PROPOSED FACTORY DEVELOPMENT FOR POKKA AT MINGALADON, YANGON, MYANMAR
SCHEDULE OF MECHANICAL FAN
UNIT
LOCATION
EST. ELECT.
POWER
(EACH)
STOREY (Kw)
GROUND STOREY
1 FAF/GF-1 GF B10 CIL ENGINEERING WORKSHOP 165 1 80 0.25 1 N ROSEMBERG
2 FAF/GF-2 GF A8 WALL MOUNTED WORKSHOP1 36 1 50 0.03 1 N ROSEMBERG C/W CHECK DAMPER
3 FAF/GF-3 GF A8 WALL MOUNTED WORKSHOP2 36 1 50 0.03 1 N ROSEMBERG C/W CHECK DAMPER
4 FAF/GF-4 GF A8 CIL ENGINEER & PRODUCTION OFFICE 115 1 80 0.25 1 N ROSEMBERG
5 FAF/GF-5 GF B5 CIL LAB 245 1 80 0.25 1 N ROSEMBERG
6 FAF/GF-6 GF A6 WALL MOUNTED MICRO BIO LAB 40 1 50 0.03 1 N ROSEMBERG C/W CHECK DAMPER
7 FAF/GF-7 GF A7 WALL MOUNTED FUME TEST 40 1 50 0.03 1 N ROSEMBERG C/W CHECK DAMPER
8 FAF/GF-8 GF A7 WALL MOUNTED LAB OFFICE 40 1 50 0.03 1 N ROSEMBERG C/W CHECK DAMPER
9 FAF/GF-9 GF F2 ROOF VENTILATOR SYRUP ROOM A 295 1 100 0.20 1 N ROSEMBERG
10 FAF/GF-10 GF D2 ROOF VENTILATOR SYRUP ROOM B 295 1 100 0.20 1 N ROSEMBERG
11 FAF/GF-11 GF F5 ROOF VENTILATOR CHANGING ROOM 46 1 100 0.10 1 N ROSEMBERG
12 EAF/GF-1 GF WALL MOUNTED MALE DRIVER TOILET 750 1 0.06 1 N ROSEMBERG C/W CHECK DAMPER
13 EAF/GF-2 GF WALL MOUNTED FEMALE DRIVER TOILET 480 1 0.05 1 N ROSEMBERG C/W CHECK DAMPER
14 EAF/GF-3 GF WALL MOUNTED MALE TEMPORARY TOILET 375 1 0.05 1 N ROSEMBERG C/W CHECK DAMPER
15 EAF/GF-4 GF WALL MOUNTED FEMALE TEMPORARY TOILET 375 1 0.05 1 N ROSEMBERG C/W CHECK DAMPER
FIRST FLOOR PLAN
16 FAF/L1-1 L1 B10 WALL MOUNTED ENGINEERING WORKSHOP STORE 109 1 50 0.05 1 N ROSEMBERG C/W CHECK DAMPER
17 FAF/L1-2 L1 B9 WALL MOUNTED ONE YEAR SUPPLY STORE 114 1 50 0.05 1 N ROSEMBERG C/W CHECK DAMPER
18 FAF/L1-3 L1 B5 WALL MOUNTED OPEN OFFICE 750 1 50 0.05 1 N ROSEMBERG C/W CHECK DAMPER
19 EAF/L1-1 L1 A7 AXIAL TOILET 2100 1 100 1 3 N ROSEMBERGInterlock with lighting
switch
QTYEST. EXT. S.P.
(Pa) EACHPHASE
NORMAL/
E-SUPPLYSPECIFIED BRAND REMARKSUNIT DESIGNATION SN.
AREA SERVED
GUIDELINE REFRENCEFAN TYPE ROOM NAME
FRESH/EXHAUST AIR
(CMH) EACH