Page 1: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

OEM- r - n ~ -

AD-781 644

FERRO-CEMENT CONSTRUCTION PANELS

H. H. Haynes, et al

Civil Engineer ing Laboratory (Navy)Port Hueneme, California

April 1974

DISTRIBUTED BY:

National Technical Intormati ServiceU. S. DEPARTMENT or COMMERCE5285 Port Royal Road, Springfield Va. 22151

Page 2: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

0) Unclassified.SECURITY CLASSIFICATION OF T.15S PAGE 'BA ,to F~.E,,-d)

REPORT DOCUMENTATION PAGE REORAD COMPLETINORM1 REPORT Numor R 11 GOVT ACCESSION NO, I RECIPIENT'S CATALOG NUMBER

TN-1341 14b _79/I65/l4 TITLE (-dA 5011k TYPE OF REPORT II PERIOD COVERED

Not finalFERRO-CEMENT CONSTRUCTION PANELS Jun 1971 to Jul i973

7 PERFORMING ORG. REPORT NUMBER

? AUTHOr;, 5 CONTRACT OR GRANT NUMBER(.)

H. H. HaynesG. S. Guthrie

9 PERFORMING ORGANIZATION NAME AND ADDRESS 10 PROGRAM EL EMENT. PROJECT. TASKI

Civil Engineering Laboratory ARE A A WORK UNI T NUMBERS

Naval Construction Battalion Center ZF 6 1-512-053Part Huenempe CA CQ3A41 ______ _______11 CON'ROLLINO OFFICE NAME AND ADDRESS 12 REPORT DAT

Director of Navy Laboratories April 1974Washington, DC 20376 13 NUMBER OF P45LS5

4214 MONITORING AGENCY NAME AADORESS,,I dI,if, J-.lII,, Off-eI IS SECURITY CLASS 10 IhlllrepII)

ITSe DCLASSIFIC ATION DOWNGRADING~EOULEIA DISTRIBUTION STATEMENT (0, IA,, Rttpo,I

Approved for public release; distribution unlimited.

I7 DISTRIBUTION STSTEMENT f0) lhe mb--0r --II~d I, Bloch 20. H d~i.,,,,, 1-,, ROp.,fI

ie SUPPLEMENTARY NOTESJ

IA KEY WORDS ,C,r,n ,r Id ,, l d It n1.-1- *,, d de-,,I It, f,, kIO 0,b,,

C:.ILI~l0.. anD>., :,;E.j i.cnicii, corrosion resistance, flexural strength, applications,joining and fastening, fabrication, field workability

20 ABSTRACT (C-~l',0~ ,o..,do it n..,,, d ,d1,fYI, bF bt.,S t-h-)A.

Two designs of multipurpose ferro-cement construction panels were evaluated as totheir versatility for military applications and their strngth under flexural loads. The recom-mended panel design has a thicknes:I of 1/2 in., width of 12 in., length of 8 ft. cross-sectionof a modified channel, and weight of 86 lbs. Ultimate load carrying ability of the panel undersingle point flexure was 1,545 lbs which corresponded to an ultimate flexural stress of 4,300psi for the ferro-cement material.

Tests on the corrosion resistance of ferro-cement were also conducted in a salt pray _yDO ',AN",5 1473 EDI1TION OF 1 NOV 13SIS OBSOLETE Unclassified

SECURITY CLASSIFICATION OF TIS PAGE Wh1. Pol. F.1IBd)

Page 3: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

Unclassified

SECURITY CLASSIFICAT10W OF THIS PAGE(WI,.. D.I. E,,.,.d)

Block 20. Continued

chambcr for up to 6 months. Visual observation of the panel surfaces showed rust stains thatindicatcd substantial corrosion of the steel reinforcement; however, the average ultimatestrength of the specimens was not significantly reduced.

Unclassified

SECURITY CL ASSIrIC ATION 1 I PAFh D- F,-,.d)

Page 4: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

ICONTENTS

Page

OBJECTIVE 1

INTRODUCTION 1

PANEL DESIGN AND APPLICATIONS 2Panel Design 2

Applications 3

TEST PROGRAM 4

Scope 4Flexural Tests on Construction Panels 4Effect of Corrosive Environment 6

DISCUSSION 9

SUMMARY 10

II

.1'i

Page 5: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

I.OBJECTIVE

The objective of the study was to develop a multipurpose

ferro-cement construction panel which would satisfy a wide range ofmilitary needs at advanced bases.

