Differential Pressure Switch DPI
Types available
Type code Type Description
Product overviewElectronic differential pressure switch for monitoring the differential pressure of air and other non-flammable and non-aggressive gases.Monitoring of air filters, fans, industrial cooling air cycles as well as over heating protection, control of air and fire dampers, anti-freeze with heat exchangers.
Technical data
EXT-TN-1071658 DPI2500 0...10V and relay, pressure range 0...2500Pa
EXT-TN-1072426 MKS100 Metal duct connector, L=100mm (2 pieces necessary per device)
Security advice !
Electrical connection
Standards CE conformity
Power supplyCurrent consumptionOutputMaterialTubingPressure connectionElectrical connectionCable entryDimensions LxWxHBursting pressureAccuracy % full scaleLong term stabilityMediaAmbient temperatureStorage temperatureProtectionWeightRelay output
DC 24V / AC 24V ±10%Max. 80mA@DC 24V0...10V, load min. 1kΩHousing and cover : ABS / PCPVC, softMale, D=5mm / 6.3mmScrewing terminals, max. 1.5mm²M16 and M2089 x 86.5 x 37.1mm30kPa±1.5% Typical <= ±1Pa / yearAir and non-aggressive gases-5...+50°C, max. 95% RH, non-condensing-20...70°CIP54 according to EN60529150g1x relay output (max. DC 30V / AC 250V / 6A )
General Data
- 89/336/EEC EMC directive- 2002/95/EEC RoHS directive
The installation and assembly of electrical equipment may only be performed by a skilled electrician.The modules must not be used with equipment that supports, directly or indirectly, human health or life or with applications that can result in danger for people or animals.
The devices are constructed for the operation of protective low voltage (SELV). For the electrical connection, the technical data of the corresponding device is valid.Sensing devices with transducer should in principle be operated in the middle of the measuring range to avoid deviations at the measuring end points. The ambient temperature of the transducer electronics should be kept constant.When switching the supply voltage on/off, power surges must be avoided on site.
- For connecting the device, the process lines must be unpressurised.- Note the suitability of the device for the medium to be measured.- Note the maximum pressure.
Mounting advice
2V1.
1 02
.201
2 · S
ubje
ct to
mod
ifica
tion
Differential Pressure Switch DPI
Installation
A pre-requisite for the operation is a proper installation of all electrical supply, control and sensing leads as well as the pressurised connec-tion line. Before installing the device, the leak tightness of the pressurised connection lines must be inspected.
MENU
BACK
OK
Settings
By pressing the button for 3 seconds, you can enter theselected menu.
By pressing the button you can return without makingchanges.
By pressing the button you can open new options or confirmchanges and return to previous display.
By pressing the buttons you can scroll the menus.
Pa, kPa, mmH2O, inchWC, mmbar
See types available
0,5...10s
Zero point calibration
High point adjustment
Reset span adjustment
Setpoint (between min...max pressure)
0...5% of the range
3V1.
1 02
.201
2 · S
ubje
ct to
mod
ifica
tion
Differential Pressure Switch DPI
Zero point calibration
Span adjustment
Terminal connection plan
Dimensions (mm)
Note! Supply voltage must be connected one hour before the zero point calibration is carried out.1) Disconnect both tubes from the pressure inlets + and –.2) Push both arrow buttons or select “Zero” from the menu. Green LED turns off and “Zero” text followed by a counter from 3 to 0 seconds is displayed.3) Wait until the green LED turns on again and then connect the tubes back to the pressure inlets.It is recommended to adjust the zero point every 12 months during normal operation.
Note! Supply voltage should be connected one hour before the span point adjustment is carried out.Span point must not be adjusted without input pressure.If the span point is adjusted with 0Pa or close to 0Pa input pressure the device may lose its accuracy and will not give out correct readings. In this case go to menu and select “Span” and then “Reset”. This resets the span adjustment.
To adjust the span you need an accurate reference meter. Follow these steps to correctly adjust the span:1) Set the zero point.2) Connect the input pressure.3) From the menu select “Span”, and then “Adjust”.4) Adjust the display or 0...10V value to match the reference meter’s value using the arrow buttons and confirm by pressing OK.
V
Vout10V
How span adjustment affects the measurement
NC
COM
NO
Relay 1
24V AC/DCPower supply
Output 0...10V
24V
GND
Pout
V+
+-
The supply cable and control cable for relay must be separate, if non SELV voltage is used in relay contacts. Both of the cables have their own cable entry.
86,5
37,1
64,5
74,5
52,589
Copyright HK Instruments Installation Version 1.0 2012
SCHEMATICS
MOUNTING THE DEVICE
INSTALLATION
STEP 1
1) Select mounting location (duct, wall, panel)2) Use the device as a template and mark the screw holes3) Mount with appropriate screws (not included)
YES NO NO
Figure 1b - Mounting Orientation
1) Mount the device in desired location (see step 1)2) Open the lid and route cable(s) through strain relief(s) and connect the wires to terminal block(s) (see step 2)3) The device is now ready for con�guration
WARNING! Apply power after the device is properly wired.
