pressure transmitter - dginstruments.com.au

128
Instruction manual Pressure transmitter 8311 © Bürkert 2003 Subject to technical change without notice

Upload: others

Post on 26-Oct-2021

14 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Pressure transmitter - dginstruments.com.au

Instruction manual

Pressure transmitter

8311

© Bürkert 2003 Subject to technical change without notice

Page 2: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

table of contents

1 safetyinstructions����������������������������������������������������������������������������������������������������������������������������������������4

1.1 Utilisation..................................................................................................................................................................................................51.2 Precautionsatinstallationandcommissioning.........................................................................................................61.3 Conformitytostandards..............................................................................................................................................................6

2 description���������������������������������������������������������������������������������������������������������������������������������������������������������������7

2.1 Design.........................................................................................................................................................................................................72.2 Measuringprinciple.........................................................................................................................................................................72.3 Availableversions..............................................................................................................................................................................82.4 Orderingtableofaccessoriesandspareparts.........................................................................................................92.5 Descriptionoftheproductlabel............................................................................................................................................9

3 technicaldata����������������������������������������������������������������������������������������������������������������������������������������������������10

4 installation�����������������������������������������������������������������������������������������������������������������������������������������������������������14

4.1 Generalrecommendations.....................................................................................................................................................144.2 Mountingonthepipe..................................................................................................................................................................144.3 Electricalconnection...................................................................................................................................................................15 4.3.1Cableplugs...........................................................................................................................................................................15

Page 3: Pressure transmitter - dginstruments.com.au

8311 3

ENGLISH

ENGLISH

4.3.2Versionwith2transistoroutputsand1currentoutput...................................................................16 4.3.3Versionwiththecurrentoutput............................................................................................................................17

5 programming��������������������������������������������������������������������������������������������������������������������������������������������������������18

5.1 Generalrecommendations.....................................................................................................................................................185.2 Functionalities...................................................................................................................................................................................185.3 Displayandprogrammingkeys...........................................................................................................................................205.4 Normalmode......................................................................................................................................................................................215.5 Calibrationmode.............................................................................................................................................................................225.6 DefaultsettingsoftheCalibrationmode....................................................................................................................315.7 TestMode.............................................................................................................................................................................................325.8 DefaultsettingsoftheTestmode.....................................................................................................................................345.9 Customersettings..........................................................................................................................................................................345.10Authorizedvaluesfortheprogrammableparameters......................................................................................36

6 maintenance����������������������������������������������������������������������������������������������������������������������������������������������������������38

6.1 Cleaning.................................................................................................................................................................................................386.2 Errormessages................................................................................................................................................................................386.3 Aproblem?...........................................................................................................................................................................................39

7 connectionexamples����������������������������������������������������������������������������������������������������������������������������������40

Page 4: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 83111 safety instructions

- always respect the safety instructions marked by the symbol opposite as well as those included in the manual.

- ensure the max. pressure the application can reach is within the chosen pressure range. it is recommended to equip the installation with a pressure relief valve.

pressurerange[bar] max�admissiblepressure destructionpressure

0-2 4 7

0-5 10 12

0-10 20 25

0-20 40 50

0-50 100 120

- the display within the normal mode flashes when the pressure is outside the measuring range.

Page 5: Pressure transmitter - dginstruments.com.au

8311 �

ENGLISH

ENGLISH

1.1 utilisation

- The 8311 transmitter has only been designed to measure the relative pressure of a liquid or a gas.

- The following units are available to display the measured pressure: bar, mbar, psi, atm, kPa, MPa, MH2O, mmHg.

When using an absolute pressure unit (mmHg, atm, mH2o), be aware that the air pressure displacement (about 1013 mbar) is not taken into account by the device.- The measuring element must be solidly screwed onto its support.

There will be no manufacturer warranty for damages caused by unexpec-ted handling or wrong usage of the device. The warranty on the device becomes invalid if any modification or change is made on the device.

the device should only be installed and repaired by specia-list staff. if any difficulties may occur with the product during installation, please contact your nearest Bürkert sales office for assistance.

Page 6: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

1.2 Precautions at installation and commissioning

- When the device is powered and the cover is open, protection against electric shocks is not effective.

- Always ensure the materials in contact with the medium to measure are chemically compatible.

- To clean the device, only use chemically compatible products.- Do not insert any object (screwdriver for instance) inside the sensor

body. If the body is dirty, use compressed air to clean it.

When dismounting the transmitter from the pipe, take all the necessary precautions linked to the process.

1.3 conformity to standards

- EMC: EN 50 081-1, 61 000-6-2- Security: EN 61 010-1- Vibration: EN 60068-2-6- Shock: EN 60068-2-27

1 safety instructions

Page 7: Pressure transmitter - dginstruments.com.au

8311 �

ENGLISH

ENGLISH

2 descriPtion2.1 designThe pressure transmitter 8311-2 wires is made up of an electronic mo-dule and a measuring element. It may switch a solenoid valve, activate an alarm or establish a control loop.The adjustments can be carried out by means of the three keys located under the display.

The transmitter housing can be turned by 180°.

The transmitter 8311 can be inserted in a fitting before being mounted on any type of pipe.

The electrical connection is carried out via an EN175301-803 connector and/or a steerable M12 multipin connector.

2.2 measuring principleThe transmitter 8311 uses a piezo-resistive ceramic cell.the cell and the electronic board are calibrated together ex works; do not use one of these elements with another transmit-ter.

Page 8: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 83112 descriPtion

2.3 available versions

supplyvoltage

pressurerange

output electricalconnection ordercode

g1/2 npt1/2 rc1/2

12-30 VDC 0-2 bar 4-20 mA + 2xPNP (NPN) 1) M12 connector 444507 444762 551739

12-30 VDC 0-2 bar 4-20 mA EN 175301-803 connector 444635 444640 444768

12-30 VDC 0-5 bar 4-20 mA + 2xPNP (NPN) 1) M12 connector 444506 444763 551740

12-30 VDC 0-5 bar 4-20 mA EN 175301-803 connector 444636 444641 444769

12-30 VDC 0-10 bar 4-20 mA + 2xPNP (NPN) 1) M12 connector 444503 444764 551741

12-30 VDC 0-10 bar 4-20 mA EN 175301-803 connector 550338 444642 444770

12-30 VDC 0-20 bar 4-20 mA + 2xPNP (NPN) 1) M12 connector 444504 444765 551742

12-30 VDC 0-20 bar 4-20 mA EN 175301-803 connector 550339 444760 551737

12-30 VDC 0-50 bar 4-20 mA + 2xPNP (NPN) 1) M12 connector 444505 444767 551743

12-30 VDC 0-50 bar 4-20 mA EN 175301-803 connector 444637 444761 551738

1) 2xPNP by default, can be modified into NPN via straps on the electronic board

Page 9: Pressure transmitter - dginstruments.com.au

8311 �

ENGLISH

ENGLISH

2.4 ordering table of accessories and spare parts

description ordercode

5-pin M12 cable plug, to be wired 917116

5 pin M12 cable plug, moulded on a shielded cable (2 m) 438680

EN175301-803 cable plug (type 2508) with cable gland 438811

EN175301-803 cable plug (type 2509) with NPT 1/2’’ reduction 162673

FKM gasket 438177

EPDM gasket 440693

2.� description of the product label

PRESS: 8311 4-20 mACERAMIC 12-30VDC2xNPN(PNP) 30V/0,7A0-50 barS-N:00033551743A W43LGM

ad

e i

n F

ran

ce 2

3456

89

10

7

1

1. Measured quantity and type of transmitter2. Current output3. Power supply4. Transistor output data5. Pressure range6. Protection class: protective insulation7. Manufacturer code8. Serial number9. Order code 10. Sensor material

Page 10: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

General features

Pipe diameter any type of pipe with a 1/2‘’ threaded connection piece (G, NPT or Rc)

Medium temperature -20 °C to +100 °C, +100 °C with a max. ambient temperature of +40 °C

Measuring range 0-2 bar, 0-5 bar, 0-10 bar, 0-20 bar or 0-50 bar

Accuracy, typical- if 0 °C < T < 70 °C ±1% of the full scale (full scale = max. value of the measuring range)- if -20 °C < T < 0 °C or 70 °C < T < 100 °C ±1% ±0.03% of the full scale /°C (full scale = max. value of the measuring range)

Repeatability, typical 0.06%Min.resolution 1,33 mbar (0-2 bar cell), 3,33 mbar (0-5 bar cell), 5 mbar (0-10 bar cell) 10 mbar (0-20 bar cell), 25 mbar (0-50 bar cell)

Measuring element ceramic cellProtection rating of the housing IP 65, connector being plugged-in and tightened (and a cable with a 6-7 mm ø with an EN 175301-803-connector)

electrical featuresInstallation class (overvoltage class) 2Power supply (V+) 12-30 VDCMax current consumption 30 mA (+700 mA max. per transistor output used)

3 tecHnical data

Page 11: Pressure transmitter - dginstruments.com.au

8311 11

ENGLISH

ENGLISH

Protection againstvoltage peaks yes, for the power supply and the transistor outputs Protection against polarity reversal yes, for the power supply and all the outputs

Transistor outputs 2 PNP or 2 NPN, can be modified by means of straps, open collector, max. 700 mA, NPN output: V+ minus 0.5 VDC / 0 VDC and PNP output: 0.5 VDC / V+

4-20 mA output possible adjustment of the 4 mA between 3,5 and 4,5 mA; possible adjustment of the 20 mA between 19 and 21 mA Response time (10% - 90%): 300 ms with filter 0 (default setting)

Max. line impedance Rload, depends on the supply voltage (V+), the loads (RL) on the 2 transistor outputs and I1 and I2 currents

Rload = V+ - 10 - RL (I1 + I2)

0,022

8311V+

I1

I20,022 A

RloadRL

RL

Page 12: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 83113 tecHnical data

Protection against short-circuits yes, for transistor outputsType of cable recommended shielded, wire section between 0.14 and 0.5 mm2

electrical connection

Version with 2 transistor outputs + 1 current output 5 pin M12 cable plug (not supplied)Version with 1 current output EN 175301-803 cable plug (type 2508 supplied)

materials

Housing polycarbonate, fiber glass reinforcedFront plate polyesterParts in contact with the medium stainless steel 316L (DIN 1.4404), FKM gasket in standard (EPDM as an option), ceramic cell (Al2O3)

environment

Ambient temperature 0 °C to +60° C, max. +40 °C if the fluid temperature is near +100 °CRelative humidity < 80%, non condensated

Page 13: Pressure transmitter - dginstruments.com.au

8311 13

ENGLISH

ENGLISH

dimensions (mm)54 22

SW 27

G1/2'' - NPT1/2'' - Rc1/2''

92

18

54

EN 175301-80330

61

M12

SW 22

54

SW 27

G1/2'' - NPT1/2'' - Rc1/2''

92

1861

40

Page 14: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 83114 installation

4.1 General recommendationsAlways check the chemical compatibility of the materials the transmitter is made of with the products it may be in contact with, for instance: alco-hols, strong or concentrated acids, aldehydes, bases, esters, aliphatics, aromatics, ketones, aromatics or halogenated hydrocarbons, oxidizing agents and chlorinated products. For more information, please contact your Bürkert sales office.4.2 mounting on the pipeThe pressure transmitter 8311 can be inserted in a fitting before being mounted on any type of pipe. During mounting, follow the instructions given with the fitting.

Always replace the cover in its initial position. The housing can then be rotated by 180°.

Do not tighten the transmitter using the housing;

use an appropriate tool.

For a G1/2”-version, ensure the gasket is in

place

do not unscrew the metallic part from the pipe

when readjusting the housing. ENTER

OUT 0....9

Page 15: Pressure transmitter - dginstruments.com.au

8311 1�

ENGLISH

ENGLISH

4.3 electrical connectionAlways ensure the power supply is switched off before working on the device. All the cable plugs must be plugged out. Use:- a shielded cable with an operating temperature > +80 °C.- a high quality voltage supply (filtered and regulated).- install a properly dimensioned fuse for the power supply.- connect the shielding to the earth, at both ends of the cable,

using a connection as short as possible.

4.3.1 cable plugs

1 2 4

31

5

22�08 cable plug (supplied)- To open the plug, unfasten screw [1]- Remove part [3] from part [2].- Unscrew cable gland [5].- Insert cable into part [2] via cable gland.- Wire part [3] (see 4.3.3).- Replace part [3] into part [2], by 90°-steps.- Tighten cable gland [5]. Place gasket [4] between the cable plug and the fixed connector of the transmitter and plug the 2508 onto the fixed connector.- Tighten screw [1] to ensure tightness and correct electrical contact.

multipin m12 cable plug (not supplied)- Loosen threaded ring [1]- Remove part [2] from the cable plug- Wire acc. to pin assignment (see 4.3.2).

Page 16: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

PNP

0 V

V+ V+

IN

0 VA

OUT1/OUT2

(*)

NPN

0 V

V+ V+

IN

0 V

A

OUT1/OUT2

(*)

4 installation

4.3.2 Version with 2 transistor outputs and 1 current output

4

5

3

1 2

0 VDC

V+(12-30 VDC)

npnoutput pnpoutput

Sensor SensorReceiver

Load

Receiver

Load

Wiringofm12fixedconnector

OUT2 (PNP1) / NPN)

OutputOutput

(*) Functional earth

pinnumberofthem12cableavailableasanaccessory(ordercode438680)

Wirecolour

1 brown2 white3 blue4 black5 grey

The transmitter is fitted with a steerable M12 fixed connector:Unfasten counternut. Turn the fixed connector to the right position, but by max. 360° to avoid twisting of the cables inside the housing. Fasten counternut using the appropriate tool while maintening the fixed connector in the right position.

OUT1 (PNP1) / NPN)

Page 17: Pressure transmitter - dginstruments.com.au

8311 1�

ENGLISH

ENGLISH

1) PNP, default; To change the configuration from PNP to NPN, do the following:- unplug the M12 power supply connector- unscrew the 4 wires of the transmitter cover- change the position of the 2 straps (attention: if one output is configured as an nPn output and the other as a PnP output, the 4-20 ma output is no more utilisable)

- Replace the cover in its initial orientation then tighten the 4 screws in an alternating pattern- plug connector M12 back

PnP configuration nPn configuration

operating safetyAlways check the wiring of the cable plugs to ensure the good operating of the device.

4.3.3 Version with the current output

0 V

V+ V+

0 VA

(*)

0 V

V+ V+

0 V

A

(*)

4-20macurrentoutputWiringofen175301-803fixedconnector

or

Not connected

1

3 2

0V

V+(12-30 VDC)

Page 18: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

�.1 General recommendations

Keep in mind that the process may be influenced by all the parameter settings you make. Fill-in the table on pages 35 -36 with your settings of the transmitter.

�.2 functionalities

The device has three operating modes:

normal mode (see p.21)Display of the measured pressure, the value of the output current and the values of the min. and max. process pressures.From the Normal mode, you can access the Calibration and Test modes.

the access to the calibration and the test modes can be protec-ted by a 4-digit code, disabled by default; it can be programmed in the calibration mode.