The study consisted of selecting a versatile panel configurationand then determining the flexural load carrying behavior of the panel.

Additional work was conducted to study the durability of the ferro-cement,aterial in a corrosive environment.

INTRODUCTION

Ferro-cement is a term applied to a highly steel reinfo.cid

portland cement mortar (mortar is a concrete which uses aggregatethat passes the 1/4 in. sieve). The predominate ?resent day application

for ferro-cement is in the amateur boat building industry where hulls30 to 50 feet 4n length are fabricated with wall thicknesses from3/4 to 1 inch.

There is no innate reason why ferro-cement should be limitedto floating craft. The physical property that makes ferro-cementdesirable for boat hulls is the high flexural strength of a thinsection of reinforced concrete material.

This same flexural property can be and has been utilized foron-land structures, for applications such as roofs, walls, andeven diving boards. Yet these applications are isolated examples andferro-cement is only slowly being recognized for its potential toon-land applications. Because it is a labor intensive constructionmaterial, its use in developed countries will always be marginal unlessautomated procedures are developed for manufacturing ferro-cementproducts. However, for underdeveloped countries, ferro-cement is anoutstanding construction material. The Board of Science andTechnology for International Development of the National Academy of

Sciences, has recently completed a study on the various applicationsof ferro-cement for developing countries [1]. The range of applicationsis most impressive and realistic: from food storage bins to smallwater tanks to simple shelters. The main feature of ferro-cement is

that the technology is not complex; the foreign nationals can fabricatetheir own structures from chicken wire, cement, and sand, and expect along usable life from the structure because of the durability of ferro-

cement.It is this durability feature in marine and tropic environments

that should be of interest to the military for advance base construction.

Wood rots quickly and steel requires much maintenance in a marine or

tropical environment. Ferro-cement has the durability of a concretetmaterial and can withstand hostile environments. The steel reinforcement

Page 6: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

is protected from corrosion by the high alkalinity (high pH)

content of the mortar matrix. An example of ferro-cement durabilityis a small, Dutch ferro-cement boat that was built in 1887 and wasstill afloat in good condition after 70 years use at the Amsterdamzoo [11.

Besides durability, there are other advantages of ferro-cementto the military. It is a very adaptable construction material.Structures of any shape can be built without the use of forms.Chicken wire is layed up into the desired shape and mortar ispla-tered on. Ferro-cement is a nonflammable material, and thisfor some applications can be a very desirable feature. Militarypersonnel not familiar with ferru-cement can build with the materialwhen supervised by a knowledgeable person. This means that manymen could be mustered to build defensive works, if necessary.

Ther are two approaches that can be taken in building withferro-cemej'-. one approach is to start with the individual componentsof steel reinforcing mesh, cement, and sand and build the structurein place from the ground up. The other approach is to use precastpanels of ferro-cement to assemble the structure.

This report is airected mostly toward the concept of using precastconstruction panels. The same features of durability and fire resistanceapply. Some "flexibility" in designs is sacrificed, but speed ofconstruction is greatly improved.

A construction panel that is designed for multi-purpose applicationscould be thought of as a unit of construction--just as a 2x4 timbermember is thought of as a unit of construction. With a ferro-cementpanel many structural needs could be satisfied. If the panel couldbe used for different applications, the logistic supply of the advancedbpce could be simplified. Numerous different types of construction

materials could be replaced with a large quantity of one item, themultipurpose ferro-cement panel.

Transportation costs of the panels could be reduced by allowingforeign nationals of an ally country or a friendly neighboring countryto manufacture the panels. The panels could be manufactured by hand

labor, a semi-automated process or a fully automated process.One of the key ingredienLs in the concept of using precast

multipurpose construction panels is the proper design of the panelitself. The following section discusses panel design.

PANEL DESIGN AND APPLICATIONS

Panel Design

Initial guideline criteria for the panel design were that thepanel must be capable of sustaining flexural and compressive loadsand that the panel should weigh less than 100 pounds. Length of thepanel w,.z defined as 8 feet because this corresponds to standaraU.S. dwelling wall height.

