Pico™ ControllerBulletin 1760
Getting Results
Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNINGIdentifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
SHOCK HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.
Table of ContentsPreface Who Should Use this Manual. . . . . . . . . . . . . . . . . . . Preface-i
Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . Preface-iiCommon Techniques Used in this Manual . . . . . . . . . Preface-iiRockwell Automation Support . . . . . . . . . . . . . . . . . Preface-iii
Chapter 1Pico Controller Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Simply Pico. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Mount Pico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Connect Pico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Pico Operating Principle . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
Chapter 2Drawing a Circuit with Pico Operation of Pico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Set the Menu Language . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Set the Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Choose Pico Operating Mode . . . . . . . . . . . . . . . . . . . . . . 2-4Pico Circuit Diagram Elements. . . . . . . . . . . . . . . . . . . . . . 2-5Example: Creating a Circuit Diagram . . . . . . . . . . . . . . . . . 2-9Function Relay Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13Example: Use a Function Relay . . . . . . . . . . . . . . . . . . . . . 2-20Basic Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Chapter 3Pico Interface Socket
Appendix ASpecifications Physical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Product Selection Table. . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Index
i Publication 1760-GR001C-EN-P - April 2005
Table of Contents ii
Publication 1760-GR001C-EN-P - April 2005
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
• Rockwell Automation support
Who Should Use this Manual
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Pico controllers.
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
i Publication 1760-GR001C-EN-P - April 2005
Preface ii
Purpose of This Manual This manual provides a basic overview of Pico and an introduction to Pico programming. For a more detailed description of how to install and use your Pico Controller, refer to publication 1760-UM001, Pico Controller User Manual.
Related Documentation
The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.
Common Techniques Used in this Manual
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
For Read this Document Document Number
A more detailed description of how to install and use your Pico controller.
Pico Controller User Manual 1760-UM001
In-depth information on grounding and wiring Allen-Bradley programmable controllers
Allen-Bradley Programmable Controller Grounding and Wiring Guidelines
1770-4.1
A description of important differences between solid-state programmable controller products and hard-wired electromechanical devices
Application Considerations for Solid-State Controls
SGI-1.1
An article on wire sizes and types for grounding electrical equipment National Electrical Code - Published by the National Fire Protection Association of Boston, MA.
A complete listing of current documentation, including ordering instructions. Also indicates whether the documents are available on CD-ROM or in multi-languages.
Allen-Bradley Publication Index SD499
A glossary of industrial automation terms and abbreviations Allen-Bradley Industrial Automation Glossary
AG-7.1
Publication 1760-GR001C-EN-P - April 2005
Preface iii
Rockwell Automation Support
Rockwell Automation offers support services worldwide, with over 75 Sales/Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for:
• sales and order support
• product technical training
• warranty support
• support service agreements
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance, please review the Troubleshooting chapter in the Pico Controller User Manual first. Then call your local Rockwell Automation representative.
You can also contact Rockwell Automation Technical Support. To reach our Technical Support, go to the following website to find the support site for your region.
• http://support.automation.rockwell.com/contactinformation/
Your Questions or Comments on this Manual
If you find a problem with this manual, or you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Rockwell AutomationControl and Information GroupTechnical Communication, Dept. A602VP.O. Box 2086Milwaukee, WI 53201-2086
or visit our internet page at:http://www.ab.com/pico or http://www.rockwellautomation.com
Publication 1760-GR001C-EN-P - April 2005
Preface iv
Publication 1760-GR001C-EN-P - April 2005
Chapter 1
Pico Controller
Safety Information
Simply Pico Clever Switching and Controlling
Pico is a compact, user-friendly and low-cost controller for simple control applications. Applications range from building and domestic automation to machine and plant control. Pico has built-in user-friendly operating elements and an LCD display.
Connect Pico and draw a circuit diagram on the display by pressing the buttons on the device. Pico works with make contacts, break contacts, and relays.
Enter a circuit diagram in Pico just like it is sketched on paper. Pico has basic and advanced functions for relays, time switches and contactors, among other functions. Make changes to the circuit by pressing the buttons on the device. Time consuming rewiring is not necessary.
ATTENTION Electrical Shock Hazard
The electrical installation and commissioning work must only be carried out by suitably qualified personnel.
Do not work on the device when the power is turned on.
Observe the relevant safety regulations:
• Turn off the power
• Make sure that the device cannot be powered on again inadvertently
• Check to make sure that no dangerous voltages are present before working on the device
1 Publication 1760-GR001C-EN-P - April 2005
1-2 Pico Controller
Applications Everywhere
• Building and domestic automation, controllers for lighting, doors, window shutters
• Control ventilators, rotating doors, greenhouses, exterior lighting, window controllers, shop display lighting
• Create controllers for temperature, ventilation and brightness levels
• Control machines and plant, presses, conveyor belts, oscillating conveyors, sorters, pumps
Overview of Pico
Item Description
1 Incoming Power
2 Inputs
3 Power/Run LED
4 Keypad
5 Socket for memory module or PC interface cable
6 Outputs
7 LCD display
8 Write-On Surface
EscOk
Del Alt
EscOk
Del Alt
7
12
34
5
6
3
5
5
8
8
7
8
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-3
Mount Pico Mount on DIN Rail
1. Hook Pico to the top edge of the DIN rail and rotate into place while pressing down slightly as shown by the arrow.
2. Pico will clip into place and is secured by the built-in spring mechanism.
Mount on a Mounting Plate
Pico can be screwed to a mounting plate with the three or four feet which are included.
