petroleum storage tank fire
TRANSCRIPT
-
7/31/2019 Petroleum Storage Tank Fire
1/5
Petroleum storage tank fire
Three basic methods of fire protection of Storage tanks are
SubSurface base injection Over the top application( Surface Application) Foam chamber Foam maker Foam Monitor Foam Tower Dike protection
Sub Surface Base injection
This method is is used on hydrocarbon fuel stored in cone roof Tanks
This method is unsuitable for protecting floating roof tank( open or covered),Cone roof tanks with
internal floater, or floating roof and dike protection
Produces foam using high back pressure foam maker located outside the storage tank. Expanded foam
is delivered through product line piping or through one dedicated for foam line.
- Discharge outlet must be one feet( minimum) above any water present at the base of the tank.-
High back pressure foam maker as pirate foam solution. It will give an expansion ratio of 2:1and 4:1.it can discharge against a back pressure as high as 40% of operating pressure (Back
pressure is the accumulation of head pressure of fuel inside the tank and the friction loss
between foam maker and the tank)
- Minimum operating pressure into HBFM -100psi- Foam velocity entering tank should not exceed 10 feet/sec for flammable liquid- Foam velocity for combustible liquid should not exceed 20 feet /sec
Discharge time and application rate for SubSurface application
Flashpoint 37.8C to 93.c 30 mins .10gpm/ftsq( 4.1 lpm/msq)
Fp
-
7/31/2019 Petroleum Storage Tank Fire
2/5
Discharge Outlets
Type -2 discharge outlets Fixed Devices that delivers foam into burning fuel partiallysubmerges the foam and produce limited agitation on the surface .e.g Foam chambers and foam
makers
Type-3 discharge outlets Fixed or portable device that delivers foam in such manner that itfalls on the surface of the liquid causing agitation e.g hose stream nozzles, monitors
CONE ROOF TANK
Requires the use of foam chambers for surface application which prevents the flammable vapors to
enter the supply pipe line( Frangible rupture disc)
Floating roof foam makers dont contain vapor seal so it cannot be used in cone roof
Surface area when protecting single storage tank -3.14r2
Surface area of multiple tanks
Calculate the surface area of the most severe hazard which is the storage tank that will requirethe most foam concentrate protection.
when all the tanks contain the same fuel consider the largest tank to be most severe. When tanks contain different fuels determine the surface area discharge time ,application rate
for each tanks and then select the one which require the most foam concentrate
Minimum Discharge time and foam application rate for type-2 foam discharge device
Flashpoint 37.8C to 93.c 30 mins .10gpm/ftsq( 4.1 lpm/msq)
Fp
-
7/31/2019 Petroleum Storage Tank Fire
3/5
Floating Roof Tank
Can be protected with floating roof foam maker or foam chambers. As flammable vapors are minimized
so vapor seal is not required. The piping from foam maker is above is above the floating roof of the tank
and open to atmosphere.
Top of seal protection requires a discharge time of 20 mins and an application rate of .30gpm/ftsq.
Below seal protection requires discharge time of 10 mins and application rate of 0.50gpm/ftsq
Supplementary hose lines and discharge times required for small spill fires or dike protection-
Fixed or portable hose lines with a minimum flow rate of 50gpm/nozzle
35 feet 1 10 min
35-65 feet 1 20mins
65 -95 feet 2 20 mins
95 to 120 feet 2 30 mins
>120 feet 3 30 mins
Dike protection
The dike area rather than individual storage tanks may be considered for hazard to be protected and a
fixed foam system using monitor, floating roof foam maker is required
Number of monitors minimum two
Floating roof foam makers 30 feet spacing discharge 60gpm flow or less
>60 gpm flow spacing 60 feet
Spill Fire protection
Hydrocarbon spill fires requires a minimum nominal foam application density of 0.1gpm/sq feet.
Therefore a 50gpm hand line has the capability to control and suppress 500sq ft of flame surface area.
Largest potential spill must be considered to determine the number type and location of the dischaegedevice as well as quantity of foam required.
Protection option Fixed system such as monitors oor portable equipment such as hand hose lines
Discharge time
15 mins for fixed systems
-
7/31/2019 Petroleum Storage Tank Fire
4/5
15 mins with portable equipmentFoam monitors & hand line
Monitors are not to be considered as primary means of protection for fixed roof tanks over 60 feet dia
Foam hand lines are not to be considered as primary means for protecting tanks over 30 feet dia or hose
over 20 feet in height
Application Density & duration
Fp 37.8.c to 93.3.c 0.16 gpm/ft2( 6.5lpm/m2) 50 mins
< 37.8.c do 65mins
Crude do 65 mins
Polar Solvents Recommended by manufacturers 65mins
Flammable liquid having boiling points less than 100.f and products which has been burning for
sometime may develop heat layer which might require application rate as high as 0.2 to .25gpm/ftsq.
Full surface fire -0.25 gpm( 10.4 lpm /ft2) application rate may be required. Burning crude oil tank may
require application rate of 0.32gpm/ft2( 12.9 lpm/m2)
Elevated application rate provides a better chance of
Foam reaching the burning surface Fall out from delivery system Losses due to thermal updraft Breakdown of foam as it trvels through the flames to reach the burning fuel and the destruction
of the foam due to hot fuel and any hot metal surface.
Cooling water requirement
Cooling water requirement of involved tank shell is estimated by tank size/dia-
100 feet dia 750gpm ( 3metre cube/min)
120 feet dia 1000gpm( 4m3/min)
160 feet dia 1250 gpm( 5m3/min)
220feet dia 1500gpm ( 6m3/min)
-
7/31/2019 Petroleum Storage Tank Fire
5/5
Cooling water required to protect each adjacent tank not shielded from the tank on fire is
500gpm(2m3/min)
Cooling water rate of0.05 gpm( 2m3/min) is sufficient to absorb 90% of the radiant heat.
Hoses
5inch dia hoses is preferred
One 5inch hose line for every 100gpm( 3.8m3/min) flow requirement.At this flow rate friction loss is 8.0
psi for every 100 feet
FOAM DAMS
Foam dam height should not be less than 12 inches
Foam dams are to be at least 1 feet but no more than 2feet from the edge of the floating roof
Number of fixed discharge points on an open top floating roof tank is determined by the circumference
of the tank
Spacing is based on height of the foam dams
40 feet of tank circumference when using 12 inch foam dam 80 feet of tank circumference when using 24 inch high foam dam