pressurisation & automatic dosing unit “dose & fill · should have been detected during...

4
Q:\Arrow Valves\Products\MFD Midi-Fill and DF Dose&Fill\dfdatasheet.docx 30-Jan-20 Arrow Valves Ltd Tel: 01442 823123 Fax: 01442 823234 www.arrowvalves.co.uk Arrow Valves Ltd reserve the right to change specifications, design and materials at any time without notice. All unit-less dimensions in mm. © Copyright Arrow Valves Ltd 2010-2020 Pressurisation & Automatic Dosing Unit Fluid Category 5 “Dose & Fill ® Model DF - Datasheet Page 1 of 4 Description Dose & Fill® has been developed to combat the growing costs and problems associated with heating systems starved of inhibitor. Modern systems frequently have aluminium heat exchangers, steel panel radiators & thin copper tubing, requiring adequate levels of inhibitor to avoid perforations, blockages and to validate the manufacturers’ warranties. Traditionally a system is manually dosed via a dosing pot after the initial fill. However this is diluted every time the pressurisation unit adds plain water following normal minor losses or after partial draining for maintenance. Dose & Fill® is a compact & wall mounted filling and automatic make-up unit for adding water to a sealed system. The Dose & Fill® incorporates the Arrow Valves “Midi-Fill Digital®” pressurisation unit, whilst the lower half of the 1 m tall enclosure contains a 20 litre chemical container. In “Auto Dose” mode, the unit monitors the quantity of water added by the pressurisation unit and then the dosing pumps automatically inject inhibitor into the heating system according to concentration set via the LCD digital display. The correct concentration is therefore maintained. Dose & Fill® has been designed to comply with the Water Regulations, providing Fluid Category 5 backflow protection for filling and top-up of “non-house” heating or systems. Filling loops with a Double Check Valve must no longer be used for “other than a house” primary circuits - see Water Regulations and WRAS interpretation. In addition to “Auto Dosing”, the unit features an internal and external manual dosing facility. This generally avoids the need for a traditional dosing pot - a significant cost saving. The external dosing facility allows a newly filled system to be dosed from the manufacture’s container stood on the floor adjacent to the Dose & Fill ®unit avoiding the need for an operative to lift and pour chemical into a potentially hot dosing pot. The primary features are – Fluid Category 5 backflow prevention – initial fill & top-up Filling pump – with anti seize daily pulse feature Twin dosing pumps – with anti seize daily pulse feature High & low pressure cut-outs with boiler control output Comprehensive BMS controls Two digital displays, setting buttons and button lock Self test monitoring system alerting of pressurisation fault before heating system is shut down Electronic water meter with monthly excessive filling warning trigger (adjustable) Pressure transducer – accurate filling and small differential 20 litre internal chemical container with level monitoring The unit is supplied fully assembled and tested. Inlet and outlet stainless steel braided hoses with Servicing Valves and push fit connections are provided to facilitate installation. Applications Filling, topping up, initial & continued automatic dosing – Primary Heating Systems LTHW Under Floor Heating Refrigerating Equipment Cooling Circuits Industrial Processes Note - the maximum concentration level that can be set is 4% and therefore not suitable for chilled systems requiring a higher level. The dosing pumps are suitable for inhibitors only - e.g. Sentinel X100 Boiler & BMS Controls Overview Dose & Fill® addresses the common weakness of pump seizure due to infrequent use by pulsing the pumps each day - no water is admitted into the system. A self test program ensures the pumps can generate pressure; otherwise the BMS fault relay activates and the specific fault is displayed on the LCD panel. This self monitoring system warns of faults before the system needs topping up and therefore helps avoid low pressure boiler shut down situations. These are invariably disruptive and costly – especially for schools. BMS relay O3 is User Configurable, allowing groups of faults and warnings to be monitored or ignored. For example, the user may wish to monitor only a single parameter, such as excessive filling for the month. The state may be reversed from Healthy = contacts open to Healthy = contacts closed. Alternatively O3 relay may be configured as a pulsed water meter. The pumps can be manually tested during maintenance and disabled during installation using the controls on the panel. The Auto Dose mode has the option “Dose Fault Stops”, meaning the main pressurisation pump stops if the dosing unit runs out of chemical - useful for unattended filling. After the initial fill the unit is normally set to Auto Dosing “Healthy” where the pressurisation unit is independent of the dosing unit - i.e. continues to function if chemical container empty. Materials Cabinet Steel (powder coated RAL 7032) Pump (wetted parts) Brass (regenerative) Cistern Polypropylene Fittings Brass or stainless steel Model shown - DF22 The left display controls the pressurisation unit, whilst the right controller and its buttons control the dosing unit Lower section encloses a 20 litre chemical container & twin dosing pumps Sizes - 15 or 22 mm. Supplied with flexible hoses incorporating Servicing Valves

