PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions nVent.com DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit designed for use with RAYCHEM BTV-MCT, QTVR-MCT and XTV-MCT industrial parallel monitor wire heating cables. This kit may be installed at temperatures as low as –40°F (–40°C). For easier installation store above freezing until just before installation. For technical support call nVent at (800) 545-6258. TOOLS REQUIRED • Wire strippers • Heat gun or propane torch • Diagonal cutters • Utility knife • Needle-nose pliers Flatblade screwdrivers, 1/8 & 1/4 inch ADDITIONAL MATERIALS REQUIRED 1 Grommet (see selection chart on page 2) • 1 Pipe strap (order separately) • Glass cloth tape - GT-66 Installation temperature above 40°F (4°C) - GS-54 Installation temperature above -40°F (-40°C) This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications, and national electrical codes, ground- fault equipment protection must be used. Arcing may not be stopped conventional circuit breakers. Approvals and performance are based on the use of nVent- specified parts only. Do not use substitute parts or vinyl electrical tape. The black heating cable core and fibers are conductive and can short. They must be properly insulated and kept dry. Connection kits and heating cable ends must be kept dry before and during installation. Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core. Use only fire-resistant insulation materials, such as fiberglass wrap or flame-retardant foam. Heat damaged components can short. Use a heat gun or torch with a soft, yellow, low-heat flame. Keep the flame moving to avoid overheating, blistering, or charring the heat- shrinkable tubes. Avoid heating other components. Replace any damaged parts. HEALTH HAZARD: Over heating heat-shrinkable tubes will produce fumes that may cause irritation. Use adequate ventilation and avoid charring or burning. Consult MSDS RAY3122 for further information. CHEMTREC 24-hour emergency telephone: (800) 424-9300 Non-emergency health and safety information: (800) 545-6258 WARNING: CAUTION: KIT CONTENTS Item Qty Description A 1 Junction box lid B 1 Junction box C 1 4-pole terminal block D 2 Black heat-shrinkable tubes E 1 Green/yellow heat-shrinkable tube F 1 Clear yellow heat-shrinkable tube G 1 Locknut H 1 Sealing ring I 1 Top (3/4 inch NPS thread) J 1 Base D E F G H I J A B C APPROVALS Class I, Div. 2, Groups B, C, D Class II, Div. 2, Groups F, G Class III Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G Class III Hazardous Locations -ws

Upload: others

Post on 19-Jan-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PMK-JLP-M - nVent...PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions ent.com om C DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit

PMK-JLP-MMonitor Wire Power Connection Kit Installation Instructions

nVent.com

nVent.com nVent.com LLC

DESCRIPTIONThe nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit designed for use with RAYCHEM BTV-MCT, QTVR-MCT and XTV-MCT industrial parallel monitor wire heating cables. This kit may be installed at temperatures as low as –40°F (–40°C). For easier installation store above freezing until just before installation.For technical support call nVent at (800) 545-6258.

TOOLS REQUIRED• Wire strippers • Heat gun or propane torch• Diagonal cutters • Utility knife• Needle-nose pliers• Flatblade screwdrivers, 1/8 & 1/4 inch

ADDITIONAL MATERIALS REQUIRED• 1 Grommet (see selection chart on page 2)• 1 Pipe strap (order separately)• Glass cloth tape

- GT-66 Installation temperature above 40°F (4°C) - GS-54 Installation temperature above -40°F (-40°C)

This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions.• To minimize the danger of fire from sustained electrical

arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications, and national electrical codes, ground-fault equipment protection must be used. Arcing may not be stopped conventional circuit breakers.

• Approvals and performance are based on the use of nVent-specified parts only. Do not use substitute parts or vinyl electrical tape.

• The black heating cable core and fibers are conductive and can short. They must be properly insulated and kept dry.

• Connection kits and heating cable ends must be kept dry before and during installation.

• Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core.

• Use only fire-resistant insulation materials, such as fiberglass wrap or flame-retardant foam.

• Heat damaged components can short. Use a heat gun or torch with a soft, yellow, low-heat flame. Keep the flame moving to avoid overheating, blistering, or charring the heat-shrinkable tubes. Avoid heating other components. Replace any damaged parts.

HEALTH HAZARD: Over heating heat-shrinkable tubes will produce fumes that may cause irritation. Use adequate ventilation and avoid charring or burning. Consult MSDS RAY3122 for further information.CHEMTREC 24-hour emergency telephone: (800) 424-9300Non-emergency health and safety information: (800) 545-6258

WARNING: CAUTION:

KIT CONTENTS

Item Qty DescriptionA 1 Junction box lidB 1 Junction boxC 1 4-pole terminal blockD 2 Black heat-shrinkable tubesE 1 Green/yellow heat-shrinkable tubeF 1 Clear yellow heat-shrinkable tubeG 1 LocknutH 1 Sealing ringI 1 Top (3/4 inch NPS thread)J 1 Base

D

E

F

G

H

I

J

A

B

C

nVent.com

nVent.com LLC

APPROVALS

Class I, Div. 2, Groups B, C, DClass II, Div. 2, Groups F, GClass III

Class I, Div. 2, Groups A, B, C, DClass II, Div. 2, Groups F, GClass III

Hazardous Locations

-ws

Page 2: PMK-JLP-M - nVent...PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions ent.com om C DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit

