plant hvac systems

91
Facilities Management Utilities & Engineering Services Duk e PLANT HVAC SYSTEMS DU-109-PP

Upload: latham

Post on 01-Feb-2016

82 views

Category:

Documents


2 download

DESCRIPTION

PLANT HVAC SYSTEMS. DU-109-PP. PLANT HVAC SYSTEMS. PURPOSE The purpose of the Operations and Maintenance Training Program is to train Operations and Maintenance Technicians in the operation of the Duke University Plant Heating, Ventilation, and Air Conditioning (HVAC) Systems. OBJECTIVES - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

DU-109-PP

Page 2: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

PURPOSE The purpose of the Operations and Maintenance Training Program

is to train Operations and Maintenance Technicians in the operation of the Duke University Plant Heating, Ventilation, and Air Conditioning (HVAC) Systems.

OBJECTIVES Trainees will demonstrate knowledge of

– HVAC System Components– HVAC System Components Operation– HVAC System Configuration– HVAC System Controls and Instrumentation

Page 3: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

PURPOSE The purpose of the Heating, Ventilation, and Air Conditioning

(HVAC) System is to:– Provide heat and cooling climate control for plant, office/control

room, and electrical room areas of the steam and chiller plants– Maintain Interior Air Quality (IAQ)– Maintain air pressure– Provide emergency exhaust

Page 4: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

HVAC AIR FUNCTIONS To understand how HVAC works, you need to be familiar with the

six functions of HVAC air.Return Air

– Air inside the building drawn back into the air handlersOutside Air

– Fresh air drawn into the air handlers from outsideSupply Air

– Air blown into the building from the air handlers

Page 5: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

HVAC AIR FUNCTIONSMakeup Air

– Air blown into the building by Makeup Air Unites (MAUs) to maintain air pressure balance when pressure is low

Relief Air– Air exhausted from the building to maintain air pressure balance

when air pressure is highExhaust Air

– Air expelled to remove contaminants from areas where chemicals, hazardous materials, and toxic gases are present

– Air exhausted from the building in case of emergency

Page 6: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

WHY AIR BALANCE IS IMPORTANTOver Pressure and Under Pressure conditions negatively affect

building efficiency. Over Pressure

– When air pressure inside a building is higher than pressure outside, the conditioned air inside the building is pushed outside.

– High air pressure can require excess energy to condition the air in the building and compensate for energy lost.

Page 7: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

WHY IS AIR BALANCE IMPORTANT?Under Pressure

– When building pressure is lower than pressure outside, the air outside is drawn inside.

– Outside air may come from undesirable sources (trash bins, open doors, cracks, construction, and so forth).

– Unfiltered or unconditioned air can affect the HVAC system’s ability to maintain the desired environment.

Page 8: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat does IAQ stand for?

– International Air Quality– Industrial Air Quality– Interior Air Quality– In-duct Air Quality

Page 9: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWER IAQ stands for Interior Air Quality.

Page 10: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat kind of air is blown into building from air handlers?

– Return Air– Outside Air– Makeup Air– Supply Air

Page 11: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERSupply Air is recirculated through the air handlers.

Page 12: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat kind of air is added when air pressure is low?

– Return Air– Outside Air– Makeup Air– Supply Air

Page 13: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERMakeup Air is blown into a building when air pressure is

low.

Page 14: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat causes Over Pressure?

– Pressure is higher on the lower level than on the mezzanine– Pressure is lower in the building than outside– Pressure is higher in the building than outside– Pressure is lower on the lower level than on the mezzanine

Page 15: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWEROver Pressure is the condition when pressure inside the

building is higher than outside.

Page 16: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat causes Under Pressure?

– Pressure is higher on the lower level than on the mezzanine– Pressure is lower in the building than outside– Pressure is higher in the building than outside– Pressure is lower on the lower level than on the mezzanine

Page 17: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERUnder Pressure is the condition when pressure inside

the building is lower than outside.

