presentation relais siemens
TRANSCRIPT
© Siemens AG 2006
Power Transmission and Distribution
Siemens Belgium-Luxemburg
Page 2 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
High Voltage Transformers Medium VoltageComponents, switchgear and turnkeyprojects for power transmission ≤ 52kV (AC and DC)
Components, switchgear and turnkeyprojects for power transmission > 52kV (AC and DC)
Power transformers up to 1,300 MVA and 765kV, distribution transformerswith oil or cast-resin insulation
Energy AutomationIntegrated control systems, protection and substation automation, telecontrol systems, power quality.
ServicesNetwork planning & consulting, assetmaintenance and maintenance management forgrids & networks, metering services
Siemens Power Transmission and DistributionWhat we have to offer
Page 3 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Air Insulated Switchgear (AIS)
Circuit-breakersArrestors, Bushings, Coils and Instrument TransformersDisconnectors
Gas Insulated Switchgear (GIS)
Highly Integrated Switchgear (HIS)
Gas Insulated Lines(GIL)
Reactive Power Compensation
High Voltage Direct Current (HVDC) Installations
PTD DivisionHigh Voltage overview
Page 4 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
63
50
40
31,5
25
0
Rated short-circuit breaking current [kA]
72,5 123 145 300 362 420 550 800Rated voltage [kV]
170 245
80
3AT2/3 3AT4/5
3AP1 FI3AP1 FG 3AP2 FI
Products and Solutions for High VoltageAIS – Circuit Breakers
Page 5 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Type 3AP1 FG up to 245 kVFor all applications: reliable and economicalStored energySpring Drive MechanismSelf compression arc quenching principleRated voltages up to 245 kVRated short circuit breaking current up to 50 kAType tested to the new IEC 62271-100Available for one or three pole operation (FG/FI)Delivered more than 50,000 breakers to more than 120 countries
Type 3AP1 FI up to 300 kVStored energy Spring Drive MechanismSelf compression arc quenching principleRated voltages up to 300 kVRated short circuit breaking current up to 50 kAType tested to the new IEC 62271-100
High-Voltage Circuit-Breaker Product Characteristics
Page 6 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Type 3AP1 DTC 72.5 up to 245 kVOne interrupter unit per poleStored energySpring Drive MechanismRated voltages up to 245 kVRated short circuit breaking currentup to 63 kAType tested to the new IEC 62271-100Equipped with bushing type current transformersAmbient temperature range from +50° C down to -55° C with pure SF6
Type 3AP2 FI up to 420 kVStored energySpring Drive MechanismSelf compression arc quenching principleRated voltages up to 420 kVRated short circuit breaking current up to 50 kAType tested to the new IEC 62271-100Easy installation and commissioning: only few subassembliesTransportation costs are minimized
High-Voltage Circuit-Breaker Product Characteristics
Page 7 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Instrument TransformersCurrent TransformersVoltage Transformers
BushingsAir Core Dry Type ReactorsLine TrapsArc Suppression Coils
CoilsAir Core Dry Type ReactorsLine TrapsArc Suppression Coils
ArresterHV: AIS (Porcellain, Polymer) & GIS; HVDC, FACTSMV: Distribution & Traction Vehicles
Products and Solutions for High VoltageArrestors, Bushings, Coils & Instrument Transformers
Page 8 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Centre Break
Ur 72,5 kV – 550 kVIr 1250 A – 4000 AIk 31,5 kA– 63 kA
Pantograph
Ur 123 kV – 420 kVIr 3150 AIk 50 kA
Vertical Break
Ur 123 kV – 550 kVIr 1250 A – 6300 AIk 31,5 kA– 63 kA
Earthing Switch
Built-onFree-standingNeutral point
Double Break
Ur 36 kV – 800 kVIr 1250 A – 5000 AIk 31,5 kA– 63 kA
Knee Type
Ur 123 kV – 550 kVIr 1250 A – 400 AIk 31,5 kA– 63 kA