Upload: others

Post on 21-Jun-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Pressurisation & Automatic Dosing Unit “Dose & Fill · should have been detected during the pre commission cleaning stage. AUTO DOSING – The dosing pumps inject 0.5 litre of chemical

Q:\Arrow Valves\Products\MFD Midi-Fill and DF Dose&Fill\dfdatasheet.docx 30-Jan-20

Arrow Valves Ltd Tel: 01442 823123 Fax: 01442 823234 www.arrowvalves.co.uk

Arrow Valves Ltd reserve the right to change specifications, design and materials at any time without notice. All unit-less dimensions in mm. © Copyright Arrow Valves Ltd 2010-2020

Pressurisation & Automatic Dosing Unit – Fluid Category 5

“Dose & Fill®” Model – DF - Datasheet Page 1 of 4

Description Dose & Fill® has been developed to combat the growing costs and problems associated with heating systems starved of inhibitor. Modern systems frequently have aluminium heat exchangers, steel panel radiators & thin copper tubing, requiring adequate levels of inhibitor to avoid perforations, blockages and to validate the manufacturers’ warranties. Traditionally a system is manually dosed via a dosing pot after the initial fill. However this is diluted every time the pressurisation unit adds plain water following normal minor losses or after partial draining for maintenance. Dose & Fill® is a compact & wall mounted filling and automatic make-up unit for adding water to a sealed system. The Dose & Fill® incorporates the Arrow Valves “Midi-Fill Digital®” pressurisation unit, whilst the lower half of the 1 m tall enclosure contains a 20 litre chemical container. In “Auto Dose” mode, the unit monitors the quantity of water added by the pressurisation unit and then the dosing pumps automatically inject inhibitor into the heating system according to concentration set via the LCD digital display. The correct concentration is therefore maintained. Dose & Fill® has been designed to comply with the Water Regulations, providing Fluid Category 5 backflow protection for filling and top-up of “non-house” heating or systems. Filling loops with a Double Check Valve must no longer be used for “other than a house” primary circuits - see Water Regulations and WRAS interpretation. In addition to “Auto Dosing”, the unit features an internal and external manual dosing facility. This generally avoids the need for a traditional dosing pot - a significant cost saving. The external dosing facility allows a newly filled system to be dosed from the manufacture’s container stood on the floor adjacent to the Dose & Fill ®unit avoiding the need for an operative to lift and pour chemical into a potentially hot dosing pot. The primary features are – Fluid Category 5 backflow prevention – initial fill & top-up Filling pump – with anti seize daily pulse feature Twin dosing pumps – with anti seize daily pulse feature High & low pressure cut-outs with boiler control output Comprehensive BMS controls Two digital displays, setting buttons and button lock Self test monitoring system alerting of pressurisation fault

before heating system is shut down Electronic water meter with monthly excessive filling

warning trigger (adjustable) Pressure transducer – accurate filling and small differential 20 litre internal chemical container with level monitoring The unit is supplied fully assembled and tested. Inlet and outlet stainless steel braided hoses with Servicing Valves and push fit connections are provided to facilitate installation.

Applications Filling, topping up, initial & continued automatic dosing – Primary Heating Systems LTHW Under Floor Heating Refrigerating Equipment Cooling Circuits Industrial Processes Note - the maximum concentration level that can be set is 4% and therefore not suitable for chilled systems requiring a higher level. The dosing pumps are suitable for inhibitors only - e.g. Sentinel X100

Boiler & BMS Controls Overview Dose & Fill® addresses the common weakness of pump seizure due to infrequent use by pulsing the pumps each day - no water is admitted into the system. A self test program ensures the pumps can generate pressure; otherwise the BMS fault relay activates and the specific fault is displayed on the LCD panel. This self monitoring system warns of faults before the system needs topping up and therefore helps avoid low pressure boiler shut down situations. These are invariably disruptive and costly – especially for schools. BMS relay O3 is User Configurable, allowing groups of faults and warnings to be monitored or ignored. For example, the user may wish to monitor only a single parameter, such as excessive filling for the month. The state may be reversed from Healthy = contacts open to Healthy = contacts closed. Alternatively O3 relay may be configured as a pulsed water meter. The pumps can be manually tested during maintenance and disabled during installation using the controls on the panel. The Auto Dose mode has the option “Dose Fault Stops”, meaning the main pressurisation pump stops if the dosing unit runs out of chemical - useful for unattended filling. After the initial fill the unit is normally set to Auto Dosing “Healthy” where the pressurisation unit is independent of the dosing unit - i.e. continues to function if chemical container empty.