� ProGramminG

Page 19: Pressure transmitter - dginstruments.com.au

8311 1�

ENGLISH

ENGLISH

calibration mode (see p.22)Access to the programming of all the parameters (unit, transistor outputs, filter, 4-20 mA output, bargraph, behaviour of the outputs if the pressure is outside the measuring range and/or when an error is displayed, access code to the Calibration and Test modes).From the Calibration mode, you can go back to the Normal Mode.

Reminder:1 bar = mbar psi atm kPa MPa mH2O mmHg

1000 14.5038 0.98692 100 0.1 10.1972 750.064

1 bar = ft H2O in. H2O in. Hg kp/cm2

33.4553 401.463 29.53 1.01972

test mode (see p.32)Entering a theoretical pressure value to test the configuration program-med in the Calibration mode. Access to zero point adjustment, K-factor adjustment, current output adjustment, reset of the Calibration and/or Test modes. From the Test mode, you can go back to the Normal Mode.

Page 20: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

12

� ProGramminG

�.3 display and programming keys

To display the measured value and the configuration (8 characters: 4 numeric et 4 alphanumeric charact.)

To modify the digital value (0…9); To go back to the previous function.

To select the character;To go to the next function.

To validate a function;To validate the entered data.

The LED lights up as soon as a transistor output is switched and the icon «1» for OUT1 or «2» for OUT2 is displayed.

To indicate the feature or the selected unit.Bargraph, active at any menu level.

Page 21: Pressure transmitter - dginstruments.com.au

8311 21

ENGLISH

ENGLISH

1

CodeOK ?

ENTER

0......9

BAR1.000

ma5.41

MIN0.01

Max1.80

2

3

> 5 s0......9

ENTER+

> 5 s

ENTER+ CODE0000ON

OFF

CodeOK ?

ENTER

CODE0000ON

OFF

0......9

0......9*

�.4 normal mode

display of the measured pressure.N.B.: When the displayed value flashes, the min. or max. value of the pressure range has been exceeded.

display of the output current value (in mA).

to go back to the previous function.

Alternating display of the min. and max. pressures reached in the process since the last reset.

To go to the next function.

The bargraph is displayed at any menu level.

(see p. 22-30: calibration mode)

(see p. 32-33: test mode)

Enter the Calibration mode to enable and program the access CODE to the Calibration and Test menus.

* Press

ENTER

for 5s to reset the min. and max. pressure values.

1

2

3

1

CODE function status?

yes

no

yes

nopress

simulta-neously

presssimulta-neously

CODE function status?

Page 22: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

� ProGramminG

Only available on versions with transistor outputs

Alternating display of the function and the selected unitto change the pressure

unit (bar, mbar, psi, atm, kPa, MPa, mH2O, mmHg).

to choose, for each tran-sistor output (out1 and out2):- the switching mode of the output (Hysteresis or Window, see below) - the low (O LO) and high (O HI) switching thresholds - whether the switching mode is inverted or not (INV, see below) - the delay before switching (DEL, in seconds)

these settings are only taken into account if mode cont has been chosen for func-tion cal fail (see p. 28-2�).

* To move the decimal point, press simultaneously keys 0......9

and

�.� calibration mode

Page 23: Pressure transmitter - dginstruments.com.au

8311 23

ENGLISH

ENGLISH

Hysteresis modeThe change of state occurs when a threshold is detected (increasing pressure: high threshold (OHI) to be detected, decreasing pressure: low threshold (OLO) to be detected).

Window modeThe change of state occurs when any thres-hold is detected.

the delay (del) is set for the both swit-ching thresholds. the switching only occurs when either threshold value (oHi - olo) is exceeded for a duration higher than the del delay.

Switching examples of the transistor outputs depending on the pressure, when function CAL FAIL is set to CONT mode

Pressure

ON

OFFOLO OHI

Hysteresis mode

Window mode

Not inverted

Not inverted

Inverted

Inverted

Not inverted

Not inverted

Inverted

Inverted

OUT1/2 OUT1/2

Pressure Pressure

Not inverted

Not inverted

Inverted

InvertedOUT1/2 OUT1/2

Pressure Pressure

ON

OFFOLO OHI

ON

OFFOLO OHI

ON

OFFOLO OHI

2 s

OHI

OLO2 s 2 s

DEL = 0 s

DEL = 2 s

DEL = 0 s

DEL = 2 s

ONOFF

ONOFF

ONOFF

ONOFF

ONOFF

ONOFF

ONOFFONOFF

OUT1/OUT2

t

Page 24: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311� ProGramminG

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

to choose the filtering level (FILT) for smoothing the pres-sure changes on the display and the current output signal (see below).

feature filt (filter)

The FILT feature provides a damping effect to prevent fluctuation within the 4-20 mA output current and the display.It has no effect on the transistor outputs.

Page 25: Pressure transmitter - dginstruments.com.au

8311 2�

ENGLISH

ENGLISH

Ten damping levels are available, from 0 (no damping effect) to 9 (max. damping effect); Furthermore, for levels 1 to 9, the reaction time for dis-playing the pressure and modifying the output current value can be cho-sen: option «FAST» for the filter to react immediately or option «SLOW» for the filter to react progressively.

tFAST FAST

SLOW SLOW

200 ms 2.7 s 4.7 s

FILTER 0 FILTER 5 FILTER 9

Page 26: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311� ProGramminG

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

* To move the decimal point, press simultaneously keys 0......9

and

to define the min. (BG LO) and max. (BG HI) values of the bargraph at the bottom of the display, in the chosen unit.

to define the process values corresponding to output cur-rents of 4 mA and 20 mA, in the selected unit (see below).

Page 27: Pressure transmitter - dginstruments.com.au

8311 2�

ENGLISH

ENGLISH

feature ma: 4-20 ma current outputThe 4-20 mA output provides an electric signal whose value expresses the pressure measured by the transmitter.The «mA» feature within the Calibration mode makes it possible to make the correspondence between the measuring range and the output cur-rent.The figure below shows an example of relationship between the measu-ring range (for pressure ranges 0-10 bar, 0-20 bar and 0-50 bar) and the 4-20 mA output:

- The current signal can be inverted, i.e the pressure value associated to the 20 mA can be lower to that associated to the 4 mA.

- The value of the output current is of 22 mA when the transmitter dis-plays an error message and, if feature «CAL FAIL mA» = 22 mA, when the measuring range is exceeded.

4

20

0 8

mA

bar-1

Page 28: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311� ProGramminG

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

to define the behaviour of each transistor output if the measuring range is exceeded or an error is displayed:- CONT: the output reacts according to the settings made within menu CAL 1OUT or CAL 2OUT- ON: the corresponding cir-cuit is closed immediately (is opened as soon as the pres-sure is again within the range or the error is cancelled)- OFF: the corresponding cir-cuit is opened immediately (is closed as soon as the pres-sure is again within the range or the error is cancelled). to define the behaviour of the current output if the measuring range is exceeded:

Only available on versionswith transistor outputs

if mode on or off has been set within cal fail for out1 and/or out2, the settings made within cal 1out and/or cal 2out are not taken into account.

Page 29: Pressure transmitter - dginstruments.com.au

8311 2�

ENGLISH

ENGLISH

4 mA <-> OLO

ONOFF

20 mA <-> OHI

OUT (Transistor)FAILOUT

CONT

ONOFF

ON

ON

OFFOFF

CONT

22 mA

FAIL mA

20 mA

4 mA

22 mA

mA

20 mA

4 mA

22 mA

P

t

t

t

t

t

t

- CONT: the output reacts according to the settings made within menu CAL mA - 22 mA: the output imme-diately delivers a 22 mA current (disappears as soon as the pressure is again within the range)

example of the behaviour of the transistor outputs (OUT) and the 4-20 mA output (mA) depending on the mode selected within CAL FAIL and/or CAL OUT, and depending on the measured pressure.Assuming:- a 4 mA current corresponds to OLO - a 20 mA current corres- ponds to OHI - the transistor outputs react according to the window mode.

Range exceeded

Range exceeded

Connection to the cell interrupted (“10 ERR”)

max. value of the measuring range

min. value of the measuring range

Page 30: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

� ProGramminG

to return to the display of the pressure in the Normal mode, with (SAVE YES) or without (SAVE NO) saving the settings made.

to choose to restrict the access to the Calibration and Test Modes by means of a 4 digit code.

Back to normal mode (see p.21)

Page 31: Pressure transmitter - dginstruments.com.au

8311 31

ENGLISH

ENGLISH

�.6 default settings of the calibration mode

Ex works the settings of the Calibration Mode are:

Pressure unit: barTransistor outputs (*): hysteresisOLO1 and 2 (*): -0,2 bar (range 0-2); -0,5 bar (range 0-5); -1 bar (range 0-10); -2 bar (range 0-20); -5 bar (range 0-50)OHI1 and 2 (*): max. of the rangeINV1 and 2 (*): noDEL1 and 2 (*): 0 sFiltre: 0, FAST4 mA: 0 bar20 mA: max. value of the measuring rangeBGLO: 0 bar BGHI: max. value of the measuring rangeFAIL: CONT (continue), for OUT1 and OUT2 22 mA, for the 4-20 mA outputCODE: OFF (not used), value 0000

(*) Only versions with transistor outputs

Page 32: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

15.20ZERO

DISP

1

CAL

3

ENTER

ENTER

0......9

ENTER

ENTER

ENTER

0......9

TEST% ZERO

TESTSIM

KFACENTER

0......9

TEST

maTEST ENTER ENTER

OFFS ma

3.95 ENTER

SPAN ma

20.50

0......9

*0......9

*

RSET RSET

RSET

ENTER

0......9

ENTER

ENTER

TEST NO

CAL

RSET

ENTERTEST

ENDENTERTEST

0......9

ENTER

ENTER

SAVENO

SAVEYES

SIM UNIT

0......9

ENTER

*

1.500SIM UNIT

0.205 ENTER

TEACH ZERO15.20 ENTER

% ZERO

01.00DISP

CAL

ENTER

ENTER

ENTER

% KFAC

9.985 ENTER

TEACH KFAC

10.00 ENTER

UNIT01.00 ENTER

% KFAC

0......9

*

2)

% ZERO < 20% ?&

% ZERO > -20% ?

% KFAC < 20% ?&

% KFAC > -20% ?

1)

1)

� ProGramminG

�.� test mode

Zero -> disPto display the difference in % between the zero point calibrated ex works and the last calibrated zero point.Zero -> calto adjust the zero point of the transmitter, at nil pres-sure, with respect to the zero point calibrated ex works.

to test the transmitter beha-viour after entering a pressure value and PRESSING THE ENTER KEY.

1) The transmitter operates with the previous calculated value.2) The transmitter memorizes the pressure applied in the process.

Zero point must be adjusted before K factor!

Kfac -> disPto display the difference in % between the K factor calibrated ex works and the last calibrated K factor.Kfac -> calto adjust the K factor of the transmitter, at a standard pressure, with respect to the K factor calibrated ex works.

Alternating display of the function and the selected unit

no

Enter the value of the standard pressure (within the measuring range) applied to the process.

no

yes

yes

Page 33: Pressure transmitter - dginstruments.com.au

8311 33

ENGLISH

ENGLISH

15.20ZERO

DISP

1

CAL

3

ENTER

ENTER

0......9

ENTER

ENTER

ENTER

0......9

TEST% ZERO

TESTSIM

KFACENTER

0......9

TEST

maTEST ENTER ENTER

OFFS ma

3.95 ENTER

SPAN ma

20.50

0......9

*0......9

*

RSET RSET

RSET

ENTER

0......9

ENTER

ENTER

TEST NO

CAL

RSET

ENTERTEST

ENDENTERTEST

0......9

ENTER

ENTER

SAVENO

SAVEYES

SIM UNIT

0......9

ENTER

*

1.500SIM UNIT

0.205 ENTER

TEACH ZERO15.20 ENTER

% ZERO

01.00DISP

CAL

ENTER

ENTER

ENTER

% KFAC

9.985 ENTER

TEACH KFAC

10.00 ENTER

UNIT01.00 ENTER

% KFAC

0......9

*

2)

% ZERO < 20% ?&

% ZERO > -20% ?

% KFAC < 20% ?&

% KFAC > -20% ?

1)

1)

to adjust the 4-20 mA output of the transmitter:- Select feature OFFS: the transmitter generates a 4 mA output current; Measure the current at the 4-20 mA output using a multimeter, enter the measured value into the OFFS feature.- Select feature SPAN: the transmitter generates a 20 mA output current; Measure the current at the 4-20 mA output using a mul-timeter, enter the measured value into the SPAN feature.

to choose to go back or not to the default configuration of the Calibration and/or Test modes (see pages 31 and 34).

to return to the display of the pressure in the Normal mode, with (SAVE YES) or without (SAVE NO) saving the settings made.

Back to normal mode (see p.21)

* To move the decimal point, press simultaneously keys 0......9

and

Page 34: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311� ProGramminG

�.8 default settings of the test mode

Ex works the settings of the Test mode are the following:OFFS: 4 mASPAN: 20 mA

�.� customer settingsunit out1mode out1thres-

holdsout1inverted out1time-

outout2mode out2thres-

holdsout2inverted out2time-

out

unit hyst�1) Win�2) olo ohi yes no del(s) hyst�1) Win�2) olo ohi yes no del(s)

1) Hysteresis mode: 2) Window mode:ON

OFFOLO OHI

ON

OFFOLO OHI

Page 35: Pressure transmitter - dginstruments.com.au

8311 3�

ENGLISH

ENGLISH

filtre currentoutput Bargraph out1failure out2failure 4-20mafailure code

n° fast/sloW 4ma 20ma Bglo Bghi cont on off cont on off cont on off

Zeroadjustment Kfactoradjustment 4-20maadjustment date signature

Zero Kfact offs span

Page 36: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311� ProGramminG

�.10 authorized values for the programmable parameters

calibration menu test menu

Measured pressure: -999 to 9999 Simulated pressure: -999 to 9999Displayed current: 0.000 to 9999 Displayed Zero/K factor: -999 to 9999%OLO1 and 2 (*): -999 to 9999 Adjusted Zero/K factor: -999 to 9999OHI1 and 2 (*): -999 to 9999 Reference pressure: -999 to 9999DEL1 and 2 (*): 0 s to 999 s Adjusted 4 mA: 3,5 to 4,5 mAFiltre: 0 to 9 Adjusted 20 mA: 19 to 21 mA

4 mA: -999 to 999920 mA: -999 to 9999 BGLO: -999 to 9999BGHI: -999 to 9999CODE: 0000 to 9999 (*) Only versions with transistor outputs

Outside these ranges the transmitter does not validate the value but displays the nearest limit.

Page 37: Pressure transmitter - dginstruments.com.au

8311 3�

ENGLISH

ENGLISH

Page 38: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 83116 maintenance

6.1 cleaningThe transmitter 8311 can be cleaned with water or any solution compa-tible with the materials the device is made of.For more information, please contact your Bürkert sales office.