To stay within the weight and length criteria, the other dimensionsof the panel were limited to approximately 1/2 inches in thickness and

h2

Page 7: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

-; 12 inches in width for a panel having a corrugated cross section. The

corrugated cross section is required to increase the flexural loadcarrying ability of the 1/2 in. thick ferro-cement.

With the approximate dimensions roughed out, the shape cf thecross-section had to be determined. Numerous shapes were evaluated(Figure 1) for their versatility in being assembled in differentways. Two basic shapes were selected as having merit, the modified

channel section (Figure 2) and the hat section (Figure 3). The actualsizes of the corrugations were determined by a trade-off betweensection modulus and versatility in assembling panels. Figures 2ar.d 3 give the final dimensions of the panels. Weight of the panelswas bb pounds for the channel sectio; a_' '2 pounds for the ht section.

Applications

Figures 4 and 5 show some of the different methods of assembling

the pa:.els. Using these assembly techniques, multipurpose panels wouldhave the following applications at advance bases:

bunkersfoxhole coversrevetmentsarmoi plating for existing structuresprotective barrier for bridge piers

- helicopter landing padsdead-man anchorsretaining wallspilessheet pilingcoffer damsquay walls

canal liningswater tankswater cisternsraftssampanspersonnel shelterswarehouses

sewerage tanksshower stallsfoundations

wallsfloorsroofsbuilt-up columns

built-up beamsforms for concrete

Several full scale panels of both the channel and hat cross-sectionwere fabricated to demonstrate assembly methods and to undergo structuraltesting. Figures 6 through 11 show some of these panels assembled for

3

Page 8: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

various applications. A sketch of a bunker constructed of panels isshown in Figure 12. Both bunkers and revetments would use the doublewall construction approach (see Figure 9) where the space between thewalls is filled with soil.

Conventional means of joining panels together would be used:nails, forced-entry fasteners, bolts and nuts, pop-rivets, or adhesivebonding. For applications requiring watertightness, adhesive bondingmay be sufficient alone or zinc-chromate compound should be used inconjunction with mechanical fasteners.

Ferro-cement materials can be "worked" in the field; that is, thepanels can be cut or drilled using portable power hand tools. Portablesaws need a masonry blade and drills need a masonry b~t. If powertools are not available then a cold steel chisel can be used to cutor punch holes in the panel.

In summary it was determined that the channel section panel was moreversatile in methods of assembly than the hat section panel. Awider range of applications cor'ld be serviced by the channel sectionpanels.

TEST PROGRAM

Scope

The test program consists of two phases. Phase 1 evaluated theflexural load carrying capability of prototype ferro-cement constructionpanels and Phase 2 investigated the effect of a corrosive environmenton the strength of ferro-cement.

Under Phase 1, six panels of t;,) cross-sectional designs weresubjected to single point flexural loads. The panels were full-scaleprototypes of multipurpose construction panels. Two reinf ementschemes for the ferro-cement were used in the fabrication of thepanels, a plain steel woven mesh ana a galvanized chicken wire.

Under Phase 2, the construction panels were cut into smallrectangular specimens, 3 by 12 in. and subjected to an acceleratedcorrosive environment in a salt spray (fog) environment. After 4 and6 months in the salt spray nvironment, the ultimate flexural strengthof specimens was determined and compared with the strength of controlspecimens.

Flexural Tests on Construction Panels

Test Specimens. The test specimens were full scale panels;three panels had a channel cross-section and the other three panelshad a hat cross-section. The physical characteristics of the panels,surh as, moment of inertia and section modulus are given in Table 1.

4

Page 9: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

I.

The ferro-cement material comprised a mortar matrix and steelreinforcement. The mortar consisted of Type II portland cement andriver wash aggregate of the following sieve sizes:

Sieve Size Percent Retained

30-50 6150-100 27on pan 12

Proportions for the mix were sand/cement ratio of 2.6, water/cementratio of 0.65, a water reducing additive (Plastoment) of 2 oz/sack,aid a chromium trioxide (Cr03) additive of 300 parts per million byweight of the mixing water. The chromium trioxide additive was usedto prevint qalvanic cell activity within a freshly poured panel [2].

