredutores do Brasil Ltda.
Rua Dr. Moacyr Antonio de Morais, 700 Parque Santo Agostinho Guarulhos – São Paulo CEP 07140-285
Tel.: +55-11-6402 88 55 Fax: +55-11-6402 88 30
Canada
NORD Gear Limited 41 West Drive Brampton, Ontario L6T 4A1
Tel.: +1-905-796 36 06 Tel.: +1-800-668 43 78 Fax: +1-905-796 81 30
Mexico
NORD GEAR CORPORATION Mexico Regional Office Av. Lázaro Cárdenas 1007 Pte. San Pedro Garza Garcia, N.L. México, C.P. 66266
Tel.: +52-81-8220 91 65 Fax: +52-81-8220 90 44
India
NORD Drivesystems Pvt. Ltd.
21 VEDAS CENTRE D.P. Road AUNDH Pune Maharashtra - 411 007
Tel.: +91-20-66 080 400 Fax: +91-20-25 888 872
Indonesia
PT NORD Indonesia Jln. Raya Serpong KM7, Kompleks Rumah Multi Guna Blok D-No. 1 Pakulonan, Serpong 15310 - Tangerang IN - West Java
Tel.: +62-21-53 12 22 22 Fax: +62-21-53 12 22 88 [email protected]
P.R. China
NORD (Beijing) Power Transmission Co. Ltd. No. 5, Tangjiacun, Guangqudonglu, Chaoyangqu CN - Beijing 100022
Tel.: +86-10-67 70 43 05 Fax: +86-10-67 70 43 30
P.R. China
NORD (Suzhou) Power Transmission Co.Ltd. No. 510 Changyang Street, Suzhou Ind. Park, Jiangsu, CN - 215021
Tel.: +86-512-85 18 02 77 Fax: +86-512-85 18 02 78
Singapore
NORD Gear Pte. Ltd. 33 Kian Teck Drive SGP – Jurong, Singapore 628850
Tel.: +65-6265-91 18 Fax: +65-6265-68 41
United States
NORD Gear Corporation 800 Nord Drive, P.O. Box 367 USA - Waunakee, WI 53597
Tel.: +1-608-849 73 00 Fax: +1-608-849 73 67 Fax: 800-373-NORD (6673)
Vietnam
NORD Gear Pte. Ltd Representative office Unit 401, 4F, An Dinh Building, 18 Nam Quoc Cang Street Pham Ngu Lao Ward District 1, Ho Chi Minh City, Vietnam
Tel.: +84-8 925 7270 Fax: +84-8 925 7271
10 Representatives and offices
BU 0020 GB 63
N O R D Subsidiaries in Europe:
Austria
Getriebebau NORD GmbH Deggendorfstr. 8 A - 4030 Linz
Tel.: +43-732-318 920 Fax: +43-732-318 920 85
Belgium
NORD Aandrijvingen Belgie N.V. Boutersem Dreef 24 B - 2240 Zandhoven
Tel.: +32-3-4845 921 Fax: +32-3-4845 924
Croatia
NORD Pogoni d.o.o. Obrtnicka 9 HR - 48260 Krizevci
Tel.: +385-48 711 900 Fax: +385-48 270 494
Czech. Republic
NORD Pohánèci Technika s.r.o Palackého 359 CZ - 50003 Hradec Králové
Tel.: +420-495 5803 -10 (-11) Fax: +420-495 5803 -12
Denmark
NORD Gear Danmark A/S Kliplev Erhvervspark 28 – Kliplev DK - 6200 Aabenraa
Tel.: +45 73 68 78 00 Fax: +45 73 68 78 10
Finland
NORD Gear Oy Aunankorvenkatu 7 FIN - 33840 Tampere
Tel.: +358-3-254 1800 Fax: +358-3-254 1820
France
NORD Réducteurs sarl. 17 Avenue Georges Clémenceau F - 93421 Villepinte Cedex
Tel.: +33-1-49 63 01 89 Fax: +33-1-49 63 08 11
Great Britain
NORD Gear Limited 11, Barton Lane Abingdon Science Park GB - Abingdon, Oxfordshire OX 14 3NB
Tel.: +44-1235-5344 04 Fax: +44-1235-5344 14
Hungary
NORD Hajtastechnika Kft. Törökkö u. 5-7 H - 1037 Budapest
Tel.: +36-1-437-0127 Fax: +36-1-250-5549
Italy
NORD Motoriduttori s.r.l. Via Newton 22 IT-40017 San Giovanni in Persiceto (BO)