6.2 error messages

typeofmessage

description todo

1 ERR The data saved following a power supply cut-off is lost.Read and/or write error: the process is stopped.

Press the ENTER key to go back to the Normal mode.If the message appears frequently, send the device back to your Bürkert sales office.

2 ERR The parameters of the Calibration menu cannot be read and/or saved. Read and/or write error: the process is stopped.

Press the ENTER key to go back to the Normal mode.The device operates with the default parameters: the Calibration parameters must be programmed again.If the message appears frequently, send the device back to your Bürkert sales office.

3 ERR The parameters of the Test menu can-not be read and/or saved.Read and/or write error: the process is stopped.

Press the ENTER key to go back to the Normal mode.The device operates with the default parameters: the Test parame-ters must be programmed again.If the message appears frequently, send the device back to your Bürkert sales office.

Page 39: Pressure transmitter - dginstruments.com.au

8311 3�

ENGLISH

ENGLISH

typeofmessage

description todo

10 ERR The connection to the measuring cell is interrupted.

Unplug the M12 power supply connectorOpen the cover and check the connection between the measuring cell and the electronic board.

If the message appears frequently, send the device back to your Bürkert sales office.

Connection of the measuring cell

6.3 a problem?

- Protection code lost (see parag. 5.4): press keys 0......9 simulta-neously for 30 seconds when the display asks for your code, to access the desired mode.

- the display flashes: The measuring range is exceeded.- «----» is displayed: The limit values that can be displayed have been

exceeded. Choose an appropriate pressure unit.- the transmitter resets as soon as at least one transistor output

switches: The line impedance is too high (see p. 11)

Page 40: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311� connection examPles

4

1

3

2

5

18 V=

8311

+ -

mA

+

-

Wiring of a version with the 4-20 ma output (en 1��301-803 connector).

Wiring of a version with 2 PnP transis-tor outputs and a 4-20 ma output (m12 connector).

connect the shielding to the earth, at both ends of the cable.

1

23

8311

18 V=+ -

+ -mA

1

23

8311

18 V=+ -

mA+

-

Load 1

Load 2

Fuse Fuse

Fuse

Page 41: Pressure transmitter - dginstruments.com.au

8311 41

ENGLISH

ENGLISH

Wiring of a version with 2 nPn transis-tor outputs and a 4-20 ma output (m12 connector).

Wiring of a version with 2 nPn tran-sistor outputs and a 4-20 ma output (m12 connector); to reduce the current flowing through the loads when the line impedance is too low or too high.

connect the shielding to the earth, at both ends of the cable.

4

1

3

2

5

18 V=

8311

+ -

mA+

-

4

1

3

2

5

18 V=

8311

+ -

mA+

-

30 V=+ -

Ι

30 V

30 V

Load 1

Load 2

Load 1

Load 2

load current

Fuse

Fuse

Fuse

Page 42: Pressure transmitter - dginstruments.com.au

ENGLISH

ENGLISH

Pressure transmitter 8311

Page 43: Pressure transmitter - dginstruments.com.au

Manuel utilisateur

TRANSMETTEUR DE PRESSION

8311

© Bürkert 2003 Sous réserve de modifications techniques

Page 44: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

Table des matières

1 consignesdesecurite����������������������������������������������������������������������������������������������������������������������������������4

1.1 Utilisation..................................................................................................................................................................................................51.2 Précautionslorsdel‘installationetlamiseenservice........................................................................................61.3 Conformitéauxnormes................................................................................................................................................................6

2 description���������������������������������������������������������������������������������������������������������������������������������������������������������������7

2.1 Construction..........................................................................................................................................................................................72.2 Elémentdemesure..........................................................................................................................................................................72.3 Versionsproposées.........................................................................................................................................................................82.4 Accessoiresetpiècesderechange...................................................................................................................................92.5 Descriptiondel’étiquetteduproduit..................................................................................................................................9

3 caracteristiquestechniques������������������������������������������������������������������������������������������������������������10

4 installation�����������������������������������������������������������������������������������������������������������������������������������������������������������14

4.1 Recommandationsgénérales...............................................................................................................................................144.2 Montagesurlaconduite...........................................................................................................................................................14

Page 45: Pressure transmitter - dginstruments.com.au

8311 3

FRANCAIS

FRANCAIS

4.3 Raccordementélectrique.........................................................................................................................................................15 4.3.1Connecteursfemelles..................................................................................................................................................15 4.3.2Versionavec2sortiestransistoret1sortiecourant..........................................................................16 4.3.3Versionaveclasortiecourant...............................................................................................................................17

5 programmation��������������������������������������������������������������������������������������������������������������������������������������������������18

5.1 Recommandationsgénérales...............................................................................................................................................185.2 Fonctionnalités.................................................................................................................................................................................185.3 Touchesdeprogrammationetafficheur.....................................................................................................................205.4 ModeNormal.....................................................................................................................................................................................215.5 ModeCalibration.............................................................................................................................................................................225.6 ConfigurationpardéfautdumodeCalibration.......................................................................................................315.7 ModeTest.............................................................................................................................................................................................325.8 ConfigurationpardéfautdumodeTest.......................................................................................................................345.9 Configurationprogrammée....................................................................................................................................................345.10Plagesdesaisiedesparamètresprogrammables..............................................................................................36

6 maintenance����������������������������������������������������������������������������������������������������������������������������������������������������������38

6.1 Entretien................................................................................................................................................................................................386.2 Messagesd‘erreur.........................................................................................................................................................................386.3 Encasdeproblème......................................................................................................................................................................39

7 exemplesderaccordement�������������������������������������������������������������������������������������������������������������������40

Page 46: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 83111 cONSIgNES DE SEcURITE

- Respecter les consignes de sécurité, repérées par le symbole ci-contre, ainsi que toutes les instructions contenues dans ce manuel.

- S‘assurer que la gamme de pression choisie est supérieure à la pression maximale pouvant être atteinte par le processus. Il est conseillé d‘équiper l‘installation d‘un surpresseur.

gammedepression[bar] pressionmax�admissible pressiondedestruction

0-2 4 7

0-5 10 12

0-10 20 25

0-20 40 50

0-50 100 120

- L’affichage dans le mode Normal clignote lorsque la gamme de pression est dépassée.

Page 47: Pressure transmitter - dginstruments.com.au

8311 �

FRANCAIS

FRANCAIS

1.1 Utilisation

- Le transmetteur 8311 est exclusivement destiné à la mesure de la pression relative de liquides ou de gaz.

- Les unités d‘affichage suivantes sont disponibles : bar, mbar, psi, atm, kPa, MPa, MH2O, mmHg.

Pour les unités de pression absolue (mmHg, atm, MH2O), le dé-calage de la pression atmosphérique (environ 1013 mbar) n‘est pas pris en compte.

- L‘élément de mesure doit être vissé solidement sur le support.

Le fabricant décline toute responsabilité pour les dommages dus à une utilisation inadéquate ou non conforme de cet appareil. Toute modifica-tion ou transformation annule la garantie applicable à ce produit.

Les travaux de montage et/ou de maintenance doivent être réalisés par un personnel qualifié. En cas de difficultés lors de l‘installation ou de la mise en service, veuillez contacter votre fournisseur Bürkert.

Page 48: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

1.2 Précautions lors de l‘installation et la mise en service

- Lorsque l‘appareil est sous tension et que le couvercle est ouvert, la protection contre les chocs électriques n‘est plus effective.

- Veillez toujours à la compatibilité chimique des matériaux en contact avec le fluide à mesurer.

- Lors du nettoyage de l‘appareil, utilisez des produits chimiquement compatibles avec les matériaux de l‘appareil.

- Ne pas introduire de corps étranger (tournevis, par ex.) dans l‘orifice du corps. En cas d‘encrassement, utiliser de l‘air comprimé.

Lors du démontage du transmetteur de la conduite, prenez tou-tes les précautions liées au procédé.

1.3 conformité aux normes

- CEM : EN 50 081-1, 61 000-6-2- Sécurité : EN 61 010-1- Tenue aux vibrations : EN 60068-2-6- Tenue aux chocs : EN 60068-2-27

1 cONSIgNES DE SEcURITE

Page 49: Pressure transmitter - dginstruments.com.au

8311 �

FRANCAIS

FRANCAIS

2 DEScRIPTION2.1 constructionLe transmetteur de pression 8311, 2 fils, se compose d‘un module élec-tronique et d‘un élément de mesure. Il permet de commuter une électro-vanne, d‘activer une alarme ou d‘établir une boucle de régulation.Trois touches de programmation permettent d‘effectuer les différents ajustements.

Le boîtier du transmetteur est orientable à 180°.

Le transmetteur 8311 peut être inséré dans un raccord pour ensuite être monté sur tout type de conduite.

Le raccordement électrique s‘effectue, selon la version, via un connecteur multibroche M12 orientable ou un connecteur EN 175301-803.

2.2 Elément de mesureLe transmetteur 8311 utilise une cellule céramique piézo-résistive.La cellule et le module électronique sont calibrés ensemble en usine ; ne pas interchanger ces éléments avec ceux d’un autre transmetteur.

Page 50: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 83112 DEScRIPTION

2.3 Versions proposées

tensiond’alimentation

gammedepression

sortie raccordementélectrique référencedecommande

g1/2 npt1/2 rc1/2

12-30 VDC 0-2 bar 4-20 mA + 2xPNP (NPN) 1) Connecteur mâle M12 444507 444762 551739

12-30 VDC 0-2 bar 4-20 mA Connecteur EN 175301-803 444635 444640 444768

12-30 VDC 0-5 bar 4-20 mA + 2xPNP (NPN) 1) Connecteur mâle M12 444506 444763 551740

12-30 VDC 0-5 bar 4-20 mA Connecteur EN 175301-803 444636 444641 444769

12-30 VDC 0-10 bar 4-20 mA + 2xPNP (NPN) 1) Connecteur mâle M12 444503 444764 551741

12-30 VDC 0-10 bar 4-20 mA Connecteur EN 175301-803 550338 444642 444770

12-30 VDC 0-20 bar 4-20 mA + 2xPNP (NPN) 1) Connecteur mâle M12 444504 444765 551742

12-30 VDC 0-20 bar 4-20 mA Connecteur EN 175301-803 550339 444760 551737

12-30 VDC 0-50 bar 4-20 mA + 2xPNP (NPN) 1) Connecteur mâle M12 444505 444767 551743

12-30 VDC 0-50 bar 4-20 mA Connecteur EN 175301-803 444637 444761 551738

1) 2xPNP par défaut, modifiables en NPN par cavaliers sur la carte électronique

Page 51: Pressure transmitter - dginstruments.com.au

8311 �

FRANCAIS

FRANCAIS

2.4 Accessoires et pièces de rechange

description référencedecommande

Connecteur femelle M12, 5 broches, à câbler 917116

Connecteur femelle M12, 5 broches, surmoulé sur câble blindé (2 m) 438680

Connecteur femelle EN175301-803 (type 2508) avec presse-étoupe 438811

Connecteur femelle EN175301-803 (type 2509) avec réduction NPT 1/2’’ 162673

Joint FKM 438177

Joint EPDM 440693

2.� Description de l’étiquette du produit

PRESS: 8311 4-20 mACERAMIC 12-30VDC2xNPN(PNP) 30V/0,7A0-50 barS-N:00033551743A W43LGM

ad

e i

n F

ran

ce 2

3456

89

10

7

1

1. Grandeur mesurée et type de transmetteur2. Sortie courant 3. Alimentation4. Caractéristiques des sorties transistor5. Gamme de pressions6. Classe de protection électrique : double isolation7. Code fabricant8. Numéro de série9. Référence de commande 10. Matériau du capteur

Page 52: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

caractéristiques générales

Diamètre des conduites tout type de conduite avec piquage taraudé 1/2’’ (G, NPT ou Rc)

Température du fluide -20 °C à +100 °C, +100 °C pour une température ambiante max. de +40 °C

Plage de mesure 0-2 bar, 0-5 bar, 0-10 bar, 0-20 bar ou 0-50 bar

Précision typique- pour 0 °C < T < 70 °C ±1% de la pleine échelle (pleine échelle = max. de la plage de mesure)- pour -20 °C < T < 0 °C ou 70 °C < T < 100 °C ±1% ±0.03% de la pleine échelle /°C (pleine échelle = max. de la plage de mesure)

Répétabilité typique 0.06%Résolution min. 1,33 mbar (cellule 0-2 bar), 3,33 mbar (cellule 0-5 bar), 5 mbar (cellule 0-10 bar) 10 mbar (cellule 0-20 bar), 25 mbar (cellule 0-50 bar)

Elément de mesure cellule en céramiqueClasse de protection du boîtier IP 65 avec connecteur enfiché et serré (et du câble de diamètre 6-7 mm si connecteur EN 175301-803)

caractéristiques électriques

Catégorie d’installation (classe de surtension) 2Alimentation (V+) 12-30 VDCConsommation maximum 30 mA (+700 mA max. par sortie transistor utilisée)

3 cARAcTERISTIqUES TEcHNIqUES

Page 53: Pressure transmitter - dginstruments.com.au

8311 11

FRANCAIS

FRANCAIS

Protection contre lespics de tension oui, pour l’alimentation et les sorties transistor Protection contre l‘inversion de polarité oui, pour l’alimentation et toutes les sorties

Sorties transistor 2 PNP ou 2 NPN, modifiables par cavaliers, collecteur ouvert, 700 mA max., sortie NPN : V+ moins 0.5 VDC / 0 VDC et sortie PNP : 0.5 VDC / V+

Sortie courant 4-20 mA, ajustement possible du 4 mA entre 3,5 et 4,5 mA ; Ajustement possible du 20 mA entre 19 et 21 mA Temps de réaction (10% - 90%) : 300 ms avec le filtre 0 (paramétrage par défaut)

Impédance de ligne max. Rload, fonction de la tension d’alimentation (V+), des résistances de ligne (RL) et des courants I1 et I2

Rload = V+ - 10 - RL (I1 + I2)

0,022

8311V+

I1

I20,022 A

RloadRL

RL

Page 54: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 83113 cARAcTERISTIqUES TEcHNIqUES

Protection contre les courts-circuits francs oui, sur sorties transistorType de câble recommandé blindé, section de fil comprise entre 0,14 et 0,5 mm2

Raccordement électrique

Version 2 sorties transistor + 1 sortie courant Connecteur femelle M12, 5 broches (non fourni)Version 1 sortie courant Connecteur femelle EN 175301-803 (type 2508 fourni)

Matériaux

Boîtier polycarbonate renforcé en fibres de verreFace avant polyesterEléments en contact avec le fluide acier inoxydable 316L (DIN 1.4404), joint en FKM en standard (EPDM en option), cellule en céramique (Al2O3)

Environnement

Température ambiante 0 °C à +60° C, +40 °C max. si la température du fluide est proche de +100 °CHumidité relative < 80%, non condensée

Page 55: Pressure transmitter - dginstruments.com.au

8311 13

FRANCAIS

FRANCAIS

Dimensions (mm)54 22

SW 27

G1/2'' - NPT1/2'' - Rc1/2''

92

18

54

EN 175301-80330

61

M12

SW 22

54

SW 27

G1/2'' - NPT1/2'' - Rc1/2''

92

1861

40

Page 56: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 83114 INSTALLATION

4.1 Recommandations généralesVérifier systématiquement la compatibilité chimique des matériaux composant le transmetteur et les produits susceptibles d‘entrer en contact avec celui-ci par exemple : alcools, acides forts ou concentrés, aldéhydes, bases, esters, composés aliphatiques, cétones, aromatiques ou hydrocarbures halogénés, oxydants et agents chlorés. Votre fournis-seur Bürkert reste à votre entière disposition pour tous renseignements complémentaires.4.2 Montage sur la conduiteLe transmetteur de pression 8311 peut être inséré dans un raccord pour l‘installation sur une conduite. Lors du montage, respecter les consignes livrées avec le raccord.