1
2
Click
Publication 1760-GR001C-EN-P - April 2005
1-4 Pico Controller
Connect Pico Pico Inputs1760-L12BBB-xx, 1760-L12BWB-xx and 1760-L12DWD-xx
Pico Inputs 1760-L12AWA-xx and 1760-L12NWA-xx
+10 V
10 V
5 V
0 V
BWB: +24 V+.. V
DWD: +12 V
~
0 5 10
0 VBWB:Ue = 24 V (20.4 - 28.8 V)Ie = 80 mA
DWD:Ue = 12 V (10.2 - 15.6 V)Ie = 140 mA
BWB: +24 VDWD: +12 V
0 Vl7, l8
> 1 A
l1 I2 I3 I4 I5 I6 I7 I8
1 ≥ 15 V
0 ≤ 5 V
28.8 Vl = 3.3 mA/24 VI7, I8 = 2.2 mA/24 V 1 ≥ 8 V
0 ≤ 4 V
l = 3.3 mA/12 VI7, I8 = 1.1 mA/12 V
15.6 V
5 - 7 lb-in
3.5 mm
COM
BWB DWD
L1
5-7 lb-in.3.5 mm
L1
L2
>1A
l1 I2 I3 I4 I5 I6 I7 I8
Ue = 120/240 V 50/60 Hz(90 to 264V)le = 40 mA 120V 20 mA 240V
l1–I6 = 0.5 mA 240 Vl1–I6 = 0.25 mA 120 VI7, I8l = 6 mA 240 Vl = 4 mA 120V
1 ≥ 79V
0 ≤ 40V
264V
L2
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-5
Pico Outputs 1760-L12AWA-xx, 1760-L12BWB-xx, 1760-L12DWD-xx, 1760-L12BBB-xx and 1760-L12NWA-xx
Pico Inputs 1760-L18BWB-EX and 1760-L18BWB-EXND
0 V , N
8 A / B 16
L1, L2, L3 (120/240 V )+ 24 V
25.000
R L
24 V 8 A120 V 8 A240 V 8 A
2 A2 A2 A
1000 W
10 x 58 W
1 2 1 2 1 2 1 2
10 000 000Q1 Q2 Q3 Q4
+10 V
10 V
5 V
0 V
+24 V0 5 10
0 V
5–7 lb-in3.5 mm
Ue = 24 V (20.4–28.8 V )Ie = 140 mA
+24 V
0 V
l7, I8
> 1 A
l1 I2 I3 I4 I5 I6 I7 I8
1 ≥ 15 V
0 ≤ 5 V
24 VI7, I8 = 2.2 mA
I9 I10 I11 I12
28.8 V
24 V
I1–I6, I9–I12 = 3.3 mA
24 V Input 24 V
z
COM
G '1D %
-
B
Publication 1760-GR001C-EN-P - April 2005
1-6 Pico Controller
Pico Inputs 1760-L18AWA-xx and 1760-L18NWA-xx
Pico Outputs 1760-L18xxx
Pico Inputs 1760-L20xxx
L1
5-7 lb-in.3.5 mm
L1
L2
> 1 A
l1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12
Ue = 120/240 V 50/60 Hz(85–264 V)
100/240 V Input 100/240 V
le = 70 mA 120 V 35 mA 240 V
l1–I6, I9 –I12 = 0.5 mA 240 Vl1–I6, I9 –I12 = 0.25 mA 120 VI7, I8l = 6 mA 240 Vl = 4 mA 120 V
1 > 79 V
0 < 40 V
264 V
L2
0 V , N
8 A / B 16
L1, L2, L3 (120/240 V ) + 24 V
< 25.000
R
24 V 8 A120 V 8 A240 V 8A
2 A2 A2 A
1000 W
10 x 58 W
1 2 2 2 2 2 21 1 1 1 1
< 10 000 000Q6Q5Q4Q3Q2Q1
L011
L012
0 V l1 I2 I7+...V
DC : +24 VDA : +12 V
F1
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-7
Pico Outputs 1760-L20xxx
Pico Inputs 1760-IB12XOB8
(20.4 – 28.8 V H)+ 24 V H
R
5 W/24 V
0.5 A
0 V H
+24 V 0 V Q1 Q2 Q3 Q4 Q5 Q6 Q7
f 2.5 A
F 10 A
24 V H 0.5 A
Q8Q Q
5–7 lb-in
3.5 mm
Ue = 24 V (20.4 –28.8 V )Ie = 140 mA
+24 V
0 V
> 1 A
1 ≥ 15 V
0 ≤ 5 V
R10R9R8R7R6R5R4R3R2R1NC NC R11 R12 +24V
28.8 V R1–R12 = 3.3 mA; 24 V
Input 24 V 24 V
COM
Publication 1760-GR001C-EN-P - April 2005
1-8 Pico Controller
Pico Outputs 1760-IB12XOB8
Pico Inputs 1760-IA12XOW6I and 1760-IB12XOW6I
S1 S2 S3 S4 S5 S6 S7 S8
2.5A
10A
R
+24V dc COM
+ 24V dc
24V 0.5A 0.5A
(20.4-28.8V dc )
5W/24V
≤
0V
0 V , N
< 8 A / B 16
L1, L2, L3 (120/240 V) + 24 V
25.000
R
24 V 8 A120 V 8 A240 V 8 A
2 A2 A2 A
1000 W
10 x 58 W
1 2 2 2 2 2 21 1 1 1 1
10 000 000S6S5S4S3S2S1
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-9
Pico Outputs 1760-IA12XOW6I and 1760-IB12XOW6I
Pico Outputs 1760-OW8
0 V , N
< 8 A / B 16
L1, L2, L3 (120/240 V) + 24 V
25.000
R
24 V 8 A120 V 8 A240 V 8 A
2 A2 A2 A
1000 W
10 x 58 W
1 2 2 2 2 2 21 1 1 1 1
10 000 000S6S5S4S3S2S1
Publication 1760-GR001C-EN-P - April 2005
1-10 Pico Controller
Pico Operating Principle Pico Operating Buttons
Button Function
Del Delete object in the circuit diagram
Alt Special functions in the circuit diagram
Cursor Buttons
Move cursor
Select menu item
Choose contact numbers, values, times, etc.
Ok Next menu level, store your entry
Esc Previous menu level, cancel your entry
Esc Ok
Del Alt
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-11
Move Through Menus to Choose Values
12-Point Status Display
Press To
Show system menu (press both keys at the same time).
• Go to next menu level.
• Select menu item.
• Store your entry.
Cancel your entry since the last Ok.
• Change menu item.
• Change value.
• Change position.
Del Altand
Ok
Esc
I12345678
MO
12:50
Q1234 RUN
Inputs
Outputs
Weekday
Time
RUN/STOP mode
On/ Off
Publication 1760-GR001C-EN-P - April 2005
1-12 Pico Controller
18-Point and 20-Point Status Display
Menu Display
1...5..8....
RE I P
MO 02:00 ST
.2..5..8 RUN
Inputs
Retention Enabled
Day, Time
Outputs
Debounce Enabled/P-Buttons Enabled
Start-up Mode
Mode
Inputs 1, 5, 8 ONOutputs 2, 5, 8 ON
PROGRAM...
