© ABB n.v. - 1 - 2006-06-07 2GCS617011A0070 PQF LV Active Filters: Bringing energy savings to you…

Upload: others

Post on 07-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v. -

1-2

006-

06-0

72G

CS6

1701

1A00

70

PQF LV Active Filters: Bringing energy savings to you…

Page 2: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

2-

2006

-06-

07

Key elements of poor LV Power Quality

Harmonics

Reactive power

Load imbalance

Energy losses and high running costs

Page 3: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

3-

2006

-06-

07

Customer inquiry

Can ABB PQF active filters help to realize energy savings?

The question becomes more popular with increasing energy prices

The answer is...

4 field reports...

Page 4: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

4-

2006

-06-

07

Field report 1: Installation on ferries

The inquiryInstall filters to solve harmonic problems due to propulsion DC drives

Perform cos ϕ compensation without overcompensation

The installationPower plant: 2 generatorsMain load: 2 DC drive propulsion units

Performance without filters:G1: 660 A, G2: 580 A cos ϕ: 0.76THDV = 22%, THDI = 25%Av. consumption:14000-15000 l/month

Page 5: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

5-

2006

-06-

07

Field report 1: Installation on ferries

Reasons for choosing ABB active filtersCompact solution (paramount given the limited space aboard)Excellent filtering performancePossibilities to perform transient-free reactive power compensation up to target cos ϕ

Customer findings and consequent actionsTechnical problems resolvedWith ABB PQF active filters operational, about 10% of fuel savings were reported resulting in drastically reduced running costs

Further actions of customer and findingsInstallation of ABB PQF active filters on other ferries of customer10% of fuel savings have also been confirmed on the other ferries

Customer gain: per ferry about 18000 l fuel per year

Page 6: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

6-

2006

-06-

07

Field report 2: Industrial extruder lines

CustomerRuns various extruder lines resulting in THDV of about 11% on LV sideExtruder lines are DC drive basedDue to the harmonics in the voltage, voltage wave form had multiple zero crossings which upset the DC drive control causing damageHopes to have reduction of losses in (long) feeding cables and feeding transformers (billing aspect and cable overheating aspect)

Page 7: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

7-

2006

-06-

07

Field report 2: Industrial extruder lines

Reasons for choosing ABB active filtersOnly supplier with long term track record for large power active filtersABB in house engineering of the product giving confidence for future supportPossibility to set cos ϕ target value and possibility to assign resources to this task

Page 8: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

8-

2006

-06-

07

Extruder 4 - Active Power P (kW) (ABB Active Filter PQF OFF)

500

600

700

800

900

1000

1100

1200

1300

0:00:00 0:07:12 0:14:24 0:21:36 0:28:48 0:36:00 0:43:12

Field report 2: Industrial extruder lines

Customer findings and consequent actionsTechnical problems in production line disappearedCos ϕ of the installation increased from 0.84 to 0.92 on averageIn house on-line power consumption monitoring indicated around 10-15% savings of active power which resulted in very short pay back time of installation

Pmin = 927 kWPmax = 1230 kW

Extruder 4 - Active Power P (kW) (ABB Active Filter PQF ON)

500.0

600.0

700.0

800.0

900.0

1000.0

1100.0

1200.0

0:00:00 0:07:12 0:14:24 0:21:36 0:28:48 0:36:00

Pmin = 827 kWPmax = 1147 kW

Page 9: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

9-

2006

-06-

07

Field report 2: Industrial extruder lines

ABB verification measurement with high precision measuring equipment indicated that

measuring equipment used by the company functions correctly

during the verification measurement with and without active filter also around 11% power savings were recorded when filter running

ABB contacted independent 3rd party European accredited measurement laboratory, ‘Labo Lemcko‘ to re-measure and verify the validity of the measurements made...

Page 10: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

10-

2006

-06-

07

Field report 2: Industrial extruder lines

Independent laboratory confirmed 14.5 % energy savings!

Not Measured! Inferior to main load

Pulse number and type 6 pulse SCR Apparent power 750 kVA

Tranformer-busbar cable Length: 150 m Cross section / phase 300 mm2 Nr parallel connections: 14

Other Load

Transformer Nominal power: 4000 kVA Short-circuit impedance 6 % Secondary Voltage 400 V

MV Network Short-circuit power: ? MVA Voltage: 10 kV Frequency: 50 Hz

Main extruder 1

Active Filter

Pulse number and type 6 pulse IGBT RMS Current: 450 A

⌦1

Energy (kWh) vs Time (h)

With filter

Without filter

Customer gain: more than 70 kUSD per year

0,00E+00

1,00E+03

2,00E+03

3,00E+03

4,00E+03

5,00E+03

6,00E+03

0 0,5 1 1,5 2 2,5 3 3,5 4

Time [hours]

Ener

gy [k

Wh]

with filterwithout filter

Page 11: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

11-

2006

-06-

07

Field report 2: Industrial extruder lines

Note: during the first year, the customer has already profit because the production line down time is reduced.

……

>2804

>2103

>1402

>701

Accumulated energy savings (kUSD)

Year

Financial analysis over time

Very short pay-back time is realized

Pay-back time

Additional profit

Page 12: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

12-

2006

-06-

07

Field Report 2: Industrial extruder lines

Further actions of customerCustomer has ordered additional ABB PQF LV Active Filters for other production lines

Page 13: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

13-

2006

-06-

07

Field report 3: AC drives – paper industry

CustomerRuns many AC drives and has set up an evaluation program of savings with and without active filterMeasurements were done over periods of one month with and without active filter (March: active filter not running, April: active filter running)

0.00010.00020.00030.00040.00050.00060.00070.00080.00090.000

0 5 10 15 20 25 30 35

Days

Pow

er (K

w). March

April

May

Page 14: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

14-

2006

-06-

07

Field report 3: AC drives – paper industry

Customer findings and consequent actions

Customer reports on average 10% savings when active filter is used

Customer is at present making inventory of all his harmonic loads and requests ABB to quote for an overall filter solution

Page 15: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

15-

2006

-06-

07

Field report 4: stadium flood lights

CustomerNeeds to offload supply cables to the flood lights (overheating problem due to cable losses)

Needs to ensure that system can run on stand alone generator basis due to international football organization rules

Installs active filters to accommodate the above

Page 16: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

16-

2006

-06-

07

Field report 4: stadium flood lights

Customer findingsCable losses are reduced by 33% resulting in acceptable operation

Technical problems (generator operation) are resolved

ConsequenceReduction of cable losses has positive impact on energy bill

Page 17: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

17-

2006

-06-

07

Large induction machine analysis

For a 1 MW induction machine a loss evaluation with and without harmonics was made

Conclusions for the machine consideredIf supply voltage contains 10% H5 distortion, the losses in the machine (due to n.p.s. current) increase by approx. 10-13%

Temperature increase in the machine due to the losses is approx. 10 Kelvin

ConsequencesLoss increase in the machine has to be paid for

The lifetime of this machine is greatly reduced due to temperature increase

Page 18: PQF-Bringing energy savings to you - WordPress.com · and financial loss Field reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and

© A

BB n

.v.-

18-

2006

-06-

07

Conclusions

More and more data emerge indicating that poor Power Quality of the electrical network results in substantially increased electrical losses and consequent down-time and financial lossField reports indicate that ABB PQF LV Active Filters offer an efficient solution to reduce down-time and bring substantial energy savings to customers

PQF LV Active FiltersBringing energy savings to you!