The compressive and split tensile strength of 3 x 6-in. controlcylinders is given in Table 2. At the age of about 63 days, the averagecompressive streng h was 6,080 psi and the average split tensile strengthwas 610 nsi.

7,o reinforcement schemes were used in the ferro-cement. The mainsys--ru was selected from an earlier study [3] and consisted of a totalof six layers of 1/4 x 1/4-in, plain woven wire mesh of 0.025-in. wirediameter. At tue center of the six layers was a single layer of1 x 2-in. galvanized welded wire of 0.0625-in. diameter. The otherreinforcement scheme was for comparison purposes and it consisted ofsix layers of 1-in. hexagonal galvanized chicken wire of 0.0325-in.diameter. Also at the center of the six layers, was a single layer of1 x 2-in. galvanized welded wire of 0.0625-in. diameter. The percentageof steel reinforcement for the panels in the longitudinal directionwas 2.9 for the panels with 1/4 x 1/4-in, mesh and 2.6 for the panelswith chicken wire. The ultimate tensile strength of the reinforcementwas 93,000 psi for the 0.025-in. diameter wire used in the 1/4 x1/4-in, mesh and 61,000 psi for the 0.0325-in. diameter wire used

in th-e chicken wire.'abrication of the specimens fo?.lowed this procedure: (1) the mesh

ieinforcement was layed up as flat sheets and were all bent at thesame time to the proper shape in a sheet metal bending machine, (2) thereinforcement was secured to the mold by tie wires passed through holesin the mold (Figure 13), (3) mortar was plastered into the mesh withthe aid of vibration and then screeded tight against the mesh, (4) after16 to 18 hours of moist curing, the top of the panel wa. wire brushedto expose some of the mesh of the top layer (Figure 14), (5) the panelwas weighed so the correct amount of mortar could be plastered overthe mesh in a thin coating to bring the final weight of the panel closeto calculated weight.

The test set-up is shown in Figure 15. A single point load wasapplied -o the panel at the center of a 7.5-foot span length. Loadswere applied in 50-pound increment.s so that strain gage and Ames dial

%5

Page 10: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

deflection readings could be obtained and inspection for the firstvisible crack could be conducted.

Result of Flexural Tests. Table 3 gives the flexural loads andstiesses at visible cracking and ultimate conditions. ---r the meshreinforced panels, a wide variation in stresses at visible cracking

and ultimate was apparent. The average stress a'- visible crackingwas 1,980 psi with an extreme range from 1,140 to 2,840 psi. The

average stress at ultimate conditions was 3,130 psi with an extremerange from 2,460 to 4,300 psi. A possible reas n for the variation inthe results is that panels CM-2 and HM-l, which showed the lower

strengths, had the drilled bolt holes (see Figures 6 and 10) on thetensile side of the panel. These holes were the locations of firstvisible cracks and the major crack at ultimate loading. How, ver,the calculated stress at the cross-section with holes was :iigher than

the stress at midspan (Table 3) by only about 100 psi.The results from the two chicken-wire-reinforceK panels showed

good consistency. The average stress at visible crackii.g was 720 ± 40psi and at ultimate loading was 2,120 ± 290 psi.

The load-deflection behavior for the panels is shown in Figures16-18.

The cracking behavior of the mesh reinforced panels was superior

to the chicken wire reinforced panels. At loads greater than the 'visibiecracking load, the mesh panels showed niimerous fine, closely spacedcracks (approximately 1/4 in. apart) on the tensile face, whereas thechicken wire panels showed large, widely spaced cracks (approximately1 inch apart). After removing the load, the cracks in the mesh panelstended co close, except for the failure crack, while the cracks in the

chicken wire panels remained sizable (Figuir 1q).;ailure behavior of the panels showed an important disadvantage

uL Ihe 1/4 x 1/4-in, mesh reinforcement; this was the low ductility of

the wires. At panel deflections between 1.4 and 2.4 inches, a sudden

major crack wou'd develop due to breaking many wires. The wires in the

chicken wire reinforced panels never broke, they continued to yield

even when the deflections were as great as 5 inches.it is possible that one reinforcement scheme could be develop .d

to combine the advantag-es of 1/4 x 1/4-in, mesh and chicken wire

reinforcement. A combina'ion of 1/4 x 1/4 mesh and chicken wire in a

lay up using two layers of mesh on each extreme face and two or three

layers of chicken wire in the center should result in a ferro-cement

panel with good flexural strength, good cracking behavior, and high

ductility.

