ROLE OF CHEMISTRY IN POWER PLANT
FEB 24/2004
![Page 2: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/2.jpg)
CONTENTS OF THE PRESENTATION
FEB 24/2004
![Page 3: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/3.jpg)
Feed water treatment
FEB 24/2004
![Page 4: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/4.jpg)
Insoluble impurit ies Insoluble impurit ies are very largely metal oxides metal oxides derived from corrosion of the plant itself, par ticularly the materials of construction of the condenser and feed systems. Such corrosion is minimised by maintaining the feed water at an alkaline pH and by removing dissolved oxygen down to very low concentrations.
![Page 5: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/5.jpg)
Soluble impurities Soluble impurities in feed water most frequently arise from in leakage of cooling water from condensers and other coolers, but can also results from poor quality of make-up water .
![Page 6: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/6.jpg)
![Page 7: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/7.jpg)
Parameters 200 MW 500 MW
Boiler Pressure, Kg/cm2 150-170 185-195
pH at 25°C 8.8-9.0 9.0-9.2
ACC Cond. µm/cm, 0.2 0.2
Silica, ppb, (Max) 20 10
DO, ppb, (Max) 5.0 5.0
Res. N2H4, ppb 10-20 12-20
Total Fe, ppb, (Max.) 10 10
Total Cu, ppb, (Max.) 5 3
Ref: Code of Practice on Power Plant chemistry, by (OS) COS-ISO-00-OGN-OPS-CHEM/015, Oct.2003
![Page 8: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/8.jpg)
o Feed water pH- the use of volatile alkalis (NH 3
)
o By making the pH of feed water slightly alkaline (9.0-9.2) the corrosion rate of ferrous alloys can be minimised. Where the system is also contain copper based alloys similar benefits can be obtained
o Oxygen Controlo Physical de-aerationo Chemical de-aeration
![Page 9: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/9.jpg)
There is no excessive accumulation of alkali in the boiler water, the volati le alkali passing out the boiler with the steam.As condensate are formed in the lower pressure section of the turbine, in the condensers and on the steam side of the feed heaters, the alkali immediately available in these par ts of the steam/water system, raising the ph of the condensates and hence suppressing corrosion .Ammonia (NH 3) is the most widely used volatile alkali because of its low cost, ready available and its stabil ity at high temperatures
![Page 10: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/10.jpg)
![Page 11: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/11.jpg)
Physical de-aeration
De-aerator
40 ppb D.O. in Condensate Water
5 ppb D.O
Solubil ity Law & Henry Law
![Page 12: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/12.jpg)
Chemical de-aerationThe most widely used agent is Hydrazine (N 2H 4).
It is steam volatile, slightly basic and reacting readily to remove even traces of dissolve oxygen at temperature above 150 0C producing only volatile or gaseous products, i.e.,
NN 22 HH 44 + O + O 22 NN 22 + H + H 22 OO
At higher temperature hydrazine itself decomposes to produce ammonia and nitrogen, i.e.,
NN 22 HH 44 4NH4NH 33 + N + N 22
![Page 13: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/13.jpg)
It is assumed that the reduction of oxygen by hydrazine probably follows a heterogeneous reaction mechanism. It is common experience to find that two or four weeks elapse after initiating hydrazine treatment before a residual can be detected in the boiler water. This is because of following reactions
6 Fe 2O 3 + N 2H 4 N 2 + 2 H 2O + 4 Fe 3O 4
4 CuO + N 2H 4 N 2 + 2 H 2O + 4 Fe 3O 4
likely that the actual reduction of oxygen takes place in two steps involving the oxidation and reduction of oxides of iron.
4 Fe 3O 4 + O 2 6 Fe 2O 3
6 Fe 2O 3 + N 2H 4 4 Fe 3O 4 + N 2 + 2 H 2O
![Page 14: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/14.jpg)
To maintain boilers and turbines at a high level of availabil ity and ef f iciency, the chemical control of water and steam purity is aimed at the prevention of:1.Corrosion of feed, boiler and steam systems.2.Scale and deposit formation on heat transfer sur faces.3.Deposition and corrosion of turbines.
