©2004 Fluke Corporation Insulation Resistance Testing 1

Insulation Resistance Testing

Page 2: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 2/30

©2004 Fluke Corporation Insulation Resistance Testing 2

Resistance 101

• Resistance is the opposition to current flow• Resistance is used to lower the amount of 

current and/or voltage flowing through a circuit

• Unit of resistance is the ohm

• Ohms symbol is omega:  

Page 3: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 3/30

©2004 Fluke Corporation Insulation Resistance Testing 3

What is megohm testing?

• It’s testing for electrical insulation failureunder controlled conditions

• Used to determine the integrity of 

• Cables

• Windings in motors and transformers• Switching gear 

• Electrical installations

• Similar to pressure-testing a water pipe

Page 4: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 4/30

©2004 Fluke Corporation Insulation Resistance Testing 4

Why different instrumentsread different ohms values

• Ohmmeter (DMM) 

• Low voltage (~1-2V).

• Low current (~1-10mA) .

• MegOhmMeter • High voltages to stress the insulation.

• Insulation Resistance Test (IRT).

•  Low Ohms Tester 

• Relatively high current (>200 mA).

• Greater accuracy for low-resistancedevices or conductors.

Page 5: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 5/30

©2004 Fluke Corporation Insulation Resistance Testing 5

Leakage current basics

• All insulators leak because all resistancesconduct some current, however small

• High voltages produce currents in insulators

• The amount of current depends on

• Applied voltage (Ohm’s Law) • System capacitance

• Total resistance

• Temperature of material

Page 6: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 6/30

©2004 Fluke Corporation Insulation Resistance Testing 6

Components of leakage current

• Polarization absorption leakage (I A

)• Conductive leakage (IL)

• Capacitive charging leakage (Ic)

Page 7: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 7/30

©2004 Fluke Corporation Insulation Resistance Testing 7

Measuring insulation resistance

• Customary: between two conductors“insulated” from each other  

• Worst case: tie one conductor to theconduit

Page 8: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 8/30

©2004 Fluke Corporation Insulation Resistance Testing 8

Measuring insulation resistance

Insulation resistance testInsulation resistance testover time for a motor  

Page 9: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 9/30

©2004 Fluke Corporation Insulation Resistance Testing 9

Be careful: I bite!

• A 5 KV tester = up to 5200V DC output• Nonlethal, but potent

• Limited to 2mA

Page 10: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 10/30

©2004 Fluke Corporation Insulation Resistance Testing 10

Installation testing

• Performed on these conductors• De-energized current-carrying (live)

• Grounded

• Grounding

• When• Construction and maintenance

•  After initial installation

• Why• #1 reason: Safety

• Establish baseline

Page 11: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 11/30

©2004 Fluke Corporation Insulation Resistance Testing 11

Maintenance testing

Reasons for regular monitoring/testing• Predicts and identifies imminent failure

• Prevents disaster 

• Lowers total cost of ownership

Performed on critical conductors

Page 12: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 12/30

©2004 Fluke Corporation Insulation Resistance Testing 12

Common voltages for testing

Equipment Voltage Rating Test Voltage

Up to 50 V 50 and 100 V

Up to 100V 100 and 250V

440 to 550V 500 and 1,000V

2,400V 1,000 to 2,500V or higher 

4,160V and above 1,000 to 5,000V or higher 

Page 13: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 13/30

©2004 Fluke Corporation Insulation Resistance Testing 13

Testing procedure

To ensure proper installation and integrity:1. Verify supply power is isolated/disconnected

from system under test.

2. Select the appropriate voltage level.

3. Connect leads.

4. Take reading.

5. Allow discharge of test voltage

6. Test each conductor.

Page 14: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 14/30

©2004 Fluke Corporation Insulation Resistance Testing 14

Using test results

• Keep records• Analyze readings

• Resolve issues

• Monitor suspect cables

Page 15: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 15/30

©2004 Fluke Corporation Insulation Resistance Testing 15

Spot-reading/Short-time test

• Connection time: 60 seconds• Applies to low-capacitance equipment

• Steady increase in resistance

• One Megohm Rule of Thumb

• Trending rates of decrease

Page 16: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 16/30

©2004 Fluke Corporation Insulation Resistance Testing 16

Step voltage test

Resistance testing at discrete voltage settings• Connection time: 60 seconds

• When: After spot test

• Looking for inconsistencies

• Flaws show at steps

Page 17: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 17/30

©2004 Fluke Corporation Insulation Resistance Testing 17

Step voltage test, good results

Page 18: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 18/30

©2004 Fluke Corporation Insulation Resistance Testing 18

Step voltage test failure

Page 19: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 19/30

©2004 Fluke Corporation Insulation Resistance Testing 19

Dielectric-absorption /time-resistance test

 Absorption characteristics: contaminated vs. good.

• During first minuteapply voltage

every 10 seconds• Apply once a

minute for 9remaining minutes

Page 20: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 20/30

©2004 Fluke Corporation Insulation Resistance Testing 20

Generator, motor, or transformer windings

Check:

• Winding to winding

• Winding to ground

• Phase to phase

Page 21: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 21/30

©2004 Fluke Corporation Insulation Resistance Testing 21

Generator or motor windings

• Disconnect stator winding and phases• Raise brushes for DC

Motor Nameplate

Voltage Rating (v)

Minimum

Acceptable

Resistance (ohms)0-1000 1 M

1000-2400 2 M

2400-5000 3 M

Page 22: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 22/30

©2004 Fluke Corporation Insulation Resistance Testing 22

1

10

100

1000

0 100 200 300 400

Stop the presses!

Newspaper printing press example

• Initially:>500 M.

•  After a day or two:10 M.

•  At about 1 M:rebuild the motor.

Page 23: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 23/30

©2004 Fluke Corporation Insulation Resistance Testing 23

Low ohms testing

Connection quality check

• Measure across connection

• Typically less than 1 ohm

• Requires lead compensation

Page 24: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 24/30

©2004 Fluke Corporation Insulation Resistance Testing 24

Electrical contractors

IR test applications:

• Leakage

• Cable insulation integrity

• Windings and switches

• Connections, fuses,breakers, and switches 

Page 25: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 25/30

©2004 Fluke Corporation Insulation Resistance Testing 25

Motor technicians

IR test applications:

• Leakage betweenwindings

• Leakage betweenwindings and

motor frame

• When to test?

Page 26: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 26/30

©2004 Fluke Corporation Insulation Resistance Testing 26

Plant maintenance

IR test applications:

• Wiring and cable

• Contacts and connections

• Grounding system integrity

Page 27: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 27/30

©2004 Fluke Corporation Insulation Resistance Testing 27

Other users

• Electrical Utility Workers 

• Low-voltage equipment

• High voltage equipment

• Elevator Technicians 

• Motors

• Wiring

• Controls

Page 28: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 28/30

©2004 Fluke Corporation Insulation Resistance Testing 28

Final tips

• Use the right tester 

• Follow the procedures

• Analyze the results

• Use proper trending

• Take corrective action

Page 29: Prezentare Fluke 1550C

7/27/2019 Prezentare Fluke 1550C

http://slidepdf.com/reader/full/prezentare-fluke-1550c 29/30

©2004 Fluke Corporation Insulation Resistance Testing 29

1520/1550 MegOhmMeter optional hands-on exercises

• Basic checks

• Normal resistance test

• Low resistance test

• High resistance test