presentation relais siemens

68
Power Transmission and Distribution Siemens Belgium-Luxemburg

Upload: oedis

Post on 07-Apr-2015

613 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Presentation Relais Siemens

© Siemens AG 2006

Power Transmission and Distribution

Siemens Belgium-Luxemburg

Page 2: Presentation Relais Siemens

Page 2 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

High Voltage Transformers Medium VoltageComponents, switchgear and turnkeyprojects for power transmission ≤ 52kV (AC and DC)

Components, switchgear and turnkeyprojects for power transmission > 52kV (AC and DC)

Power transformers up to 1,300 MVA and 765kV, distribution transformerswith oil or cast-resin insulation

Energy AutomationIntegrated control systems, protection and substation automation, telecontrol systems, power quality.

ServicesNetwork planning & consulting, assetmaintenance and maintenance management forgrids & networks, metering services

Siemens Power Transmission and DistributionWhat we have to offer

Page 3: Presentation Relais Siemens

Page 3 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Air Insulated Switchgear (AIS)

Circuit-breakersArrestors, Bushings, Coils and Instrument TransformersDisconnectors

Gas Insulated Switchgear (GIS)

Highly Integrated Switchgear (HIS)

Gas Insulated Lines(GIL)

Reactive Power Compensation

High Voltage Direct Current (HVDC) Installations

PTD DivisionHigh Voltage overview

Page 4: Presentation Relais Siemens

Page 4 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

63

50

40

31,5

25

0

Rated short-circuit breaking current [kA]

72,5 123 145 300 362 420 550 800Rated voltage [kV]

170 245

80

3AT2/3 3AT4/5

3AP1 FI3AP1 FG 3AP2 FI

Products and Solutions for High VoltageAIS – Circuit Breakers

Page 5: Presentation Relais Siemens

Page 5 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Type 3AP1 FG up to 245 kVFor all applications: reliable and economicalStored energySpring Drive MechanismSelf compression arc quenching principleRated voltages up to 245 kVRated short circuit breaking current up to 50 kAType tested to the new IEC 62271-100Available for one or three pole operation (FG/FI)Delivered more than 50,000 breakers to more than 120 countries

Type 3AP1 FI up to 300 kVStored energy Spring Drive MechanismSelf compression arc quenching principleRated voltages up to 300 kVRated short circuit breaking current up to 50 kAType tested to the new IEC 62271-100

High-Voltage Circuit-Breaker Product Characteristics

Page 6: Presentation Relais Siemens

Page 6 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Type 3AP1 DTC 72.5 up to 245 kVOne interrupter unit per poleStored energySpring Drive MechanismRated voltages up to 245 kVRated short circuit breaking currentup to 63 kAType tested to the new IEC 62271-100Equipped with bushing type current transformersAmbient temperature range from +50° C down to -55° C with pure SF6

Type 3AP2 FI up to 420 kVStored energySpring Drive MechanismSelf compression arc quenching principleRated voltages up to 420 kVRated short circuit breaking current up to 50 kAType tested to the new IEC 62271-100Easy installation and commissioning: only few subassembliesTransportation costs are minimized

High-Voltage Circuit-Breaker Product Characteristics

Page 7: Presentation Relais Siemens

Page 7 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Instrument TransformersCurrent TransformersVoltage Transformers

BushingsAir Core Dry Type ReactorsLine TrapsArc Suppression Coils

CoilsAir Core Dry Type ReactorsLine TrapsArc Suppression Coils

ArresterHV: AIS (Porcellain, Polymer) & GIS; HVDC, FACTSMV: Distribution & Traction Vehicles

Products and Solutions for High VoltageArrestors, Bushings, Coils & Instrument Transformers

