plan -...
TRANSCRIPT
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001390000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT4'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900139 VPF 48X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001390000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
4'-0" TYPOUTSIDE
2'-1158"
3'-1114"
2'-6"TYP
3" INFLUENT PIPING(BY OTHERS)
3" EFFLUENT PIPING(BY OTHERS)
1'-3"TYP
4" TYP
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING
3" INFLUENT/BACKWASHTANK CONNECTION
3" MANUAL BACKWASHRATE SET VALVE
2" INFLUENTVALVE
3" BACKWASHWASTE VALVE
3" EFFLUENTTANK CONNECTION
3" EFFLUENTVALVE
2" DRAINVALVE
2" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
5'-0"
8"
1'-834"
5'-358"
6'-438"
7'-5"
9'-514"
0'-0"
1'-158"
8'- 716"
5'-0"STRAIGHT
SIDEHEIGHT
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001400000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT4'-6" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900140 VPF 54X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001400000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
4'-6" TYPOUTSIDE
3'-258"
4'-214"
2'-9"
3" INFLUENT PIPING(BY OTHERS)
4" EFFLUENT PIPING(BY OTHERS)
1'-518"
4"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING3" INFLUENT/BACKWASHTANK CONNECTION
3" MANUAL BACKWASHRATE SET VALVE
2" INFLUENTVALVE
3" BACKWASHWASTE VALVE
3" EFFLUENTTANK CONNECTION
3" EFFLUENTVALVE
2" DRAINVALVE
2" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
5'-6"TYP
8"
1'-934"
5'-434"
6'-512"
7'-618"
9'-71116"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-158"
8'-278"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001410000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT5'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900141 VPF 60X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001410000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
5'-0" TYPOUTSIDE
3'-558"
4'-514"
3'-0"
3" INFLUENT PIPING(BY OTHERS)
4" EFFLUENT PIPING(BY OTHERS)
1'-714"
4"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING3" INFLUENT/BACKWASHTANK CONNECTION
3" MANUAL BACKWASHRATE SET VALVE
2" INFLUENTVALVE
3" BACKWASHWASTE VALVE
3" EFFLUENTTANK CONNECTION
3" EFFLUENTVALVE
2" DRAINVALVE
2" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
6'-0"TYP
8"
1'-934"
5'-558"
6'-638"
7'-7"
9'-9 516"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-158"
8'-412"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001420000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT5'-6" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900142 VPF 66X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001420000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
5'-6" TYPOUTSIDE
3'-958"
4'-1078"
3'-3"
4" INFLUENT PIPING(BY OTHERS)
4" EFFLUENT PIPING(BY OTHERS)
1'-938"
4"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING4" INFLUENT/BACKWASHTANK CONNECTION
4" MANUAL BACKWASHRATE SET VALVE
3" INFLUENTVALVE
4" BACKWASHWASTE VALVE
4" EFFLUENTTANK CONNECTION
4" EFFLUENTVALVE
3" DRAINVALVE
3" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
6'-6"TYP
8"
1'-11"
5'-538"
6'-838"
7'-1118"
10'-12"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-258"
8'-71116"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001430000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT6'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900143 VPF 72X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001430000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
6'-0" TYPOUTSIDE
4'-58"
5'-178"
3'-6"
4" INFLUENT PIPING(BY OTHERS)
6" EFFLUENT PIPING(BY OTHERS)
1'-11"
5"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING4" INFLUENT/BACKWASHTANK CONNECTION
4" MANUAL BACKWASHRATE SET VALVE
3" INFLUENTVALVE
4" BACKWASHWASTE VALVE
4" EFFLUENTTANK CONNECTION
4" EFFLUENTVALVE
3" DRAINVALVE
3" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
7'-0"TYP
8"
2'-12"
5'-658"
6'-958"
8'-38"
10'-234"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-258"
8'-978"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001440000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT6'-6" DIAMETER, 60" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900144 VPF 78X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001440000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
6'-6" TYPOUTSIDE
4'-358"
5'-538"
3'-9"
4" INFLUENT PIPING(BY OTHERS)
6" EFFLUENT PIPING(BY OTHERS)
2'-118"
5"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING4" INFLUENT/BACKWASHTANK CONNECTION
4" MANUAL BACKWASHRATE SET VALVE
3" INFLUENTVALVE
4" BACKWASHWASTE VALVE
4" EFFLUENTTANK CONNECTION
4" EFFLUENTVALVE
3" DRAINVALVE
3" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
7'-6"TYP
9"
2'-112"
5'-838"
6'-1138"
8'-218"
10'-5 516"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-358"
9'-12"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001450000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT7'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900145 VPF 84X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001450000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
7'-0" TYPOUTSIDE
4'-818"
5'-1138"
4'-0"
6" INFLUENT PIPING(BY OTHERS)
6" EFFLUENT PIPING(BY OTHERS)
2'-314"
5"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
3" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
3" DRAINVALVE
3" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
8'-0"TYP
9"
2'-318"
5'-818"
7'-214"
8'-8"
10'-958"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-518"
9'-434"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001460000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT7'-6" DIAMETER, 60" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-24JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900146 VPF 90X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001460000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