Le couvercle doit toujours être replacé dans son orientation initiale. Le boîtier peut ensuite

être tourné de 180°.

Ne pas utiliser le boîtier pour serrer le transmetteur.

Utiliser un outil approprié.

Pour la version G1/2’’, s’assurer que le joint torique est en place

Veillez à ne pas dévisser la partie métallique de la

canalisation lors-que vous réorientez le boîtier.

ENTEROUT 0....9

Page 57: Pressure transmitter - dginstruments.com.au

8311 1�

FRANCAIS

FRANCAIS

4.3 Raccordement électriqueAssurez-vous toujours que l‘appareil est hors tension avant d‘effectuer toute intervention. Tous les connecteurs doivent être débranchés. Utilisez :- un câble blindé avec une température limite de service > +80 °C.- une alimentation de qualité (filtrée et régulée).- Utiliser impérativement un fusible correctement dimensionné

pour l‘alimentation.- Relier le blindage à la terre, aux deux extrémités du câble,

avec une liaison la plus courte possible.4.3.1 connecteurs femelles

1 2 4

31

5

2connecteur femelle 2�08 (fourni)- Pour ouvrir le connecteur, retirer la vis "1".- Extraire la partie "3" de la partie "2".- Dévisser le presse-étoupe [5].- Passer les câbles dans le presse-étoupe puis à travers la partie [2].- Effectuer les connexions (voir 4.3.3).- Replacer la partie "3" dans la partie "2". La partie "3" est orientable par pas de 90° avant d'être insérée dans la partie "2".- Serrer le presse-étoupe "5". Replacer le joint "4" entre le connecteur 2508 et son embase sur le transmetteur puis insérer le connecteur 2508 sur l’embase.- Resserrer la vis "1" pour assurer l’étanchéité ainsi qu’un contact électrique correct.

connecteur multibroche M12 femelle (non fourni)- Desserrer complètement l‘écrou [1]- Enlever la partie arrière [2] du connecteur.- Effectuer les connexions (voir 4.3.2)

Page 58: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

PNP

0 V

V+ V+

IN

0 VA

OUT1/OUT2

(*)

NPN

0 V

V+ V+

IN

0 V

A

OUT1/OUT2

(*)

4 INSTALLATION

4.3.2 Version avec 2 sorties transistor et 1 sortie courant

4

5

3

1 2

0 VDC

V+(12-30 VDC)

sortienpn sortiepnp

Capteur CapteurRécepteur

Charge

Récepteur

Charge

câblagedel’embasem12dutransmetteur

OUT2 (PNP1) / NPN)

SortieSortie

(*) Terre fonctionnelle

Brocheducâblem12disponibleenoption(réf�decommande438680)

couleurduconducteur

1 brun2 blanc3 bleu4 noir5 gris

L’embase M12 est orientable :Désserrer le contre-écrou. Tourner l’embase jusqu’à la position souhaitée, de 360° max. pour ne pas tordre les câbles à l’intérieur du boîtier. Resserrer le contre-écrou à l’aide d’une clé en maintenant l’em-base dans la position souhaitée.

OUT1 (PNP1) / NPN)

Page 59: Pressure transmitter - dginstruments.com.au

8311 1�

FRANCAIS

FRANCAIS

1) PNP par défaut ; Pour modifier les sorties transistor PNP en NPN, procéder comme suit :- Débrancher le connecteur d’alimentation M12- Dévisser les 4 vis du couvercle du transmetteur- Modifier la position des 2 cavaliers (Attention : si vous configurez l’une des sorties transistor en NPN et l’autre en PNP, la sortie 4-20 mA n’est plus exploitable)

- Repositionner le couvercle dans son orientation initiale puis revisser les 4 vis en croix- Rebrancher le connecteur M12

configuration PNP configuration NPN

Sécurité de fonctionnementVérifiez toujours le câblage des connecteurs avant la mise sous tension pour assurer le bon fonctionnement de l‘appareil.

4.3.3 Version avec la sortie courant

0 V

V+ V+

0 VA

(*)

0 V

V+ V+

0 V

A

(*)

sortiecourant4-20macâblagedel’embaseen175301-803dutransmetteur

ou

Non connecté

1

3 2

0V

V+(12-30 VDC)

Page 60: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

�.1 Recommandations générales

Tous les réglages peuvent influer sur le déroulement correct du procédé. Notez les valeurs des paramètres que vous avez programmées (dans les tableaux p. 35-36).

�.2 Fonctionnalités

L‘appareil comprend trois modes d‘utilisation :

Mode Normal (voir p.21)Affichage de la pression, de la valeur du courant de sortie et des valeurs de pression minimale et maximale.Depuis le mode Normal, vous accédez aux modes Calibration et Test.

L’accès aux modes calibration et Test peut être protégé par un code à 4 chiffres, inactif par défaut ; il est programmable dans le menu calibration.

� PROgRAMMATION

Page 61: Pressure transmitter - dginstruments.com.au

8311 1�

FRANCAIS

FRANCAIS

Mode calibration (voir p. 22)Réalisation de l‘ensemble des réglages nécessaires au fonctionnement (unité, sorties transistor, filtre, sortie 4-20 mA, bargraphe, comportement des sorties en cas de dépassement de gamme et/ou d’erreur, code d’ac-cès aux modes Calibration et Test).Depuis le mode Calibration, vous pouvez retourner au mode Normal.

Pour information:1 bar = mbar psi atm kPa MPa mH2O mmHg

1000 14.5038 0.98692 100 0.1 10.1972 750.064

1 bar = ft H2O in. H2O in. Hg kp/cm2

33.4553 401.463 29.53 1.01972

Mode Test (voir p. 32)Saisie d‘une valeur théorique afin de tester la configuration programmée dans le mode Calibration. Ce mode permet également d’ajuster le point zéro, d’ajuster le facteur K, d’ajuster la sortie courant et de revenir aux paramètres par défaut des modes Calibration et/ou Test. Depuis le mode Test, vous pouvez retourner au mode Normal.

Page 62: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

12

� PROgRAMMATION

�.3 Touches de programmation et afficheur

Affiche la valeur mesurée et la configu-ration (8 caractères : 4 numériques et 4 alphanumériques)

Modifie la valeur numérique (0…9) ; Permet de passer à la fonction précédente.

Sélectionne le caractère ;Permet de passer à la fonction suivante.

Valide le choix d’une fonction ;Valide les paramètres saisis.

La LED s’allume lorsque l’une des sorties transistor commute et l’icone «1» pour OUT1 ou «2» pour OUT2 s’affiche.

Indique la fonction ou l’unité sélectionnée. Bargraphe actif à tous les niveaux

des menus.

Page 63: Pressure transmitter - dginstruments.com.au

8311 21

FRANCAIS

FRANCAIS

1

CodeOK ?

ENTER

0......9

BAR1.000

ma5.41

MIN0.01

Max1.80

2

3

> 5 s0......9

ENTER+

> 5 s

ENTER+ CODE0000ON

OFF

CodeOK ?

ENTER

CODE0000ON

OFF

0......9

0......9*

�.4 Mode Normal

Affichage de la pression mesurée.N.B. : Lorsque l’affichage cli-gnote, la valeur min. ou max. de la gamme est dépassée.

Affichage de la valeur du courant de sortie (en mA).

Retour à la fonction précédente.

Affichage, alternativement, des pressions min. et max. atteintes dans le process de-puis la dernière mise à zéro.

Aller à la fonction suivante.

Le bargraphe est affiché à tous les niveaux de menus.

(voir p. 22-30 : Mode calibration)

(voir p. 32-33 : Mode Test)

L’utilisation et la programmation d’un CODE d’accès aux menus Cali-bration et Test sont définies dans le mode Calibration.

* Appuyer sur

ENTER

pendant 5s pour mettre les pressions min. et max. à zéro.

1

2

3

1

Etat fonction CODE ?

Etat fonction CODE ?

oui

non

oui

non

appuisimultané

appuisimultané

Page 64: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

� PROgRAMMATION

Disponible uniquement sur versionsavec sorties transistor

Affichage, alternativement, de la fonc-tion et de l’unité sélectionnéechoix de l’unité de pression

(bar, mbar, psi, atm, kPa, MPa, mH2O, mmHg).

choix, pour chaque sortie transistor (OUT1 et OUT2) :- du mode de commutation de la sortie (Hystérésis ou Fenêtre, voir ci-dessous) - des seuils de commutation bas (O LO) et haut (O HI) - du mode inversé ou non (INV, voir ci-dessous) - du délai avant commutation (DEL, en secondes).

ces paramètres ne sont pris en compte que si la fonction cAL FAIL est en mode cONT (voir p. 28-2�).

* Pour déplacer la virgule, appuyer simultanément sur 0......9

et

�.� Mode calibration

Page 65: Pressure transmitter - dginstruments.com.au

8311 23

FRANCAIS

FRANCAIS

Mode HystérésisLe changement d‘état s‘effectue lorsqu‘un seuil est détecté (pression croissante : seuil haut (OHI) à détecter, pression décroissante : seuil bas (OLO) à détecter).

Mode FenêtreLe changement d‘état s‘effectue lorsqu‘un seuil est détecté.

La temporisation (DEL) est valable pour les deux seuils de sortie. La commutation n‘est effectuée que si l‘un des seuils (OHI - OLO) est dépassé pendant une durée supérieure à la temporisation DEL.

Exemples de comportement des sorties transistor (OUT1, OUT2) du 8311 en fonction de la pression, lorsque la

fonction cAL FAIL est en mode cONT

Pression

ON

OFFOLO OHI

Mode Hystérésis

Mode Fenêtre

Non inversé

Non inversé

Inversé

Inversé

Non inversé

Non inversé

Inversé

Inversé

OUT1/2 OUT1/2

Pression Pression

Non inversé

Non inversé

Inversé

InverséOUT1/2 OUT1/2

Pression Pression

ON

OFFOLO OHI

ON

OFFOLO OHI

ON

OFFOLO OHI

2 s

OHI

OLO2 s 2 s

DEL = 0 s

DEL = 2 s

DEL = 0 s

DEL = 2 s

ONOFF

ONOFF

ONOFF

ONOFF

ONOFF

ONOFF

ONOFFONOFF

OUT1/OUT2

t

Page 66: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311� PROgRAMMATION

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

choix du niveau de filtrage (FILT) des variations de pres-sion, à l’affichage et sur le signal de sortie courant (voir ci-dessous).

Fonction FILT (Filtre)

La fonction Filtre permet d’éviter les fluctuations de l’affichage et du si-gnal de sortie courant lorsque des variations de pression se produisent dans le process.Elle n’a aucun effet sur les sorties transistor.

Page 67: Pressure transmitter - dginstruments.com.au

8311 2�

FRANCAIS

FRANCAIS

Dix niveaux d’atténuation, de 0 (aucune atténuation) à 9 (atténuation maximale des fluctuations), sont proposés ; de plus, pour les niveaux 1 à 9, il est possible de choisir le temps de réaction pour l’affichage du débit et de la modification de la valeur du courant de sortie : avec l’option «FAST» (rapide), le filtre réagit immédiatement et avec l’option «SLOW» (lent), le filtre réagit progressivement.

tFAST FAST

SLOW SLOW

200 ms 2.7 s 4.7 s

FILTRE 0 FILTRE 5 FILTRE 9

Page 68: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311� PROgRAMMATION

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

* Pour déplacer la virgule, appuyer simultanément sur 0......9

et

Définition des valeurs min. (BG LO) et max. (BG HI) du bargraphe au bas de l’afficheur, dans l’unité sélec-tionnée.

Définition des valeurs de process correspondant aux courants de sortie 4 mA et 20 mA, dans l’unité sélectionnée (voir ci-dessous).

Page 69: Pressure transmitter - dginstruments.com.au

8311 2�

FRANCAIS

FRANCAIS

Fonction mA : sortie courant 4-20 mALa sortie 4-20 mA fournit un signal électrique dont la valeur reflète la pression mesurée par le transmetteur.La fonction «mA» du mode Calibration permet de faire correspondre la plage de mesure du transmetteur à la sortie courant.La courbe ci-dessous donne un exemple de relation entre la plage de mesure (pour les gammes de pression 0-10 bar, 0-20 bar et 0-50 bar) et la sortie 4-20 mA :

- Le signal peut être inversé, c’est-à-dire que la valeur de pression asso-ciée au 20 mA peut être inférieure à celle associée au 4 mA.

- La sortie courant délivre un courant de 22 mA lorsque le transmetteur signale une erreur de fonctionnement et, si la fonction «CAL FAIL mA» = 22 mA, lorsque la gamme de pression est dépassée.

4

20

0 8

mA

bar-1

Page 70: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311� PROgRAMMATION

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

Définition du comportement de chaque sortie transistor en cas de dépassement de la gamme de pression ou de l’affichage d’une erreur :- CONT : la sortie fonctionne selon la programmation du menu CAL 1OUT ou CAL 2OUT- ON : le circuit correspon-dant se ferme immédiatement (s’ouvre dès que la pression est dans la gamme ou que l’erreur est acquittée) - OFF : le circuit correspondant s’ouvre immédiatement (se ferme dès que la pression est dans la gamme ou que l’erreur est acquittée). Définition du comportement de la sortie 4-20 mA en cas de dépassement de la gamme de pression :

Disponible uniquement sur versionsavec sorties transistor.

Si vous programmez la fonction cAL FAIL en mode ON ou OFF pour OUT1 et/ou OUT2, les paramètres programmés dans la fonction cAL 1OUT et/ou cAL 2OUT ne sont pas pris en compte.

Page 71: Pressure transmitter - dginstruments.com.au

8311 2�

FRANCAIS

FRANCAIS

4 mA <-> OLO

ONOFF

20 mA <-> OHI

OUT (Transistor)FAILOUT

CONT

ONOFF

ON

ON

OFFOFF

CONT

22 mA

FAIL mA

20 mA

4 mA

22 mA

mA

20 mA

4 mA

22 mA

P

t

t

t

t

t

t

- CONT : la sortie fonctionne selon la programmation du menu CAL mA - 22 mA : la sortie délivre immédiatement un courant de 22 mA (disparait dès que la pression est dans la gamme)

Exemple de comportement des sorties transistor (OUT) et 4-20 mA (mA) en fonction du mode sélectionné dans CAL FAIL et/ou CAL OUT, en fonction de la pression mesurée.En supposant que :- un courant de 4 mA correspond à OLO - un courant de 20 mA correspond à OHI - les sorties transistor réagissent en fonction du mode fenêtre.

