Rethinking data centers
Chuck Thacker
Microsoft Research
October 2007
“There is nothing more difficult to take in hand, more perilous to conduct, or more uncertain in its success, than to take the lead in the introduction of a new order of things” – Niccolo Machiavelli
Problems
• Today, we need a new order of things. • Problem: Today, data centers aren’t designed as
systems. We need apply system engineering to:– Packaging– Power distribution– Computers themselves – Management– Networking
• I’ll discuss all of these.• Note: Data centers are not mini-Internets
System design: Packaging
• We build large buildings, load them up with lots of expensive power and cooling, and only then start installing computers.
• Pretty much need to design for the peak load (power distribution, cooling, and networking).
• We build them in remote areas.– Near hydro dams, but not near construction workers.
• They must be human-friendly, since we have to tinker with them a lot.
Packaging: Another way• Sun’s Black Box• Use a shipping container – and build a parking lot instead of a
building.• Don’t need to be human-friendly. • Assembled at one location, computers and all. A global shipping
infrastructure already exists.• Sun’s version uses a 20-foot box. 40 might be better (They’ve got
other problems, too).• Requires only networking, power, and cooled water, so build near a
river. Need a pump, but no chiller (might have environmental problems).
• Expand as needed, in sensible increments.• Rackable has a similar system. So (rumored) does Google.
The Black Box
Sun’s problems
• Servers are off-the-shelf (with fans).• They go into the racks sideways, since they’re
designed for front-to-back airflow.• Servers have a lot of packaging (later slide).• Cables exit front and back (mostly back).• Rack must be extracted to replace a server
– They have a tool, but the procedure is complex.
• Rack as a whole is supported on springs.• Fixing these problems: Later slides.
Packaging
• A 40’ container holds two rows of 16 racks.• Each rack holds 40 “1U” servers, plus network
switch. Total container: 1280 servers.• If each server draws 200W, the rack is 8KW, the
container is 256 KW.• A 64-container data center is 16 Mw, plus
inefficiency and cooling. 82K computers.• Each container has independent fire
suppression. Reduces insurance cost.
System Design: Power distribution
• The current picture:– Servers run on 110/220V 60Hz 1Φ AC.– Grid -> Transformer -> Transfer switch ->
Servers.– Transfer switch connects batteries -> UPS/
Diesel generator.– Lots and lots of batteries. Batteries require
safety systems (acid, hydrogen).– The whole thing nets out at ~40 – 50%
efficient, => Large power bills.
Power: Another way• Servers run on 12V 400 Hz 3Φ AC.
– Synchronous rectifiers on motherboard make DC (with little filtering).• Rack contains a step-down transformer. Distribution voltage is 480
VAC• Diesel generator supplies backup power.• Uses a flywheel to store energy until the generator comes up.
– When engaged, the frequency and voltage drop slightly, but nobody cares.
• Distribution chain:Grid -> 60Hz motor -> 400Hz generator -> Transformer -> Servers.Much more efficient (probably > 85%).
• The Cray 1 (300 KW, 1971) was powered this way.• Extremely high reliability.
The Computers
• We currently use commodity servers designed by HP, Rackable, others.
• Higher quality and reliability than the average PC, but they still operate in the PC ecosystem.– IBM doesn’t.
• Why not roll our own?
Designing our own
• Minimize SKUs– One for computes. Lots of CPU, Lots of
memory, relatively few disks. – One for storage. Modest CPU, memory, lots
of disks.• Like Petabyte?
– Maybe one for DB apps. Properties TBD.– Maybe Flash memory has a home here.
• What do they look like?
More on Computers• Use custom motherboards. We design them, optimizing for our
needs, not the needs of disparate application.• Use commodity disks.• All cabling exits at the front of the rack.
– So that it’s easy to extract the server from the rack.• Use no power supplies other than on-board inverters (we have
these now).• Error correct everything possible, and check what we can’t correct.• When a component doesn’t work to its spec, fix it or get another,
rather than just turning the “feature” off.• For the storage SKU, don’t necessarily use Intel/AMD processors.
– Although both seem to be beginning to understand that low power/energy efficiency is important.
Management
• We’re doing pretty well here.– Automatic management is getting some traction, opex isn’t
overwhelming.
• Could probably do better– Better management of servers to provide more fine-grained
control than just reboot, reimage.– Better sensors to diagnose problems, predict failures.– Measuring airflow is very important (not just finding out whether
the fan blades turn, since there are no fans in the server).– Measure more temperatures than just the CPU.
• Modeling to predict failures?– Machine learning is your friend.
