POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY STORAGE SYSTEM Blake Rector, PhD, Powin Energy Mike McGuffin, Customized Energy Solutions Energy Storage and Distributed Energy Resources Workshop CAISO – 16 January 2018

Upload: others

Post on 08-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

POWIN ENERGY

MILLIKAN I PROJECTBATTERY ENERGY STORAGE SYSTEM

Blake Rector, PhD, Powin EnergyMike McGuffin, Customized Energy Solutions

Energy Storage and Distributed Energy Resources WorkshopCAISO – 16 January 2018

Page 2: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

Full Range of Energy Market Services

Market IQWholesale

ServicesRetail Services

Demand Response

Congestion Mgmt Renewable MgmtEmerging

Technologies

CES

ISO Reporting

Rule Changes

RegulatoryDispatch

Scheduling

Monitoring

Bidding

Telemetry

Settlements

24 Hour Desk

Market Participant

Market Optimization

DA / RT Strategies

CES|GOLD

Market Entry

EDI/Billing

Forecasting

Scheduling

Settlements

Pricing

Congestion Management

Headroom Analysis

Managed Portfolio Services

DR Mgmt

CES|GREEN

SecureNet

Tracking

Settlement

ARR Analysis

FTR Analysis

Congestion Analysis

Power Flow Studies

RPS Management

Plant Registration

REC Optimization

Compliance

Storage IQ

CoMETS Valuation Models

Forecasting Storage Market Size

Market Entry & Business Strategies

Storage Rules

Technology Due Diligence

Microgrids

Page 3: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

CES Offices

Page 4: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

4

Customized Energy Solutions (CES)

• CES manages approximately 9,000 MWs of capacity across six

ISO/RTOs in North America including over 100MWs of Energy Storage.

• CES is a certified CAISO Scheduling Coordinator under the affiliate

name of Galt Power.

• CES has been scheduling in the CAISO market since 2010.

• Currently schedule for Dispatchable Renewables, Direct Access

Load, Proxy Demand Resources, and Energy Storage.

CES is objective and independent--not affiliated with any trading, marketing, distribution or transmission companies

Page 5: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

OUTLINE

• Project Owner / Project Information (3 slides)

• Market Participation Issues (1 slide each)

- Infeasible AGC Dispatch

- Persistent AGC Dispatch

- Accuracy Scores

Page 6: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

Project Owner: esVolta

Highlights esVolta launched in 4Q 2017• Develop, build, own, operate business model

• Focus on greenfield development and M&A in the North American utility-scale storage market

• Contracted project portfolio of 116 MWhs

• Additional 800+ MWhs in development pipeline

Strengths Resourced to achieve market scale• Dedicated team for project development, financing, management and operations

• Long-term capital commitment from Blue Sky Alternative Investments, a global infrastructure investor

• Strategic procurement relationship with Powin Energy Corporation, a leading lithium-ion battery storage technology integrator

esVolta is a leading North American utility-scale energy storage platform

`

`

Page 7: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

PROJECT INFORMATION

• Size: 2 MW/8 MWh• Technology:

• Powin Energy BP400+ BESS• Lixin LiFePO4 cells (lithium iron phosphate)• Eaton Energy Xpert 2 MW inverter

• Operation: Day Ahead and Real Time Energy, Regulation

• Interconnection: SCE medium-voltage grid Virgo 12 kV distribution line out of Estrella 66/12 kV substation

Page 8: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

PROJECT INFORMATION• BESS Control

• Industry exclusive Powin bp-OS• Battery OdometerTM

• Warranty TrackerTM

• BMS• Patented in US and China

• Modular design• Scalability• Speed of deployment

• CES Secure|Net Remote Intelligent Gateway (RIG)

Page 9: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

INFEASIBLE AGC DISPATCH

• Continuing to receive AGC signals to CHARGE after hitting MAX SOC

• CIDI Ticket filed in August 2017 – Received several iterations of

responses, but nothing conclusive

• Observed improvements soon thereafter

• Recently started seeing infeasible dispatches again

• 8 such occurrences of sustained infeasible dispatch week of 1/1/2018

Page 10: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

PERSISTENT AGC DISPATCH

• Many occurrences of >1hr constant

Reg Down CHARGE signal

• Consistent dispatch pattern occurring in certain hours

-2500

-2000

-1500

-1000

-500

0

0:00 0:30 1:00 1:30 2:00 2:30

kW

Time Duration

Dispatch Power - AGC Signal

Page 11: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

ACCURACY SCORES

• ISO Settlement Accuracy data is not what we see in our internal data

-2500

-2000

-1500

-1000

-500

0

500

1000

1500

2000

2500

0:00 0:01 0:02 0:04 0:05 0:07 0:08 0:10 0:11

kW

Time Duration

Example AGC Signal and Powin Response - 4 second data

DispatchPower - AGC Signal PCSPower - Powin Response

Page 12: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

ACCURACY SCORES

• How is latency treated?

• Lack of clarity on calculation…

➢ 4 Second data used in calculation not published

• Ramp Rate determination – lacks transparency

➢ Ramp rates calculated by ISO from Operational Test versus Regulation Test were very different

and both were not representative of experience during the test or unit capability.

-2.5

-2

-1.5

-1

-0.5

0

0.5

9:59:54 10:00:12 10:00:29 10:00:46 10:01:03 10:01:21 10:01:38 10:01:55

MW

AGC vs Response – as seen by ISO - 4 sec data

Telemetry AGC SetPt

Page 13: POWIN ENERGY MILLIKAN I PROJECT BATTERY ENERGY … · 2018. 2. 10. · and both were not representative of experience during the test or unit capability. -2.5-2-1.5-1-0.5 0 0.5 9:59:54

POWIN ENERGY - MILLIKAN I • Blake Rector, PhD – Director of Analytics,

Powin [email protected]

• Mike McGuffin – Director of Wholesale Services West, Customized Energy Solutions

[email protected]