Dépassement de la gamme

Dépassement de la gamme

Rupture connexion cellule («10 ERR»)

Max. de la gamme

Min. de la gamme

Page 72: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

� PROgRAMMATION

Retour à l’affichage de la pression dans le mode Nor-mal, avec sauvegarde (SAVE YES) ou non (SAVE NO) des paramètres programmés.

choix de protéger ou non par un code de 4 chiffres l’accès aux modes Calibration et Test.

Retour au mode Normal (voir p. 21)

Page 73: Pressure transmitter - dginstruments.com.au

8311 31

FRANCAIS

FRANCAIS

�.6 configuration par défaut du mode calibration

A la première mise sous tension, la configuration du 8311 est la suivante :

Unité de pression : barSorties transistor (*) : hystérésisOLO1 et 2 (*) : -0,2 bar (gamme 0-2) ; -0,5 bar (gamme 0-5) ; -1 bar (gamme 0-10) -2 bar (gamme 0-20) ; -5 bar (gamme 0-50)OHI1 et 2 (*) : max. de la gammeINV1 et 2 (*) : nonDEL1 et 2 (*) : 0 sFiltre : 0, FAST (rapide)4 mA : 0 bar20 mA : max. de la gammeBGLO : 0 bar BGHI : max. de la gammeFAIL : CONT (continue), pour OUT1 et OUT2 22 mA, pour la sortie 4-20 mACODE : OFF (inutilisé), valeur 0000

(*) Uniquement sur versions avec sorties transistor

Page 74: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

15.20ZERO

DISP

1

CAL

3

ENTER

ENTER

0......9

ENTER

ENTER

ENTER

0......9

TEST% ZERO

TESTSIM

KFACENTER

0......9

TEST

maTEST ENTER ENTER

OFFS ma

3.95 ENTER

SPAN ma

20.50

0......9

*0......9

*

RSET RSET

RSET

ENTER

0......9

ENTER

ENTER

TEST NO

CAL

RSET

ENTERTEST

ENDENTERTEST

0......9

ENTER

ENTER

SAVENO

SAVEYES

SIM UNIT

0......9

ENTER

*

1.500SIM UNIT

0.205 ENTER

TEACH ZERO15.20 ENTER

% ZERO

01.00DISP

CAL

ENTER

ENTER

ENTER

% KFAC

9.985 ENTER

TEACH KFAC

10.00 ENTER

UNIT01.00 ENTER

% KFAC

0......9

*

2)

% ZERO < 20% ?&

% ZERO > -20% ?

% KFAC < 20% ?&

% KFAC > -20% ?

1)

1)

� PROgRAMMATION

�.� Mode Test

ZERO -> DISPAffichage de l’écart en % entre le zéro calibré en usine et le dernier zéro calibré.ZERO -> cALAjustement du zéro du capteur, à pression nulle, par rapport au zéro calibré en usine.

Simulation du comporte-ment du transmetteur avec une valeur de pression théorique.

1) Le transmetteur fonctionne en utilisant la valeur précédente.2) Le transmetteur mémorise la pression appliquée dans le process.

Le zéro du capteur doit impérative-ment être calibré avant le facteur K

KFAc -> DISPAffichage de l’écart en % entre le facteur K calibré en usine et le dernier facteur K calibré.KFAc -> cALAjustement du facteur K du capteur, à une pression étalon, par rapport au facteur K calibré en usine.

Affichage, alternativement, de la fonction et de l’unité sélectionnée

non

Saisir la valeur de la pression étalon (comprise dans la gamme de mesure) appliquée au process.

non

oui

oui

Page 75: Pressure transmitter - dginstruments.com.au

8311 33

FRANCAIS

FRANCAIS

15.20ZERO

DISP

1

CAL

3

ENTER

ENTER

0......9

ENTER

ENTER

ENTER

0......9

TEST% ZERO

TESTSIM

KFACENTER

0......9

TEST

maTEST ENTER ENTER

OFFS ma

3.95 ENTER

SPAN ma

20.50

0......9

*0......9

*

RSET RSET

RSET

ENTER

0......9

ENTER

ENTER

TEST NO

CAL

RSET

ENTERTEST

ENDENTERTEST

0......9

ENTER

ENTER

SAVENO

SAVEYES

SIM UNIT

0......9

ENTER

*

1.500SIM UNIT

0.205 ENTER

TEACH ZERO15.20 ENTER

% ZERO

01.00DISP

CAL

ENTER

ENTER

ENTER

% KFAC

9.985 ENTER

TEACH KFAC

10.00 ENTER

UNIT01.00 ENTER

% KFAC

0......9

*

2)

% ZERO < 20% ?&

% ZERO > -20% ?

% KFAC < 20% ?&

% KFAC > -20% ?

1)

1)

Ajustement de la sortie 4-20 mA du transmetteur :- sélectionner la fonction OFFS : le transmetteur génère un courant de 4 mA ; mesurer la valeur du courant sur la sortie 4-20 mA à l’aide d’un multimètre puis saisir cette valeur dans la fonction OFFS- sélectionner la fonction SPAN : le transmetteur génère un courant de 20 mA ; mesurer la valeur du courant sur la sortie 4-20 mA à l’aide d’un multimètre puis saisir cette valeur dans la fonction SPAN.

choix de réattribuer ou non les valeurs programmées en usine aux paramètres des modes Calibration et/ou Test (voir pages 31 et 34).

Retour à l’affichage de la pression dans le mode Nor-mal, avec sauvegarde (SAVE YES) ou non (SAVE NO) des paramètres programmés.

Retour au mode Normal (voir p. 21)

* Pour déplacer la virgule, appuyer simultanément sur 0......9

et

Page 76: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311� PROgRAMMATION

�.8 configuration par défaut du mode Test

La configuration du mode Test au départ de l’usine est la suivante :OFFS : 4 mASPAN : 20 mA

�.� configuration programmée

unité modeout1 seuilsout1 inverséout1 tempo�out1 modeout2 seuilsout2 inverséout2 tempo�out2

unit hyst�1) Fen�2) olo ohi Yes no del(s) hyst�1) Fen�2) olo ohi Yes no del(s)

1) Mode Hystérésis : 2) Mode Fenêtre :ON

OFFOLO OHI

ON

OFFOLO OHI

Page 77: Pressure transmitter - dginstruments.com.au

8311 3�

FRANCAIS

FRANCAIS

Filtre sortiecourant Bargraphe erreurout1 erreurout2 erreur4-20ma code

n° Fast/sloW 4ma 20ma Bglo Bghi cont on oFF cont on oFF cont on oFF

ajust�Zéro ajust�facteurK ajust�4-20ma date signature

Zero KFact oFFs span

Page 78: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311� PROgRAMMATION

�.10 Plages de saisie des paramètres programmables

Menu calibration Menu Test

Pression mesurée : -999 à 9999 Pression simulée : -999 à 9999Courant affiché : 0.000 à 9999 Zéro/Facteur K affiché : -999 à 9999%OLO1 et 2 (*) : -999 à 9999 Zéro/Facteur K calibré : -999 à 9999OHI1 et 2 (*) : -999 à 9999 Pression étalon : -999 à 9999DEL1 et 2 (*) : 0 s à 999 s 4 mA calibré : 3,5 à 4,5 mAFiltre : 0 à 9 20 mA calibré : 19 à 21 mA

4 mA : -999 à 999920 mA : -999 à 9999 BGLO : -999 à 9999BGHI : -999 à 9999CODE : 0000 à 9999 (*) Uniquement sur versions avec sorties transistor

En dehors des limites, le transmetteur ne valide pas la valeur mais affiche la valeur limite la plus proche.

Page 79: Pressure transmitter - dginstruments.com.au

8311 3�

FRANCAIS

FRANCAIS

Page 80: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 83116 MAINTENANcE

6.1 EntretienLe transmetteur 8311 peut être nettoyé avec de l‘eau ou un produit com-patible avec les matériaux qui le composent.Votre fournisseur Bürkert reste à votre entière disposition pour tous renseignements complémentaires.

6.2 Messages d‘erreur

messageaffiché signification quefaire?

1 ERR Les données sauvegardées après une coupure d’alimentation sont perdues.Erreur de lecture et/ou d’écriture : le processus est interrompu.

Appuyer sur la touche ENTER pour retourner au mode Normal.Si ce message s’affiche de façon répétitive, renvoyer l’appareil à votre fournisseur Bürkert.

2 ERR Les paramètres du menu Calibra-tion ne peuvent pas être lus et/ou enregistrés. Erreur de lecture et/ou d’écriture : le processus est interrompu.

Appuyer sur la touche ENTER pour retourner au mode Normal.L’appareil fonctionne avec la configuration usine: il faut reprogram-mer les paramètres du menu Calibration.Si ce message s’affiche de façon répétitive, renvoyer l’appareil à votre fournisseur Bürkert.

3 ERR Les paramètres du menu Test ne peuvent pas être lus et/ou enregistrés.Erreur de lecture et/ou d’écriture : le processus est interrompu.

Appuyer sur la touche ENTER pour retourner au mode Normal.L’appareil fonctionne avec la configuration usine: il faut reprogram-mer les paramètres du menu Test.Si ce message s’affiche de façon répétitive, renvoyer l’appareil à votre fournisseur Bürkert.

Page 81: Pressure transmitter - dginstruments.com.au

8311 3�

FRANCAIS

FRANCAIS

messageaffiché signification quefaire?

10 ERR La liaison avec la cellule de me-sure est coupée.

Débrancher le connecteur d’alimentation.Ouvrir le couvercle et vérifier la connexion de la sonde à la carte électronique.

Si ce message s’affiche de façon répétitive, renvoyer l’appareil à votre fournisseur Bürkert.

Connexion cellule de mesure

6.3 En cas de problème- Perte du code de protection (voir parag. 5.4) : appuyer simultané-

ment sur les touches 0......9 pendant 30 secondes au moment de la demande de saisie du code, pour accéder au mode souhaité.

- L’affichage clignote : dépassement de la gamme de pression.- «----» est affiché : les valeurs limites affichables sont dépassées.

Choisir une unité de pression appropriée.- Le transmetteur reset dès que l’une au moins des sorties transistor commute : l’impédance de ligne est trop élevée (voir p. 11)

Page 82: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311� ExEMPLES DE RAccORDEMENT

4

1

3

2

5

18 V=

8311

+ -

mA

+

-

Raccordement d’une version avec sortie 4-20 mA seule (connecteur EN 1��301-803).

Raccordement d’une version avec 2 sor-ties transistor PNP et la sortie 4-20 mA (connec-teur M12).

Relier impérativement le blindage des câbles à la terre aux deux extrémités.

1

23

8311

18 V=+ -

+ -mA

1

23

8311

18 V=+ -

mA+

-

Charge 1

Charge 2

Fusible Fusible

Fusible

Page 83: Pressure transmitter - dginstruments.com.au

8311 41

FRANCAIS

FRANCAIS

Raccordement d’une version avec 2 sorties transistor NPN et la sortie 4-20 mA (connec-teur M12).

Raccordement d’une version avec 2 sorties transistor NPN et la sortie 4-20 mA (connecteur M12) permettant de rédui-re les courants dans les charges en cas de problème d’im-pédance de ligne.

Relier impérativement le blindage des câbles à la terre aux deux extrémités.

4

1

3

2

5

18 V=

8311

+ -

mA+

-

4

1

3

2

5

18 V=

8311

+ -

mA+

-

30 V=+ -

Ι

30 V

30 V

Charge 1

Charge 2

Charge 1

Charge 2

de charge

Fusible

Fusible

Fusible

Page 84: Pressure transmitter - dginstruments.com.au

FRANCAIS

FRANCAIS

Transmetteur de pression 8311

Page 85: Pressure transmitter - dginstruments.com.au

Bedienungsanleitung

Druck-TransmiTTer

8311

© Bürkert 2003 Technische Änderung vorbehalten

Page 86: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

inhaltsverzeichnis

1 AllgemeineSicherheitShinweiSe����������������������������������������������������������������������������������������������������������4

1.1 BestimmungsgemäßeVerwendung...................................................................................................................................51.2 GefahrenbeiderInstallationundInbetriebnahme.................................................................................................61.3 Normenbezüge....................................................................................................................................................................................6

2 BeSchreiBung���������������������������������������������������������������������������������������������������������������������������������������������������������7

2.1 Aufbau/Funktion................................................................................................................................................................................72.2 Messprinzip.............................................................................................................................................................................................72.3 Ausführungen.......................................................................................................................................................................................82.4 ZubehörundErsatzteile...............................................................................................................................................................92.5 BeschreibungdesTypenschilds............................................................................................................................................9

3 techniScheDAten��������������������������������������������������������������������������������������������������������������������������������������������10

4 inStAllAtion�����������������������������������������������������������������������������������������������������������������������������������������������������������14

4.1 AllgemeineHinweise...................................................................................................................................................................144.2 EinbauindieRohrleitung.........................................................................................................................................................144.3 ElektrischerAnschluss..............................................................................................................................................................15 4.3.1Gerätesteckdosen...........................................................................................................................................................15

Page 87: Pressure transmitter - dginstruments.com.au

8311 3

DEU

TSCH

DEU

TSCH

4.3.2Ausführungmit2Transistor-und1Strom-Ausgang........................................................................16 4.3.3AusführungmitdemStromausgang................................................................................................................17

5 BeDienung���������������������������������������������������������������������������������������������������������������������������������������������������������������18

5.1 AllgemeineHinweise...................................................................................................................................................................185.2 Funktionsübersicht........................................................................................................................................................................185.3 Bedien-undAnzeigeelemente............................................................................................................................................205.4 Normalmodus....................................................................................................................................................................................215.5 Kalibriermodus..................................................................................................................................................................................225.6 GrundeinstellungdesKalibriermodus...........................................................................................................................315.7 Test-Modus..........................................................................................................................................................................................325.8 GrundeinstellungdesTestmodus.....................................................................................................................................345.9 Kunden-EinstellungdesTransmitters............................................................................................................................345.10EingabebereichdereinstellbarenParametern......................................................................................................36

6 wArtung��������������������������������������������������������������������������������������������������������������������������������������������������������������������38

6.1 Reinigung..............................................................................................................................................................................................386.2 Fehleranzeige....................................................................................................................................................................................386.3 GibteseinProblem?...................................................................................................................................................................39

7 AnSchluSS-BeiSpiele�������������������������������������������������������������������������������������������������������������������������������������40

Page 88: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter83111 allgemeinesicherheiTshinweise

- BeachtensieinjedemFalldienachfolgendenundindener-läuterungenaufgeführtensicherheitshinweise.Diekennzeich-nungdersicherheitshinweiseerfolgtdurchdasnebenstehen-desymbol.

- Vergewissernsiesich,dassderbeidemProzesserreichbareDruckinnerhalbdesgewähltenDruckbereichsliegt.Dieinstal-lationsolltemiteinemÜberdruckventilversehenwerden.