Materials Cabinet Steel (powder coated RAL 7032) Pump (wetted parts) Brass (regenerative) Cistern Polypropylene Fittings Brass or stainless steel

Model shown - DF22 – The left display controls the

pressurisation unit, whilst the right controller and its buttons control the

dosing unit

Lower section encloses a 20 litre chemical container & twin dosing

pumps

Sizes - 15 or 22 mm. Supplied with flexible hoses incorporating

Servicing Valves

Page 2: Pressurisation & Automatic Dosing Unit “Dose & Fill · should have been detected during the pre commission cleaning stage. AUTO DOSING – The dosing pumps inject 0.5 litre of chemical

Q:\Arrow Valves\Products\MFD Midi-Fill and DF Dose&Fill\dfdatasheet.docx 30-Jan-20

Arrow Valves Ltd Tel: 01442 823123 Fax: 01442 823234 www.arrowvalves.co.uk

Arrow Valves Ltd reserve the right to change specifications, design and materials at any time without notice. All unit-less dimensions in mm. © Copyright Arrow Valves Ltd 2010-2020

BMS COMMON FAULT (02) WARNING RELAY (03) FOR

EXCESSIVE MONTHY CONSUMPTION. THIS CAN BE PARALLED WITH FAULT.

BOILER RUN (04) WHEN SYSTEM PRESSURE IS -

ABOVE LOW CUT-OUT AND BELOW HIGH CUT-OUT

AS SET ON FRONT PANEL.

Pressurisation Unit – Fluid Category 5

“Dose & Fill®” Model – DF - Datasheet Page 2 of 4

Water Regulations Clause G24.2 (page 8.24) allows a temporary connecting pipe (quick fill loop) to be used for a house heating system only - since the Fluid Category is 3. For “other than a house” applications, the risk is Fluid Category 4 (unless risk assessed by the water supplier and downgraded) and a quick fill loop must not be used – not even temporarily (page 6.6, 4a). For systems that have been risk assessed and downgraded to Fluid Category 3 refer to datasheet “Autofill” – model AFCA. The non-house system could be filled through an RPZ valve or AB air gap and pump, the latter arrangement is incorporated into the Dose & Fill®.

Dose & Fill® does not require annual servicing and does not need to be notified to the local water company.

Digital Controller (Pressurisation) The unit is factory commissioned for systems up to 10 m head. For taller buildings, the cold-fill pressure can be increased using the buttons on the front panel. Note - the buttons can be locked to prevent tampering. The following adjustments are permitted –

Cold fill High cut-out pressure Excessive monthly water consumption warning trigger

Note - the buttons can be locked to prevent tampering The controller ensures a workable program; since settings must be in range. E.g. the low cut-out pressure is automatically adjusted to 0.5 bar below cold fill. The high cut-out pressure cannot be set with less than 0.5 bar above the cold-fill value. Panel display messages include – System healthy Last filled date Water consumption – since zeroing Water consumption – since 1st of that month Low level fault Low system pressure fault High system pressure fault Pump fault Excessive monthly water usage warning

Electronic Water Meter (Pressurisation) The Dose & Fill® incorporates a built-in electronic water meter, which determines the system volume; enabling the quantity of inhibitor to be added via a dosing pot if preferred. The meter also indicates any system leakage. The meter can be zeroed from the panel. An excessive monthly consumption warning feature is also provided, where a second meter reading illustrates the filling since the 1st of the month. If the filling exceeds the user defined trigger value, a visual warning is displayed on the panel and the warning relay closes. Note – the boiler control is unaffected and the warning will automatically clear on the 1st of each month – if not cleared manually earlier. Where a pulsed water meter is required to monitor water consumption, the user configurable BMS relay can be used as a pulsed water meter (1 pulse / litre) – rather than BMS faults.

