plant hvac systems
DESCRIPTION
PLANT HVAC SYSTEMS. DU-109-PP. PLANT HVAC SYSTEMS. PURPOSE The purpose of the Operations and Maintenance Training Program is to train Operations and Maintenance Technicians in the operation of the Duke University Plant Heating, Ventilation, and Air Conditioning (HVAC) Systems. OBJECTIVES - PowerPoint PPT PresentationTRANSCRIPT
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
DU-109-PP
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
PURPOSE The purpose of the Operations and Maintenance Training Program
is to train Operations and Maintenance Technicians in the operation of the Duke University Plant Heating, Ventilation, and Air Conditioning (HVAC) Systems.
OBJECTIVES Trainees will demonstrate knowledge of
– HVAC System Components– HVAC System Components Operation– HVAC System Configuration– HVAC System Controls and Instrumentation
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
PURPOSE The purpose of the Heating, Ventilation, and Air Conditioning
(HVAC) System is to:– Provide heat and cooling climate control for plant, office/control
room, and electrical room areas of the steam and chiller plants– Maintain Interior Air Quality (IAQ)– Maintain air pressure– Provide emergency exhaust
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
HVAC AIR FUNCTIONS To understand how HVAC works, you need to be familiar with the
six functions of HVAC air.Return Air
– Air inside the building drawn back into the air handlersOutside Air
– Fresh air drawn into the air handlers from outsideSupply Air
– Air blown into the building from the air handlers
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
HVAC AIR FUNCTIONSMakeup Air
– Air blown into the building by Makeup Air Unites (MAUs) to maintain air pressure balance when pressure is low
Relief Air– Air exhausted from the building to maintain air pressure balance
when air pressure is highExhaust Air
– Air expelled to remove contaminants from areas where chemicals, hazardous materials, and toxic gases are present
– Air exhausted from the building in case of emergency
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
WHY AIR BALANCE IS IMPORTANTOver Pressure and Under Pressure conditions negatively affect
building efficiency. Over Pressure
– When air pressure inside a building is higher than pressure outside, the conditioned air inside the building is pushed outside.
– High air pressure can require excess energy to condition the air in the building and compensate for energy lost.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
WHY IS AIR BALANCE IMPORTANT?Under Pressure
– When building pressure is lower than pressure outside, the air outside is drawn inside.
– Outside air may come from undesirable sources (trash bins, open doors, cracks, construction, and so forth).
– Unfiltered or unconditioned air can affect the HVAC system’s ability to maintain the desired environment.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat does IAQ stand for?
– International Air Quality– Industrial Air Quality– Interior Air Quality– In-duct Air Quality
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWER IAQ stands for Interior Air Quality.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat kind of air is blown into building from air handlers?
– Return Air– Outside Air– Makeup Air– Supply Air
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERSupply Air is recirculated through the air handlers.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat kind of air is added when air pressure is low?
– Return Air– Outside Air– Makeup Air– Supply Air
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERMakeup Air is blown into a building when air pressure is
low.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat causes Over Pressure?
– Pressure is higher on the lower level than on the mezzanine– Pressure is lower in the building than outside– Pressure is higher in the building than outside– Pressure is lower on the lower level than on the mezzanine
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWEROver Pressure is the condition when pressure inside the
building is higher than outside.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat causes Under Pressure?
– Pressure is higher on the lower level than on the mezzanine– Pressure is lower in the building than outside– Pressure is higher in the building than outside– Pressure is lower on the lower level than on the mezzanine
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERUnder Pressure is the condition when pressure inside
the building is lower than outside.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
PLANT HVAC COMPONENTS Air Handler Units (AHUs) Makeup Air Units (MAUs) Fan Coil Units (FCUs) Exhaust fans Supply fans Emergency exhaust fans
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
AHU COMPONENTSThe Mixing Box section contains:
– Return Air Damper which connects to the Return Air Duct• The Relief Air Damper also connects to the Return Air Duct
– Outside Air Damper which connects to the duct to the building exterior
RETURN AIRDAMPER
OUTSIDE AIRDAMPER
RELIEF AIRDAMPER
MIXING BOX
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
AHU COMPONENTSThe Filter section contains:
– Access door for filter element replacement– W.C. Meter mounted in door
• Filter is replaced when air pressure reaches maximum resistance
FILTER MIXING BOX
RETURN AIR
RELIEF AIR
OUTSIDE AIR
W.C. METER
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
AHU COMPONENTSThe Cooling Coil section contains:
– In and Out connections for chilled water– Cooling coil heat exchanger
MIXING BOXFILTERCOOLINGCOIL
RETURN AIR
RELIEF AIR
OUTSIDE AIR
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
AHU COMPONENTSThe Heating Coil section contains:
– In and Out connections for steam– Heating coil heat exchanger
FILTER
COOLINGCOIL
HEATINGCOIL
MIXING BOX
RETURN AIR
RELIEF AIR
OUTSIDE AIR
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
AHU COMPONENTSThe Fan section contains:
– Fan and motor– Starter Box mounted on
exterior or nearby
FILTERCOOLINGCOIL
HEATINGCOIL
MIXING BOX
RETURN AIR
OUTSIDE AIR
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat is accomplished in the AHU mixing box?