Druckbereich[bar] max�zulässigerDruck Zerstörungsdruck

0-2 4 7

0-5 10 12

0-10 20 25

0-20 40 50

0-50 100 120

- Dieanzeigeblinktimnormal-modus,wenndasDruckmessbe-reichunter-oderüberschrittenwird.

Page 89: Pressure transmitter - dginstruments.com.au

8311 �

DEU

TSCH

DEU

TSCH

1.1 BestimmungsgemäßeVerwendung

- DerDruck-Transmitter8311darfnurzurDruckmessunginFlüssig-keitenundGaseneingesetztwerden.

- DieMesswertekönneninfolgendenDruck-Einheitenangezeigtwer-den:bar,mbar,psi,atm,kPa,MPa,MH2O,mmHg.

Beiabsolutdruck-einheiten(mmhg,atm,mh2O)wirddieluftdruck-Verschiebung(ung.1013mbar)nichtinanspruchgenommen.

- DabeimussdasMessgerätsichermitdemBehältnisübereineSchraubverbindungverbundensein.

FürSchädenausunsachgemäßemodernichtbestimmungsgemäßemGebrauchhaftetderHerstellernicht.AndemGerätdürfenkeineUm-bautenoderVeränderungenvorgenommenwerden.

einbauund/oderreparaturdürfennurdurcheingewiesenesPersonalerfolgen.solltenbeiderinstallationoderderinbe-triebnahmeschwierigkeitenauftreten,setzensiesichbittemitBürkertinVerbindung.

Page 90: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

1.2 gefahrenbeiderinstallationundinbetriebnahme

- BeimEntfernendesGehäusedeckelsundbeimEinschaltenderVer-sorgungsspannungistderBerührungsschutzaufgehoben.

- BeachtenSiebeispeziellenMessmedien,inkl.MedienfürdieReini-gung,dieMaterialbeständigkeitvonmediumsberührendenTeilen.

- EsdarfkeinerleiObjekt(z.B.Schraubendreher)indieÖffnungdesSensor-Körperseingeführtwerden.VerwendenSieDruckluftzumReinigendesGerätes.

DemverwendetenProzessentsprechendmüssengeeigneteVorsichtsmaßnahmengetroffenwerden,bevorderTransmitterabgebautwird.

1.3 normenbezüge

- EMV:EN50081-1,61000-6-2- Sicherheit:EN61010-1- Vibration:EN60068-2-6- Stoß:EN60068-2-27

1 allgemeinesicherheiTshinweise

Page 91: Pressure transmitter - dginstruments.com.au

8311 �

DEU

TSCH

DEU

TSCH

2 BeschreiBung2.1 aufbau/FunktionDer2-drahtigeDruck-Transmitter8311bestehtauseinemElektronikmo-dulundeinemMesselement.Erwurdedafürausgelegt,einMagnetventilzuschalten,einAlarmauszulösenodereineRegelschleifezuerrichten.DieParameter-EinstellungenwerdenmittelsdreiFolientastenunterdemDisplaydurchgeführt.

DasTransmitter-Gehäuseistdrehbarum180°.

DerTransmitter8311kannineinFittingeingebautwerden,umeineneinfachenEinbauinjedeRohrleitungzuermöglichen.

DerelektrischeAnschlusserfolgt,jenachAusführung,übereinenverstell-barenMultipinM12-SteckerodereinenEN175301-803-Stecker.

2.2 messprinzipDerTransmitter8311verwendeteinepiezoresistiveKeramik-Zelle.DieZelleunddaselektronikmodulwerdenmiteinanderimwerkkalibriert;VerwendensiekeinerdieserelementemiteinemanderenTransmitter.

Page 92: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter83112 BeschreiBung

2.3 ausführungen

Versorgungs-spannung

messbereich Ausgang elektrischerAnschluss Bestell-nummer

g1/2 npt1/2 rc1/2

12-30VDC 0-2bar 4-20mA+2xPNP(NPN)1) M12-Gerätestecker 444507 444762 551739

12-30VDC 0-2bar 4-20mA EN175301-803-Gerätestecker 444635 444640 444768

12-30VDC 0-5bar 4-20mA+2xPNP(NPN)1) M12-Gerätestecker 444506 444763 551740

12-30VDC 0-5bar 4-20mA EN175301-803-Gerätestecker 444636 444641 444769

12-30VDC 0-10bar 4-20mA+2xPNP(NPN)1) M12-Gerätestecker 444503 444764 551741

12-30VDC 0-10bar 4-20mA EN175301-803-Gerätestecker 550338 444642 444770

12-30VDC 0-20bar 4-20mA+2xPNP(NPN)1) M12-Gerätestecker 444504 444765 551742

12-30VDC 0-20bar 4-20mA EN175301-803-Gerätestecker 550339 444760 551737

12-30VDC 0-50bar 4-20mA+2xPNP(NPN)1) M12-Gerätestecker 444505 444767 551743

12-30VDC 0-50bar 4-20mA EN175301-803-Gerätestecker 444637 444761 551738

1)2xPNPWerkab,könnenmittelsSteckbrückenaufElektronik-PlatineaufNPNgeändertwerden

Page 93: Pressure transmitter - dginstruments.com.au

8311 �

DEU

TSCH

DEU

TSCH

2.4 Zubehörundersatzteile

Bezeichnung Bestell-nummer

5-PinM12-Gerätesteckdose,zumkabeln 917116

5-PinM12-Gerätesteckdose,amKabelangespritzt(2m) 438680

EN175301-803-Gerätesteckdose(Typ2508)mitKabelverschraubung 438811

EN175301-803-Gerätesteckdose(Typ2509)mitNPT1/2’’-Reduktion 162673

DichtungausFKM 438177

DichtungausEPDM 440693

2.� BeschreibungdesTypenschilds

PRESS: 8311 4-20 mACERAMIC 12-30VDC2xNPN(PNP) 30V/0,7A0-50 barS-N:00033551743A W43LGM

ad

e i

n F

ran

ce 2

3456

89

10

7

1

1. MessgrößeundTypdesTransmitters2. Stromausgang3. Versorgungsspannung4. Transistor-Ausgänge-Kenngrößen5. Druckmessbereich6. ElektrischeSchutzklasse:Schutzisolierung7. WerkinterneNummer8. Serien-Nummer9. Bestell-Nummer10. WerkstoffdesSensors

Page 94: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

allgemeineDaten

Rohrleitungsdurchmesser jedeRohrleitungmit1/2’’-Innengewinde(G,NPToderRc)

Flüssigkeitstemperatur -20°Cbis+100°C,+100°CbeieinermaximalenUmgebungstemperaturvon+40°C

Messbereich 0-2bar,0-5bar,0-10bar,0-20baroder0-50bar

Genauigkeit,typisch-bei0°C<T<70°C ±1%vomEndwert(Endwert=max.WertdesMessbereichs)-bei-20°C<T<0°Coder70°C<T<100°C ±1%±0,03%vomEndwert/°C(Endwert=max.WertdesMessbereichs)

Wiederholbarkeit,typisch 0.06%Min.Auflösung 1,33mbar(0-2bar-Zelle),3,33mbar(0-5bar-Zelle),5mbar(0-10bar-Zelle) 10mbar(0-20bar-Zelle),25mbar(0-50bar-Zelle)

Messelement Keramik-ZelleSchutzartdesGehäuses IP65miteingestecktemundfestgeschraubtemStecker(undeinemKabelmit6-7mm DurchschnittbeidemEN175301-803-Stecker)

elektrischeDaten

Anlage-Klasse(Überspannungsklasse) 2Spannungsversorgung(V+) 12-30VDCMax.Stromaufnahme 30mA(+700mAmax.fürjedenverwendentenTransistor-Ausgang)

3 TechnischeDaTen

Page 95: Pressure transmitter - dginstruments.com.au

8311 11

DEU

TSCH

DEU

TSCH

SchutzgegenSpannungs-spitzen vorhanden,fürStromversorgungundTransistor-AusgängeSchutzgegenFalschpolung vorhanden,fürStromversorgungundalleAusgänge

Transistor-Ausgang 2PNPoder2NPN,mittelsSteckbrückenveränderbar,opencollector,max.700mA, NPN-Ausgang:V+minus0.5VDC/0VDCundPNP-Ausgang:0.5VDC/V+

4-20mA-Ausgang Anpassungdes4mAzwischen3,5und4,5mAmöglich;Anpassungdes20mAzwischen 19und21mAmöglich Ansprechzeit(10%-90%):300msmitFilter0(Grundeinstellung)

MaximaleBürdenimpedanz Rload,vonderBetriebsspannung(V+),denLasten(RL)aufdenbeidenTransistor-Ausgängen unddenI1undI2-Stromwertenabhängig.

Rload = V+ - 10 - RL (I1 + I2)

0,022

8311V+

I1

I20,022 A

RloadRL

RL

Page 96: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter83113 TechnischeDaTen

Kurzschlusschutz vorhandenfürdieTransistor-AusgängeEmpfohlenerKabel-Typ abgeschirmt,Drahtquerschnittzwischen0,14und0,5mm2

elektrischeranschluss

Ausführungmit2Transistor-+1Stromausgang 5-PinM12-Gerätesteckdose(nichtgeliefert)Ausführungmit1Strom-ausgang EN175301-803-Gerätesteckdose(Typ2508geliefert)

werkstoffe

Gehäuse Polycarbonat,GlasfaserverstärktFolieFrontplatte PolyesterFlüssigkeitsbenetzteTeile Edelstahl316L(DIN1.4404),FKM-DichtungalsStandard(EPDMaufAnfrage), Keramik-Zelle(Al2O3)

umgebung

Umgebungstemperatur 0°Cbis+60°C,max.+40°CwenndieMediumstemperatur+100°CerreichtRelativeFeuchte <80%,nichtkondensierend

Page 97: Pressure transmitter - dginstruments.com.au

8311 13

DEU

TSCH

DEU

TSCH

abmessungen(mm)54 22

SW 27

G1/2'' - NPT1/2'' - Rc1/2''

92

18

54

EN 175301-803

30

61

M12

SW 22

54

SW 27

G1/2'' - NPT1/2'' - Rc1/2''

92

1861

40

Page 98: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter83114 insTallaTiOn

4.1 allgemeinehinweiseBeachtenSieimmerdiechemischeKompatibilitätderTransmitter-Werk-stoffemitdenendasGerätinKontaktkommt(z.B.Alkoholen,zustarkenoderkonzentriertenSäuren,Aldehyden,Basen,Esteren,Aliphaten,Ke-tonen,AromatenoderHalogenkohlenwasserstoffen,OxidierungsmittelnundgechlortenMitteln).FürweitereAuskünfte,stehtIhnenBürkertzurVerfügung.4.2 einbauindierohrleitungDerDruck-Transmitter8311kannmiteinemFittingindieRohrleitungeingebautwerden.BeimEinbaudesFittingsmüssendieEinbauvorschriftenbeachtetwer-den,diedenFittingsbeiliegen.

SetzenSiedenDeckelimmergemäßoriginalerOrientierungauf.DannkanndasGehäuseum

180°gedrehtwerden.

DenTransmitternichtamKopffestziehen.

BenutzenSiedafüreingeeignetesHandwerkzeug.

BeiderG1/2’’-Ausfüh-rung,vergewissernSiesich,dassderO-Ring

eingesetztist.

VergewissernsiesichbeiderOrientierungdesgehäuses,dass

sichdermetallischeTeilnichtvonderrohr-leitunglöst.

ENTEROUT 0....9

Page 99: Pressure transmitter - dginstruments.com.au

8311 1�

DEU

TSCH

DEU

TSCH

4.3 elektrischeranschlussVergewissernSiesichstets,dassdieStromversorgungunterbrochenist,bevorEingriffeindasGerät/Systemvorgenommenwerden.DieSteckermüssenalleausgestecktsein.VerwendenSie:- einabgeschirmtesKabelmiteinerBetriebsgrenztemperaturhöherals+80°C.- EineSpannungsversorgungguterQualität(gefiltertundgeregelt).- Obligatorischisteinegeeignetesicherungfürdiestromver-sorgungzuinstallieren.

- erdensiedieabschirmungmittelseinersokurzwiemög-lichenVerbindunganbeidenendendeskabels.

4.3.1 gerätesteckdosen

1 2 4

31

5

22�08-gerätesteckdose(geliefert)- Schraube[1]aufschrauben.- Innenteil[3]ausAußenteil[2]herausnehmen.- Kabeldurchführung[5]aufschrauben.- KabeldurchKabelverschraubungdanndurch Teil[2]führen.- Teil[3]verkabeln(siehe4.3.3)- Innenteil[3]zurückstecken.Kannbeliebigin 90°-Schrittegedrehtwerden.- Kabeldurchführung[5]festschrauben.Dichtung[4]zwischender GerätesteckdoseunddemSteckverbinderdesTransmitterseinsetzen, dannGerätesteckdoseandenSteckverbinderanschließen.- Schraube[1]festziehen,umdieDichtheitsowiegutenelektrischen Kontaktzuvergewissern.

multipin-m12-gerätesteckdose(nichtgeliefert)- ZumÖffnendesSteckers Ringmutter[1]vollständiglösen- Steckerhinterteil[2]abnehmen.-GemäßAnschlussbelegungbeschalten (Siehe4.3.2)

Page 100: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

PNP

0 V

V+ V+

IN

0 VA

OUT1/OUT2

(*)

NPN

0 V

V+ V+

IN

0 V

A

OUT1/OUT2

(*)

4 insTallaTiOn

4.3.2 ausführungmit2Transistor-und1strom-ausgang

4

5

3

1 2

0 VDC

V+(12-30 VDC)

npn-Ausgang pnp-Ausgang

Sensor SensorEmpfänger

Last

Empfänger

Last

Verkabelungdesm12-gerätesteckers

OUT2(PNP1)/NPN)

AusgangAusgang

(*)FunktionnelleErde

pin-nummerdesalsZubehörverfügbarenm12-Kabels(Bestell-nummer438680)

FarbederAdern

1 braun2 weiß3 blau4 schwarz5 grau

DerM12-Gerätesteckeristbeliebigverstellbar:Gegenmutteraufschrauben.GerätesteckerbiszurgewünschtenPositiondrehen,abermaximalvon360°,umdieKabelinnerhalbdesGerätesnichtzuverdre-hen.GerätesteckeringewünschterPositionfesthaltenundGegenmuttermittelseinesgeeignetenSchlüsselsfestschrauben.

OUT1(PNP1)/NPN)

Page 101: Pressure transmitter - dginstruments.com.au

8311 1�

DEU

TSCH

DEU

TSCH

1)PNPWerkab;UmdieTransistor-AusgängevonPNPaufNPNzuändern:- ZiehenSiedenM12-Steckerheraus- LösenSiedie4SchraubendesTransmitterdeckels-Versetzensiediesteckbrücken(achtung:fallsSieeinenNPN-undeinenPNP- Ausgangkonfigurieren,istdas4-20mA-Ausgangssignalnichtmehrverwertbar)

- SetzenSiedenDeckelimmergemäßoriginalerOrientierungauf,dannschraubenSiedie4 Schraubenüberkreuzfest.- SchaltenSiedieStromversorgungwiederein.