Effec- of Corrosive Environment

The purpose of this test was to obtain an indication of the effect

of a corrosive environment on the steel reinforcement in ferro-cement.

More basically, do the small diameter wires corrode to the point of

6

Page 11: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

reducing the strength of the ferro-cament without giving visualevidence of corrosion? Or, if corrosion is evident from visual rust

stains, what effect does this degree of corrosion have on the ultimate

strength of the ferro cement?

Test Description. Ferro-cement specimens were subjected to a salt

spray (fog) test described in ASTM Method B117-64. The salt-spraysolution was 5% by weight of sodium chloride dissolved in demineralizedwater and the temperature of the salt spray chai'U-r was maintained at950 ± 30F.

In all, 39 specimens nf size 1/2 x 3 x 12 inches were cut from theundamaged sections of the zonstruction panels. Twenty-seven specimenshad the 1/4 1/4-in. mesh as the reinforcement; three of these werctested at zero time, 9 were placed in the fog room, and 15 were Placed

in the salt spray chamber. Three of the spe!cimens marked for the saltspray chamber were coated with an epoxy wat-erproofing material. The

remaining 12 specimens had chicken wire as the reinforcement, of whichthree were tested at time zero, and the remaining 9 were placed in the

salt spray chamber.Specimens were tested under flexural loading after beinc, exposed

to the salt spray for 0, 4, and 6 months. The 6-month s-ecimens were

L -ended for 8 months exposure; however, at the end of 4 months thesal: spray chamber failed and required replacement. Thus, for 2 months

the sl -im~ns were stored at room condizions before tcsting was resumed.

Cc7-. anion control specimens were stored in a fresh water ig

environment and tested at 4 and 8 months.The method used to determine the effect of the environment or.

the specimens was to compare the ultim&te flexural strength of the salt

spray chamber specimens with (1) zero time data, (2) the strength of

fog room specimens, and (3) the strength of salt spray chamber specimensthat were coated with an epoxy material.

Distribution of the reinforcement across the thickness of the panelswas nonuniform. The layers of mesh or chicken wire were grouped more

heavily on the bottom side of the construction panel; this side was

desJjnated as the tensile face for the t,'st specimens.' .riation in test specimens was a problem; aside from a variable

spacing of reinforcement layers, the thick ness of the panels also

varied from 3/8 to 9/16 inch. To avoid bias in selecting specimens

for testing at 0-, 4-, and 6-month periods, a random selection

procedure was used.

Result of Corrosive Environment Test. Ultimate flexural strengths

were obtained from sracirnens expos-d to the salt spr environment for

0, 4, and 6 months and from contro*l specimens expos :o a freshwaterenvircnment for 0, 4, and 8 months. Table 4 shows ultimate flexuralstrengths ana Figure 20 plots the strengths versus -.me. The results

show no major decrease in strength. After 4 and 6 months' exposure tothe salt spray environment, the standard deviation of the flexure

strengths was quite large denoting that either corrosion had someeffect or that mesh placement varied significantly for these specimens.

Page 12: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

The importan- finding from the results was that no major decreasein strength occurred even though there was considerable visual evidenceof steel corrosion (Figure 21).