Factory (Default) Settings – Cold Fill Switch on 1.2 bar (falling)

Switch off 1.4 bar (rising) Low cut-out (automatic) 0.3 below cold fill = 0.9 bar (falling) High cut-out 2.8 bar (rising) Electronic water meter monthly trigger point 50 Litres

Adjustable Parameters (Pressurisation) The following are adjustable via the buttons below the LCD display (assuming buttons have not been locked).

Cold Fill Switch on 0.6 – 3.2 bar (falling) (max. suggested head 30 m) Switch off 0.8 – 3.4 bar (rising)

High cut-out 5.8 bar max (rising) Must be at least 0.5 bar more than cold fill. E.g. if left at 2.8 bar default, cold fill cannot be set above 2.3 bar

Electronic water meter monthly trigger point 10 – 1000 Litres

Display (Pressurisation) Four examples of typical messages -

Normal – alternates last fill / cold fill Fault – Excessive pressure

Water consumption since zeroing Consumption that month Note – in normal “Healthy” Auto Dose mode, the pressurisation unit will continue

to operate normally even if there is a fault with the dosing unit (e.g. chemical container empty)

Specification - Mechanical Connection hoses 15 or 22 mm stainless braided

(supplied) metal push fit with serv. valve Pressure Supply min. 1.0 bar dynamic Pressure Supply max. 10 bar Enclosure Wall mounted with lockable door Weight (wet) 50 kg Water Regulations Approval 1707367 Patent No. 2555798

Specification – Electrical Volts/Phase/Frequency 230/1/50 Supply via 6 A MCB isolator (not supplied) RCBO recommended Motor type Induction (brushless) Low level cut out Stops pump (BMS & warning lamp

on door) – auto reset Max. current BMS relays 8 A resistive @ 230 V a.c. Control circuit protection 3 A fuse inside enclosure Switch Enclosure IP65 Cable Entries M20 hole Solenoid (22 mm only) 230 V 50 Hz IP65 IP Rating EN60529 IP65 (controls) Power Consumption 625 W (DF15), 635 W (DF22) Full Load Current 2.7 A (DF15), 2.8 A (DF22)

Page 3: Pressurisation & Automatic Dosing Unit “Dose & Fill · should have been detected during the pre commission cleaning stage. AUTO DOSING – The dosing pumps inject 0.5 litre of chemical

Q:\Arrow Valves\Products\MFD Midi-Fill and DF Dose&Fill\dfdatasheet.docx 30-Jan-20

Dosing Unit “Dose & Fill®” Model – DF - Datasheet Page 3 of 4

Digital Controller (Dosing) The following functions are available – Internal dose pot (manual dosing) External dose pot (manual dosing) Pump test / run Tare zeroing (allowing for alternative container weights) Concentration – range: 0.5 – 4%

Dosing Modes “Flash corrosion” occurs when oxygen rich raw water is admitted to a clean system, resulting in heavy corrosion and magnetite sludge within a few hours. To avoid this, it is recommended that the system is filled in “Auto Dosing” mode which will add the correct amount of inhibitor. This also avoids volume calculations and manual dosing. Any system leaks should have been detected during the pre commission cleaning stage. AUTO DOSING – The dosing pumps inject 0.5 litre of chemical after it detects that the appropriate quantity of water has been admitted. E.g. @ 1.0% concentration, every 50 Lt of water. The normal mode allows the pressurisation unit to function if dosing unit develops a fault - e.g. out of chemical. The “DOSE FAULT STOPS!” mode is selectable for commission allowing unattended filling and dosing. If chemical runs out, filling stops. EXTERNAL DOSING POT – Place the 2 m long hose (supplied) into the manufacturer’s container and then set the required quantity via the LCD display & buttons. Note - Since the Dose & Fill® cannot weigh the container it uses a time-estimation and the user must supervise, monitoring the quantity injected and ensuring the pumps do not run dry. INTERNAL DOSING POT – Fill the 20 litre internal container and then set the required quantity via the LCD display & buttons. The 18 litre usable quantity @ 1.0% concentration will dose 1800 litres, generally equating to 150 kW. Refill the container as required. This method is accurate (98%) and the pumps will stop once the unit detects less than 2 Lt of chemical remaining.