PnP-konfiguration nPn-konfiguration

sichererBetriebZumsicherenBetrieballeSchaltungenüberprüfen,bevordasGerät/Sys-temunterSpannunggesetztwird.

4.3.3 ausführungmitdemstromausgang

0 V

V+ V+

0 VA

(*)

0 V

V+ V+

0 V

A

(*)

4-20mA-StromausgangVerkabelungdesen175301-803-gerätesteckers

oder

Nichtbelegt

1

3 2

0V

V+(12-30 VDC)

Page 102: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

�.1 allgemeinehinweise

BeachtenSie,dassalleEinstellungenderParameterAuswirkungenaufdenordnungsgemäßenProzessverlaufhabenkönnen.DokumentierenSiedieeingestelltenParameter(TabelleS.35-36).

�.2 Funktionsübersicht

DieBedienunggliedertsichindreiEbenen:

normalmodus(siehes.21)HierwerdendenDruck,denWertdesStromausgangsunddieminimalenundmaximalenDruckwerteangezeigt.VomNormalmodusausgelangtmanindenKalibrier-undindenTestmo-dus.

DerZugriffzudenkalibrier-undTestmodikannmittelseines4-Ziffercodesgesperrtwerden(grundeinstellung:ungesperrt);Programmierungdescodesimkalibriermodus.

� BeDienung

Page 103: Pressure transmitter - dginstruments.com.au

8311 1�

DEU

TSCH

DEU

TSCH

kalibriermodus(siehes.22)HierwerdenallezumBetriebnotwendigenEinstellungen(Einheit,Transistor-Ausgänge,Filter,4-20mA-Ausgang,Bargraph,VerhaltenderAusgängebeiFehlermeldungund/oderUnter-oderÜberschreitendesDruckbereichs,Kalibrier-undTestmodiZugriffscode)durchgeführt.VomKalibriermodusgelangtmanindenNormalmoduszurück.

ZurInformation:1bar= mbar psi atm kPa MPa mH2O mmHg

1000 14.5038 0.98692 100 0.1 10.1972 750.064

1bar= ftH2O in.H2O in.Hg kp/cm2

33.4553 401.463 29.53 1.01972

Testmodus(siehes.32)HierkanneintheoretischerWerteingegebenwerden,sodassdieSchaltschwellengetestetwerden.HierwerdenauchdenNullpunkt,denK-Faktor,denAusgangsstromeingestellt.HierkannmanzuderGrund-einstellungdesKalibriermodusund/oderTestmoduszurückkommen.VomTestmodusausgelangtmanindenNormalmoduszurück.

Page 104: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

12

� BeDienung

�.3 Bedien-undanzeigeelemente

Messwert-undKonfigurationsanzeige(8Stellen:4numerischeund4alphanumerische)

Zahlenwert(0…9)jeStelleverändern;Menüdurchlaufen.

Stelleauswählen;Menüdurchlaufen.

Menüpunktebestätigen.Eingabenbestätigen.

RoteLEDleuchtetbeiUmschalteneinesderTransistor-AusgängeundZiffer„1“fürOUT1oderZiffer„2“fürOUT2wirdangezeigt.

AnzeigederFunktionoderderEinheit.

BargraphinallenMenüpunktenaktiv.

Page 105: Pressure transmitter - dginstruments.com.au

8311 21

DEU

TSCH

DEU

TSCH

1

CodeOK ?

ENTER

0......9

BAR1.000

ma5.41

MIN0.01

Max1.80

2

3

> 5 s0......9

ENTER+

> 5 s

ENTER+ CODE0000ON

OFF

CodeOK ?

ENTER

CODE0000ON

OFF

0......9

0......9*

�.4 normalmodus

Anzeigedesaktuellgemes-senenDrucks.Bemerkung:WennderangezeigteWertblinkt,istderminimalebzw.maximaleDruckdesBereichsunter-bzw.überschrittenworden.

AnzeigedesWertesdesAusgangsstroms(inmA).

ZugriffzuvorigerFunktion.

AbwechselndeAnzeigederimProzesserreichtenDruck-Mindest-undHöchstwerte.

ZugriffzunächsterFunktion.

BargraphwirdinjedemMenüpunktangezeigt.

(siehes.22-30:kalibriermodus)

(siehes.32-33:Testmodus)

DieVerwendungundProgrammierungdesZugriffscodeszudenKali-brier-undTestmodiwerdenimKalibriermoduseingestellt.

*DrückenSie

ENTER

während5s,umdieseWerteaufNullzurückzusetzen.

1

2

3

1

StatusCODE-Funktion?

StatusCODE-Funktion?

ja

nein

ja

nein

gleichzeitigdrücken

gleichzeitigdrücken

Page 106: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

� BeDienung

NurbeiAusführungenmitTransistorausgängen.

AbwechselndeAnzeigederFunktionundderausgewähltenEinheit

wahlderDruck-Einheit(bar,mbar,psi,atm,kPa,MPa,mH2O,mmHg).

wahlfürjedenTransistor-ausgang(OuT1undOuT2):- desAusgangsverhaltens (HystereseoderFenster, Sieheunten) - derunteren(OLO)und oberen(OHI)Schalt- schwellenwerte- obderSchaltmodus umgekehrtistodernicht (INV,sieheunten)- derSchaltverzögerungszeit (DEL,inSekunden).

Dieseeinstel-lungenwerdennurinanspruchge-nommen,wenndieFunktioncalFailaufdencOnT-mo-duseingestelltwird(siehes.28-2�).

*DerKommawirddurchDrückenderTasten0......9

und verschoben.

�.� kalibriermodus

Page 107: Pressure transmitter - dginstruments.com.au

8311 23

DEU

TSCH

DEU

TSCH

2 s

OHI

OLO2 s 2 s

DEL = 0 s

DEL = 2 s

DEL = 0 s

DEL = 2 s

ONOFF

ONOFF

ONOFF

ONOFF

ONOFF

ONOFF

ONOFFONOFF

OUT1/OUT2

t

hysteresemodusDieStatusänderungerfolgtbeiErkennungeinerSchwelle.(ZunehmenderDruck:hoheSchwelle(OHI)zuerkennen,abnehmenderDruck:niedrigeSchwelle(OLO)zuerkennen).

FenstermodusDieStatusänderungerfolgtsobaldeinSchwel-lenwerterkanntwird.

DiegewählteVerzögerung(Del)istfürbeideausgangschwellenwirksam.DieschaltungerfolgtnurbeimÜberschreiteneinesderzweigrenzwerten(Ohi-OlO)währendeinerZeitgrösseralsdieausgewählteVerzögerungDel.

BeispieledesvomDruckabhängigenVerhaltensderTransistor-Ausgänge(OUT1,OUT2),wenndieFunktion

CALFAILaufCONTeingestelltwurde

Druck

ON

OFFOLO OHI

HystereseModus

FensterModus

Nichtumgekehrt

Nichtumgekehrt

Umgekehrt

Umgekehrt

Nichtumgekehrt

Nichtumgekehrt

Umgekehrt

Umgekehrt

OUT1/2 OUT1/2

Druck Druck

Nichtumgekehrt

Nichtumgekehrt

Umgekehrt

UmgekehrtOUT1/2 OUT1/2

Druck Druck

ON

OFFOLO OHI

ON

OFFOLO OHI

ON

OFFOLO OHI

Page 108: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311� BeDienung

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

wahlderFilterstufe(FILT)fürdenangezeigtenDruckunddenAusgangsstrom(sieheunten).

Filter-Funktion(FilT)

DieFilter-FunktionbieteteinenMesswertglättungseffekt,umSchwan-kungendesAusgangsstromsunddesangezeigtenDruckszuunterdrü-cken.DieFunktionhataufdieTransistor-AusgängekeineWirkung.

Page 109: Pressure transmitter - dginstruments.com.au

8311 2�

DEU

TSCH

DEU

TSCH

ZehnFilterstufenvon0(keinMesswertglättungseffekt)bis9(maximalerGlättungseffekt)stehenzurVerfügung;FürStufen1bis9wirdauchdieReaktionszeitderAnzeigedesgemessenenDrucksundderÄnderungdesAusgangsstromwertesbestimmt,entweder„FAST“(schnell),wobeiderFiltersofortreagiert,oder„SLOW“(langsam),wobeiderFilterall-mählichreagiert.

tFAST FAST

SLOW SLOW

200 ms 2.7 s 4.7 s

FILTER0 FILTER5 FILTEr9

Page 110: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311� BeDienung

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

*DerKommawirddurchDrückenderTasten0......9

und verschoben.

BestimmungderMindest-(BGLO)undHöchst-Werte(BGHI)desBargraphs,inderausgewähltenEinheit.

Bestimmungderden4mA-und20mA-Ausgangs-stromwertenentsprechendenProzesswerte(sieheunten).

Page 111: Pressure transmitter - dginstruments.com.au

8311 2�

DEU

TSCH

DEU

TSCH

menüpunktma:4-20ma-stromausgangDer4-20mA-AusganglieferteindemdurchdenTransmittergemessenenDruckproportionaleselektrischesSignal.ImMenüpunkt„mA“desKalibriermoduswirdderMessbereich,derdem4-20mA-Ausgangsstromentspricht,definiert.DiefolgendeKurvestellteinenBeispielfürdieBeziehungzwischendemAusgangsstromunddementsprechendenMessbereichdar(beiZellenmitDruckbereich0-10,0-20oder0-50bar):

- DerMessbereichsanfangswertkanngrößerseinalsderEndwert(inver-tiertesSignal).

- DerStromausganglieferteinen22mA-Stromwertaus,sobaldderTransmittereinenFehlermeldetund,wenndieFunktion„CALFAILmA“auf„22mA“eingestelltwurde,sobaldderDruckbereichunter-oderüberschrittenwird.

4

20

0 8

mA

bar-1

Page 112: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311� BeDienung

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

auswahldesVerhaltensvonjedemTransistor-AusgangbeieinerFehlermeldungoderdemUnter-oderÜberschrei-tendesDruckbereichs:-CONT:DerAusgangreagiertentspr.deninCAL1OUTbzw.CAL2OUTein-gestelltenParameternweiter-ON:Derentspr.Stromkreiswirdsofortgeschlossen(wirdgeöffnetsobaldderDruckimMessbereichliegtodernachDrückenderEnter-Taste)-OFF:Derentspr.Strom-kreiswirdsofortgeöffnet(wirdgeschlossensobaldderDruckimMessbereichliegtodernachDrückenderEnter-Taste)auswahldesVerhaltensdes4-20mA-AusgangsbeidemUnter-oderÜberschreitendesDruckbereichs:

NurbeiAusführungenmitTransistorausgängen.

wenndieFunktioncalFailaufOnoderOFFfürOuT1bzw.OuT2eingestelltwird,werdendieimmenücal1OuTbzw.cal2OuTeingestelltenParameternnichtinanspruchgenommen.

Page 113: Pressure transmitter - dginstruments.com.au

8311 2�

DEU

TSCH

DEU

TSCH

4 mA <-> OLO

ONOFF

20 mA <-> OHI

OUT (Transistor)FAILOUT

CONT

ONOFF

ON

ON

OFFOFF

CONT

22 mA

FAIL mA

20 mA

4 mA

22 mA

mA

20 mA

4 mA

22 mA

P

t

t

t

t

t

t

-CONT:DerAusgangarbei-tetgemäßdenEinstellungendesMenüsCALmA-22mA:DerAusgangliefertsoforteinen22mA-Stromaus(normales4-20mA-Si-gnalsobaldderDruckwiederimMessbereichliegt)

BeispielfürdenVerhaltenderTransistor-Ausgänge(OUT)unddes4-20mA-Ausgangs(mA)inAbhängig-keitderEinstellungenindenMenüsCALFAILund/oderCALOUTunddemgemes-senenDruck.FolgendeAussetzungengelten:- ein4mA-StromentsprichtOLO-ein20mA-StromentsprichtOHI-dieTransistor-AusgängereagierengemäßdemFen-ster-Modus.

ÜberschreitendesMess-bereichs

ÜberschreitendesMessbereichs

ZellenAnschlussunterbrochen(“10ERR“)

maximalerWertdesMessbereichs

minimalerWertdesMessbereichs

Page 114: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

0.500

BAR

1 OUT 1 mode

OHI>OLO

1

mMHG

1 mode

2

NO 001

YES ENTER

ENTER

ENTER

ENTER

ENTER

0......9

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

ENTER

0......9

...

* *

CAL1 OLO UNIT

1.5001 OHI UNIT

CALUNIT

1 INV

1 INV

1 DEL SEC

2 OUTENTERCAL

FILT FILT

ENTERENTERCAL 1

FAST

slowENTER

ENTER

0......9

MaENTER ENTERCAL

0......9

4Ma UNIT

0.500 ENTER

20Ma UNIT

2.500

0......9

*0......9

*

BRGRENTER ENTERCAL

BGLO UNIT

0.500 ENTER

BGHI UNIT

2.500

0......9

*0......9

*

FAIL 1 OUT

1 OUT

ENTER

0......9

ENTER

ENTER

CAL CONT

ON

1 OUT

ENTEROFF

2 OUT

2 OUT

0......9

ENTER

ENTER

CONT

ON

2 OUT

ENTEROFF

0......9

ENTER

ENTER

mACONT

mA22

CODEENTERCAL

0......9

ENTER

ENTER

CODEON

CODEOFF

ENTER

CODE9876

ENDENTERCAL

0......9

ENTER

ENTER

SAVENO

SAVEYES

1 OLO UNIT

0.5002 mode

OHI>OLO

2 mode

NO 001

YES ENTER

0......9

ENTER

ENTER 0......9 0......9

0......9

ENTERENTERENTER

0......9

* *

2 OLO UNIT

1.5002 OHI UNIT 2 INV

2 INV

2 DEL SEC

ENTER

� BeDienung

ZurückzurAnzeigedesDrucksimNormalmodusmitAbspeichern(SAVEYES)odernicht(SAVENO)dereingestelltenDaten.

auswahldenZugriffzumKalibriermodusbzw.TestmodusmittelseinesCodeszusperren.

normalmodus(siehes.21)

Page 115: Pressure transmitter - dginstruments.com.au

8311 31

DEU

TSCH

DEU

TSCH

�.6 grundeinstellungdeskalibriermodus

MitdemEinschaltenerhaltenSiefolgendeGrundeinstellungderParameter:

Druck-Einheit: barTransistor-Ausgänge(*) HystereseOLO1und2(*) -0,2bar(Bereich0-2);-0,5bar(Bereich0-5);-1bar(Bereich0-10) -2bar(Bereich0-20);-5bar(Bereich0-50)OHI1und2(*) max.desBereichsINV1und2(*) NeinDEL1und2(*) 0sFilter: 0,FAST(schnell)4mA: 0bar20mA: maximalerWertdesMessbereichsBGLO: 0bar BGHI: maximalerWertdesMessbereichsFAIL: CONT(weiter),fürOUT1undOUT2 22mA,fürden4-20mA-AusgangCODE: OFF(nichtverwendet),Wert0000

(*)NurbeiAusführungenmitTransistor-Ausgängen

Page 116: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311

15.20ZERO

DISP

1

CAL

3

ENTER

ENTER

0......9

ENTER

ENTER

ENTER

0......9

TEST% ZERO

TESTSIM

KFACENTER

0......9

TEST

maTEST ENTER ENTER

OFFS ma

3.95 ENTER

SPAN ma

20.50

0......9

*0......9

*

RSET RSET

RSET

ENTER

0......9

ENTER

ENTER

TEST NO

CAL

RSET

ENTERTEST

ENDENTERTEST

0......9

ENTER

ENTER

SAVENO

SAVEYES

SIM UNIT

0......9

ENTER

*

1.500SIM UNIT

0.205 ENTER

TEACH ZERO15.20 ENTER

% ZERO

01.00DISP

CAL

ENTER

ENTER

ENTER

% KFAC

9.985 ENTER

TEACH KFAC

10.00 ENTER

UNIT01.00 ENTER

% KFAC

0......9

*

2)

% ZERO < 20% ?&

% ZERO > -20% ?