Products and Solutions for High Voltage Disconnectors & Earthing Switches from 36 kV to 800 kV
Page 9 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Voltage(kV)
80
72.5
63
50
40
25
0123 145 300 362 420 550 800
8DR1
8DQ1
8DN9
170 245
HIS 8DN8
HIS 8DQ1
8DN8
Rated short-circuit breaking current (kA)
8DQ1
31,5
Products and Solutions for High voltageGas Insulated Switchgear (GIS)
Page 10 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Rated voltage up to 145 kVRated frequency 50 / 60 HzRated power frequency withstand voltage (1 min) up to 275 kVRated lightning impulse withstand voltage (1,2/50 µs ) up to 650 kV
Rated busbar current up to 3150 ARated feeder current up to 3150 ARated breaking current up to 40 kARated short-time current up to 40 kALeakage rate per year and gas compartment < 0.5 %
Bay width 800 mmBay height 2850 mmBay depth 3500 mmBay weight 3 t
Gas Insulated Switchgear (GIS)8DN8.2 switchgear
Page 11 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Gas Insulated Switchgear (GIS) 8DN9 switchgear
Rated voltage up to 245 kVRated frequency 50 / 60 HzRated power frequencywithstand voltage (1 min) up to 460 kVRated lightning impulsewithstand voltage (1,2/50 µs) up to 1050 kVRated busbar current up to 3150 ARated feeder current up to 3150 ARated breaking current up to 50 kARated short-time current up to 50 kALeakage rate per year andgas compartment < 0.5 %Bay width 1500 mmBay height 3500 mmBay depth 4700 mmBay weight 5 t
Page 12 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Savings HIS*Savings HIS*
Site price 60 %
Civil works 20 %
Secondary cables 35 %
Steel structures 30 %
Earthing 70 %
Erection, tests, commissioning 70 %
Compact
Low cost
Modular
Suitable for in- and outdoor use
* compared to air insulated switchgear
Products and Solutions for High voltage Highly Integrated Switchgear (HIS)
Page 13 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Domaine d’utilisation des installationsmoyenne tension
G
x x
x xxx xx x
x
Niveau de production et Réseau de Transport
Niveau de distribution primaire
Niveau de distribution secondaire
Basse tension
Page 14 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Secondary distributionswitchgear
Gas-insulated (SF6 )8DH108DJ10/8DJ20
Air-insulatedSIMOSEC
Medium Voltage: Overview
Primary distributionswitchgear
Gas-insulated (SF6 )NX PLUS CNX PLUS8DA/8DB
Air-insulatedNX AIR NX AIR MNX AIR PSIMOPRIME
MV DC-Multifunctional Link
SIPLINK
Components
Vacuum tubesVacuum circuit-breakersVacuum contactorsOther Components
Page 15 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
8DAType-tested, single-phase encapsulation, metal-cladProved design, Single BusbarModular design with standard enclosures allows single- and double phase applicationsMore than 15 years of operating experience
Medium Voltage Products for Primary DistributionSF6-Insulated Switchgear
8DBType-tested, single-phase encapsulation, metal-cladProved design, Double BusbarModular design with standard enclosuresBusbars and busbar-disconnectors in separate gas compartmentsMore than 15 years of operating experience
up to 4000 Aup to 40 kAup to 40.5 kVDelivery Program
up to 4000 Aup to 40 kAup to 40.5 kVDelivery Program
Page 16 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
NX AIR MType-tested, IEC 62271-200, metal-clad, loss of service continuity category: LSC 2B, partition class: PM, internal arc classification: IAC A FLR ≤25 kA, 1sSingle- and Double Busbar(back/back, front/front)Vacuum circuit-breaker withdrawableMax. renewed availability by modular designSelective shutdown by bushing type transformers and pressure resistant compartmentsMax. operating safety by selfexplanatory logical operating elementsMaintenance intervals > 10 years