RUN...
PARAMETER
SET CLOCK..
RUN...
PARAMETER
SET CLOCK..
PASSWORD..Current choice blinks in the Pico menu
Main menu with and without password enabled
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-13
Cursor Display
Circuit Diagram Menu
Each rung can hold four instructions, three input instructions (contacts) and one output instruction (coil or relay). Rungs are connected together through branches at the three positions between instructions. All programming of Pico can be done using the display and keypad.
WINTER TIME
DAY : MO
TIME : 01 25
WINTER TIME
DAY : MO
TIME : 01:25
There are two different cursor types:
Full block navigation is shown as a flashing block:
• Move cursor with the left/right arrows
• When in circuit diagram, also use up/down arrows
Parameter change cursor flashes the selected parameter:
• Change position with left/right arrows
• Change values with up/down arrows
Flashing values/menus are highlighted in grey in this manual.
I1 -I2 -T1 -{Q1
I2 - 1
InputContacts
OutputCoil Field
Circuit Connections/Rungs
Branch Connections
Publication 1760-GR001C-EN-P - April 2005
1-14 Pico Controller
Circuit Diagram Symbols
PI
QMTC
A
:RS
I1 -M2 -T1 -{Q1
I2 -Q1
D
I3-M2-T2----{Q2
Cursor button as input
Contact for input
Contact for output
Contact for internal marker bits
Contact for timer relay
Contact for counter relay
Contact for real time clock switch
Analog comparator contactContact for text display (1)
Contact for jump (1)
Expansion Inputs (1)
Contact for internal marker relay or Expansion Output (1)
Coil Field
1st circuit connection2nd circuit connection3rd circuit connection
41st circuit connection
Last circuit connection
…
…
(1) For 1760-L18xxx only
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-15
Menu Structure Main Menu Without Optional Password Protection
PROGRAM...STOP RUN åPARAMETERINFO...SET CLOCK
PROGRAMDELETE PROGCARD ...
Circuit Diagram
Parameters
PROGRAM
CARD ...
DELETE PROGPROGRAM
DELETE ?
DEVICE->CARDCARD->DEVICEDELETE CARD
REPLACE ?
DEVICE->CARD
DELETE CARDREPLACE ?
DEVICE->CARD
CARD->DEVICE
DELETE ?
PROGRAM...
PARAMETERRUN
STOP
PROGRAM...
PROGRAM...RUNPARAMETER
SUMMER TIME
DC TC LCDOS: 1.00.027CRC: 02752
DELETE PROG
CARD ...
CARD->DEVICE
DELETE CARD
PARAMETER
SET CLOCK
INFO...
SET CLOCK
PROGRAM...RUNPARAMETERINFO...
SET CLOCK
INFO...SET CLOCK
INFO...SET CLOCK
STOP RUN
STOP RUN
T1 X
S1 10.000S2 +0
+S
T:
T1 XT2 ÜC1 NO1
M:S++++
S
HH:MM --:--
DD.MM
YEAR ----
--.--
HH:MM 14:23
DD.MM
YEAR 2004
17.03
RUN
STOP
STOP: Circuit diagram menuRUN: Power flow display
Parameter Display
Parameter Display
Display for Setting Clock
Information Display of Device
Publication 1760-GR001C-EN-P - April 2005
1-16 Pico Controller
Main Menu Setting Summer Time
SET CLOCK
NONE åRULE...EUGBUS
SUMMER TIME
SUMMER START
SUMMER END
PROGRAM...RUNPARAMETERINFO...
SET CLOCK
SET CLOCK
NONE RULE...EUGBUS
SUMMER TIME
SUMMER START
SUMMER END
SET CLOCK
NONE RULE...EUGBUS
SUMMER TIME
SUMMER START
SUMMER END
SET CLOCK
NONE RULE...EUGBUS
SUMMER TIME
DD.MM:00.00
AM --HH:MM --
HH.MM:00:00
DIFF: 0:00
--
DD.MM:00.00
AM --HH:MM --
HH.MM:00:00
DIFF: 0:00
--
Publication 1760-GR001C-EN-P - April 2005
Pico Controller 1-17
Main Menu with Password Protection
PASSWORD...RUNPARAMETER
Password DELETE ALL
PASSWORD...RUN
INFO...SET CLOCK
Main MenuUnlock
Password Entry
Four Wrong Entries
Correct Entry
Status Display
TIP If you do not know the password, you can delete the old password, but the circuit diagram and data will also be deleted. To delete the password, press Ok to DELETE ALL after entering four incorrect passwords. (Pressing Esc retains the circuit diagram and data. You can then make another four attempts to enter the password.)
Publication 1760-GR001C-EN-P - April 2005
1-18 Pico Controller
System Menu
sECURITY...SYSTEM... RANGE...LANGUAGE ...CONFIGURATOR
CONFIGURATOR
Password
RANGE...Password
ENTER PASSW:
XXXX
ENTER PASSW:
XXXXCHANGE PW
ACTIVATE PW
SECURITY...
LANGUAGE...
CHANGE PW
P ONSTOP MODE
DEBOUNCE OFF
DEBOUNCE ON
DEBOUNCE OFFP ONSTOP MODE
DEBOUNCE OFFP ON
DEBOUNCE OFF
STOP MODEP ON
P OFF
MODE: STOP
MODE: RUN
RETENTION ON
RETENTION OFF
ACTIVATE PW
CHANGE PWACTIVATE PW
SYSTEM...
CONFIGURATOR
SECURITY...
LANGUAGE...SYSTEM...
CONFIGURATOR
SECURITY...
LANGUAGE...SYSTEM...
DEBOUNCE OFF
P ON
STOP MODE
RETENTION ON(2) (2)
(2)
PROGRAM åPARAMETER
CLOCK
OPRTNG MODE
INTERFACEDELETE FUNCT
PROGRAM åPARAMETER åCLOCK åOPRTNG MODE åINTERFACE åDELETE FUNCT å
ENGLISH
DEUTSCH
FRANCAIS
ESPANOL
ITALIANO
PORTUGUES
NEDERLANDS
SVENSKA
POLSKI
TURKCE
CESKY
MAGYAR
SystemSet Password
Change Password
Password Entry
(1) Only for Pico 1760-L18xxx(2) Only for Pico 1760-L12BWB-xx, -L12DWD and -L18xxx.