Page 8: Presentation Relais Siemens

Page 8 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Centre Break

Ur 72,5 kV – 550 kVIr 1250 A – 4000 AIk 31,5 kA– 63 kA

Pantograph

Ur 123 kV – 420 kVIr 3150 AIk 50 kA

Vertical Break

Ur 123 kV – 550 kVIr 1250 A – 6300 AIk 31,5 kA– 63 kA

Earthing Switch

Built-onFree-standingNeutral point

Double Break

Ur 36 kV – 800 kVIr 1250 A – 5000 AIk 31,5 kA– 63 kA

Knee Type

Ur 123 kV – 550 kVIr 1250 A – 400 AIk 31,5 kA– 63 kA

Products and Solutions for High Voltage Disconnectors & Earthing Switches from 36 kV to 800 kV

Page 9: Presentation Relais Siemens

Page 9 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Voltage(kV)

80

72.5

63

50

40

25

0123 145 300 362 420 550 800

8DR1

8DQ1

8DN9

170 245

HIS 8DN8

HIS 8DQ1

8DN8

Rated short-circuit breaking current (kA)

8DQ1

31,5

Products and Solutions for High voltageGas Insulated Switchgear (GIS)

Page 10: Presentation Relais Siemens

Page 10 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Rated voltage up to 145 kVRated frequency 50 / 60 HzRated power frequency withstand voltage (1 min) up to 275 kVRated lightning impulse withstand voltage (1,2/50 µs ) up to 650 kV

Rated busbar current up to 3150 ARated feeder current up to 3150 ARated breaking current up to 40 kARated short-time current up to 40 kALeakage rate per year and gas compartment < 0.5 %

Bay width 800 mmBay height 2850 mmBay depth 3500 mmBay weight 3 t

Gas Insulated Switchgear (GIS)8DN8.2 switchgear

Page 11: Presentation Relais Siemens

Page 11 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Gas Insulated Switchgear (GIS) 8DN9 switchgear

Rated voltage up to 245 kVRated frequency 50 / 60 HzRated power frequencywithstand voltage (1 min) up to 460 kVRated lightning impulsewithstand voltage (1,2/50 µs) up to 1050 kVRated busbar current up to 3150 ARated feeder current up to 3150 ARated breaking current up to 50 kARated short-time current up to 50 kALeakage rate per year andgas compartment < 0.5 %Bay width 1500 mmBay height 3500 mmBay depth 4700 mmBay weight 5 t

Page 12: Presentation Relais Siemens

Page 12 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Savings HIS*Savings HIS*

Site price 60 %

Civil works 20 %

Secondary cables 35 %

Steel structures 30 %

Earthing 70 %

Erection, tests, commissioning 70 %

Compact

Low cost

Modular

Suitable for in- and outdoor use

* compared to air insulated switchgear

Products and Solutions for High voltage Highly Integrated Switchgear (HIS)

Page 13: Presentation Relais Siemens

Page 13 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Domaine d’utilisation des installationsmoyenne tension

G

x x

x xxx xx x

x

Niveau de production et Réseau de Transport

Niveau de distribution primaire

Niveau de distribution secondaire

Basse tension

Page 14: Presentation Relais Siemens

Page 14 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Secondary distributionswitchgear

Gas-insulated (SF6 )8DH108DJ10/8DJ20

Air-insulatedSIMOSEC

Medium Voltage: Overview

Primary distributionswitchgear

Gas-insulated (SF6 )NX PLUS CNX PLUS8DA/8DB

Air-insulatedNX AIR NX AIR MNX AIR PSIMOPRIME

MV DC-Multifunctional Link

SIPLINK

Components

Vacuum tubesVacuum circuit-breakersVacuum contactorsOther Components

Page 15: Presentation Relais Siemens

Page 15 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

8DAType-tested, single-phase encapsulation, metal-cladProved design, Single BusbarModular design with standard enclosures allows single- and double phase applicationsMore than 15 years of operating experience