NX AIRType-tested, IEC 62271-200, metal-clad, loss of service continuity category: LSC 2B, partition class: PM, internal arc classification: IAC A FLR ≤40 kA, 1sSingle- and double busbar(back/back, front/front)Vacuum circuit-breaker withdrawableVacuum contactor withdrawableMax. renewed availability by modular designSelective shutdown by bushing type transformers and pressure resistant compartmentsMax. operating safety by self-explanatory logical operating elementsMaintenance intervals > 10 years
up to 2500 Aup to 40 kAup to 12 kVDelivery Program
up to 2500 Aup to 25 kA17.5 / 24 kVDelivery Program
Medium Voltage Products for Primary DistributionAir-Insulated Switchgear (AIS)
Page 17 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
8DJ20Type-testedIndependent of climateMaintenance-freeBlock-type construction, for 1-5 baysHermetically-sealed welded switch-gear enclosuresCompact and clear designNo sealingsHighest Quality LevelShortest Delivery Periods
8DJ10Type-testedIndependent of climateMaintenance-freeBlock-type construction, for 3-6 baysHermetically-sealed welded switch-gear enclosuresCompact and clear designNo sealingsHighest Quality LevelShortest Delivery PeriodsSmallest floor space for substations
up to 630 Aup to 25 kAup to 24 kVDelivery Program
up to 630 Aup to 25 kAup to 24 kVDelivery Program
Medium Voltage Products for Secondary DistributionSF6-Insulated Switchgear
Page 18 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Independent power producers(wind generators, solar plants)
City
Large-scale power plant
Consumers withsensitive processes
Hospital
Manufacturing, trade,small industry withoutin-plant generation
Large-scale industrywith in-plant generation
New Switching Technologies for Distribution SystemsImproves Cost-Effectiveness, Availability and Power Quality
MV DC-Multifunctional Link - SIPLINK
Page 19 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
High reliability
Excellent field experience with more than 2 million vacuum interrupters
Tailormade development
Wide product range for any application
For use in
LV and MV circuit-breakers, load-break switches and contactors
Autoreclosers
Transformer Tap Changers
up to 6300 Aup to 72 kA7.2 up to 40.5 kVup to 2500 Aup to 65 kA690 up to 1300 V
Delivery Program
Medium Voltage ComponentsVacuum Tubes
Page 20 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
PTD Division Transformers
Do lor situs cum habilitarum itumalus causticusimanenter Status landum exus riuslaudanum tum.
Lorem exit vulnareusplexus est. Vulnapausta rhus tex, per itum falor sit wunt. Sit itum causticusaurum eum et explindus.Cum
Power transformers
Distribution transformers withoil or cast-resininsulation
Page 21 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Generatortransformer
Systeminterconnectingtransformer
Shuntreactor
Oil-immerseddistribution transformer
GEAFOLcast-resin transformer
Tractiontransformer
HVDC
Systemtransformer
Special purpose transformers for industrial application
Voltageregulator
Phase angle regulator
TLMSiemens Transformer Life Management(condition assessment,life-extension,on-site-services,monitoring, ...)
Siemens Transformers at all Levels of Transmission and Distribution
Page 22 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Ratings from 10 MVA up to 1.100 MVA / 1200 kV
Three-phase and single-phase
Power Transformers
Page 23 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Cast-resin distributiontransformers
Ratings from 50 kVA up to40MVA
Possibility for on-linetapchanger
Static converter transformers
Distribution TransformersGEAFOL
Page 24 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Distribution TransformersOil-immersed
Ratings from 50 up to 4.000 kVA
(TUNORMA and TUMETIC)
Page 25 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
PTD Division Energy Automation
Do lor situs cum habilitarum itumalus causticusimanenter Status landum exus riuslaudanum tum.