Publication 1760-GR001C-EN-P - April 2005
Chapter 2
Drawing a Circuit with Pico
Operation of Pico Buttons for Drawing Circuit Diagrams
Button Function
Delete branch, contact, relay, or empty rung in the circuit diagram
• Toggle between break and make contact
• Connect contacts and relays
• Add circuit connections
Up/down arrows:
• Change value
• Move cursor up and down
Left/right arrows:
• Move cursor to left and right
• Change between parameters
• Go to previous menu level
• Undo settings from previous Ok
• Exit current display
• Go to next menu level
• Change, add contact/relay
• Save setting
Del
Alt
Esc
Ok
1 Publication 1760-GR001C-EN-P - April 2005
2-2 Drawing a Circuit with Pico
Set the Menu Language Power Up Pico for the First Time
When you power-up Pico for the first time, you are asked to select the menu language.
Use the up and down cursor buttons to select a language. Definitions of the language abbreviations are shown below.
Press Ok to confirm your choice or press Esc to exit the menu. The unit then switches to the status display. You can also change the language setting at a later date.
If you do not set the language, Pico displays this menu and waits for you to select a language every time the unit is powered up.
TIP A brief current surge is produced when powering on the unit for the first time. Do not switch the unit using reed contacts, since these may burn or melt.
Language LCD display Abbreviaton
English ENGLISH GB
German DEUTSCH D
French FRANCAIS F
Spanish ESPANOL E
Italian ITALIANO I
Portuguese PORTUGUES –
Dutch NEDERLANDS –
Swedish SVENSKA –
Polish POLSKI –
Turkish TURKCE –
Czexh CESKY –
Hungarian MAGYAR –
ENGLISH
DEUTSCH
FRANCAIS
ESPANOL
ITALIANO
PORTUGUES
NEDERLANDS
SVENSKA
POLSKI
TURKCE
CESKY
MAGYAR
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-3
Set the Time Controllers with the “-NC” designation do not have real time clocks.
Set the Real Time Clock
Set Week Day and Time
I 1 2 3 4 5 6 7 8
MO
14:15
Q1234 STOP
1 ...5 ..8 ....
RE I P
MO 02:00 ST
.2 ..5 ..8 RUN
PROGRAM ...
RUN
PARAMETER
PROGRAM ...
RUN
PARAMETER
SET CLOCK
SET CLOCK
SUMMER TIMEOk
Ok
12-I/O Pico 18-I/O Pico
or
SET CLOCK
SUMMER TIME
WINTER TIME
DAY : MO
TIME : 14:15
Ok
Ok
Esc
Esc
left/right arrows: Move cursorup/down arrows: Change valuesSave settingKeep previous value
Exit Menu
Publication 1760-GR001C-EN-P - April 2005
2-4 Drawing a Circuit with Pico
Winter/Summer Time (Daylight Savings Time)
Choose Pico Operating Mode
The two Pico operating modes are RUN and STOP.
• RUN: Pico processes the circuit diagram.
• STOP: Create and modify the circuit diagram.
The alternating RUN/STOP menu shows either RUN or STOP as follows:
• STOP mode active: RUN is shown
• RUN mode active: STOP is shown
Selectable Start-up Behavior
It is possible to select the operating mode to be activated when Pico is powered up. You can choose start-up in “RUN” mode or in “STOP” mode through the System Menu.
SET CLOCK
SUMMER TIME
Ok
Esc
Display: SUMMER TIME Winter time is setDisplay: WINTER TIMESummer time is set
Toggle Settings
Exit Menu
PROGRAM ...
RUN
PARAMETER
SET CLOCK ..
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-5
Pico Circuit Diagram Elements
Contacts
Contacts are used to modify the flow of current in the circuit diagram. Contacts in the circuit diagram are either make or break contacts. Make contacts are open when off (de-energized) and closed when on. Break contacts are closed when off and open when on.
Pico works with different contacts, which can be used in any order in the contact fields of the circuit diagram.
Contact Pico Representation
Make contact; Open when off I, Q, M, A, C, T, P, D, S, :, R
Break contact; Closed when off I, Q, M, A, C, T, P, D, S, R
Contact Type Make Contact
Break Contact
1760-L12xxx 1760-L18xxx1760-L20xxx
Controller Inputs I I I1 to I8 I1 to I12
0 signal I13 I13
Expansion Status – I14(3)
Short-circuit/overload I16 I15 to I16
Soft Inputs - Keypad P P P1 to P4 P1 to P4
Controller Outputs Q Q Q1 to Q4 Q1 to Q8
Internal Marker Bits M M M1 to M16 M1 to M16
Internal Marker Bits N N N1 to N16 N1 to N16
Counters C C C1 to C16 C1 to C16
Timers T T T1 to T16 T1 to T16
Real Time Clock(1)
Analog Setpoint Compare(2)
A A A1 to A16 A1 to A16
Text Display D D D1 to D16 D1 to D16
Expansion Outputs or Internal Marker Bits
S S S1 to S8 S1 to S8
Jump to Label : – :1 to :8 :1 to :8
Expansion Inputs R R – R1 to R12
Expansion Overload Detection
R R – R15 and R16(3)
1 to 8 1 to 8
Publication 1760-GR001C-EN-P - April 2005
2-6 Drawing a Circuit with Pico
Relays
Pico has thirteen different types of relay for use in a circuit diagram.
The switching behavior of these relays is set using coil functions and parameters. The coil functions and parameters are listed with the description of each function relay type.
Operating Hours Counter O O O1 to O4 O1 to O4
Year Time Switch Y Y Y1 to Y8 Y1 to Y8
Master Reset Z Z Z1 to Z3 Z1 to Z3
(1) Not available on “-NC” models.
(2) This applies only to the 1760-LxxBWB-xx and 1760-L12DWD.
(3) This applies only to 1760-L18xxx-EX models. R15 and R16 are used for expansion overload detection for the transistor expansion module, 1760-IB12XOB8, as described on page 9-4.