– Return air is mixed with relief air– Supply air is mixed with return air– Supply air is mixed with outside air– Return air is mixed with outside air
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERReturn air is mixed with outside air in the AHU mixing box.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat kind of meter is mounted in the filter section door of an
AHU?– Temperature sensor– Pressure gauge– W.C. meter– Anemometer
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERA W.C. meter is mounted in the door of the filter section. The
W.C. (Water Column) meter measures resistance through the filter in inches to indicate when the filter needs to be changed.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhere is the starter box located for an AHU?
– Exterior of the fan section or nearby– Mixing box– Control Room– AHUs do not need starters
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERThe starter box is mounted on the fan section of the AHU or
nearby.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
MAU COMPONENTSThe Fan section contains:
– Fan and motor– Outside Air Damper which connects to the duct to the building
exterior
OUTSIDE AIRDAMPER
FAN
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
MAU COMPONENTSThe Coil section contains:
– In and Out connections for steam and chilled water
– Heating and cooling coil heat exchangers
COOLINGCOIL
HEATINGCOIL
OUTSIDE AIRDAMPER
FAN
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
MAU COMPONENTSThe Filter section contains:
– Filters– Supply Air Damper
COOLINGCOIL
HEATINGCOIL
OUTSIDE AIRDAMPER
FAN
FILTER
SUPPLY AIRDAMPER
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
MAU COMPONENTSThe Starter box is located next to the MAU.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat is one way an MAU differs from an AHU?
– The MAU takes in return air and outside air– The MAU takes in relief air only– The MAU takes in outside air only– The MAU takes in return air only
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERThe MAU takes in outside air only.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat does MAU stand for?
– Main Air Unit– Maximum Air Unit– Mini Air Unit– Makeup Air Unit
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERMAU stands for Makeup Air Unit.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat is another way an MAU differs from an AHU?
– The MAU has a mixing box– The MAU does not have a mixing box– The MAU has a cooling coil– The AHU has a cooling coil
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERThe MAU does not have a mixing box.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
FCU COMPONENTSOutside Air DamperElectric Duct Heater
SUPPLY AIR
OUTSIDE AIR DAMPER
RETURN AIR
ELECTRIC DUCT HEATER
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
FCU COMPONENTSFilterCooling CoilFan and Motor
COOLING COIL
FAN
FILTER
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat does the FCU use to heat supply air?
– Steam – Hot water– Electricity– Friction
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERThe FCU uses an Electric Duct Heater to heat air in the supply
air duct.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat does FCU stand for?
– Forced Cooling Unit– Facilities Control Unit– Furnace Coil Unit– Fan Coil Unit
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERFCU stands for Fan Coil Unit.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
PLANT HVAC SYSTEMS CONFIGURATION AND PROCESS FLOWThe flow for Chiller Plant #2 is used as an example.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Temperature Transmitters on the Return Air Duct, Supply Air Duct,
and Mixing Box of AHU-21 send readings to the Local Controller Digital Control System (DCS).
LOCAL CONTROLLER DCS
RETURN AIR DUCT
SUPPLY AIR DUCTMIXING BOX
AHU-21
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM The local DCS controls heating and cooling by modulating the
Cooling Coil chilled water control valve and the steam valve supplying the Heating Coil.
LOCAL CONTROLLER DCS
MIXING BOX
CHILLED WATER CONTROL VALVESTEAM VALVE
COOLING COIL
HEATING COIL
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM The Outside Air Damper is set at 2,000 CFM. The Return Air Damper is set at 30,000 CFM.
MIXING BOX OUTSIDE AIR DAMPERD-21F
SUPPLY AIR DAMPERD-21E
AHU-21
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM 1,000 CFM exhausted continuously from Chemical Treatment area
by Exhaust Fan EF-23. 350 CFM exhausted continuously from the Break Room, Men’s and
Women’s Restrooms, Shower, and Janitor’s Closet by Exhaust Fan EF-24.