Medium Voltage Products for Primary DistributionSF6-Insulated Switchgear

8DBType-tested, single-phase encapsulation, metal-cladProved design, Double BusbarModular design with standard enclosuresBusbars and busbar-disconnectors in separate gas compartmentsMore than 15 years of operating experience

up to 4000 Aup to 40 kAup to 40.5 kVDelivery Program

up to 4000 Aup to 40 kAup to 40.5 kVDelivery Program

Page 16: Presentation Relais Siemens

Page 16 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

NX AIR MType-tested, IEC 62271-200, metal-clad, loss of service continuity category: LSC 2B, partition class: PM, internal arc classification: IAC A FLR ≤25 kA, 1sSingle- and Double Busbar(back/back, front/front)Vacuum circuit-breaker withdrawableMax. renewed availability by modular designSelective shutdown by bushing type transformers and pressure resistant compartmentsMax. operating safety by selfexplanatory logical operating elementsMaintenance intervals > 10 years

NX AIRType-tested, IEC 62271-200, metal-clad, loss of service continuity category: LSC 2B, partition class: PM, internal arc classification: IAC A FLR ≤40 kA, 1sSingle- and double busbar(back/back, front/front)Vacuum circuit-breaker withdrawableVacuum contactor withdrawableMax. renewed availability by modular designSelective shutdown by bushing type transformers and pressure resistant compartmentsMax. operating safety by self-explanatory logical operating elementsMaintenance intervals > 10 years

up to 2500 Aup to 40 kAup to 12 kVDelivery Program

up to 2500 Aup to 25 kA17.5 / 24 kVDelivery Program

Medium Voltage Products for Primary DistributionAir-Insulated Switchgear (AIS)

Page 17: Presentation Relais Siemens

Page 17 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

8DJ20Type-testedIndependent of climateMaintenance-freeBlock-type construction, for 1-5 baysHermetically-sealed welded switch-gear enclosuresCompact and clear designNo sealingsHighest Quality LevelShortest Delivery Periods

8DJ10Type-testedIndependent of climateMaintenance-freeBlock-type construction, for 3-6 baysHermetically-sealed welded switch-gear enclosuresCompact and clear designNo sealingsHighest Quality LevelShortest Delivery PeriodsSmallest floor space for substations

up to 630 Aup to 25 kAup to 24 kVDelivery Program

up to 630 Aup to 25 kAup to 24 kVDelivery Program

Medium Voltage Products for Secondary DistributionSF6-Insulated Switchgear

Page 18: Presentation Relais Siemens

Page 18 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Independent power producers(wind generators, solar plants)

City

Large-scale power plant

Consumers withsensitive processes

Hospital

Manufacturing, trade,small industry withoutin-plant generation

Large-scale industrywith in-plant generation

New Switching Technologies for Distribution SystemsImproves Cost-Effectiveness, Availability and Power Quality

MV DC-Multifunctional Link - SIPLINK

Page 19: Presentation Relais Siemens

Page 19 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

High reliability

Excellent field experience with more than 2 million vacuum interrupters

Tailormade development

Wide product range for any application

For use in

LV and MV circuit-breakers, load-break switches and contactors

Autoreclosers

Transformer Tap Changers

up to 6300 Aup to 72 kA7.2 up to 40.5 kVup to 2500 Aup to 65 kA690 up to 1300 V

Delivery Program

Medium Voltage ComponentsVacuum Tubes

Page 20: Presentation Relais Siemens

Page 20 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

PTD Division Transformers

Do lor situs cum habilitarum itumalus causticusimanenter Status landum exus riuslaudanum tum.

Lorem exit vulnareusplexus est. Vulnapausta rhus tex, per itum falor sit wunt. Sit itum causticusaurum eum et explindus.Cum

Power transformers

Distribution transformers withoil or cast-resininsulation

Page 21: Presentation Relais Siemens

Page 21 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Generatortransformer

Systeminterconnectingtransformer

Shuntreactor

Oil-immerseddistribution transformer

GEAFOLcast-resin transformer

Tractiontransformer

HVDC

Systemtransformer

Special purpose transformers for industrial application

Voltageregulator

Phase angle regulator

TLMSiemens Transformer Life Management(condition assessment,life-extension,on-site-services,monitoring, ...)