Contact Type Make Contact
Break Contact
1760-L12xxx 1760-L18xxx1760-L20xxx
Relay type Pico Symbol 1760-L12xxx 1760-L18xxx1760-L20xxx
Coil Function
Parameter
Controller Outputs Q Q1 to Q8 Q1 to Q8 X –
Internal Marker Bits M M1 to M16 M1 to M16 X –
Internal Marker Bits N N1 to N16 N1 to N16 X –
Counters C C1 to C16 C1 to C16 X X
Timers T T1 to T16 T1 to T16 X X
Real Time Clock(1) – X
Operating Hours Counters O O1 to O4 O1 to O4 X X
Analog Setpoint Compare(2) A A1 to A16 A1 to A16 – X
Text Display D D1 to D16 D1 to D16 X X
Jump to Label : :1 to :8 :1 to :8 X –
Expansion Outputs or Internal Marker Bits
S S1 to S8 (as marker) S1 to S8 X –
Year Time Switch Y Y1 to Y8 Y1 to Y8 – X
Master Reset Z Z1 to Z3 Z1 to Z3 X –
(1) Not available on “-NC” models.
(2) This applies only to the 1760-LxxBWB-xx and 1760-L12DWD.
1 to 8 1 to 8
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-7
The options for setting output and marker relays are listed with the description of each coil function.
Retentive Actual Values
With Pico 1760-L12BWB-xx, 1760-L12DWD, and 1760-L18xxx, it is possible to save the actual values of markers, timers and counters in the event of a power failure. The quantities and values that may be retained are found in the following table.
For further information see the Pico Controller User Manual, publication number 1760-UM001B-EN-P.
Retentive Relays
Relay Type Pico Symbol
1760-L12BWB-xx 1760-L12DWD
1760-L18xxx
Internal Marker Bits M 4 (M13 to M16) 4 (M13 to M16)
Counters C 1 (C8) 4 (C5, C6, C7, C8)
Timers T 1 (T8) 2 (T7, T8)
Text Display D – 8 (D1 to D8)
Publication 1760-GR001C-EN-P - April 2005
2-8 Drawing a Circuit with Pico
{
S,R
Basic Output Energize
Maintained/Flip-Flop Output
Latching Output
Instruction
Output
Instruction
Output
Reset Instruction
Output
Set Instruction
On
On
On
On
On
On
On
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-9
Example: Creating a Circuit Diagram
Interconnect Contacts and Relays
Draw Circuit in Circuit Diagram Menu
Insert Contact “I1”
I1-I2----{Q1
S1 S2CR1
M1CR1
Connecting Pico
1. Connect S1 to Pico input terminal I1
2. Connect S2 to Pico input I2
3. Connect load M1 to Pico output Q1
Pico circuit diagram
I 1 2 3 4 5 6 7 8
MO
14:15
Q1234 STOP
1 ...5 ..8 ....
RE I P
MO 02:00 ST
.2 ..5 ..8 RUN
PROGRAM...
RUN
PROGRAM...
DELETE PROGOkOk
Ok
OkOk
or
12-I/O Pico 18-I/O Pico
Start Status Display
I1
I1
I1
Ok
Ok
Ok
Circuit Diagram Display
Publication 1760-GR001C-EN-P - April 2005
2-10 Drawing a Circuit with Pico
Insert Contact “I2”
Draw Connection Between Contact and Relay Coil
Choose Relay Coil “Q1”
I1I1 I1
I1 I1
I1 I2
I1 I2
Ok
Ok
Ok
I1-I2
I1-I2---
I1-I2---
I1-I2Alt
I1-I2---
I1-I2------{Q1
I1-I2------{Q1
I1-I2------{Q1Ok
Ok
Ok
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-11
Change Operating Mode
Test Circuit Diagram
I1-I1----{Q1 PROGRAM
PROGRAM...
PROGRAM...
DELETE PROG
RUN
RUN
PARAMETER
SET CLOCK..Ok
Esc
Esc
Pico now in RUN mode
PROGRAM...
STOP
PARAMETER
SET CLOCK...
PROGRAM...
PARAMETER
SET CLOCK...
STOP
I1-I2----{Q1
Ok
Power flow display
Publication 1760-GR001C-EN-P - April 2005
2-12 Drawing a Circuit with Pico
Operate Switch “S1” and “S2”
Return to Status Display with ESC
I1-I2----{Q1
I1-I2----{Q1
I1-I2----{Q1“S1” on
“S2” on
Relay “Q1” picks up
I1-I2----{Q1 I 1 2 3 4 5 6 7 8
MO
13:34
Q1234 STOP
12............
RE I P
MO 02:00 ST
1.........RUN
PROGRAM...RUN
PARAMETER
SET CLOCK..
Esc
Esc
OkOk
or
12-I/O Pico 18-I/O Pico
In the next example, a timing relay will be added to the circuit.
Status display is activated.
Choose STOP mode.
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-13
Function Relay Types
Timing Relay
Circuit Diagram Symbol
Function Relay Type
Timing relay with on-delay, with and without random switching
Timing relay with off-delay, with and without random switching
Timing relay, single pulse
Timing relay, flashing
Counter relay, up/down counter
Time switch, weekday/time (only in Pico models with clock)
Analog comparator relay (only in Pico models with 24V dc)
X ?X
Trigger
Reset
on
on
on
t t t
Timing Relay with on delay, with and without random switching
Timer Output
Publication 1760-GR001C-EN-P - April 2005
2-14 Drawing a Circuit with Pico
With random switching, the relay contact switches randomly at any time up to the specified time value (shown shaded in figure).
?
Trigger
Reset
on
on
on
t t
Timing Relay with Off-Delay, with and without Random Switching
Timer Output
t t
Timing Relay, Single Pulse
on
on
onOutput
Reset
Trigger
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-15
Parameter Display for Timing Relays
tt t
Timing Relay, Flashing
Trigger
Reset
Timer Output
Flash Frequency = 1/2 x setpoint
on
on
on
RES
T1
+
S 30.00
{ TRG
00.00Switch Function
Time Units
Trigger (Connected)
Reset (Not Connected)
Accumulated Time
Setpoint
Timer Number
Parameter Display(Access Control)
Publication 1760-GR001C-EN-P - April 2005
2-16 Drawing a Circuit with Pico
Counter Relay
Parameter Display for Counter Relays
86420
7531
Count Input
Direction
Reset
Accumulated Value (setpoint = 6)
Counter Output
on
on
on
on
C1 N +AAAAASSetpoint
Accumulated Value
Counter Number Parameter Display(Access Control)
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-17
Real Time Switch
Example: Real Time Switch 1 switches on Monday through Friday between 6:30 and 9:00 and again between 17:00 and 22:30 (5:00 pm and 10:30 pm).