% KFAC < 20% ?&

% KFAC > -20% ?

1)

1)

� BeDienung

�.� Test-modus

ZerO->DisPanzeigederAbweichungin%zwischendemimWerkkalibriertenNullpunktunddemletztenangepasstenNullpunkt.ZerO->calanpassungdesSensornullpunktesbeinullemDruckgegenüberdemimWerkkalibriertenNullpunkt.

TestdesVerhaltensdesTransmittersnachEingabeeinesbeliebigenDruck-wertesundDRUCKAUFDIEENTER-TASTE.

1)DerTransmitterfunktionniertmitdemvorigenfestgelegtenWert.2)DerTransmitterspeichertdenProzessdruck.

Dersensornullpunktmussobliga-torischvordemk-Faktorangepasstwerden!

kFac->DisPanzeigederAbweichungin%zwischendemimWerkkalibriertenK-FaktorunddemletztenangepasstenK-Faktor.kFac->calanpassungdesSensor-K-FaktorsbeieinemVergleichs-druckgegenüberdemimWerkkalibriertenK-Faktor.

AbwechselndeAnzeigederFunktionundderausgewähltenEinheit

nein

GebenSiedenVergleichsdruck,denSieimProzesshaben,ein(WertinnerhalbdesMessbereichs).

nein

ja

ja

Page 117: Pressure transmitter - dginstruments.com.au

8311 33

DEU

TSCH

DEU

TSCH

15.20ZERO

DISP

1

CAL

3

ENTER

ENTER

0......9

ENTER

ENTER

ENTER

0......9

TEST% ZERO

TESTSIM

KFACENTER

0......9

TEST

maTEST ENTER ENTER

OFFS ma

3.95 ENTER

SPAN ma

20.50

0......9

*0......9

*

RSET RSET

RSET

ENTER

0......9

ENTER

ENTER

TEST NO

CAL

RSET

ENTERTEST

ENDENTERTEST

0......9

ENTER

ENTER

SAVENO

SAVEYES

SIM UNIT

0......9

ENTER

*

1.500SIM UNIT

0.205 ENTER

TEACH ZERO15.20 ENTER

% ZERO

01.00DISP

CAL

ENTER

ENTER

ENTER

% KFAC

9.985 ENTER

TEACH KFAC

10.00 ENTER

UNIT01.00 ENTER

% KFAC

0......9

*

2)

% ZERO < 20% ?&

% ZERO > -20% ?

% KFAC < 20% ?&

% KFAC > -20% ?

1)

1)

einstellungdes4-20mA-AusgangsdesTransmitters:-wählenSieMenüpunktOFFSaus:DerTransmittererzeugteinen4-mA-Strom;MessenSiediesenStromamStromausgangmittelseinesUniversal-Messgeräts,gebenSiediesenWertunterOFFSein.-wählenSieMenüpunktSPANaus:DerTransmittererzeugteinen20-mA-Strom;MessenSiediesenStromamStromausgangmittelseinesUniversal-Messgeräts,gebenSiediesenWertunterSPANein.auswahlzuderGrundein-stellungdesKalibriermodusund/oderdesTestmoduszurückzugehen.(sieheSeiten31und34).

ZurückzurAnzeigedesDrucksimNormalmodusmitAbspeichern(SAVEYES)odernicht(SAVENO)dereingestelltenDaten.

normalmodus(siehes.21)

*DerKommawirddurchDrückenderTasten0......9

und verschoben.

Page 118: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311� BeDienung

�.8 grundeinstellungdesTestmodus

DieGrundeinstellungdesTestmodusWerkabistfolgende:OFFS: 4mASPAN: 20mA

�.� kunden-einstellungdesTransmitterseinheit modusout1 Schwellen

out1umgekehrt

out1Verz�out1 modusout2 Schwellen

out2umgekehrt

out2Verz�out2

unit hyst�1) Fen�2) olo ohi Yes no Del(s) hyst�1) Fen�2) olo ohi Yes no Del(s)

1)hysterese-modus: 2)Fenster-modus:ON

OFFOLO OHI

ON

OFFOLO OHI

Page 119: Pressure transmitter - dginstruments.com.au

8311 3�

DEU

TSCH

DEU

TSCH

Filter Stromausgang Bargraph Fehlerout1 Fehlerout2 Fehler4-20mA code

nr FASt/Slow 4mA 20mA Bglo Bghi cont on oFF cont on oFF cont on oFF

%-nullpunkt %-K-Faktor einstell�4-20mA Datum unterschrift

Zero KFAct oFFS SpAn

Page 120: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311� BeDienung

�.10 eingabebereichdereinstellbarenParametern

kalibriermodus Testmodus

GemessenerDruck: -999bis9999 Druckwert: -999bis9999AngezeigterStrom: 0.000bis9999 AngezeigterNullpunkt/K-Faktor: -999bis9999%OLO1und2(*): -999bis9999 AngepassterNullpunkt/K-Faktor: -999bis9999OHI1und2(*): -999bis9999 Referenzdruck: -999bis9999DEL1und2(*): 0sbis999s Angepasster4mA: 3,5bis4,5mAFilter: 0bis9 Angepasster20mA: 19bis21mA

4mA: -999bis999920mA: -999bis9999 BGLO: -999bis9999BGHI: -999bis9999CODE: 0000bis9999 (*)NurbeiAusführungenmitTransistor-Ausgängen

AußerhalbdieserBereichehältderTransmitterdenWertalsungültigundzeigtdensichamnähstenbefindendenGrenzwertan.

Page 121: Pressure transmitter - dginstruments.com.au

8311 3�

DEU

TSCH

DEU

TSCH

Page 122: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter83116 warTung

6.1 reinigungZurReinigungdesGerätesverwendetmanWasserodereinfürdieMate-rialienderFittingsgeeignetesLösungsmittel.FürweitereAuskünfte,stehtIhnenBürkertzurVerfügung.

6.2 Fehleranzeige

Anzeige Beschreibung Fehlerbehebung

1ERR DienacheinerStromversor-gungsunterbrechunggespei-chertenDatensindverlorengegangen.Lese-bzw.Schreibfehler:derProzessistunterbrochen.

NachDrückenderENTER-TastewirddasHauptmenüerreicht(Normalmodus).SolltedieseMeldungöfterserscheinen,schickenSiedasGerätanBürkertzurück.

2ERR DieDatendesKalibriermoduskönnennichtgespeichertbzw.gelesenwerden.Lese-bzw.Schreibfehler:derProzessistunterbrochen.

NachDrückenderENTER-TastewirddasHauptmenüerreicht(Normalmodus).DasGerätbefindetsichinderGrundeinstellung:DieParameterdesKalibrier-modusmüssenneuerfasstwerden.SolltedieseMeldungöfterserscheinen,schickenSiedasGerätanBürkertzurück.

3ERR DieDatendesTestmoduskönnennichtgespeichertbzw.gelesenwerden.Lese-bzw.Schreibfehler:derProzessistunterbrochen.

NachDrückenderENTER-TastewirddasHauptmenüerreicht(Normalmodus).DasGerätbefindetsichinderGrundeinstellung:DieParameterdesTestmo-dusmüssenneuerfasstwerden.SolltedieseMeldungöfterserscheinen,schickenSiedasGerätanBürkertzurück.

Page 123: Pressure transmitter - dginstruments.com.au

8311 3�

DEU

TSCH

DEU

TSCH

Anzeige Beschreibung Fehlerbehebung

10ERR DerAnschlussandieZel-leistunterbrochen.

- ZiehenSiedenVersorgungs-Steckerheraus.- ÖffnenSiedenDeckeldesGehäusesundüberprüfenSiedenKabelanschlusszwischenderZelleundderElektronik-Platine.

SolltedieseMeldungöfterserscheinen,schickenSiedasGerätanBürkertzurück.

Zellenanschluss

6.3 gibteseinProblem?- siehabendensperrcodevergessen(S.5.4):DrückenSiegleich-

zeitigTasten 0......9 während30SekundenbeiderCode-AnfrageaufdemAnzeiger,umZugriffzumgewünschtenModuszubekommen.

- Dieanzeigeblinkt:DerDruckistaußerhalbdesMessbereichs.- «----»wirdangezeigt:DeranzeigbareGrenzwertwurdeüberschrit-ten;WählenSieeinegeeigneteEinheitaus.

- DerTransistorwirdzurückgestelltsobaldeinTransistor-aus-gangumschaltet:DiemaximaleBürdenimpedanzliegtzuhoch(sieheS.11)

Page 124: Pressure transmitter - dginstruments.com.au

DEU

TSCH

DEU

TSCH

Druck-Transmitter8311� anschluss-BeisPiele

4

1

3

2

5

18 V=

8311

+ -

mA

+

-

anschlusseinerausführungmiteinemeinzigen4-20ma-ausgang(en1��301-803-ste-cker).

anschlusseinerausführungmitzweiPnP-ausgängenundeinem4-20ma-ausgang(m12-stecker)

erdensiedieabschirmunganbeidenendendeskabels.

1

23

8311

18 V=+ -

+ -mA

1

23

8311

18 V=+ -

mA+

-

Last1

Last2

Sicherung Sicherung

Sicherung

Page 125: Pressure transmitter - dginstruments.com.au

RK

ER

T

RK

ER

T

Bürkert WorldwideEuropeAustriAPhone: +43(0)1-8941333Fax: +43(0)1-8941300E-mail: [email protected]

BelgiumPhone: +32(0)3-3258900Fax: +32(0)3-3256161E-mail: [email protected]

CzeCh rep.Phone: +420543-252505Fax: +420543-252506E-mail: [email protected]

DenmArkPhone: +4544-507500Fax: +4544-507575E-mail: [email protected]

estoniAPhone: +3726440698Fax: +3726313759E-mail: [email protected]

FinlAnDPhone: +358(0)207412550Fax: +358(0)207412555E-mail: [email protected]

FrAnCePhone: +33(0)388-589111Fax: +33(0)388-572008E-mail: [email protected]

itAlyPhone: +3902-959071Fax: +3902-95907251E-mail: [email protected]

norwAyPhone: +4763-844410Fax: +4763-844455E-mail: [email protected]

netherlAnDsPhone: +31(0)346-581010Fax: +31(0)346-563717E-mail: [email protected]

portugAlPhone: +351212898275Fax: +351212898276E-mail: [email protected]

polAnDPhone: +48(0)22-8406010Fax: +48(0)22-8406011E-mail: [email protected]

spAinPhone: +3493-4777980Fax: +3493-4777981E-mail: [email protected]

sweDenMalmöPhone: +46(0)40-6645100Fax: +46(0)40-6645101E-mail: [email protected]

Stockholm Phone: +46(0)8-7240120 Fax: +46(0)8-6046105

switzerlAnDPhone: +41(0)41-7856666Fax: +41(0)41-7856633E-mail: [email protected]

turkeyPhone: +90(0)232-4595395Fax: +90(0)232-4597694E-mail: [email protected]

uniteD kingDomPhone: +44(0)1453-731353Fax: +44(0)1453-731343E-mail: [email protected]

Page 126: Pressure transmitter - dginstruments.com.au

RK

ER

T

RK

ER

T

Bürkert WorldwideAsia Pacific

AustrAliAPhone: +611300888868Fax: +611300888076E-mail: [email protected]

Victoria Phone: +61385459700 Fax: +61395626599

Queensland Phone: +61733269640 Fax: +61733269621

WesternAustralia Phone: +61894443980 Fax: +61894449353

ChinAPhone: +8621-58682119Fax: +8621-58682120E-mail: [email protected]

Beijing Phone: +861064399783 Fax: +861064399612

Chengdu Phone: +862884439064 Fax: +862884451341

Guangzhou Phone: +862087698379,87678703 Fax: +862087671131

Shanghai Phone: +862164865110 Fax: +862164874815

Suzhou Phone: +8651262659881 Fax: +8651262659882

hong kongPhone: +85224801202Fax: +85224181945E-mail: [email protected]

inDiAPhone: +91(0)44-42303456Fax: +91(0)44-42303232E-mail: [email protected]

JApAnPhone: +81(0)3-5827-0066Fax: +81(0)3-5827-0067E-mail: [email protected] Osaka Phone: +81(0)6-6320-0880 Fax: +81(0)6-6320-0881

koreAPhone: +82(0)2-34625592Fax: +82(0)2-34625594E-mail: [email protected]

mAlAysiAPhone: +60(0)4-6435008Fax: +60(0)4-6437010E-mail: [email protected]

new zeAlAnDPhone: +64(0)9-2567777Fax: +64(0)9-2567748E-mail: [email protected]

philippinesPhone: +63(0)2-7764384Fax: +63(0)2-7764382E-mail: [email protected]

singAporePhone: +6568442233Fax: +6568443532E-mail: [email protected]

tAiwAnPhone: +886(0)2-26537868Fax: +886(0)2-26537968E-mail: [email protected]

Page 127: Pressure transmitter - dginstruments.com.au

RK

ER

T

RK

ER

T

Bürkert Worldwide

Africa

south AFriCAPhone: +27(0)11-5746000Fax: +27(0)11-4541477E-mail: [email protected]

North and South America

BrAzilPhone: +55(0)11-51820011Fax: +55(0)11-51828899E-mail: [email protected]

CAnADAPhone: +1905-6323033Fax: +1905-6323833E-mail: [email protected]

usAPhone: +1949-2233100Fax: +1949-2233198E-mail: [email protected]

Germany

HEADQUARTER AND SERVICE CENTERIngelfingenBürkertGmbH&Co.KGChristian-Bürkert-Straße13-17DE-74653IngelfingenTelefon: +49(0)7940-10-111Fax: +49(0)7940-10-448E-mail: [email protected]

Page 128: Pressure transmitter - dginstruments.com.au

RK

ER

T

RK

ER

T

Bürkert Worldwide