Lorem exit vulnareusplexus est. Vulnapausta rhus tex, per itum falor sit wunt. Sit itum causticusaurum eum et explindus.Cum
Information and network controltechnology
Protection and substation auto-mation, telecon-trolsystems, power quality
Page 26 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
System control centersSpectrum PowerCCSINAUT Spectrum
Station control & automationSICAM PASSAT 1703 / SAT 230
Protection/PowerQuality/Bay Control
SIPROTECREYROLLEBC 1703 ACPSIMEAS
Communications& networking
PLCModems …
RTU’sSAT 1703SICAM eRTU / miniRTUTG 805 / TG 5700Tools
SICAM TOOLBOXIMM DIGSI…
Energy Market Mgmt.EMMFDWHPROPHET SolutionsAMIS…
Energy Automation Strong products and brands on all levels
Page 27 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
LE BUT DE LA PROTECTION SELECTIVE EST:-Assurer la continuité de service du réseau d’energie , par
élimination de l’élément défaillant et de lui seul-Eviter des dégâts au niveau des équipements affectés par
les défauts(câbles,transformateurs…)
SIPROTEC 4
Page 28 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
LE SYSTEME DE PROTECTION =
TI/TP + Relais+ Disjoncteur
Sélectif,rapide,fiable
SIPROTEC 4
Page 29 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
SIPROTEC 4 is a
family of numericalProtection, Control- and
Automation Devices from
SIEMENS
SIPROTEC 4 - What does it mean?
Page 30 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
O/C protection 7SJ6Distance protection 7SA6Line differential protection 7SD5 / 7SD6Transformer diff. protection 7UT6Generator protection 7UM6Station protection 7SS52
SIPROTEC 4
Page 31 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
O/C protection7SJ6
SIPROTEC 4
Page 32 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Time-overcurrent protection Functions
Time-overcurrent protection
Criteria for fault: overcurrent
Criteria for selectivity: time
Page 33 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Time-overcurrent protection Characteristics
t [sec]
0.5
1.0
1.5
2.0
x IN0.5 1.0 1.5 2.0 2.5I> I>>
Tripping area
Tripping characteristic of a two stage time-overcurrentprotection device - definite time
Page 34 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Time-overcurrent protection Characteristics
x IN0.5 1.0 1.5 2.0 2.5
t [sec]
0.5
1.0
1.5
2.0
Tripping characteristic of a time-overcurrent protection device -inverse time
Characteristics:IECANSIuser defined
Page 35 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Time-overcurrent protection Application
Used as:
Line protectionSelectivity by time-grading
1
x
O/C
x
O/C
1
x
M
O/C
2x
O/C
3
As main protection
2 Motor protectionwith short circuit- and overload protection,start protection,start inhibit
3 Transformer protectionfor network transformerswith short circuit- and overload protection,Inrush-stabilisation
Page 36 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Time-overcurrent protection Application
Main protection as line protection
x x x x
O/C O/C O/C O/C
t = 0mst = 300mst = 600mst = 900ms
Advantage: simple device,only current transformers are necessary
Disadvantage: near infeed higher tripping time
Ttrip
distance
backup
Page 37 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Reverse Interlocking Application
1Outgoing protection initiates and blocksthe infeed protection stage within 50 ms
2Infeed protection gives a trip after50 ms since no outgoing feeder has picked up and blocked the infeed protection
M
O/CO/C
O/C
O/C
T = 50ms t = xxms
start start. start. + ++
Blocking
1
Energy direction 2
Page 38 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
4 CT inputs
7SJ61
O/C protection with motor protectionO/C protection with motor protection
Over current protection(Phase/Earth)Inrush BlockingMotor ProtectionOverload ProtectionUnbalanced Load ProtectionAuto reclosureTrip Circuit SupervisionBreaker Failure ProtectionLock out
SIPROTEC 4
Page 39 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Distance protectionDistance protection
SIPROTEC 4
Page 40 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Why impedance protection?