![Page 15: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/15.jpg)
Parameters 200 MW 500 MW
Boiler Pressure, Kg/cm2 150-170 185-195
pH at 25°C 9.2-9.5 9.1-9.4
Cond. µS/cm, (Max) 30 30
Silica, ppm, (Max) 0.2 0.1
Phosphate, ppm 2-4 1-2
Chloride, ppm, (Max.) 1.0 0.5
Ref: Code of Practice on Power Plant chemistry, by (OS) COS-ISO-00-OGN-OPS-CHEM/015, Oct.2003
![Page 16: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/16.jpg)
Trisodium phosphate (Na 3PO 4) and disodium phosphate (Na2HPO4) can both effectively produce alkalinity by hydrolysis in water:
Na 3PO 4 + H 2O Na 2HPO 4 + NaOH
Na 2HPO 4 + 2 H 2O NaH 2PO 4 + NaOHThe impor tant dif ference between this source of alkal inity and that produced by free caustic soda l ies in the reversibi l i ty of the above reactions. If acid species appear in the boiler water they wil l be neutral ised by the sodium hydroxide:
HCl + NaOH NaCl + H 2O
![Page 17: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/17.jpg)
Recommended parameters of Super heated Steam Purity GuidelinesParameters 200 MW 500 MW
pH at 25°C 8.8-9.0 9.0-9.2
ACC Cond. µm/cm, 0.2 0.2
Silica, ppb, (max) 20 10
Sodium, ppb, (max) 5.0 5.0
NH3, ppm, (max) 0.5 1.0
Total Fe, ppb, (max.) 10 10
Total Cu, ppb, (max.) 5 3
Ref: Code of Practice on Power Plant chemistry, by (OS) COS-ISO-00-OGN-OPS-CHEM/015, Oct.2003
![Page 18: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/18.jpg)
o Solubility of impurities in steam decreases as steam expands in turbine
o NaCl and NaOH most corrosive chemicals o Solubility of caustic exceeds 100 ppb at HP
turbine pressure and temp. o In LP turbine, caustic solubility in steam
decreases and deposit concentration goes up to 90%.
![Page 19: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/19.jpg)
![Page 20: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/20.jpg)
o 15 Conductivity analyserso 5-6 pH analyserso 1 multi -channel Sil ica analyser (@ 5
channels)o 1 Hydrazine analysero 2-3 D.O. analyserso 1-2 Sodium analyserso 1 Phosphate analyser + some more...
![Page 21: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/21.jpg)
CEP dischargeCEP dischargeDirect and af ter cation conductivity
measurements, supplemented by sodium monitoring, to provide warning of condenser leakage. Dissolved oxygen measurements are also required in order to establish the adequacy of oxygen removal at the condenser .
![Page 22: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/22.jpg)
Condensate Polishing Plant outletCondensate Polishing Plant outletConductivity, ACC, Reactive Sil ica, Na + in
outlet water are required to monitor the per formance of the plant and for need of resin bed regeneration. Additionally, the measurement of Chloride & sulphate in the outlet water has assumed increasing impor tance.
![Page 23: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/23.jpg)
De-aeratorDe-aerator
D.O. measurement at Inlet & Outlet of de-aerator.
For testing purposes it is necessary to have the facil ity to sample and monitor oxygen at both inlet and outlet of the de-aerator to insure satisfactory per formance.
![Page 24: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/24.jpg)
Final Feed WaterFinal Feed Water
Conductivity, ACC, D.O, pH, Na +, Cl -, SO - -4 &
Total Iron.
Comprehensive chemical monitoring of feed water just before it enters the boiler, to provide a f inal check on quality and acceptabil ity .
![Page 25: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/25.jpg)
Boiler WaterBoiler WaterConductivity, pH, Phosphate, Cl -, reactive
si l ica are required to conform the correct boiler water conditions are being maintained.
![Page 26: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/26.jpg)
Steam (SS & MS)Steam (SS & MS)Measurement of pH, reactive si l ica,
ammonia, sodium, conductivity to ensure that criteria based on the need to minimize salt deposition in the superheaters, reheaters and turbines are being met.