Parameter Display for Real Time Switches
D MO-FR
06:30
09:00
ON
OFF
1 A +
D MO-FR
17:00
22:30
ON
OFF
1 B +
on
on
on
D SU
ON --:--
OFF --:--
1 A +
Week Day(s) from - to
On Time
Off Time
Real Time Switch NumberParameter Display(Access Control)
Publication 1760-GR001C-EN-P - April 2005
2-18 Drawing a Circuit with Pico
Analog Comparator
Available functions:
• I7 ≥ I8, I7 ≤ I8• I7 ≥ Setpoint, I7 ≤ Setpoint
• I8 ≥ Setpoint, I8 ≤ Setpoint
The analog comparator can compare voltages from 0V to 10V (setpoints “0.0” to “10.0”).
Parameter Displays for Analog Comparators
Compare inputs I7 and I8.
TIP Analog signals of sensors typically fluctuate by several millivolts. For stable switching the setpoints should differ by at least 0.2V (switching hysteresis). Do not use any relay with output energize or impulse relay coil functions.
ANALOG
I7 8.0 V
A1
I8 4.2 V +
ANALOGI7 8.0 V
A1
+3.2
Input I7
Input I8
Compare Function
Current Value
Analog Compare Number
Parameter Display(Access Control)
Current Value
Input I7/I8
Compare Function
Setpoint
Current Value
Relay Number
Parameter Display(Access Control)
Compare input “I7” to a setpoint.
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-19
Text Display
The Text Display is used to display eight freely definable messages on the Pico screen. Each text block displays up to 48 characters from the Pico display character set (ASCII + Pico special characters). If the Text Display is enabled, the text entered via PicoSoft is displayed. If several Text Displays are enabled, the next screen is displayed every 4 seconds. When Text Display D1 is enabled it stays displayed (fault indication).
Press Ok to switch to the menus at any time.
Current values or parameters of function relays can be displayed in lines 2 and 3.
Examples:
CAUTION!
PUMP 1
MOTOR
MALFUNCTION
THE TIME
IS
14:42
TIME RELAY 1
SETP99.00 S
QUANTITY
ACTV 0042
PCS
SETP0100
ACTV 42.00 S
Fault Signals Time with Text Display
Display Current Value and Parameter of Timing RelayDisplay Counter Value
Publication 1760-GR001C-EN-P - April 2005
2-20 Drawing a Circuit with Pico
Example: Use a Function Relay
Conventional Circuit
Select an Internal Marker Relay
Select Marker Contact and Connect to New Output Relay
I1-I2----{M1
M1-------TT1
T1-------{Q1
S1 S2CR1
T1M1
T1CR1 10.0 sec
Pico switches M1 with 10 seconds delay.
Pico Circuit Diagram
I1-I2----{Q1 I1-I2----{Q1
I1-I2----{M1
I1-I2----{M1
Ok
Ok
Start Circuit from first examplePosition cursor on “Q”
2 X
I1-I2----{M1 I1-I2----{M1I1
I1-I2----{M1
M1------ {Q1
Ok
OkOkAlt
2 X 2 X3 X
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-21
Select Trigger Relay for Time
Insert Timing Relay Contact
Select Parameter Access
I1-I2----{M1 I1-I2----{M1
I1-I2----{M1
M1-------{Q1 M1-------TT1
M1-------TT1Ok
2 X
I1-I2----{M1 I1-I2----{M1
I1-I2----{M1
M1-------TT1
M1-------TT1
M1-------TT1
T1
I1
Ok
2 X
I1-I2----{M1
M1-------TT1
T1
X
S 00.00
{ TRG T1
RES +
Ok
2 X
Publication 1760-GR001C-EN-P - April 2005
2-22 Drawing a Circuit with Pico
Set “10 Seconds”
Connect Timing Relay Contact to New Output Relay
Change Pico to RUN to test the program. Test the circuit as shown for the first example. To display and access the parameters for the timing relay and change the time value in RUN mode, position the cursor in the circuit diagram on the “T” of “T1” and press Ok.
T1 X
S 00.00
TRG
RES
Ok
+ T1 X
S 00.00
TRG
RES
+
T1 X
S 10.00
TRG
RES
+2 X
2 X back to circuit diagram
I1-I2----{M1 I1-I2----{M1
I1-I2----{M1
M1-------TT1M1-------TT1
M1-------TT1
T1 T1
T1-------{Q1
Alt
Ok
3 X 3 X
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-23
Basic Circuits Significance of Logic Values
Negation (NOR)
Permanent Contact (Unconditional Rung)
Flip-Flop Output
Value Function
“0” Make contact open, break contact closed, relay coil not energized
“1” Make contact closed, break contact open, relay coil energized
I1 Q1
1 0
0 1
--- Q1
1 1
I1 State Q1 Q1
0 0 0
0 to 1
0 1
0 1 1
0 to 1
1 0
I1---------{Q1
-----------{Q1
I1--------- Q1
Publication 1760-GR001C-EN-P - April 2005
2-24 Drawing a Circuit with Pico
Series Connection (AND)
Parallel Connection (OR)
Exclusive OR Circuit (XOR)
I1 I2 I3 Q1 Q2
0 0 0 0 1
1 0 0 0 0
0 1 0 0 0
1 1 0 0 0
0 0 1 0 0
1 0 1 0 0
0 1 1 0 0
1 1 1 1 0
I1 I2 I3 Q1 Q2
0 0 0 0 1
1 0 0 1 1
0 1 0 1 1
1 1 0 1 1
0 0 1 1 1
1 0 1 1 1
0 1 1 1 1
1 1 1 1 0
I1 I2 Q1
0 0 0
1 0 1
0 1 1
1 1 0
I1-I2-I3-{Q1
I1-I2-I3-{Q2
I1--------{Q1
I2
I3
I1--------{Q2
I2
I3
I1-I2------{Q1
I1-I2
Publication 1760-GR001C-EN-P - April 2005
Drawing a Circuit with Pico 2-25
Motor Start/Stop Circuit
I1 I2 Contact
Q1Coil Q1
0 0 0 0
1 0 1 1
0 0 1 1
0 1 0 0
1 1 0 0
I1--I2-----{Q1
Q1
I1--------SQ1
I2--------RQ1
Alternatively:
Publication 1760-GR001C-EN-P - April 2005
2-26 Drawing a Circuit with Pico
Publication 1760-GR001C-EN-P - April 2005
Chapter 3
Pico Interface Socket
The Pico interface socket, which is beneath a protective cap, accepts the optional Pico memory module, or connects Pico to a PC using the optional PC interface cable and the PicoSoft software. This allows you to copy the circuit diagrams to and from the PC and/or memory module.