Inspection of the steel -einforcement showed the following:

a. After 6 months' exposure to a salt spray environment, the1/4 x 1/4-in, plain steel woven wire mesh was attacked ratherjignificantly from a v4 sual standpoint. Worst corrosion occurred at

the intersection of two wires ad in some isolated instances the.ires were corroded through. Evidence of corrosion products werefound at the center of the 1/2 in. .ick panel.

b. After 6 months' exposure to a sal, spray environment, the

galvanized ciL'cken wire showed white corrosion products on the wires,in some cases, even at the center of the 1/2 in. thickness. The attackwas not advanced and the strength of the wires was not harmed. Wireshaving no mortar cover showed typical brown rust.

c. After 6 nonthz' exposure to the salt spray environment, the1/4 x 1/4 in. plain steel woven wire mesh speciens that were coatedwith an epoxy material showed Lome localized areas of corrosion whichwere not harmful to the strengt, of the wire and which were limitedto the layers c2osest to the surface having a cover of 1/16 to 1/8

inch.

d. After 8 months' exposure to freshwater fog, the 1/4 x i/4-inch

pl~in steel woven wire mesh showed some localized areas of coriosionwhich were not harmful to thc strength of the wire and which werelimited to the- layers closest to the surface having a cover of 1/16 to1/8 inch.

Correlation between the salt spray environment of the test chamber andnatural weather conditions is very poor; therefore, the results from thesalt spray chamber cannot be translated into real time exposure data.

Table 5 gives the compressive strengths ri 3 x 6-inch cylindersthat were exposed to salt spray and freshwater fog. There was noindication that the salt spray environment deteriorated the mortar.

In summary, the galvanized stael reinforcement corroded less thanthe plain steel reinforcement, and thp erox, coating was an effectivebarrier to preventing ccirosion. From a practical standpoint, it is

valuable to know that corrosion of the steel reinforcement in ferro-cement can be observeu visually I-efore the corrosion is severe enough

to cause a weakening of the material ultimate strength. For the ferro-cemen construction panels, it is recommended that a waterproof coatingbe applied to assure an extended life.

8

Page 13: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

uISCUSSION

A corparison of strengths between ferro-centent, wood, and steelpanels, all 12 inches wide and 8 ft long is given in Table 6. The woodand steel items are off-the-snelf products so their strengths aretabularized (except for the steel decking under compression) (4,51.The strengths for ferro-cement panels are given in Table 6 for bothchicken wire and 1/4 x 1/4-inch mesh reinforcement; these allowablefiexural strengths are equal to the average stress at visible cracking.This resulted in a factor of safety against ultimate strength of 3.0for the chicken wire panels and 1.5 for the 1/4 x 1/4 mesh panels.The allowable compressive stress in the ferro cement was 0.45 f , whichconforms to the ACI code [6].

The flexural strength properties of ferro-cement relate ratherclosely to wood; however, ferro-cement under compression can withstandgreater loads than the wood, especially if the wood is wet.

As would be expected, the live-load-to-dead-weight ratio of thesteel panel is superior to ferro-cement or wood; however, the steelpanel is essentially a flexural member only. Its compressive capabilityis about one-eighth that of the ferro-cement panels. Hence, ferro-cementshould be conlp;tred more closely to wood because wood is a flexure andcompressive member, as is ferro-cement.

From a cost standpoint, ferro-cement appears to be competitivewith wood (Table 6). The common basis for the cost comparison was retailprices (1973) in CONUS.* It was assumed that the ferro-cement panelswere manufactured using fully autonated procedures.

Between the two panel designs, the more versatile configuration wasthe channel section (Figure 2). From a flexural load carrying ability,the choice was not as straightforward. The channel section showed thehighest and the lowest ultimate loads (Table 3) in its strong and weakorientations, whereas the hat section showed more nearly equal strengthin the strong and weak orientations.

The authors believe that the channel section is the betterconfiguration for the multipurpose panel. Versatility is the mostimportant criterion, and the channel section is better in that category.

Ferro-cement appears to be a good choice as the constructionmaterial because it can resist flexural and compressive loads. Thematerial has a history of good durability in corrosive environments,and this study showed that if and when corrosion of reinforcement doesoccur, the corrosion products will be seen on the surface of the panel.Hence, corrective actions can be taxen before harmful deterioration ofpanel strength can occur, or stated another way, the panel will notlose its strength due to corrosion without visually alerting the users.A waterproof coating on the panel will lengthen the useful life of thepanel.

*Continental United States.

F9

Page 14: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

SUMMARY

A ferro-cement construction panel for multipurpose applicationsat advanced military bases appears to be feasible. The design for sucha panel was selected as having a modified channel cross-section (Figure 2)and overall dimensions of 1/2 in. thickness, 12 in. width, and 96 in.length. The weight of the panel is 86 lb. The range of applications forthis panel is broad, such as bunkers, armor for existing structures,sheet piling, water tanks, rafts, and permanent forms for concretebeams or columns to name a few examples. Further development of a specificapplication is not planned as of this writing.