Page 18: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

PLANT HVAC COMPONENTS Air Handler Units (AHUs) Makeup Air Units (MAUs) Fan Coil Units (FCUs) Exhaust fans Supply fans Emergency exhaust fans

Page 19: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

AHU COMPONENTSThe Mixing Box section contains:

– Return Air Damper which connects to the Return Air Duct• The Relief Air Damper also connects to the Return Air Duct

– Outside Air Damper which connects to the duct to the building exterior

RETURN AIRDAMPER

OUTSIDE AIRDAMPER

RELIEF AIRDAMPER

MIXING BOX

Page 20: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

AHU COMPONENTSThe Filter section contains:

– Access door for filter element replacement– W.C. Meter mounted in door

• Filter is replaced when air pressure reaches maximum resistance

FILTER MIXING BOX

RETURN AIR

RELIEF AIR

OUTSIDE AIR

W.C. METER

Page 21: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

AHU COMPONENTSThe Cooling Coil section contains:

– In and Out connections for chilled water– Cooling coil heat exchanger

MIXING BOXFILTERCOOLINGCOIL

RETURN AIR

RELIEF AIR

OUTSIDE AIR

Page 22: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

AHU COMPONENTSThe Heating Coil section contains:

– In and Out connections for steam– Heating coil heat exchanger

FILTER

COOLINGCOIL

HEATINGCOIL

MIXING BOX

RETURN AIR

RELIEF AIR

OUTSIDE AIR

Page 23: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

AHU COMPONENTSThe Fan section contains:

– Fan and motor– Starter Box mounted on

exterior or nearby

FILTERCOOLINGCOIL

HEATINGCOIL

MIXING BOX

RETURN AIR

OUTSIDE AIR

Page 24: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat is accomplished in the AHU mixing box?

– Return air is mixed with relief air– Supply air is mixed with return air– Supply air is mixed with outside air– Return air is mixed with outside air

Page 25: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERReturn air is mixed with outside air in the AHU mixing box.

Page 26: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat kind of meter is mounted in the filter section door of an

AHU?– Temperature sensor– Pressure gauge– W.C. meter– Anemometer

Page 27: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERA W.C. meter is mounted in the door of the filter section. The

W.C. (Water Column) meter measures resistance through the filter in inches to indicate when the filter needs to be changed.

Page 28: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhere is the starter box located for an AHU?

– Exterior of the fan section or nearby– Mixing box– Control Room– AHUs do not need starters

Page 29: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERThe starter box is mounted on the fan section of the AHU or

nearby.

Page 30: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

MAU COMPONENTSThe Fan section contains:

– Fan and motor– Outside Air Damper which connects to the duct to the building

exterior

OUTSIDE AIRDAMPER

FAN

Page 31: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

MAU COMPONENTSThe Coil section contains:

– In and Out connections for steam and chilled water

– Heating and cooling coil heat exchangers

COOLINGCOIL

HEATINGCOIL

OUTSIDE AIRDAMPER

FAN

Page 32: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

MAU COMPONENTSThe Filter section contains:

– Filters– Supply Air Damper

COOLINGCOIL

HEATINGCOIL

OUTSIDE AIRDAMPER

FAN

FILTER

SUPPLY AIRDAMPER

Page 33: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

MAU COMPONENTSThe Starter box is located next to the MAU.

Page 34: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat is one way an MAU differs from an AHU?

– The MAU takes in return air and outside air– The MAU takes in relief air only– The MAU takes in outside air only– The MAU takes in return air only

Page 35: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERThe MAU takes in outside air only.

Page 36: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat does MAU stand for?

– Main Air Unit– Maximum Air Unit– Mini Air Unit– Makeup Air Unit

Page 37: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERMAU stands for Makeup Air Unit.

Page 38: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat is another way an MAU differs from an AHU?