BREAK ROOM
WOMEN’S RESTROOM
MEN’S RESTROOM
JANITOR’S CLOSET
SHOWER
EXHAUST FANEF-24
EXHAUST TO OUTSIDE
LOUVER L-28
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Supply Fans SF-21 and SF-22 run continuously to recirculate air
within the plant.
SUPPLY FAN SF-21
SUPPLY FAN SF-22
EF-24
AHU-21
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Economizer Operation
Based on outside air enthalpy and outside air temperature, when less than 60°F AHU-21 operates in economizer cycle modulating the outside and return air dampers to maintain 60°F supply air temperature.
LOCAL CONTROLLER DCS
RETURN AIR DAMPER
OUTSIDE AIR DAMPER
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Economizer Operation
The chilled water valve to AHU-21 is closed during economizer cycle. In the event of damper failure or mixed air temperature below 35°F, a
freezestat shuts down AHU-21 and sends an alarm.
LOCAL CONTROLLER DCS
FREEZESTAT
CHILLED WATER VALVE
Facilities ManagementUtilities & Engineering ServicesDuk
e
RELIEF DAMPER RD-21
PRESSURE SENSOR A7AT 0.05” W.C.
AHU-21
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Economizer Operation
Relief Air Damper RD-21 is controlled by differential pressure to maintain a 0.05 inch W.C. positive pressure in the building by modulating the damper.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Emergency Exhaust
During emergency when refrigerant accumulates above 100 PPM due to leak or rupture, air recirculation dampers to Exhaust Fans EF-21 and EF-22 close and exhaust dampers open forcing the refrigerant from the building.
NORTH EMERGENCY
EXHAUST EF-21
SOUTH EMERGENCY
EXHAUST EF-22
EMERGENCY EXHAUST DAMPER
L-26
EMERGENCY EXHAUST DAMPER
L-25
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Emergency Exhaust
Supply Fans SF-21 and SF-22 shut down.The outside air damper to AHU-21 opens fully and the return air
damper closes.Additional outside air (30,000 CFM) brought into the building from
AHU-21 is exhausted through Positive Relief Damper RD-1.When the refrigerant detectors no longer sense a low refrigeration
concentration of 100 PPM, exhaust air dampers to EF-21 and 22 close and the air recirculation dampers open. SF-21 and 22 then energize and AHU-21 returns to a modulating damper cycle.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-21 SYSTEM Emergency Exhaust
If an emergency occurs when the supply air temperature is less than 60°F, a temperature sensor opens steam valve TCV-AHU-21B to maintain a supply air temperature of 60°F.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONBased on outside air enthalpy and outside air temperature,
what is the lowest temperature at which AHU-21 will operate before entering the economizer cycle?– 80°F– 40°F
– 60°F
– 72°F
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERBased on outside air enthalpy and outside air temperature,
when less than 60°F AHU-21 operates in economizer cycle.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhen do Supply Fans SF-21 and SF-22 run?
– Only when building pressure is low– Continuously– Only when building pressure is high– Only at night
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERSupply Fans SF-21 and SF-22 run continuously to recirculate
air within the plant.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhere do the temperature transmitters on the ducts and
mixing box on AHU-21 send readings?– Local Controller DCS– AHU-22– Directly to the Control Room– Chiller Plant #1
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERTemperature Transmitters on the Return Air Duct, Supply Air
Duct, and Mixing Box of AHU-21 send readings to the Local Controller Digital Control System (DCS).
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-22 SYSTEM AHU-22 supplies 10,000 CFM of cooling to the Electric Room. The local DCS modulates the cooling coil chilled water valve in response to
temperature sensors in the supply and return air ducts and mixing box.
LOCAL CONTROLLER DCS
COOLING COIL
COOLING COIL CHILLED WATER VALVE TCV-AHU-
22A
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-22 SYSTEM The Outside Air Damper is set at 9,940 CFM. 60 CFM is exhausted continuously through the Gravity Relief Damper in
the mezzanine floor.
GRAVITY RELIEF DAMPER
RD-22
AHU-22
OUTSIDE AIR DAMPER
L-23
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-22 SYSTEM Economizer Operation
Based on outside air enthalpy and outside air temperature, when less than 60°F AHU-22 operates in economizer cycle modulating the outside and return air dampers to maintain 60°F supply air temperature.