Figure 1a - Surface Mounting
DIMENSIONAL DRAWINGS
Figure 1c - Application Connections
Static Pressure Filter/DamperMonitoring
Fan/BlowerMonitoring
NotConnected
24V GND 0-10V
Terminal Block Terminal Block for relays
NC COM NO NC COM NO
?
(86.5)
?
(74.5)
?
(64.
5)
?
(52.
5)
?
(37.1)
?
(89.
0)
Copyright HK Instruments Installation Version 1.0 2012
CONFIGURATION
1) Select the desired measurement unit2) Select the desired measurement range 3) Select the desired response time 4) Con�gure the relay(s)5) Zero the device6) Calibrate the span point7) Connect pressure tubes. Connect positive pressure to port labeled "+" and negative pressure to port "-". The device is now ready to use.
STEP 3
CONFIGURATIONFIGURE 3
For CE compliance, a properly grounded shielding cable is required
1) Unscrew strain relief and route cable(s). Use separate strain relief for 0-10V output cable and relay cable(s).2) Connect the wires as shown in �gure 2a and 2b.3) Tighten the strain relief.
WIRING DIAGRAMS STEP 2 CONTINUED
24V
GND
Pout
Power Supply24VDC / 24VAC
Figure 2a - Wiring Diagram 0-10V Output
+
Outout 0...10V
V
+
Figure 2b - Wiring Diagram Relay(s)
NC
COM
NO
Relay 1
NC
COM
NO
Relay 2
with the MENU button you can enter the menu by pressing the button for 3 seconds,when in menu you can exit anywhere without making changes
with the BACK button you can return without making changes
with the OK button you can open new options or con�rm changes and return to previous display
with the button you can scroll the menus
SPAn
ZEro
rEL 1/2
rESP
PSEL
Unit Pa, kPa, mmH2O, inchWC, mbar
Pressure range selection
Response time
Relay menu(s)
Zero point calibration
Response time
High point calibration menu
rES
Adu High point calibration
Reset high point calibration
HYS
SP
dir Relay activation menu
Relay setpoint
Relay hysteresis 0-5% of range
FALL
rISE Relay activation on increasing pressure
Relay activation on decreasing pressure
Copyright HK Instruments Installation Version 1.0 2012
ZERO THE DEVICE STEP 6
To zero the device two options are available:1) Manual Pushbutton Auto Zero2) function
Does my transducer have an function? See the product label. If it shows –AZ in the model number, then you have the function.
1) Manual Pushbutton Auto ZeroNOTE: Supply voltage must be connected at least one hour prior to zero point adjustment. a) Disconnect both pressure tubes from the pressure ports labeled + and –. b) Push both arrow buttons on top of the lid or go to con�guration menu and select “Zero”. c) The zeroing of the device will proceed automatically when the green led on top of the lid turns off and “Zero” text followed by a counter from 3 to 0 seconds appears on the display. Zeroing is complete when the green led turns on again. d) Reinstall the pressure tubes, ensuring the High pressure tube is connected to the port labeled +, and the Low pressure tube is connected to the port labeled −.
NOTE: The zero point should be calibrated via manual auto zero, one hour after installation and at least every 12 months during normal operations.
2) functionIf the device includes the optional e-zero circuit, no action is required.
(-AZ) is a True Auto Zero function in the form of an automatic zeroing circuit built into the PCB board. The function electronically adjusts the transducer zero at predetermined time intervals (every 10 minutes). The function eliminates all output signal drift due to thermal, electronic or mechanical effects, as well as the need for technicians to remove high and low pressure tubes when performing initial or periodic transducer zero point calibration. The adjustment takes 4 seconds after which the device returns to its normal measuring mode. During the 4 second adjust-ment period, the output and display values will freeze to the latest measured value.
Transducers equiped with the function are virtually mainte-nance free.
FIGURE 3WARRANTY POLICY
(a) WARRANTY COVERAGE: HK warrants to the original end user of the Products that the Products will, at the date of initial purchase, meet the applicable speci�cation for such Products (as described by HK in its product literature) and, under normal use and service, will be free from any defects in materials or manufac-ture for (a) one (1) year from date of sale to end user for electrome-chanical Products and (b) �ve (5) years from date of manufacture for electronic Products.
(b) NO WARRANTY OF PRODUCT SUITABILITY: Neither HK nor the manufacturer of the Products to be sold hereunder (“Manufacturer”) makes any warranty that Products are suitable for a particular purpose, application or design. Many states and localities have differing codes or regulations governing the installa-tion and/or use of HK products. HK does not guarantee compli-ance with such codes or regulations; the end user is solely responsible for safe and correct installation and use of the Prod-ucts and for compliance with such codes and regulations.