– The MAU has a mixing box– The MAU does not have a mixing box– The MAU has a cooling coil– The AHU has a cooling coil

Page 39: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERThe MAU does not have a mixing box.

Page 40: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

FCU COMPONENTSOutside Air DamperElectric Duct Heater

SUPPLY AIR

OUTSIDE AIR DAMPER

RETURN AIR

ELECTRIC DUCT HEATER

Page 41: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

FCU COMPONENTSFilterCooling CoilFan and Motor

COOLING COIL

FAN

FILTER

Page 42: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat does the FCU use to heat supply air?

– Steam – Hot water– Electricity– Friction

Page 43: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERThe FCU uses an Electric Duct Heater to heat air in the supply

air duct.

Page 44: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat does FCU stand for?

– Forced Cooling Unit– Facilities Control Unit– Furnace Coil Unit– Fan Coil Unit

Page 45: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERFCU stands for Fan Coil Unit.

Page 46: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

PLANT HVAC SYSTEMS CONFIGURATION AND PROCESS FLOWThe flow for Chiller Plant #2 is used as an example.

Page 47: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Temperature Transmitters on the Return Air Duct, Supply Air Duct,

and Mixing Box of AHU-21 send readings to the Local Controller Digital Control System (DCS).

LOCAL CONTROLLER DCS

RETURN AIR DUCT

SUPPLY AIR DUCTMIXING BOX

AHU-21

Page 48: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM The local DCS controls heating and cooling by modulating the

Cooling Coil chilled water control valve and the steam valve supplying the Heating Coil.

LOCAL CONTROLLER DCS

MIXING BOX

CHILLED WATER CONTROL VALVESTEAM VALVE

COOLING COIL

HEATING COIL

Page 49: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM The Outside Air Damper is set at 2,000 CFM. The Return Air Damper is set at 30,000 CFM.

MIXING BOX OUTSIDE AIR DAMPERD-21F

SUPPLY AIR DAMPERD-21E

AHU-21

Page 50: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM 1,000 CFM exhausted continuously from Chemical Treatment area

by Exhaust Fan EF-23. 350 CFM exhausted continuously from the Break Room, Men’s and

Women’s Restrooms, Shower, and Janitor’s Closet by Exhaust Fan EF-24.

BREAK ROOM

WOMEN’S RESTROOM

MEN’S RESTROOM

JANITOR’S CLOSET

SHOWER

EXHAUST FANEF-24

EXHAUST TO OUTSIDE

LOUVER L-28

Page 51: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Supply Fans SF-21 and SF-22 run continuously to recirculate air

within the plant.

SUPPLY FAN SF-21

SUPPLY FAN SF-22

EF-24

AHU-21

Page 52: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Economizer Operation

Based on outside air enthalpy and outside air temperature, when less than 60°F AHU-21 operates in economizer cycle modulating the outside and return air dampers to maintain 60°F supply air temperature.

LOCAL CONTROLLER DCS

RETURN AIR DAMPER

OUTSIDE AIR DAMPER

Page 53: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Economizer Operation

The chilled water valve to AHU-21 is closed during economizer cycle. In the event of damper failure or mixed air temperature below 35°F, a

freezestat shuts down AHU-21 and sends an alarm.

LOCAL CONTROLLER DCS

FREEZESTAT

CHILLED WATER VALVE

Page 54: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

RELIEF DAMPER RD-21

PRESSURE SENSOR A7AT 0.05” W.C.

AHU-21

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Economizer Operation

Relief Air Damper RD-21 is controlled by differential pressure to maintain a 0.05 inch W.C. positive pressure in the building by modulating the damper.

Page 55: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Emergency Exhaust

During emergency when refrigerant accumulates above 100 PPM due to leak or rupture, air recirculation dampers to Exhaust Fans EF-21 and EF-22 close and exhaust dampers open forcing the refrigerant from the building.

