polypipe terrain firetrap sleeve and fire collar · 2019. 12. 18. · terrain product information...

5
Photo/isometric drawing provided by manufacturer Photo/isometric drawing provided by manufacturer Polypipe Terrain Firetrap Sleeve and Fire Collar Description of Product This is an assessment of Terrain Firetrap, Fire protection for above ground drainage systems. The sleeve can be quickly and simply fitted onto the pipe and slid into the penetration ensuring that there are no air gaps around the sleeves by filling with mortar or mastic. In a fire situation the sleeve expands to fill the available space (15mm max) between the pipe and the penetration and will crush and close off plastic drainage pipes. The pipe forms a solid char preventing the passage of fire and smoke to the adjacent compartment. Terrain Firetrap Collars have been specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by services such as Terrain Fuze or Terrain Acoustic dB12. Key Factors Assessed Safety in case of Fire Health, Hygiene and Environmental Safety in Use Validity This certificate was first issued on 3 rd November 2011 and is valid until 1 st November 2021 Issue Dated 21 st November 2018 Certificate No: EW96

Upload: others

Post on 04-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • Photo/isometric drawing

    provided by manufacturer Photo/isometric drawing

    provided by manufacturer

    Polypipe Terrain Firetrap Sleeve and Fire Collar

    Description of Product

    This is an assessment of Terrain Firetrap, Fire

    protection for above ground drainage systems.

    The sleeve can be quickly and simply fitted

    onto the pipe and slid into the penetration

    ensuring that there are no air gaps around the

    sleeves by filling with mortar or mastic. In a

    fire situation the sleeve expands to fill the

    available space (15mm max) between the pipe

    and the penetration and will crush and close

    off plastic drainage pipes. The pipe forms a

    solid char preventing the passage of fire and

    smoke to the adjacent compartment.

    Terrain Firetrap Collars have been specifically

    designed to re-instate the fire resistance of a

    wall or floor which has been penetrated by

    services such as Terrain Fuze or Terrain Acoustic dB12.

    Key Factors Assessed

    Safety in case of Fire

    Health, Hygiene and Environmental

    Safety in Use

    Validity

    This certificate was first issued on 3rd November 2011 and is valid until 1st November 2021

    Issue Dated 21st November 2018

    Certificate No: EW96

  • The Terrain Firetrap range comprises:

    Terrain Firetrap Sleeves

    • Ideal for Terrain Fuze stacks

    • Up to 4 hour fire protection

    • Quick to install in new build and retro-fit

    • Protects compartment above and below slab

    Terrain Firetrap Collars

    • Suitable for all Terrain drainage systems

    • Can be surface mounted or built in

    • Up to 4 hour fire protection

    In addition, independent testing has been carried out on both Firetrap Sleeves and Firetrap Collars in typical floor installations.

    These test results form the basis of the Terrain Firetrap Product Selector.

    Terrain Firetrap Collars (for PVC soil and waste) have been specifically designed to re-instate the fire resistance of a wall or floor

    which has been penetrated by services such as plastic pipe systems used in soil & waste. The collars will seal pipes from 50mm

    to 160mm diameter and can be face fixed or set-in to a wall or ceiling structure. They are suitable for use on concrete, masonry

    and plasterboard partitions. The collars will seal pipes from 50mm to 315mm diameter and can be face fixed or set-in to a wall

    or ceiling structure. They are suitable for use on concrete, masonry and plasterboard partitions. They have a 2 hour or 4 hour

    fire rating and feature adjustable mounting tabs for quick and easy installation.

    Complies with Building Regulations Part B3. Up to 4 hours resistance for HDPE and UPVC pipe up to 160mm dia. passing

    through masonry or concrete penetrations. Fire Collar achieves 2 Hour fire rating (up to 160mm) and 4 Hour fire rating (200mm

    to 315mm).

    Seal the gap between the hole and the pipe. If a wide gap exists, the space must be sealed using fire-proof mortar or

    alternatively, an intumescent sealing agent.

    To protect against the spread of smoke and gas within the first few minutes the remaining gap between the plastic pipe and the

    opening must be sealed on one side of the wall using an appropriate sealing agent.

    The anchoring hooks can be applied to various points of the collar’s metal structure, enabling the anchoring points to be

    positioned in line with the space available. To ensure optimum performance, the hooks must be placed as symmetrically as

    possible.

    Ensure the collar is positioned correctly to enable the anchoring hooks to be fixed.

    The fire collar must be installed flush with the lower surface when installed at ceiling level. Insert one collar on each side in the

    case of a wall installation, if a gap remains around the installed collar, this must be filled with mortar.

  • LABC consider that, Polypipe Terrain Firetrap Sleeve and Fire Collar, will meet the functional

    requirements of the Building Regulations (listed below) if the criteria detailed in this certificate are met;

    The Building Regulations 2010 (as amended) England & Wales

    Regulation 7 Materials and workmanship

    Note: The products are acceptable.

    AD B Fire Safety

    Note: Subject to limitations detailed within the Scope section.

    AD H Drainage and Waste Disposal

    Note: Subject to limitations detailed within the Scope section.

    The Building Regulations 2010 (as amended) England

    None presently

    The Building Regulations 2010 (as amended) Wales

    None presently

    The Building (Scotland) Regulations 2004 (as amended)

    If you would like to discuss a specific use of the product in Scotland it will require an additional

    assessment under the Scottish Building Regulations and accordingly you should contact the LABSS

    STAS Administrator at www.labss.org

    http://www.labss.org/

  • LABC Warranty

    The use of the Polypipe Terrain Firetrap Sleeve and Fire Collar has not been assessed to meet the

    requirements of the LABC Warranty Technical Manual. If you would like to discuss a specific use

    please make an enquiry to [email protected]

    Terrain Product Information PT23 HDPE installation and fire protection in fire rated duct,

    Terrain Product Information PT24 HDPE installation and fire protection in fire rated duct,

    Terrain Firetrap Installation Guidance document

    IF09065 Rev A Chiltern Fire 110mm Olympic setup Report

    IF09092 Chiltern Fire 116mm Olympic setup Report

    Terrain Firetrap Sleeves are fire tested in accordance with BS 476: Part 20: 1987, BS EN 1366-3.

    Constructions covered - Plasterboard partition and solid walls and floors.

    Firetrap Sleeves were acoustically tested in a plasterboard partition system under UKAS conditions in accordance with BS EN

    ISO 140-3:1995 and BS EN ISO 717-1:1997 to be fixed.

    Firetrap Collars for Terrain Fuze and Terrain Acoustic dB12 are tested in accordance with BS 476 Part 20 and Warres Test

    Reports: Nos. 62293/A, 62293/B, 62293/C, 60300/A,

    60300 /B, C 81542, 69750/A, 69751/B, 69752, 69853.

    Terrain PVC collars are fire tested in accordance with BS 476: Part 22: 1987, BS EN1366-4 and other international standards.

    mailto:[email protected]

  • Polypipe Terrain

    New Hythe Business Park

    College Road

    Aylesford

    Kent

    ME20 7PJ

    Tel: 01622 795200

    Email: [email protected]