(c) EXCLUSION OF IMPLIED WARRANTIES: THE WARRANTY HEREIN IS THE ONLY WARRANTY APPLICABLE TO THE PROD-UCTS AND EXCLUDES ALL OTHER WARRANTIES, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND ANY IMPLIED WARRANTY ARIS-ING FROM COURSE OF DEALING OR USAGE OF TRADE.
(d) REMEDIES FOR NON-CONFORMITY OR BREACH OF WAR-RANTY: If the Product purchased does not conform to the appli-cable warranty, HK will provide, at its option, one of the following remedies: (1) repair of the non-conforming Product, (2) replace-ment with a conforming Product, or (3) refund of the original purchase price. THESE REMEDIES SHALL BE THE EXCLUSIVE AND SOLE REMEDY for any breach of warranty. HK and Manufac-turer have no other responsibility or liability for breach of warranty or otherwise.
(e) LIMITATION OF LIABILITY: NEITHER HK NOR MANUFAC-TURER WILL BE LIABLE FOR ANY INCIDENTAL, SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES UNDER ANY CIRCUMSTANCE, INCLUDING WITHOUT LIMITATION ANY DEFECT IN THE PRODUCT PURCHASED.
(f) FURTHER LIMITATIONS: The warranty herein does not cover damage caused by lightning, �ood or other natural phenomenon; normal wear and tear; accident, improper or careless handling, abnormal use, overloading, improper storage or abuse; incorrect installation, care or reconstruction; or alteration, calibration, recon�guration, maintenance or installation work done by unquali-�ed personnel. Should Manufacturer alter the structure of any Product in the future, HK and Manufacturer shall not be obligated to make comparable changes to Products already purchased. HK will give a new warranty for Products being replaced or repaired within the warranty period, however only to the expiration of the original Product’s warranty period. The warranty includes the repair of a defective part or device, or if needed, a new part or device, but no other costs except as otherwise stated in the HK Distributor Terms and Conditions.
1V1.
1 02
.201
2 · S
ubje
ct to
mod
ifica
tion
Differential Pressure Switch PS
Types available
Type code Type Description
Standards CE conformity
Product overviewDifferential pressure switch for monitoring the differential pressure of air and other non-flammable and non-aggressive gases.Possible applications: monitoring of air filters, fans, industrial cooling air cycles as well as overheating protection, control of air and fire dampers, anti-freeze with heat exchangers.
Technical Data
HousingHousing coverMembraneDuct connectorsTubingProtectionDimensions (LxWxH)Maximum pressureMediaOperation temperatureStorage temperatureSub miniature switches
Service lifeConnectionsCable entryWeight
ABSPCSiliconeABSPVC, softIP54105 x 73 x 63mm50kPaAir and non-aggressive gases20...60°C40...85°CGold contacts : PS200Silver contacts : PS300 / PS500 / PS1500 / PS4500>1,000,000 switching operationsScrew terminalsM16150g (without accessories)
Measuring rangeSwitching differenceSwitching load
30...300Pa20Pa3A resistive / 2A inductive load (max. AC 250V)
General data
PS300
Measuring rangeSwitching differenceSwitching load
30...500Pa20Pa3A resistive / 2A inductive load (max. AC 250V)
PS500
Measuring rangeSwitching differenceSwitching load
100...1500Pa80Pa3A resistive / 2A inductive load (max. AC 250V)
PS1500
Measuring rangeSwitching differenceSwitching load
500...4500Pa180Pa5A resistive / 2A inductive load (max. AC 250V)
PS4500
- 2006/95/EC Low voltage- 2004/108/EC EMC
EXT-TN-1500288 PS200 Measuring range 20...200Pa
EXT-TN-1066753 PS300 Measuring range 30...300Pa
EXT-TN-1066760 PS500 Measuring range 30...500Pa
EXT-TN-1071610 PS1500 Measuring range 100...1500Pa
EXT-TN-1071627 PS4500 Measuring range 500...4500Pa
EXT-TN-1072426 MKS100 Metal duct connector, L=100mm (2 pieces necessary per device)
Security advice !
The installation and assembly of electrical equipment may only be performed by a skilled person.The modules must not be used with equipment that supports, directly or indirectly, human health or life or with applications that can result in danger for people or animals.
Measuring rangeSwitching differenceSwitching load
20...200Pa10Pa0.1A resistive load (max. AC 250V)
PS200
2V1.
1 02
.201
2 · S
ubje
ct to
mod
ifica
tion
Differential Pressure Switch PS
Mounting advice
Installation
Terminal connection plan
Dimensions (mm)
The pressure switch is factory calibrated in the vertical position. If installed horizontally, this will affect the switching point as follows:- with cover facing upwards, +15Pa- with cover facing downwards, -15Pa
A prerequisite for the operation is a proper installation of all electrical supply, control and sensing leads as well as the pressurised connection line. Before installing the device, the leak tightness of the pressurised connection lines must be inspected.
When differential pressure increases:- 1-3 open- 1-2 close
2 3 1NO NC COM
P