7'-6" TYPOUTSIDE
4'-1118"
6'-358"
4'-3"
6" INFLUENT PIPING(BY OTHERS)
6" EFFLUENT PIPING(BY OTHERS)
2'-538"
5"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
4" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
4" DRAINVALVE
4" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
8'-6"TYP
10"
2'-418"
5'-10"
7'-418"
8'-1018"
11'-14"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-618"
9'-738"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001470000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT8'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900147 VPF 96X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001470000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
8'-0" TYPOUTSIDE
5'-218"
6'-658"
4'-6"
6" INFLUENT PIPING(BY OTHERS)
6" EFFLUENT PIPING(BY OTHERS)
2'-712"
5"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
4" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
4" DRAINVALVE
4" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
9'-0"
10"
2'-418"
5'-1114"
7'-538"
8'-1138"
11'-234"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-618"
9'-978"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001480000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT8'-6" DIAMETER, 60" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-27JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900148 VPF 102X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001480000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
8'-6" TYPOUTSIDE
5'-518"
6'-958"
4'-9"
6" INFLUENT PIPING(BY OTHERS)
6" EFFLUENT PIPING(BY OTHERS)
2'-712"
9"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
4" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
4" DRAINVALVE
4" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
9'-6"TYP
10"
2'-418"
6'-18"
7'-614"
9'-14"
11'-4 716"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-618"
9'-1112"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001490000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT9'-0" DIAMETER, 60" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-27JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900149 VPF 108X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001490000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
9'-0" TYPOUTSIDE
5'-818"
7'-58"
5'-0"
6" INFLUENT PIPING(BY OTHERS)
8" EFFLUENT PIPING(BY OTHERS)
2'-958"
9"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
4" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
4" DRAINVALVE
4" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
10'-0"TYP
10"
2'-518"
6'-78"
7'-7"
9'-1"
11'-6 116"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-618"
10'-118"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001500000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT9'-6" DIAMETER, 60" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-27JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900150 VPF 114X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001500000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
9'-6" TYPOUTSIDE
5'-1118"
7'-358"
5'-3"
6" INFLUENT PIPING(BY OTHERS)
8" EFFLUENT PIPING(BY OTHERS)
2'-1134"
9"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
4" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
4" DRAINVALVE
4" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
10'-6"TYP
10"
2'-518"
6'-218"
7'-814"
9'-214"
11'-8 916"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-618"
10'-358"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001510000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT10'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900151 VPF 120X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001510000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
10'-0" TYPOUTSIDE
6'-218"
7'-814"
5'-6"
8" INFLUENT PIPING(BY OTHERS)
8" EFFLUENT PIPING(BY OTHERS)
3'-178"
9"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING6" INFLUENT/BACKWASHTANK CONNECTION
6" MANUAL BACKWASHRATE SET VALVE
6" INFLUENTVALVE
6" BACKWASHWASTE VALVE
6" EFFLUENTTANK CONNECTION
6" EFFLUENTVALVE
6" DRAINVALVE
6" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
11'-0"TYP
11"
2'-618"
6'-378"
7'-10"
9'-518"
11'-1118"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-718"
10'-6 316"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001520000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT11'-0" DIAMETER, 60" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-28JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900152 VPF 132X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001520000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
11'-0" TYPOUTSIDE
6'-918"
8'-414"
6'-0"
8" INFLUENT PIPING(BY OTHERS)
8" EFFLUENT PIPING(BY OTHERS)
3'-6 316"
9"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING
8" INFLUENT/BACKWASHTANK CONNECTION
8" MANUAL BACKWASHRATE SET VALVE
6" INFLUENTVALVE
8" BACKWASHWASTE VALVE
8" EFFLUENTTANK CONNECTION
8" EFFLUENTVALVE
6" DRAINVALVE
6" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
12'-0"TYP
11"
2'-712"
6'-458"
8'-118"
9'-914"
12'-438"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-818"
10'-1138"
PLAN
SECTION A-AEND
A A
REV
-SHEETDOCUMENT NUMBER
9001530000 1 OF 1
TITLE VERTICAL PRESSURE FILTERGENERAL ARRANGEMENT12'-0" DIAMETER, 5'-0" STRAIGHT SIDE, 3 TANK, WATERWASH
2014-10-21JA20BA91DESIGNER CHECKER APPROVER
THIS DRAWING IS PROPERTY OF WESTECH ENGINEERING, INC. AND IS TRANSMITTED IN CONFIDENCE. NEITHER RECEIPT NOR POSSESSION CONFERS OR TRANSFERS ANY RIGHTS TOREPRODUCE, USE, OR DISCLOSE, IN WHOLE OR IN PART, DATA CONTAINED HEREIN FOR ANY PURPOSE, WITHOUT THE WRITTEN PERMISSION OF WESTECH ENGINEERING, INC.