Situation: Meshed network and two infeedsDirectional overcurrent time relays
0,6s
0,6s
0,3s
0,3s
0,6s
0,6s
0,3s
0,3s
non-selective trip
Page 41 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Localization of short-circuits by means of an impedance measurement:
fault on the protected line
fault outside the protected line
Z1
relay A
selectivity
relay A
Z2
Basic principle of impedance protection
Page 42 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Distance measurement (principle)
6 loops: 3 phase- phase loops and3 phase- ground loops
phase- phase -loop:
The same applies to the remaining loops
UL1-L2 = ZL ( IL1 - IL2)
Measured currentmeasured voltage
06.08.97dtgerdis3
ZL = RL + j XL
ZE = RE +j XE
IL1
IL2
IL3
IE
ZL
ZEUL1UL2UL3
Page 43 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
phase-ground-loop: UL1 = ΙL1 · ( RL + j XL )- ΙE · ( RE +j XE)
ΙL1, ΙE measured currentUL1 measured voltage
06.08.97dtgerdis3
The same applies to the remaining loops
Distance measurement (principle)
IL1
IL2
IL3
IE
ZL
ZE
UL1UL2UL3
ZL = RL + j XL
ZE = RE +j XE
Page 44 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Numerical filtered phasor measurement
1. Fast operation ⇒ Use short data window
2. High accuracy ⇒ High selectivity
3. Signal distortion does not cause delay or maloperation
X
R
Page 45 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
ni2sin ⋅π
ni2cos ⋅π
C(k)S(k)(k) j III ⋅+=S(k)I
C(k)Ij ⋅ )(kI
)( inki +−
k-n
0 1 2 . . . n
ϕ
i
C(k)I
S(k)I
k
Fourier analysis of measured values
Sampledmeasuringvalues
Resulting phasor
Page 46 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Load and short-circuit impedances
ZL
ZLF1
ZLF2
RF RF
ZLoadDF1 F2
X
R
ZL
ZLF2
j SC1
j SC2
j L
RR
ZF1
ZF2
RR
ZLoad
ZLF1
Fault area
distance relayoperating characteristic
Increasing load
Fault in reverse
direction Load area
Minimum Load Impedance:Minimum voltage 0,9 UnMaximum current 1,1 InMaximum angle ± 30°
Phase - Phase Fault
RR ≈ RF / 2
Phase - Earth Fault
RR ≈ RF /(1 + RE/RL)
Page 47 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Graded distance zones
time
D1 D2 D3
t1
t2
t3
Z1
Z2
Z3
distance
∆t = grading time
A CB D
Z1 = 0,85 ZAB
Z2 = 0,85 (ZAB + 0,85 ZBC)Z3 = 0,85 (ZAB + 0,85 (ZBC + 0,85 ZCD))
Safety margin is 15 %:
line errorCT, VT errormeasuring error
Grading rules:
Page 48 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
ϕSC
Current area forforward faults
ΙSCCurrent area for reverse faults
ΙSC
USC
R
ZSC
Z'SC
Impedance area for forward faults
Impedance area forreverse faults
X
ϕSC
Determination of fault direction
current / voltage diagram impedance diagram
Fault location Where is the fault ?
The impedance also shows the direction, but ....
Page 49 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Fault detection techniques
Over-current fault detectionVoltage dependant over-current fault detection
Voltage and angle dependantover-currentfault detection
I
U
I >>I > I ϕ >
R
X
Impedancefaultdetection
Not in 7SA522
Page 50 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
X
R
forwards
forwards
reverse
reverse
ϕ LoadLoad
Z1
Z2
Z4
Z3
Z1B
Z5
Line
α
Impedance zones of digital relays
Distance zonesInclined with line angle ϕAngle α prevents overreach of
Z1 on faults with fault resistance that are fed from both line ends
Fault detectionno fault detection polygon: the
largest zone determines the fault detection characteristic
simple setting of load encroachment area with Rmin and ϕLoad
Page 51 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Zone grading chart, radial feeder
D
A
D
B
D
C
Ι>>
D
Ι>t∆Ι
ZT
Z1
Z2
Z3
Z1 = 0.85 ZA-B
Z3 = 0.85 [ ZA-B + 0.85 (ZB-C+ 0.85 ZC-D) ]Z2 = 0.85 (ZA-B + 0.85 ZB-C)
Grading accordingthe recommendationwith the safety margin of 15%.