Flexural tests were conducted on prototype construction panelsto obtain stresses at visible cracking and ultimate conditions. Using6 layers of 1/4 x 1/4-in, mesh of plain steel reinforcement, the stressat visible cracking was 2,630 psi and at ultimate ;as 4,300 psi.

Accelerated corrosive environment tests on ferro-cement showedthat after 6 months exposure considerable visual evidence of steelreinforcement corrosion occurred; however, the ferro-cement materialsdid not show any significant reduction in flexural strength.

10

Page 15: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

Approximate size 12" wide96" long112" thick

Figure 1. Cross-sectional shapes considered for multipurpose construction panel.

, )! 11

Page 16: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

1

CL

0

CN

CC

m CD

C., cm

~L.

12

Page 17: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

E Q

C?

C14U

CNC

C4C

C14

13

Page 18: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

hollow beam, hollow column, or permanent two-layer roof or wall

form for concrete column

permanent form for conrrete beam

floor

beam

methods of making right angle connection

Finure 4. Different assemblies of channel section

14

Page 19: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

hollow beam, hollow column, or permanent formfor concrete column

two-layer roof or wall

two-layer roof or wall

permanent form for concrete beam

floor

beam

method of making a right angle connection

Figure 5. Different assemblies of hat section.

15

Page 20: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

Figure 6. Channel section panel carrying a live load of 720 lbs.

Jil

II

Figure 7. Channel section panels assembled for roof or wall construction.

16

Page 21: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

FIgUre 8. Channel sectionl paniels assembled as permnanents form work for a concrete beamn.

Fiqjr 9. Chane secion panels asse mbled as im etment where interior space wotd hef ile I with sandl or g~ravel.

17

Page 22: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

E E

EEc

CLE

07

vcca

) CL

c Ea 0

~ 0)

18

Page 23: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

roof, 2 ; *vers or more

'7'

double wall with soil filler

Figure 12. Bunker constructed of panels

19

Page 24: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

Figure 13. Tie wires securely hold mesh to the rrjld.

II

Figure 14. After 16 to 18 hour% of mnoist curing, the sortaice of the panels were wire

b~ru shed to expose sorme mesh iin prepijr ition for th lifnal nor ti covei.

20

Page 25: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

21

Page 26: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

AROR 00PM

1,4300

CM-i

1,200

1,0004

800

I CM-2

FlLiflI600

400

Reinforcement: 1/4 x 1/4-in, mesh

200

£Appearance of visible crack

0110 0.5 1.0 1.5 2.0 2.5Deflection (in.)

Figure 16. Load-deflection relation for channel cross-section panels reinforcedwith 1/4 x 1/4-ut.. mesh.

22

Page 27: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

V I

1,200

HM-1

1,000

800

CO

0 H-

600

400

Reinforcement: 1/4 x 1/4-in, mesh

200

A appearance of visible crack

0 _0 0.5 1.0 1.5 2.0 2.5 3.0

Deflection (in.)

Figure 17. Load-deflection relation foj- ho't cross-section panels reinforced with 1/4 x 1/4-in, mesh.

23

Page 28: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

00

uC

'a0

w CU S 0

- U,

- - (qi) peol

24

Page 29: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

Ij

CC

.00

0C

> C

m 0

0

E 0)j E E >.)000 IL Lf X~

C L

w0

0) w0 x x x -19 -

-E

C E 00

C" CL0

C.)

av)

06 d

(!sd) qii6uajls ;einxall aiewlim~

25

Page 30: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

exposed to sit spray exposed to freshwaterenvitonhnrjrt environment

Figure 21 View of tnsile side of mesh reinrforce~d specimens (1/2 x 3 x 12 in.)after 4 moth of exposure.