NORTH EMERGENCY

EXHAUST EF-21

SOUTH EMERGENCY

EXHAUST EF-22

EMERGENCY EXHAUST DAMPER

L-26

EMERGENCY EXHAUST DAMPER

L-25

Page 56: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Emergency Exhaust

Supply Fans SF-21 and SF-22 shut down.The outside air damper to AHU-21 opens fully and the return air

damper closes.Additional outside air (30,000 CFM) brought into the building from

AHU-21 is exhausted through Positive Relief Damper RD-1.When the refrigerant detectors no longer sense a low refrigeration

concentration of 100 PPM, exhaust air dampers to EF-21 and 22 close and the air recirculation dampers open. SF-21 and 22 then energize and AHU-21 returns to a modulating damper cycle.

Page 57: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-21 SYSTEM Emergency Exhaust

If an emergency occurs when the supply air temperature is less than 60°F, a temperature sensor opens steam valve TCV-AHU-21B to maintain a supply air temperature of 60°F.

Page 58: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONBased on outside air enthalpy and outside air temperature,

what is the lowest temperature at which AHU-21 will operate before entering the economizer cycle?– 80°F– 40°F

– 60°F

– 72°F

Page 59: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERBased on outside air enthalpy and outside air temperature,

when less than 60°F AHU-21 operates in economizer cycle.

Page 60: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhen do Supply Fans SF-21 and SF-22 run?

– Only when building pressure is low– Continuously– Only when building pressure is high– Only at night

Page 61: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERSupply Fans SF-21 and SF-22 run continuously to recirculate

air within the plant.

Page 62: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhere do the temperature transmitters on the ducts and

mixing box on AHU-21 send readings?– Local Controller DCS– AHU-22– Directly to the Control Room– Chiller Plant #1

Page 63: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERTemperature Transmitters on the Return Air Duct, Supply Air

Duct, and Mixing Box of AHU-21 send readings to the Local Controller Digital Control System (DCS).

Page 64: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-22 SYSTEM AHU-22 supplies 10,000 CFM of cooling to the Electric Room. The local DCS modulates the cooling coil chilled water valve in response to

temperature sensors in the supply and return air ducts and mixing box.

LOCAL CONTROLLER DCS

COOLING COIL

COOLING COIL CHILLED WATER VALVE TCV-AHU-

22A

Page 65: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-22 SYSTEM The Outside Air Damper is set at 9,940 CFM. 60 CFM is exhausted continuously through the Gravity Relief Damper in

the mezzanine floor.

GRAVITY RELIEF DAMPER

RD-22

AHU-22

OUTSIDE AIR DAMPER

L-23

Page 66: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-22 SYSTEM Economizer Operation

Based on outside air enthalpy and outside air temperature, when less than 60°F AHU-22 operates in economizer cycle modulating the outside and return air dampers to maintain 60°F supply air temperature.

LOCAL CONTROLLER DCS

RETURN AIR DAMPER

OUTSIDE AIR DAMPER

Page 67: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-22 SYSTEM Economizer Operation

Relief Air Damper RD-21 is controlled by differential pressure to maintain a 0.05 inch W.C. positive pressure in the building by modulating the damper.

RELIEF DAMPER RD-21

PRESSURE SENSOR A7AT 0.05” W.C.

AHU-22

Page 68: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 AHU-22 SYSTEM Economizer Operation

The chilled water valve to AHU-22 is closed during economizer cycle. In the event of damper failure or mixed air temperature below 35°F, a

freezestat shuts down AHU-22 and sends an alarm.

LOCAL CONTROLLER DCS

FREEZESTAT

CHILLED WATER VALVE

Page 69: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat area is cooled by AHU-22?

– Control Room– Janitor’s closet– Chemical Treatment Area– Electric Room

Page 70: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERAHU-22 cools the Electric Room.

Page 71: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhere Is the Gravity Relief Damper located?

– Control Room– Mezzanine floor– Electric Room– Operating floor

Page 72: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERThe Gravity Relief Damper is in the mezzanine floor.