Siemens Transformers at all Levels of Transmission and Distribution

Page 22: Presentation Relais Siemens

Page 22 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Ratings from 10 MVA up to 1.100 MVA / 1200 kV

Three-phase and single-phase

Power Transformers

Page 23: Presentation Relais Siemens

Page 23 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Cast-resin distributiontransformers

Ratings from 50 kVA up to40MVA

Possibility for on-linetapchanger

Static converter transformers

Distribution TransformersGEAFOL

Page 24: Presentation Relais Siemens

Page 24 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Distribution TransformersOil-immersed

Ratings from 50 up to 4.000 kVA

(TUNORMA and TUMETIC)

Page 25: Presentation Relais Siemens

Page 25 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

PTD Division Energy Automation

Do lor situs cum habilitarum itumalus causticusimanenter Status landum exus riuslaudanum tum.

Lorem exit vulnareusplexus est. Vulnapausta rhus tex, per itum falor sit wunt. Sit itum causticusaurum eum et explindus.Cum

Information and network controltechnology

Protection and substation auto-mation, telecon-trolsystems, power quality

Page 26: Presentation Relais Siemens

Page 26 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

System control centersSpectrum PowerCCSINAUT Spectrum

Station control & automationSICAM PASSAT 1703 / SAT 230

Protection/PowerQuality/Bay Control

SIPROTECREYROLLEBC 1703 ACPSIMEAS

Communications& networking

PLCModems …

RTU’sSAT 1703SICAM eRTU / miniRTUTG 805 / TG 5700Tools

SICAM TOOLBOXIMM DIGSI…

Energy Market Mgmt.EMMFDWHPROPHET SolutionsAMIS…

Energy Automation Strong products and brands on all levels

Page 27: Presentation Relais Siemens

Page 27 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

LE BUT DE LA PROTECTION SELECTIVE EST:-Assurer la continuité de service du réseau d’energie , par

élimination de l’élément défaillant et de lui seul-Eviter des dégâts au niveau des équipements affectés par

les défauts(câbles,transformateurs…)

SIPROTEC 4

Page 28: Presentation Relais Siemens

Page 28 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

LE SYSTEME DE PROTECTION =

TI/TP + Relais+ Disjoncteur

Sélectif,rapide,fiable

SIPROTEC 4

Page 29: Presentation Relais Siemens

Page 29 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

SIPROTEC 4 is a

family of numericalProtection, Control- and

Automation Devices from

SIEMENS

SIPROTEC 4 - What does it mean?

Page 30: Presentation Relais Siemens

Page 30 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

O/C protection 7SJ6Distance protection 7SA6Line differential protection 7SD5 / 7SD6Transformer diff. protection 7UT6Generator protection 7UM6Station protection 7SS52

SIPROTEC 4

Page 31: Presentation Relais Siemens

Page 31 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

O/C protection7SJ6

SIPROTEC 4

Page 32: Presentation Relais Siemens

Page 32 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Time-overcurrent protection Functions

Time-overcurrent protection

Criteria for fault: overcurrent

Criteria for selectivity: time

Page 33: Presentation Relais Siemens

Page 33 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Time-overcurrent protection Characteristics

t [sec]

0.5

1.0

1.5

2.0

x IN0.5 1.0 1.5 2.0 2.5I> I>>

Tripping area

Tripping characteristic of a two stage time-overcurrentprotection device - definite time

Page 34: Presentation Relais Siemens

Page 34 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Time-overcurrent protection Characteristics

x IN0.5 1.0 1.5 2.0 2.5

t [sec]