![Page 27: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/27.jpg)
A potential major source of ingress of impurity into the boiler water system is from leakage of cooling water into the main condenser steam space (because, steam space is maintained by vacuum) which is called condenser leakage
![Page 28: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/28.jpg)
o Online sodium increases (normal <2ppb).o Af ter Cation Conductivity increases
( normal value <0.2 µS/cm for 500MW plant)
o Total hardness of condensate wil l be high.o Boiler and condensate sil ica wil l go on
increasing and cannot be control led without CBD and/or CPU.
o Hot well makeup wil l be low as well as level wil l be high.
o De-aerator level wil l go high.
![Page 29: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/29.jpg)
1. Open CBD 100%, makeup wil l go high. (Heat as well as DM water loss)
2. Increase the concentration of phosphate and free alkalinity in boiler.
3. Limit as for as possible the boiler de-superheater spray water to prevent contamination of the system.
4. Isolate one path of condenser, and see the results and vice versa.
5. Put CPU into service if available.
![Page 30: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/30.jpg)
I f the leak is in minor in nature:If the leak is in minor in nature:o In running units, isolate one half the
condenser at a t ime and minor the chemical parameters and f ind out which half is leaking.
o Isolate the leaky half por tion.o Plug or repair the leak.o Normalise and comeback to full load.
![Page 31: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/31.jpg)
First is path detection Flood test Candle Test Dye test Foam Test Bubbler Method
![Page 32: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/32.jpg)
Parameters 200 MW 500 MW
pH at 25°C 8.8-9.0 9.0-9.2
ACC Cond. µm/cm, 0.3 0.2
Silica, ppb, (max) 20 10
DO, ppb, (max) 40 40
NH3, ppm, (max) 0.5 1.0
Total Fe, ppb, (max.) 10 10
Total Cu, ppb, (max.) 5 3
Sodium, ppb, max - 5
Ref: Code of Practice on Power Plant chemistry, by (OS) COS-ISO-00-OGN-OPS-CHEM/015, Oct.2003
![Page 33: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/33.jpg)
Condensate polishing is employed to purify the return steam condensate in order to meet the quality requirements of high pressure thermal cycles and minimize consumption of make-up water.
![Page 34: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/34.jpg)
Improvement in the quality of condensate and "cycle" clean up
Reduced blow down & make up requirements
Improvement in boiler water quality for drum type boilers
Quick star t up and as a result, ful l load conditions are reached early giving economics
![Page 35: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/35.jpg)
![Page 36: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/36.jpg)
S.NO. PARAMETER CONTROL LIMITS FREQUENCY OF TESTING
WITHOUTALKALIZER
WITHALKALIZER
1. Conductivity at
25oC, µS/cm
<1.5(preferably below 0.5)
<2.2 Continuous
2. Dissolved oxygen,
µg/l
<100 <10 Continuous
3. Total copper, µg/l <20 <20 Once in 2-months
4. Total iron, µg/l <20 <20 Once in 2-months
5. pH at 25oC 6.0-8.0 8.5-9.0 Once in 2-months
![Page 37: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/37.jpg)
Conductivity is the basic criteria of quality for the stator cooling water and a low level must be maintained to el iminate the possibi l i ty of f lashover. Dissolved oxygen in stator water is the main reason for corrosion. Dissolved oxygen in stator cooling water is generally removed by purging with nitrogen gas of high purity (99.99%, min.) . Removal of dissolved oxygen depends on the nitrogen pressure which is normally maintained at 0.2 kg/cm 2 with alarm for nitrogen pressure in primary water tank set at 0.4 kg/cm 2 for better ef f iciency.
![Page 38: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/38.jpg)
![Page 39: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/39.jpg)
A bypass ion exchange polishing plant is commonly installed to control the conductivity of the stator water and can also trap some of the suspended matter in water.
Polishing plant is generally designed to treat about 2-5% of total stator water f low. The polisher contains a bed of mixed resins consisting of strong cation resin in h-form and strong anion resin in oh-form. Analysis of the exhausted resin can be used to know how much corrosion products are removed by the mixed bed.
![Page 40: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/40.jpg)
![Page 41: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/41.jpg)
![Page 42: POWER PLANT CHEMISTRY](https://reader033.vdocuments.site/reader033/viewer/2022042504/55a6b33b1a28ab52218b45a7/html5/thumbnails/42.jpg)