Memory Module
Memory modules are available as an optional accessory. Each memory module can store a single Pico circuit diagram. Information stored on the memory module is non-volatile (the information is not lost when the power is turned off). The memory module can be used to make a backup copy of a program and/or to transfer it to another Pico controller.
Each memory module can hold one Pico program, up to 32K.
Each memory module stores:
• the circuit diagram
• all parameter settings of the circuit diagram
• system settings
1760-MM1 for all 1760-L12xxx controllers
1760-MM2 for the 1760-L18xxx controllers
1 Publication 1760-GR001C-EN-P - April 2005
3-2 Pico Interface Socket
Load or Store the Circuit Diagram
You can only transfer the program from Pico to the memory module or vice versa in the STOP mode.
DEVICE - CARD: Transfer circuit diagram and parameter settings from Pico to the memory module.
CARD - DEVICE: Transfer circuit diagram and parameter settings from the memory module to Pico.
DELETE CARD: Delete the contents of the memory module.
Available Memory Modules
The following memory modules are available as Pico accessories.
Programs including all relevant data can be transferred from the 1760-MM2B memory module to the Series B Pico Controllers. The existing 1760-MM1 and 1760-MM2 memory modules are Read-Only when used with Series B Pico Controllers. The 1760-MM2B memory module will not work with Series A Pico Controllers.
ATTENTION ELECTRICAL SHOCK HAZARD
The memory module and PC-cable socket are at the potential of L2. There is a danger of electric shock if L2 is not grounded. Do not make contact with electrical components under the socket cover.
Pico Controller Memory Module
1760-L12xxx 1760-MM1 (Series A only)
1760-L18xxx 1760-MM2 (Series A only)
Series B Pico Controllers 1760-MM2B
DEVICE -> CARD
CARD -> DEVICE
DELETE CARD
Publication 1760-GR001C-EN-P - April 2005
Pico Interface Socket 3-3
PicoSoft
PicoSoft is an optional PC program that creates, stores, and manages Pico circuit diagrams. It transfers the circuit diagrams from the PC to Pico or vice versa using a special PC interface cable.
The PicoSoft software also includes extensive on-line Help.
To use the on-line Help, start PicoSoft and choose Contents in the Help menu. Context sensitive help is also available. Choose a menu item with the mouse and press F1 while keeping the mouse button pressed.
Software Compatibility
If you are using programming software to program the Pico controller, be sure that you are using the correct software version.
Find the Series Letter
The Series letter is printed on the side of the housing as shown.
Download the Software
You can download a free copy of PicoSoft version 6.1 from our web site. Go to http://www.ab.com/picosoft6.
For PicoSoft Pro, please contact your Allen-Bradley Distributor or Rockwell Automation representative.
ATTENTION The PC interface cable is catalog number 1760-CBL-PM02 and is available as an accessory item. Only use the Pico interface cable. Do not attempt to make your own cable as this can cause damage to the unit or present a shock hazard.
IMPORTANT PicoSoft version 6.1 or higher must be used to for the Series B Pico controller. Earlier versions of PicoSoft can only be used with Series A Pico controllers.
Publication 1760-GR001C-EN-P - April 2005
3-4 Pico Interface Socket
Publication 1760-GR001C-EN-P - April 2005
Appendix A
Specifications
Physical Specifications
Product Selection Table Controllers
Specification 1760-L12xxx 1760-L18xxx, 1760-L20xx1760-IA12XOW6I,1760-IA12XOW4I1760-IB12XOB81760-IB12XOB8
1760-OW2
Weight 200g (7 oz) 300g (10.6 oz) 70g (0.154 lb)
Ambient temperature, (operation) -25°C to + 55°C (-18°F to 131°F)
Storage Temperature -40°C to +70°C (-40°F to +158°F)
Operating Humidity 5 to 95%, non-condensing
Emitted interference, interference immunity
EN 55011, EN 55022, Class B
Standards and regulations Approvals
EN 50178UL, CSA, CE, C-Tick
Catalog Number Inputs Outputs Line Power Real Time Clock
Display and Keypad
Analog
1760-L12AWA 8 (120/240V ac) 4 (relay) 100 - 240V ac Yes Yes No
1760-L12AWA-NC(1) No Yes
1760-L12AWA-ND(2) Yes No
1760-L18AWA 12 (120/240V ac) 6 (relay) Yes Yes
1760-L18AWA-EX(3) Yes Yes
1760-L18AWA-EXND(2)(3) Yes No
1 Publication 1760-GR001C-EN-P - April 2005
A-2 Specifications
1760-L12BWB 8 (24V dc) 4 (relay) 24V dc Yes Yes 2 (0 to 10V dc)
1760-L12BWB-NC(1) No Yes
1760-L12BWB-ND(2) Yes No
1760-L12BBB 4 (MOSFET) Yes Yes 2 (0 to 10V dc)
1760-L12BBB-ND Yes No
1760-L12NWA 8 (24V ac) 4 (relay) 24V ac Yes Yes
1760-L12NWA-ND Yes No
1760-L12DWD 8 (12V dc) 12V dc Yes Yes
1760-L12DWD-ND Yes No
1760-L18BWB-EX(3) 12 (24V dc) 6 (relay) 24V dc Yes Yes
1760-L18BWB-EXND(2)(3) 6 (relay) Yes No 2 (0 to 10V dc)
1760-L20BBB-EX(3) 8 (MOSFET) Yes Yes 4 (0 to 10V dc)
1760-L20BBB-EXND(2)(3) 8 (MOSFET) Yes No
1760-L18DWD-EX(3) 12 (12V dc) 6 (relay) 12V dc Yes Yes
1760-L18DWD-EXND(2)(3) 6 (relay) 12V dc Yes No
1760-L18NWA-EX(3) 12 (24V ac) 6 (relay) 24V ac Yes Yes 4 (0 to 10V dc)
1760-L18NWA-EXND(2)(3) 12 (24V ac) 6 (relay) Yes No
(1) NC = no real time clock
(2) ND = no display
(3) EX = suitable for use with expansion modules
Catalog Number Inputs Outputs Line Power Real Time Clock
Display and Keypad
Analog
Publication 1760-GR001C-EN-P - April 2005
Specifications A-3
Expansion Modules
Accessories
Catalog Number Inputs Outputs Line Power
1760-IA12XOW6I 12 (100 - 240V ac) 6 (relay) 100 - 240V ac
1760-IA12XOW4IF 12 (100 - 240V ac) 4 (relay) 100 - 240V ac
1760-IB12XOW6I 12 (24V dc) 6 (relay) 24V dc
1760-IB12XOB8 12 (24V dc) 8 (transistor) 24V dc
1760-OW2 - 2 (relay) 24V dc
Catalog Number Description
1760-MM1 Memory Module for 12 I/O Pico Controller
1760-MM2 Memory Module for 18 I/O Pico Controller
1760-MM2B Memory Module for Pico Series B Controllers
1760-CBL-PM02 Programming Cable for Pico Controller
1760-RPLCONN Expansion Module Connector - included with expansion module. Catalog number listed is replacement part.