0.5

1.0

1.5

2.0

Tripping characteristic of a time-overcurrent protection device -inverse time

Characteristics:IECANSIuser defined

Page 35: Presentation Relais Siemens

Page 35 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Time-overcurrent protection Application

Used as:

Line protectionSelectivity by time-grading

1

x

O/C

x

O/C

1

x

M

O/C

2x

O/C

3

As main protection

2 Motor protectionwith short circuit- and overload protection,start protection,start inhibit

3 Transformer protectionfor network transformerswith short circuit- and overload protection,Inrush-stabilisation

Page 36: Presentation Relais Siemens

Page 36 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Time-overcurrent protection Application

Main protection as line protection

x x x x

O/C O/C O/C O/C

t = 0mst = 300mst = 600mst = 900ms

Advantage: simple device,only current transformers are necessary

Disadvantage: near infeed higher tripping time

Ttrip

distance

backup

Page 37: Presentation Relais Siemens

Page 37 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Reverse Interlocking Application

1Outgoing protection initiates and blocksthe infeed protection stage within 50 ms

2Infeed protection gives a trip after50 ms since no outgoing feeder has picked up and blocked the infeed protection

M

O/CO/C

O/C

O/C

T = 50ms t = xxms

start start. start. + ++

Blocking

1

Energy direction 2

Page 38: Presentation Relais Siemens

Page 38 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

4 CT inputs

7SJ61

O/C protection with motor protectionO/C protection with motor protection

Over current protection(Phase/Earth)Inrush BlockingMotor ProtectionOverload ProtectionUnbalanced Load ProtectionAuto reclosureTrip Circuit SupervisionBreaker Failure ProtectionLock out

SIPROTEC 4

Page 39: Presentation Relais Siemens

Page 39 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Distance protectionDistance protection

SIPROTEC 4

Page 40: Presentation Relais Siemens

Page 40 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Why impedance protection?

Situation: Meshed network and two infeedsDirectional overcurrent time relays

0,6s

0,6s

0,3s

0,3s

0,6s

0,6s

0,3s

0,3s

non-selective trip

Page 41: Presentation Relais Siemens

Page 41 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Localization of short-circuits by means of an impedance measurement:

fault on the protected line

fault outside the protected line

Z1

relay A

selectivity

relay A

Z2

Basic principle of impedance protection

Page 42: Presentation Relais Siemens

Page 42 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Distance measurement (principle)

6 loops: 3 phase- phase loops and3 phase- ground loops

phase- phase -loop:

The same applies to the remaining loops

UL1-L2 = ZL ( IL1 - IL2)

Measured currentmeasured voltage

06.08.97dtgerdis3

ZL = RL + j XL

ZE = RE +j XE

IL1

IL2

IL3

IE

ZL

ZEUL1UL2UL3

Page 43: Presentation Relais Siemens

Page 43 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

phase-ground-loop: UL1 = ΙL1 · ( RL + j XL )- ΙE · ( RE +j XE)

ΙL1, ΙE measured currentUL1 measured voltage

06.08.97dtgerdis3

The same applies to the remaining loops

Distance measurement (principle)

IL1

IL2

IL3

IE

ZL

ZE

UL1UL2UL3

ZL = RL + j XL

ZE = RE +j XE

Page 44: Presentation Relais Siemens

Page 44 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Numerical filtered phasor measurement

1. Fast operation ⇒ Use short data window

2. High accuracy ⇒ High selectivity

3. Signal distortion does not cause delay or maloperation

X

R

Page 45: Presentation Relais Siemens

Page 45 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

ni2sin ⋅π

ni2cos ⋅π

C(k)S(k)(k) j III ⋅+=S(k)I

C(k)Ij ⋅ )(kI

)( inki +−

k-n

0 1 2 . . . n

ϕ

i

C(k)I

S(k)I

k

Fourier analysis of measured values

Sampledmeasuringvalues

Resulting phasor

Page 46: Presentation Relais Siemens

Page 46 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Load and short-circuit impedances