Page 52 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Ring feeder: with grading against opposite end
0.6
0.3
grading time(s)
The same grading from both sides
Page 53 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Line differential protection
7SD61 / 7SD52
SIPROTEC 4
Page 54 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Kirchhoff: I1+I2+I3+I4+I5=0
I1
I2
I3
I4
I5
Measuring Principle
Page 55 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Trip Characteristic
1:1(3Y)
1:1(3Y)
IX IY
IX IY
0 6 12 0 6 12
1 p.u. 1 p.u.
Internal Fault
Page 56 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Trip Characteristic
Internal Fault
IX
IY
0 6 12
0 6 12
3
ID = IX + IY IR = IX + IY
ID = (+1)+ (+1) = 2 IR = +1 + +1 = 2
Page 57 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Idiff
Istab
fault line (k=1)
internal fault
external fault oroperation condition
Ideal internal faultIdiff = I1Istab = I1fault is on fault line
External faultIdiff = 0Istab = |I1|+|I2|+...|In|
security for CT deviations
Trip Characteristic
Page 58 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Differential Current may cause maloperation in case of CT-saturation
i1
i2
⎟ i_diff⎟
T 2T 3T 4Tt
t
t
Differential Current due to CT-Saturation
Page 59 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Current transformer saturation
Saturation during steady-state current
Saturation during offset current
Page 60 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Line differential protectionLine differential protection
SIPROTEC 4
Current Comparison Protection for all applications for cables and overhead linesTwo up to six line endsHandles transformers in the protected zone (integrated vector group matching)Direct connection to communication networksCommunication via copper and ISDN networksFault LocatorFast tripping (less than 15 ms)Automatic reclosure
Page 61 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
over 3 line ends
7SD52
7SD52
7SD52
SIPROTEC 4 Line differential protection
ConfigurationsConfigurations
Page 62 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
direct FO connection up to 100 kmdigital communication network (G703, X21)ISDN-connection2 or 3 wire pilot wire (twisted, screened)
Digitalcommunication network
or7SD
5
ISDN
or2/3 wire pilot wire (Cu)
FOor
7SD
5OEEO
EO
EO
OE
OE
No restrictions for communicationNo restrictions for communication
Communication with …
SIPROTEC 4
Page 63 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
ring topology
I3
I2
I1
side 1
side 2
Side 3
Partial current summation
I3
I2
I1
side 1
side 2
side 3
I3+I1 I2
I1+I2 I3
I3+I1I1+I2
connection toother devices
Topology detection, exampleTopology detection, example
SIPROTEC 4
Page 64 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Line differential protection and distance protection in one device
Comprehensive function mix for 2-6 line end applications
Any combination of DIF and DIS, as main or backup protection
Emergency / backup protection as additional backup level
Full control functionality (graphic display)
.....11010110.....∆ IZ<
∆ IZ<
Z1 Z1B
Z1Z1B
7SD52 V4.3 Line protection
Universal line protection for HV and EHV applications
Page 65 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Multifunctional Protectionfor
Transformers and Generators 7UT6
SIPROTEC 4
Page 66 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Measuring Preprocessing, Example for CT Matching (Part 1)
IP1 = 500A(load current)
IP2 = 1833A(load current)
1000/5A 2000/5AUN1 = 110kV UN2 = 30kV
SN = 100MVA
winding 1 winding 2
7UT512
IDiff = ? IStab= ?
IN, Trafo = 525A IN, Trafo = 1924A
IS1 = 2.5A IS2 = 4.58A measuredsecondary currents
Page 67 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
Method of Vector Group Determination
IL1,S1IL1,S2 = IL1 - IL2
330°(n * 30°)
Vector group isY d 11
Side 2: Side 1:
1L1
1L2
1L3
2L1
2L2
2L3
Page 68 28/11/2007
© Siemens AG 2006Power Transmission and DistributionA.belvaux
SICAM PASSystem with IEC61850 and further services
100 Mbit/s switched and redundant Ethernet ring
62,5µ or 50µ FO
Ethernet-Switch
DIGSI 4
Web-Monitor
Ethernetpatch-cable
Station unitSICAM PCC
Stand byconnection
max. 6devicesperswitch
GooseMessage
Inforeport