Display - Dosing Four examples of typical messages –

Normal – alternates last dose / chemical remaining

Manual Dosing - “Internal Dosing Pot” “Auto Dosing” in Progress message

Boiler & BMS Controls Four volt free SPST N.O. relays are provided in the control box for BMS monitoring. The operation is shown in the table below, where ● = contacts closed. The installer has a choice of running one, two, three or four BMS monitoring signals back to the panel. Where just one pair of wires is available the installer can choose between - BMS for faults only (relay O2) or combined faults/warnings (relay O3) - see table below and drawing AM176*. Note – factory wiring has the dosing warning and faults linked to the pressurisation controller. If required, the dosing unit links can be removed to provide volt free relays.

Note - power is required to power relays and run boiler.

CONDITION FAULTS ONLY

BMS USER

CONFIGUR-ABLE

BOILER RUN /

INTER-LOCK

PRESSURISATION (RELAY NUMBER) O2 O3 O4

NO POWER (e.g. unit isolated or power cut)

HEALTHY (no faults or warnings) ●

FAULT – LOW LEVEL (internal tank water level) ● ● G1 ●

FAULT – LOW CUT-OUT (low system cut-out pressure) ● ● G1

FAULT – HIGH CUT-OUT (high system cut-out pressure) ● ● G1

FAULT – PUMP SEIZED? TRANSDUCER FAULT? (inc. self test) ● ● G1 ●

FAULT – FLOOD PROTECTION SYSTEM ● ● G1 ●

DOSE FAULT STOPS! mode ● G2 ●

FILLING DISABLED ● G2 ●

WARNING – EXCESSIVE FILLING THIS MONTH ● G3 ●

PULSED WATER METER OUTPUT ENABLED INSTEAD OF BMS ● ● ● ● ● ●

DOSING

HEALTHY (no faults) ●

FAULT – LOW CHEMICAL LEVEL < 2 litres (dosing disabled) ● ● G5 ●

FAULT – DOSE PUMP OVERHEAT ● ● G5 ●

FAULT – NOT AUTO DOSING ● ● G5 ●

WARNING – AUTO DOSING DISABLED ● G4 ●

WARNING – DOSING DISABLED – PRESSURE ABOVE LIMIT ● G4 ●

WARNING – LOW CHEMICAL LEVEL < 4 litres (dosing operative) ● G4 ●

User configurable relay O3 notes –

G1, G2, G3, G4, G5 refer to groups, which can be ignored (disabled). Factory default – as above – all faults and warnings enabled.

Pulsed water meter disabled.

CONTROL TERMINALS AM176*

Arrow Valves Ltd Tel: 01442 823123 Fax: 01442 823234 www.arrowvalves.co.uk

Arrow Valves Ltd reserve the right to change specifications, design and materials at any time without notice. All unit-less dimensions in mm. © Copyright Arrow Valves Ltd 2010-2020

Page 4: Pressurisation & Automatic Dosing Unit “Dose & Fill · should have been detected during the pre commission cleaning stage. AUTO DOSING – The dosing pumps inject 0.5 litre of chemical

Q:\Arrow Valves\Products\MFD Midi-Fill and DF Dose&Fill\dfdatasheet.docx 30-Jan-20

Ancillaries The sealed heating system requires a correctly sized expansion vessel and controls. Available from Arrow Valves – Wall Mounting Bracket – MIDIBRA Stainless Steel Drip Tray – BTDT3 Bespoke programming Expansion Vessels - EVCP Expansion Vessel Servicing Valve

c/w Drain Tap – BVEV Dosing Pots - DP Dirt & Air Removers (Deaerators) – ADR

Model - EVCP

Pressurisation & Automatic Dosing Unit – Fluid Category 5

“Dose & Fill®” – DF – Datasheet Page 4 of 4

Model Selection Based On Boiler Size The table below shows the filling rates for both the 15 & 22 mm models. The 22 mm version has a fast-filling solenoid in place of a float valve and a faster system filling rate.

Model DF15 DF22 Filling rate Litres/hour 720 @ 1 bar 1000 @ 1 bar Suggested boiler size 0 – 200 kW Above 200 kW

Typical volume assuming 12 Lt/kW 332 - 2400 2400 + Chemical @ 1.0% Concentration 4 - 24 24 +

Note - systems requiring more than 40 litres of chemical may benefit from a 20 litre dosing pot. Also where non-inhibitor chemicals need to be added.

Codes and Descriptions

Size Code Description 15 mm DF15 Dose & Fill® Pressurisation & Dosing Unit 22 mm DF22 Dose & Fill® Pressurisation & Dosing Unit

Installation Schematic

Dimensions