ZL

ZLF1

ZLF2

RF RF

ZLoadDF1 F2

X

R

ZL

ZLF2

j SC1

j SC2

j L

RR

ZF1

ZF2

RR

ZLoad

ZLF1

Fault area

distance relayoperating characteristic

Increasing load

Fault in reverse

direction Load area

Minimum Load Impedance:Minimum voltage 0,9 UnMaximum current 1,1 InMaximum angle ± 30°

Phase - Phase Fault

RR ≈ RF / 2

Phase - Earth Fault

RR ≈ RF /(1 + RE/RL)

Page 47: Presentation Relais Siemens

Page 47 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Graded distance zones

time

D1 D2 D3

t1

t2

t3

Z1

Z2

Z3

distance

∆t = grading time

A CB D

Z1 = 0,85 ZAB

Z2 = 0,85 (ZAB + 0,85 ZBC)Z3 = 0,85 (ZAB + 0,85 (ZBC + 0,85 ZCD))

Safety margin is 15 %:

line errorCT, VT errormeasuring error

Grading rules:

Page 48: Presentation Relais Siemens

Page 48 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

ϕSC

Current area forforward faults

ΙSCCurrent area for reverse faults

ΙSC

USC

R

ZSC

Z'SC

Impedance area for forward faults

Impedance area forreverse faults

X

ϕSC

Determination of fault direction

current / voltage diagram impedance diagram

Fault location Where is the fault ?

The impedance also shows the direction, but ....

Page 49: Presentation Relais Siemens

Page 49 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Fault detection techniques

Over-current fault detectionVoltage dependant over-current fault detection

Voltage and angle dependantover-currentfault detection

I

U

I >>I > I ϕ >

R

X

Impedancefaultdetection

Not in 7SA522

Page 50: Presentation Relais Siemens

Page 50 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

X

R

forwards

forwards

reverse

reverse

ϕ LoadLoad

Z1

Z2

Z4

Z3

Z1B

Z5

Line

α

Impedance zones of digital relays

Distance zonesInclined with line angle ϕAngle α prevents overreach of

Z1 on faults with fault resistance that are fed from both line ends

Fault detectionno fault detection polygon: the

largest zone determines the fault detection characteristic

simple setting of load encroachment area with Rmin and ϕLoad

Page 51: Presentation Relais Siemens

Page 51 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Zone grading chart, radial feeder

D

A

D

B

D

C

Ι>>

D

Ι>t∆Ι

ZT

Z1

Z2

Z3

Z1 = 0.85 ZA-B

Z3 = 0.85 [ ZA-B + 0.85 (ZB-C+ 0.85 ZC-D) ]Z2 = 0.85 (ZA-B + 0.85 ZB-C)

Grading accordingthe recommendationwith the safety margin of 15%.

Page 52: Presentation Relais Siemens

Page 52 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Ring feeder: with grading against opposite end

0.6

0.3

grading time(s)

The same grading from both sides

Page 53: Presentation Relais Siemens

Page 53 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Line differential protection

7SD61 / 7SD52

SIPROTEC 4

Page 54: Presentation Relais Siemens

Page 54 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Kirchhoff: I1+I2+I3+I4+I5=0

I1

I2

I3

I4

I5

Measuring Principle

Page 55: Presentation Relais Siemens

Page 55 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Trip Characteristic

1:1(3Y)

1:1(3Y)

IX IY

IX IY

0 6 12 0 6 12

1 p.u. 1 p.u.