DATE
C:\vault\Design\Standard Products\General Filter\9000\900153 VPF 144X60\Waterwash 3 Tank Arrangement\Workgroup\IDW Files\9001530000-GA.idw
ADDITIONAL NOTES:
1.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST. ADDITIONAL PIPING, PIPESUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDED WITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTSTO BE INSTALLED AT JOBSITE, BY CUSTOMER.
2.) WHEN PRESSURE AERATION OCCURS BEFORE FILTRATION THERE NEEDS TO BE A PROVISION MADE FOR AIR RELEASE INTHE HIGHEST POINT OF THE INLETPIPING.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTING ENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. TO BE DESIGNED BY THE CONSULTING ENGINEER AND SUPPLIED BY THE INSTALLINGCONTRACTOR.
5.) DO NOT SUPPORT PIPING OR OTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
6.) MINIMUM RECOMMENDED CEILING HEIGHT: ALLOW 6" CLEARANCE ABOVE THE AIR RELEASE PIPING.
7.) BACKWASH WASTE SUMP SIZING AND LOCATION DESIGN IS BY THE CONSULTING ENGINEER. SUMP TO BE DESIGNED FORMAXIMUM DESIGN BACKWASH RATE.
15°TYP
12'-0" TYPOUTSIDE
7'-318"
8'-1014"
6'-6"
8" INFLUENT PIPING(BY OTHERS)
10" EFFLUENT PIPING(BY OTHERS)
3'-10 716"
9"
14" X 18"MANWAY
0.75" AUTOMATICAIR RELEASE
PIPING8" INFLUENT/BACKWASHTANK CONNECTION
8" MANUAL BACKWASHRATE SET VALVE
6" INFLUENTVALVE
8" BACKWASHWASTE VALVE
8" EFFLUENTTANK CONNECTION
8" EFFLUENTVALVE
6" DRAINVALVE
6" DRAIN/FILTER TOWASTE PIPING
NOTES:
1.) FOLLOW THE LISTED WESTECH REFERENCE DOCUMENTS EXCEPT AS NOTED ON THISDRAWING.
2.) EQUIPMENT FURNISHED BY WESTECH IS DESCRIBED IN A SEPARATE EQUIPMENT LIST.ADDITIONAL PIPING, PIPE SUPPORTS, AND CONNECTION FITTINGS ARE NOT INCLUDEDWITH STANDARD UNIT. MAJOR EQUIPMENT AND COMPONENTS TO BE INSTALLED AT THEJOBSITE BY THE INSTALLING CONTRACTOR.
3.) EQUIPMENT CONCRETE DESIGN IS THE RESPONSIBILITY OF THE CONSULTINGENGINEER.
4.) PIPE SUPPORTS ARE NOT SHOWN. SUPPORTS TO BE DESIGNED BY THE CONSULTINGENGINEER AND SUPPLIED BY THE INSTALLING CONTRACTOR. DO NOT SUPPORT PIPING OROTHER STRUCTURES FROM THE TANK OR TANK PROJECTIONS.
REFERENCE DOCUMENTSREV REVISION DESCRIPTION ECN DESIGNER APPROVER DATE
LOSS OF HEADINDICATOR
BACKWASH RATEOF FLOW INDICATOR
13'-0"
11"
2'-912"
6'-658"
8'-318"
9'-1114"
12'-8 716"
0'-0"
5'-0"STRAIGHT
SIDEHEIGHT
1'-818"
11'-3 716"