Networking
• A large part of the total cost.• Large routers are very expensive, and command
astronomical margins.• They are relatively unreliable – we sometimes see
correlated failures in replicated units.• Router software is large, old, and incomprehensible –
frequently the cause of problems.• Serviced by the manufacturer, and they’re never on site.• By designing our own, we save money and improve
reliability.• We also can get exactly what we want, rather than
paying for a lot of features we don’t need (data centers aren’t mini-Internets).
Data center network differences
• We know (and define) the topology
• The number of nodes is limited
• Broadcast/multicast is not required.
• Security is simpler.– No malicious attacks, just buggy software and
misconfiguration.
• We can distribute applications to servers to distribute load and minimize hot spots.
Data center network design goals
• Reduce the need for large switches in the core.
• Simplify the software. Push complexity to the edge of the network.
• Improve reliability
• Reduce capital and operating cost.
One approach to data center networks
• Use a 64-node destination-addressed hypercube at the core.
• In the containers, use source routed trees.
• Use standard link technology, but don’t need standard protocols.– Mix of optical and copper cables. Short runs
are copper, long runs are optical.
Basic switches• Type 1: Forty 1 Gb/sec ports, plus 2 10 Gb/sec ports.
– These are the leaf switches. Center uses 2048 switches, one per rack.– Not replicated (if a switch fails, lose 1/2048 of total capacity)
• Type 2: Ten 10 Gb/sec ports– These are the interior switches– There are two variants, one for destination routing, one for tree routing.
Hardware is identical, only FPGA bit streams differ.– Hypercube uses 64 switches, containers use 10 each. 704 switches
total. • Both implemented with Xilinx Virtex 5 FPGAs.
– Type 1 also uses Gb Ethernet Phy chips– These contain 10 Gb Phys, plus buffer memories and logic.
• We can prototype both types with BEE3.– Real switches use less expensive FPGAs
Data center network64-switch Hypercube
63 * 4 links toother containers
One container:
4 links
Level 0: 32 40-port 1 Gb/sec switches
Level 1: 8 10-port 10 Gb/sec switches
64 10 Gb/sec links
16 10 Gb/sec links
Level 2: 2 10-port 10 Gb/sec switches
1280 Gb/sec links
4X4Sub-cube
4X4Sub-cube
4X4Sub-cube
4X4Sub-cube
16links
16links
16links
16links
Hypercube properties
• Minimum hop count• Even load distribution for all-all communication.• Reasonable bisection bandwidth.• Can route around switch/link failures.• Simple routing:
– Outport = f(Dest xor NodeNum)– No routing tables
• Switches are identical. – Use destination – based input buffering, since a given link
carries packets for a limited number of destinations.• Link–by–link flow control to eliminate drops.
– Links are short enough that this doesn’t cause a buffering problem.
A 16-node (dimension 4) hypercube
0
3
2
1
0 0
1
2
3 3
1 1
3
0 2021 5 4
6732
10 11 15 14
8 9 13 12
1 1 1 1
1 1 1 1
1 1 1 1
3 3 3 3
2
2
2
2
2
2
2
2
2
2
2
2
0
0
0
0
0
0
0
0
0
0
0
0
3 3 3 3
3 3 3 3
Routing within a container
A B
40 * 1Gb 40 * 1Gb
10 Gb 10 Gb 64 Links10 Gb 10 Gb
A B
10 Gb 10 Gb 16 Links10 Gb 10 Gb
10 Gb 10 Gb10 Gb 10 Gb
16 Links (Two 2-link trunks)
Trunk A Trunk B
2 Type 2 Switches
8 Type 2 Switches
32 Type 1 Switches
1280 1 Gb/sec links to servers
Bandwidths
• Servers –> network: 82 Tb/sec
• Containers –> cube: 2.5 Tb/sec
• Average will be lower .
Objections to this scheme
• “Commodity hardware is cheaper”– This is commodity hardware. Even for one center (and we build
many).– And in the case of the network, it’s not cheaper. Large switches
command very large margins.• “Standards are better”
– Yes, but only if they do what you need, at acceptable cost.• “It requires too many different skills”
– Not as many as you might think.– And we would work with engineering/manufacturing partners
who would be the ultimate manufacturers. This model has worked before.
• “If this stuff is so great, why aren’t others doing it”?– They are.
Conclusion
• By treating data centers as systems, and doing full-system optimization, we can achieve:– Lower cost, both opex and capex.– Higher reliability.– Incremental scale-out.– More rapid innovation as technology
improves.
Questions?