Internal Fault

Page 56: Presentation Relais Siemens

Page 56 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Trip Characteristic

Internal Fault

IX

IY

0 6 12

0 6 12

3

ID = IX + IY IR = IX + IY

ID = (+1)+ (+1) = 2 IR = +1 + +1 = 2

Page 57: Presentation Relais Siemens

Page 57 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Idiff

Istab

fault line (k=1)

internal fault

external fault oroperation condition

Ideal internal faultIdiff = I1Istab = I1fault is on fault line

External faultIdiff = 0Istab = |I1|+|I2|+...|In|

security for CT deviations

Trip Characteristic

Page 58: Presentation Relais Siemens

Page 58 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Differential Current may cause maloperation in case of CT-saturation

i1

i2

⎟ i_diff⎟

T 2T 3T 4Tt

t

t

Differential Current due to CT-Saturation

Page 59: Presentation Relais Siemens

Page 59 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Current transformer saturation

Saturation during steady-state current

Saturation during offset current

Page 60: Presentation Relais Siemens

Page 60 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Line differential protectionLine differential protection

SIPROTEC 4

Current Comparison Protection for all applications for cables and overhead linesTwo up to six line endsHandles transformers in the protected zone (integrated vector group matching)Direct connection to communication networksCommunication via copper and ISDN networksFault LocatorFast tripping (less than 15 ms)Automatic reclosure

Page 61: Presentation Relais Siemens

Page 61 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

over 3 line ends

7SD52

7SD52

7SD52

SIPROTEC 4 Line differential protection

ConfigurationsConfigurations

Page 62: Presentation Relais Siemens

Page 62 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

direct FO connection up to 100 kmdigital communication network (G703, X21)ISDN-connection2 or 3 wire pilot wire (twisted, screened)

Digitalcommunication network

or7SD

5

ISDN

or2/3 wire pilot wire (Cu)

FOor

7SD

5OEEO

EO

EO

OE

OE

No restrictions for communicationNo restrictions for communication

Communication with …

SIPROTEC 4

Page 63: Presentation Relais Siemens

Page 63 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

ring topology

I3

I2

I1

side 1

side 2

Side 3

Partial current summation

I3

I2

I1

side 1

side 2

side 3

I3+I1 I2

I1+I2 I3

I3+I1I1+I2

connection toother devices

Topology detection, exampleTopology detection, example

SIPROTEC 4

Page 64: Presentation Relais Siemens

Page 64 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Line differential protection and distance protection in one device

Comprehensive function mix for 2-6 line end applications

Any combination of DIF and DIS, as main or backup protection

Emergency / backup protection as additional backup level

Full control functionality (graphic display)

.....11010110.....∆ IZ<

∆ IZ<

Z1 Z1B

Z1Z1B

7SD52 V4.3 Line protection

Universal line protection for HV and EHV applications

Page 65: Presentation Relais Siemens

Page 65 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Multifunctional Protectionfor

Transformers and Generators 7UT6

SIPROTEC 4

Page 66: Presentation Relais Siemens

Page 66 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Measuring Preprocessing, Example for CT Matching (Part 1)

IP1 = 500A(load current)

IP2 = 1833A(load current)

1000/5A 2000/5AUN1 = 110kV UN2 = 30kV

SN = 100MVA

winding 1 winding 2

7UT512

IDiff = ? IStab= ?

IN, Trafo = 525A IN, Trafo = 1924A

IS1 = 2.5A IS2 = 4.58A measuredsecondary currents

Page 67: Presentation Relais Siemens

Page 67 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

Method of Vector Group Determination

IL1,S1IL1,S2 = IL1 - IL2

330°(n * 30°)

Vector group isY d 11

Side 2: Side 1:

1L1

1L2

1L3

2L1

2L2

2L3

Page 68: Presentation Relais Siemens

Page 68 28/11/2007

© Siemens AG 2006Power Transmission and DistributionA.belvaux

SICAM PASSystem with IEC61850 and further services

100 Mbit/s switched and redundant Ethernet ring

62,5µ or 50µ FO

Ethernet-Switch

DIGSI 4

Web-Monitor

Ethernetpatch-cable

Station unitSICAM PCC

Stand byconnection

max. 6devicesperswitch

GooseMessage

Inforeport