LOCAL CONTROLLER DCS
RETURN AIR DAMPER
OUTSIDE AIR DAMPER
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-22 SYSTEM Economizer Operation
Relief Air Damper RD-21 is controlled by differential pressure to maintain a 0.05 inch W.C. positive pressure in the building by modulating the damper.
RELIEF DAMPER RD-21
PRESSURE SENSOR A7AT 0.05” W.C.
AHU-22
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 AHU-22 SYSTEM Economizer Operation
The chilled water valve to AHU-22 is closed during economizer cycle. In the event of damper failure or mixed air temperature below 35°F, a
freezestat shuts down AHU-22 and sends an alarm.
LOCAL CONTROLLER DCS
FREEZESTAT
CHILLED WATER VALVE
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat area is cooled by AHU-22?
– Control Room– Janitor’s closet– Chemical Treatment Area– Electric Room
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERAHU-22 cools the Electric Room.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhere Is the Gravity Relief Damper located?
– Control Room– Mezzanine floor– Electric Room– Operating floor
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERThe Gravity Relief Damper is in the mezzanine floor.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhat volume of cooling air is supplied to the Electric Room by
AHU-22?– 1,250 CFM– 2,000 CFM– 10,000 CFM– 30,000 CFM
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERAHU-22 supplies 10,000 CFM of cooling to the Electric Room.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 FCU-21 SYSTEM FCU-21 supplies 1,285 CFM of cooling to the Control Room, break
room, office, and vestibule. Cooling is controlled by modulating the cooling coil chilled water
valve in response to a temperature sensor in the Control Room.
LOCAL CONTROLLER DCS
COOLING COIL
COOLING COIL CHILLED WATER VALVE
FCU-21ACONTROL ROOM
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
CHILLER PLANT #2 FCU-21 SYSTEM Outside air is set at 175 CFM during cooling with 1,110 CFM of return air. Heating is provided by a 6 KW Electric Duct Heater located in the supply
air duct.
FCU-21
ELECTRIC DUCT HEATER DH-21
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhere is the Electric Duct Heater located?
– In the return air duct– In the supply air duct– In the relief air duct– In the makeup air duct
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERThe Electric Duct Heater is located in the supply air duct.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhich of the following areas is cooled by FCU-21?
– Operating floor– Chemical treatment area– Electric Room– Control Room
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWERFCU-21 supplies cooling to the Control Room, break room,
office, and vestibule.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
OPERATIONS MONITORING– Operation of the Plant HVAC Systems is monitored through the Control
Room on the top floor of Chilled Water Plant #2.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
PLANT ROUNDS– During an Operator’s routine shift, Rounds are accomplished to
record key information and visually assess HVAC Water System operation.
– Each Plant has a Rounds Sheet to be filled out by the Operator.– Each plant has different requirements for plant rounds.– The information is recorded, not only for the current status, but
also to record system trends.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
EXAMPLE ROUNDS SHEET (front and back)
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
HVAC DAILY ROUNDS– Chiller Plants #1 and #2
• Outside temperature• Outside humidity• Outside enthalpy• AHU (On/Off)• Supply Fans (On/Off)• Exhaust Fans (On/Off)
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
HVAC DAILY ROUNDS– West and East Campus Steam Plants
• Outside temperature• AHU
• Online/Offline• Space temperature• Supply air temperature
• Supply Fan• Online/Offline
• Space temperature
• Supply air temperature
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
HVAC DAILY ROUNDS– West and East Campus Steam Plants
• Exhaust Fan (not all exhaust fans are checked for all conditions)• Online/Offline
• Space temperature
• Supply air temperature
• Firm alarm OK• Gas alarm OK• E-Stop alarm OK
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
TYPICAL PROBLEMS ASSOCIATED WITH PLANT HVAC SYSTEMS– Stuck dampers
• Most likely cause is corrosion or debris– Blocked coils
• Most likely cause is corrosion, faulty filters– Malfunctioning control components
• Components damaged or out of calibration– Clogged condensate drains
• Most likely cause is debris or damage to pipes
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhere does Operations Monitoring take place?
– Control Room in each steam plant– Control Room in West Campus Steam Plant– Control Room in Chilled Water Plant #2– Control Room in Chilled Water Plant #1
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWEROperations Monitoring takes place In the Control Room in
Chilled Water Plant #2.
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
QUESTIONWhich air pressure condition in a building is preferable?
– Under Pressure– Over Pressure– Balanced– Air pressure is not a concern of HVAC
Facilities ManagementUtilities & Engineering ServicesDuk
e
PLANT HVAC SYSTEMS
ANSWEROperations Monitoring takes place In the Control Room in
Chilled Water Plant #2.