2 | nVent.com

Inner jacket

Braid

Outer jacket

Plastic wrap

SpacerConductive fiber

XTV-MCTBus wire

BTV-MCT, QTVR-MCTBus wire

Conductive core

Inner jacket

Braid

Outer jacket Monitor

wireMonitor wire

IDENTIFY HEATING CABLE TYPE

1

Heating cable Grommet3BTV1-MCT N3BTV2-MCT N5BTV1-MCT N5BTV2-MCT N10BTV1-MCT F10BTV2-MCT F10QTVR1-MCT G10QTVR2-MCT G20QTVR1-MCT F20QTVR2-MCT F

Heating cable Grommet5XTV1-MCT-T3 N5XTV2-MCT-T3 N10XTV1-MCT-T3 N10XTV2-MCT-T3 N15XTV1-MCT-T2 N15XTV2-MCT-T3 N20XTV1-MCT-T2 N20XTV2-MCT-T2 N

• Determine correct grommet (order separately) from chart below.

WARNING: Use of the wrong grommet can result in leaks, cracked components, shock or fire, and will invalidate approvals and certifications.

18 in(46 cm)

2

• Allow approximately 18 in (46 cm) of heating cable for installation.

3

• Slide parts onto heating cable.

7 1/2 in(190 mm)

4

• Lightly score outer jacket.

• Bend heating cable to break jacket at score, then peel off jacket.

WARNING: Do not cut through braid into inner jacket. This could result in a short circuit.

Page 3: PMK-JLP-M - nVent...PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions ent.com om C DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit

nVent.com | 3

7

For XTV-MCT Only:• Remove plastic wrap.

5

• Push braid back toward outer jacket to create a pucker.

• At pucker, open braid using screwdriver.

9 1/2 in(241 mm)

Monitor wire

• Lightly score partially around inner jacket as shown. Do not score jacket over monitor wire.

WARNING: Damaged monitor wire insulation can cause a short. Do not score inner jacket next to the monitor wire.

• Bend heating cable to break jacket at score, then peel off jacket. Use diagonal cutters to remove remaining jacket next to monitor wire.

9A  BTV-MCT AND QTVR-MCT

Go to Page 4, Step 9B

Go to Step 9ABTV-MCT, QTVR-MCT

XTV-MCT

8

6

• Bend heating cable and work it through opening in braid.

• Determine heating cable type and continue as shown.

1/4 in(6 mm)

• Notch core.

• Peel bus wire from core.

10A  BTV-MCT AND QTVR-MCT

Page 4: PMK-JLP-M - nVent...PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions ent.com om C DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit

4 | nVent.com

6 1/2 in(165 mm)

WARNING: Do not cut or damage bus wires. Damaged bus wires can overheat or short.

9B  XTV-MCT

• Cut and remove fiber strands.

10B  XTV-MCT

Go to Step 12

11A  BTV-MCT AND QTVR-MCT

• Score core between bus wires and inner jacket.

• Bend and snap core.

• Peel core from bus wires and remove any remaining material from bus wires.

• Lightly score around inner jacket as shown. Be careful not to cut monitor wire insulation.

11B  XTV-MCT

1/2 in(13 mm)

12

• Remove insulation from end of monitor wire. Do not cut wire strands.

• Score and remove center spacer.• Remove any remaining fiber

material from bus wires.

• Bend heating cable to break jacket at score, then peel off jacket.

Page 5: PMK-JLP-M - nVent...PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions ent.com om C DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit

nVent.com | 5

15

1 in(25 mm)

16

• Seat grommet and position parts so that 1 in. (25 mm) of heating cable outer jacket extends past top of threads.

• Tighten screws.

Pipe strap

17

• Fasten base to pipe with strap.

• Loop and tape extra heating cable to pipe.

• Install sealing ring.

18

• Install box with locknut.

Instructions for Using a Heat Gun or Torch:• Read important warnings on Page 1 and follow safety

precautions provided with heat gun or torch.• When using a torch use a soft yellow, low-heat flame. Apply

just enough heat to do the job.• Keep torch or heat gun moving continuously to distribute the

heat evenly to avoid overheating, blistering or charring the heating cable and heat-shrinkable tubes.

• Replace any heat-damaged parts.

13

• Slide two black tubes onto bus wires and green/yellow tube onto braid. 1/2 in

(13 mm)

14

• Center clear yellow tube over end of base jacket.• Heat tube until it shrinks and adhesive flows out ends.

While still hot, pinch between wires and hold for 5 seconds.

• Use a heat gun or propane torch to heat tubes until they are fully recovered.

Note: See Step 15 for proper heating techniques.

Page 6: PMK-JLP-M - nVent...PMK-JLP-M Monitor Wire Power Connection Kit Installation Instructions ent.com om C DESCRIPTION The nVent RAYCHEM PMK-JLP-M is a Type 4X-rated power connection kit

120/277 Vac shown

Signal light or othermonitoring device.

Terminal block

Ø

NGround

End seal connectionfor -MCT heating cable

Braid

Monitor wire

Heating cable bus wires

• Connect wires to terminal block.

19

Weather seal

Insulation

Use a conduit drainto prevent condensation and water build-up

nVent.com

nVent.com LLC

nVent.com nVent.com LLC

nVent.com

20

• Install lid.• Apply insulation and cladding.• Weather-seal the stand entry.• Leave these installation instructions with the end user for

future reference.

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

Raychem-IM-H54055-PMKJLPM-EN-1805