26

Page 31: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

*n OD w OD4 OD

4J A.4q4j o a r'- r- C

004 c0 0 c 0;

)OD OD ODOD O~ CD 0 0 ODO m ON~*

0)

4 NdP *n

44J

No44 0 O . J' V- 0) rt~ . 44 *U 10 4444 -4I -4 N 0 w > 4 0 Q) 0 w N W0 L n _4 r ~ l -

0 0 Q) 1) -O 4J I1N 1S -2.4 '0 V44) 0 qwN N O W $4- '0 (Dr4 .)-4 0 4 X. X In W - 03t A 0

a4 4-4 41 .,f C4 O U) >idJ N N w0 N c4 0

E- t - ~ > W m 1-4 U) - - 4 1 0W0 r0- I i ~ - O ~ 4 4 'U )0) 94J I 'U .0 -e -4 C (d4 *-40 d) 0 4

%D -4 '1 to o 0) 3c0 o D-4 w 0 o0 -4 > t d)

-4 'U '

V4.) 0 V

~4 0

r-4 - 40

41 Id* 4.0

0~ U 41 A

U)0

.1.) 41

4' CI4 0

U) a 'u

27

Page 32: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

Table 2. Control Cylinder Data for Construction Panels

A Average a aSpecimen Age of Compressive AverageaSei in Cylinders Strength, Split Tensile

(days) f' (psi) Strength (psi)c

04-1 69 6450 620

CM-2 58 5830 690

HM-l 69 6450 620

HM-2 58 5830 690

CC-I 64 5960 520

HC-1 64 5960 520

aAverage of three 3 x 6 in. long specimens.

2

28

Page 33: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

L) - 14 (1 -n 0 H v OCD 40 V N~ N~ M N -1

W 44

4) 1

m ed CD 4 C H 1-.-4 w J

4JtA 0 0) Ln Ln LA

N rlI- W C-4 -4V 0O

-4 4J

Sx aen 00

G~~~~~- .4 Hr.,4 L 0 L

E4

(A U) $

Al H , -4lr

CON ____

429

Page 34: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

0C

U5

E~ 3c. z,~

E

C 0 -D U.

0. '

(U~ ~ ~~ 0 . (4--

.n .04-(

0L U __ 20 __ _ _ __ _

4- a 5

N c

4 ,

N cC

x 5.0))

a, 4mC

2 E- E.. .

0 0

E- EEL

0a0

.M 0 ( a

300

Page 35: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

4J - 0 a

to r-

H 0

-to

04 0 0 04

I::: ~ ~ 0 $-. 4 .- :

o4 to ~ to O 0

V° 0

$ 1 ( jj n 0

o o - ja) Q) ) 4>. Q*-H t# 0 0

p 0

o oJ

W 44 000LH 1 04 $4

0•4,- - '.01

0 Ea.,

10' 0

E S -4

U d 0

0 NoCO

2-4 C-4

LA ~ U) 4

4) 90 - a e-4 04) U 44 t

04 14 - .

to S 4.)

E4 0. toto

31

Page 36: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

0 0L CL 0-C w

@ E 0 04 Ln

CS

C06

L) V

E 1

00 .L

3 u

Co 0@In

> 0EO ~ 1 -

01 - N

CC

D CDt;

@32

Page 37: DISTRIBUTED BY: National Technical Intormati …. OBJECTIVE The objective of the study was to develop a multipurpose ferro-cement construction panel which would satisfy a wide range

REFERENCES

1. National Academy of Sciences. Ferro cement: Applications indeveloping countries. Washington, D.C., Feb 1973.

2. Structural Engineering Laboratory, University of California.Report No. UC SESM 71-14: Solving the galvanic cell problem in ferro-cement, by K. A. Christensen and R. B. Williamson. Berkeley, CA,Jul 1971.

3. Naval Civil Engineering Laboratory. Technical Report R-772: Flexuralstrength of ferro-cement panels, by J. E. Tancreto and H. H. Haynes.Port Hueneme, CA, Aug 1972.

4. National Forest Products Association. National Design Specificationfor Stress-Grade Lumber and Its Fastenings, Supplement to 1968 Edition.Washington, D.C., Nov 1970.

5. H. H. Robertson Company, Robertson Q-Floor Catalogue, Pittsburgh, PA.

6. American Concrete Institute. Building Code Requirements forReinforced Concrete, ACI 318-71, Detroit, MI, 1971.

~3)