Page 73: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhat volume of cooling air is supplied to the Electric Room by

AHU-22?– 1,250 CFM– 2,000 CFM– 10,000 CFM– 30,000 CFM

Page 74: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERAHU-22 supplies 10,000 CFM of cooling to the Electric Room.

Page 75: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 FCU-21 SYSTEM FCU-21 supplies 1,285 CFM of cooling to the Control Room, break

room, office, and vestibule. Cooling is controlled by modulating the cooling coil chilled water

valve in response to a temperature sensor in the Control Room.

LOCAL CONTROLLER DCS

COOLING COIL

COOLING COIL CHILLED WATER VALVE

FCU-21ACONTROL ROOM

Page 76: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

CHILLER PLANT #2 FCU-21 SYSTEM Outside air is set at 175 CFM during cooling with 1,110 CFM of return air. Heating is provided by a 6 KW Electric Duct Heater located in the supply

air duct.

FCU-21

ELECTRIC DUCT HEATER DH-21

Page 77: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhere is the Electric Duct Heater located?

– In the return air duct– In the supply air duct– In the relief air duct– In the makeup air duct

Page 78: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERThe Electric Duct Heater is located in the supply air duct.

Page 79: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhich of the following areas is cooled by FCU-21?

– Operating floor– Chemical treatment area– Electric Room– Control Room

Page 80: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWERFCU-21 supplies cooling to the Control Room, break room,

office, and vestibule.

Page 81: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

OPERATIONS MONITORING– Operation of the Plant HVAC Systems is monitored through the Control

Room on the top floor of Chilled Water Plant #2.

Page 82: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

PLANT ROUNDS– During an Operator’s routine shift, Rounds are accomplished to

record key information and visually assess HVAC Water System operation.

– Each Plant has a Rounds Sheet to be filled out by the Operator.– Each plant has different requirements for plant rounds.– The information is recorded, not only for the current status, but

also to record system trends.

Page 83: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

EXAMPLE ROUNDS SHEET (front and back)

Page 84: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

HVAC DAILY ROUNDS– Chiller Plants #1 and #2

• Outside temperature• Outside humidity• Outside enthalpy• AHU (On/Off)• Supply Fans (On/Off)• Exhaust Fans (On/Off)

Page 85: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

HVAC DAILY ROUNDS– West and East Campus Steam Plants

• Outside temperature• AHU

• Online/Offline• Space temperature• Supply air temperature

• Supply Fan• Online/Offline

• Space temperature

• Supply air temperature

Page 86: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

HVAC DAILY ROUNDS– West and East Campus Steam Plants

• Exhaust Fan (not all exhaust fans are checked for all conditions)• Online/Offline

• Space temperature

• Supply air temperature

• Firm alarm OK• Gas alarm OK• E-Stop alarm OK

Page 87: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

TYPICAL PROBLEMS ASSOCIATED WITH PLANT HVAC SYSTEMS– Stuck dampers

• Most likely cause is corrosion or debris– Blocked coils

• Most likely cause is corrosion, faulty filters– Malfunctioning control components

• Components damaged or out of calibration– Clogged condensate drains

• Most likely cause is debris or damage to pipes

Page 88: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhere does Operations Monitoring take place?

– Control Room in each steam plant– Control Room in West Campus Steam Plant– Control Room in Chilled Water Plant #2– Control Room in Chilled Water Plant #1

Page 89: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWEROperations Monitoring takes place In the Control Room in

Chilled Water Plant #2.

Page 90: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

QUESTIONWhich air pressure condition in a building is preferable?

– Under Pressure– Over Pressure– Balanced– Air pressure is not a concern of HVAC

Page 91: PLANT HVAC SYSTEMS

Facilities ManagementUtilities & Engineering ServicesDuk

e

PLANT HVAC SYSTEMS

ANSWEROperations Monitoring takes place In the Control Room in

Chilled Water Plant #2.