1760-SIM Input Simulator for 12 I/O 24V dc Pico Controller
1760-PICOSOFT Configuration Software for Pico Controllers.
D1760GR001BENP Pico Controllers Getting Results Manual, publication number 1760-GR001B-EN-P
D1760UM001BENP Pico Controllers User Manual, publication number 1760-UM001B-EN-P
Publication 1760-GR001C-EN-P - April 2005
A-4 Specifications
Dimensions Pico 1760-L12xxx
Pico 1760-L18xxx, 1760-L20xxx and Expansion Modules
10.75 50 1.97"
M4
35.75 1.41"
71.5 2.81"
90 3
.54"
102
4.0
2"
110
4.3
3"
47.5 1.87"
56.5 2.22"
58 2.28"
45 1
.77"
4.5 0.177"
0.423"
903.54"
1024.02"
1104.33"
M4
107.5 4.23"
75 2.96" 16.2516.25
47.5 1.87"
56.5 2.22"
58 2.28"
451.77"
4.5 0.177"
0.640"0.640"
Publication 1760-GR001C-EN-P - April 2005
Specifications A-5
Pico 1760-OW2 Expansion Module
Dimensions of the 1760-RM… Remote Processor modules
M4
7.5
35.5 1.4"
7.5 0.295"
0.295"
90
3.54
"
102
4.0
1"
110
4.3
3"
176-RM… 1760-DU… and 176-RM…
75 2.95"
58
2.2
8"
36.2 1.43"22.50.89"
22.50.89"
30 1.18"
20.50.81"
27.51.08"
43.2 1.7"
Publication 1760-GR001C-EN-P - April 2005
A-6 Specifications
Publication 1760-GR001C-EN-P - April 2005
Index
Aaccessories A-3Allen-Bradley
contacting for assistance Preface-iiisupport Preface-iii
Analog comparator 2-18
BBasic circuit
Exclusive OR circuit (XOR) 2-24Flip-flop output 2-23Impulse relay 2-23Motor start/stop circuit 2-25Negation (NOR) 2-23Permanent contact 2-23Series connection (AND) 2-24
Break contact 2-5Buttons 1-10
Use in circuit diagrams 2-1
CCable 3-3Change operating mode 2-4Circuit diagram
Access relay parameters 2-21Choosing relay type 2-10Displaying 2-9Example 2-9, 2-20Inserting contacts 2-9Loading 3-2Select marker relay 2-20Storing 3-2Symbols 1-14Testing 2-11Using a function relay 2-20Using buttons in 2-1
Circuit diagram elements 2-5Coil function 2-8common techniques used in this manual
Preface-iicontacting Allen-Bradley for assistance
Preface-iiiContactor function 2-8Contacts
Overview 2-5Counter relay 2-16
Parameter display 2-16Cursor display 1-13
D
dimensions1760-L12 A-41760-L18 A-41760-L20 A-41760-OW2 A-51760-RM A-5expansion modules A-4
EExample
Basic circuits 2-23Circuit diagram 2-9Contacts and relays 2-9
Example of function relay 2-20
FFunction relays
Analog comparator 2-18Counter relay 2-16Overview 2-13Text display 2-19Time switch 2-17Timing relay 2-13
KKeypad 1-10
LLogic tables 2-23
MMake contact 2-5manuals, related Preface-iiMemory Module (optional) 3-1Menu guidance 1-11Menu structure 1-15Mounting 1-3
OOperating buttons 1-10
PParameter display
Analog comparator 2-18Counter relay 2-16For timing relays 2-15Time switch 2-17
Publication 1760-GR001C-EN-P - April 2005
2 Index
physical specifications A-1Overview of Pico 1-2PicoSoft 3-3Programming cable 3-3publications, related Preface-iiPurpose of this Manual Preface-ii
Rrelated publications Preface-iiRelay types
Overview 2-6
Sselection table
controllers A-1selections table
expansion modules A-3Setting the time 2-3Setting week day 2-3Software 3-3specifications
physical A-1Startup behavior 2-4Status display 1-12Summer time 2-4
Symbols in circuit diagram 1-14System menu 1-18
TTerminals, inputs/outputs 1-4Text display 2-19Time switch 2-17
Parameter display 2-17Timing relays 2-13
Parameter display 2-15troubleshooting
contacting Allen-Bradley for assistance Preface-iii
WWinter time 2-4Wiring diagrams
1760-L12AWA-NC, 1760-L12AWA, and 1760-L12AWA-ND 1-4
1760-L12AWA-xx and 1760-L12BWB-xx 1-5
1760-L12BWB and 1760-L12BWB-NC 1-4
1760-L18AWA 1-91760-OW2 1-9
Publication 1760-GR001C-EN-P - April 2005
Publication 1760-GR001C-EN-P - April 2005 2 PN 40072-085-01(3)Supersedes Publication 1760-GR001B-EN-P - July 2001 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
New Product Satisfaction Return
Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States 1.440.646.3223
Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for return procedure.