Tel.: +39-051-6870 711 Fax: +39-051-6870 793
Netherlands
NORD Aandrijvingen Nederland B.V. Voltstraat 12 NL - 2181 HA Hillegom
Tel.: +31-2525-29544 Fax: +31-2525-22222
Norway
Nord Gear Norge A/S Solgaard Skog 7, PB 85 N-1501 Moss
Tel.: +47-69-206 990 Fax: +47-69-206 993
Poland
NORD Napedy Sp. z.o.o. Ul. Grottgera 30 PL – 32-020 Wieliczka
Tel.: +48-12-288 22 55 Fax: +48-12-288 22 56
Russian Federation
OOO NORD PRIVODY Ul. A. Nevsky 9 RU-191167 St.Petersburg
Tel.: +7-812-327 0192 Fax: +7-812-327 0192
Slowakia
NORD Pohony, s.r.o Stromová 13 SK - 83101 Bratislava
Tel.: +421-2-54791317 Fax: +421-2-54791402
Spain
NORD Motorreductores Ctra. de Sabadell a Prats de Llucanès Aptdo. de Correos 166 E - 08200 Sabadell
Tel.: +34-93-7235322 Fax: +34-93-7233147
Sweden
NORD Drivsystem AB Ryttargatan 277 / Box 2097 S - 19402 Upplands Väsby
Tel.: +46-8-594 114 00 Fax: +46-8-594 114 14
Switzerland
Getriebebau NORD AG Bächigenstr. 18 CH - 9212 Arnegg
Tel.: +41-71-388 99 11 Fax: +41-71-388 99 15
Turkey
NORD-Remas Redüktör San. ve Tic. Ltd. Sti.Tepeören Köyü TR - 34959 Tuzla – Istandbul
Tel.: +90-216-304 13 60 Fax: +90-216-304 13 69
Ukraine
GETRIEBEBAU NORD GmbH Repräsentanz Vasilkovskaja, 1 office 306 03040 KIEW
Tel.: + 380-44-537 0615 Fax: + 380-44-537 0615
Ma
t. N
r. 6
07
02
02
/ 3
80
6
NORD Offices in Germany
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 22941 Bargteheide
Telephone 04532 / 401 - 0 Telefax 04532 / 401 - 253
www.nord.com
North Branch South Branch
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 22941 Bargteheide
Telephone 04532 / 401 - 0 Telefax 04532 / 401 - 253
Getriebebau NORD GmbH & Co. KG
Katharinenstr. 2-6 70794 Filderstadt- Sielmingen
Telephone 07158 / 95608 - 0 Telefax 07158 / 95608 - 20
Bremen sales office
Getriebebau NORD GmbH & Co. KG
Stührener Weg 27 27211 Bassum
Telephone 04249 / 9616 - 75 Telefax 04249 / 9616 - 76
Nürnberg sales office
Getriebebau NORD GmbH & Co. KG
Schillerstr. 3 90547 Stein
Telephone 0911 / 67 23 11 Telefax 0911 / 67 24 71
Representative:
Hans-Hermann Wohlers Handelsgesellschaft mbH
Ellerbuscher Str. 179 32584 Löhne
Telephone 05732 / 40 72 Telefax 05732 / 123 18
Munich sales office
Getriebebau NORD GmbH & Co. KG
Untere Bahnhofstr. 29a 82110 Germering
Telephone 089 / 840 794 - 0 Telefax 089 / 840 794 - 20
West Branch East Branch
Getriebebau NORD GmbH & Co. KG
Großenbaumer Weg 10 40472 Düsseldorf
Telephone 0211 / 99 555 - 0 Telefax 0211 / 99 555 - 45
Getriebebau NORD GmbH & Co. KG
Leipzigerstr. 58 09113 Chemnitz
Telephone 0371 / 33 407 - 0 Telefax 0371 / 33 407 - 20
Butzbach sales office
Getriebebau NORD GmbH & Co. KG
Marie- Curie- Str. 2 35510 Butzbach
Telephone 06033 / 9623 - 0 Telefax 06033 / 9623 - 30
Berlin sales office
Getriebebau NORD GmbH & Co. KG
Heinrich- Mann- Str. 8 15566 Schöneiche
Telephone 030 / 639 79 413 Telefax 030 / 639 79 414