comparison of previous and new models - mitsubishi …. comparison of previous and new models series...

35
1. Product Lineup …………………………………………… 2 2. Comparison of Previous and New Models ……………… 3 3. Replacement of Previous Models with New Models …… 6 4. Compatibility of Optional Accessories …………………… 9 5. Outline Dimensions of Previous and New Models ……… 12 (30 to 250A Frame) Comparison of Previous and New Models MOLDED-CASE CIRCUIT BREAKERS & EARTH-LEAKAGE CIRCUIT BREAKERS MOLDED-CASE CIRCUIT BREAKERS & EARTH-LEAKAGE CIRCUIT BREAKERS

Upload: truongduong

Post on 07-Mar-2018

235 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

1. Product Lineup …………………………………………… 2

2. Comparison of Previous and New Models……………… 3

3. Replacement of Previous Models with New Models …… 6

4. Compatibility of Optional Accessories…………………… 9

5. Outline Dimensions of Previous and New Models……… 12

( 3 0 t o 2 5 0 A F r a m e )

Comparison of Previous and New Models

MOLDED-CASE CIRCUIT BREAKERS & EARTH-LEAKAGE CIRCUIT BREAKERS

MOLDED-CASE CIRCUIT BREAKERS &EARTH-LEAKAGE CIRCUIT BREAKERS

Page 2: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

1. Product LineupFrame A

Series3032

125 160 250 400 630 800 1000 1250 160063

Frame A

Series

Frame A

Series

3032

125 160 250 400 630 800 1000 125063

3032

125 25063

Mol

ded-

case

circ

uit b

reak

ers

Ear

th-le

akag

e ci

rcui

t bre

aker

sF

or m

otor

prot

ectio

n

NF-CCommercial product

NF-SGeneral-purpose product

NV-CCommercial product

NV-SGeneral-purpose product

NF-HHigh-performance product

NV-HHigh-performance product

NF-UUltra current-limiting breaker

MBMotor breaker

NF63-CV NF125-CV

NF125-SGV

NF125-SEV

NF160-SGV

NF160-LGV

NF160-HGV

NF125-LGVNF125-HV

NF125-HGVNF125-HEV

NF250-CV

NF250-RGV

NF250-UGV

NF30-CS

NF32-SV 400-SW 630-SW 800-SDW

400-SEW 630-SEW 800-SEW

400-HEW 630-HEW 800-HEW

400-REW 630-REW 800-REW

400-UEW 800-UEW

NF 1000-SEW

NF 1250-SEW

NF 1600-SEW

NF63-SV

NF63-HV

NF125-SV

NV63-CV NV125-CV

NV32-SV

NF32-SV MB

NV63-SV

NV63-HV

NV125-SV

NV125-HV

NF125-UGV

NF125-RGV

NF250-SV

NF250-SGV

NF250-SEV

NV250-CV

NV250-SV

NV250-SEV

NV250-HEV

NV250-HV

NF63-CV MB

NF63-SV MB

NF125-SV MB NF250-SV MB

NF250-LGVNF250-HV

NF250-HGVNF250-HEV

400-CW

400-SW

400-SEW

400-HEW

400-REW

400-CW

630-SW

630-SEW

630-HEW 800-HEW

800-SEW630-CW

630-CW 800-CEW

MB30-CS

New models

NV125-SEV

NV125-HEV

− 1 −

Page 3: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

2. Comparison of Previous and New Models

Series Previous W & WS Series New WS-V Series Differences in dimensions and performance between previous and new models

NF-C

NF63-CW NF63-CV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsChange to running on both AC/DCIncrease in breaking capacity

NF125-CW NF125-CV No changes in dimensions and performance

NF250-CW NF250-CVSame dimensionChange in instantaneous value of 250 A rated model (from 10 times to 12 times ± 20%)Increase in breaking capacity

NF-S

NF32-SW NF32-SV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsChange to running on both AC/DCIncrease in breaking capacity

NF63-SW NF63-SV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsChange to running on both AC/DCIncrease in breaking capacity

NF125-SW NF125-SVSame dimensionIncrease in breaking capacityCapable of breaking 690 V AC

NF125-SGW RT NF125-SGVChange in depth (from 86 mm to 68 mm)Change in rated current adjustable rangeAdjustable instantaneous value ➞ Unadjustable

NF125-SGW RE NF125-SEV Change in depth (from 86 mm to 68 mm)

NF160-SW NF250-SV 125 150 160A Addition of 160 A model

NF160-SGW RT NF160-SGV Change in depth (from 86 mm to 68 mm)Adjustable instantaneous value ➞ Unadjustable

NF160-SGW RE NF250-SEV 80-160A Change in depth (from 86 mm to 68 mm)Addition of 80-160 A model

NF250-SW NF250-SV

Same dimensionChange in instantaneous value of 250 A rated model (from 10 times to 12 times ± 20%)Increase in breaking capacityCapable of breaking 690 V AC

NF250-SGW RT NF250-SGV Change in depth (from 86 mm to 68 mm)Adjustable instantaneous value ➞ Unadjustable

NF250-SGW RE NF250-SEV Change in depth (from 86 mm to 68 mm)

− 2 −

Page 4: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Series Previous W & WS Series New WS-V Series Differences in dimensions and performance between previous and new models

NF-H

NF63-HW NF63-HV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsChange to running on both AC/DCIncrease in breaking capacity

NF125-HW NF125-HVSame dimensionApplicable to rated current of 125 AIncrease in breaking capacity

NF125-HGW RT NF125-HGV

Change in depth (from 86 mm to 68 mm)Change in rated current adjustable rangeAdjustable instantaneous value ➞ UnadjustableDecrease in breaking capacity at 690 V AC

NF125-HGW RE NF125-HEV Change in depth (from 86 mm to 68 mm)Decrease in breaking capacity at 690 V AC

NF160-HW NF250-HV 125 150 160A Addition of 160 A model

NF160-HGW RT NF160-HGVChange in depth (from 86 mm to 68 mm)Adjustable instantaneous value ➞ UnadjustableDecrease in breaking capacity at 690 V AC

NF160-HGW RE NF250-HEV 80-160AAddition of 80-160 A modelChange in depth (from 86 mm to 68 mm)Decrease in breaking capacity at 690 V AC

NF250-HW NF250-HVSame dimensionApplicable to rated current of 250 A (instantaneous value = 12 times ± 20%)Increase in breaking capacity

NF250-HGW RT NF250-HGVChange in depth (from 86 mm to 68 mm)Adjustable instantaneous value ➞ UnadjustableDecrease in breaking capacity at 690 V AC

NF250-HGW RE NF250-HEV Change in depth (from 86 mm to 68 mm)Decrease in breaking capacity at 690 V AC

NF-U

NF125-RGW RT NF125-RGV

Changes in dimensions (height: from 240 mm to 165 mm, depth: from 86 mm to 68 mm)Change in rated current adjustable rangeApplicable to rated current of 125 AIncrease in breaking capacity at 415 V AC or lessRated working voltage of below 500 V AC

NF125-UGW RT NF125-UGV

Change in depth (from 86 mm to 68 mm)Change in rated current adjustable rangeApplicable to rated current of 125 ADecrease in breaking capacity at 690 V AC

NF250-RGW RT NF250-RGV

Changes in dimensions (height: from 240 mm to 165 mm, depth: from 86 mm to 68 mm)Applicable to rated current of 250 AIncrease in breaking capacity at 415 V AC or lessRated working voltage of below 500 V AC

NF250-UGW RT NF250-UGVChange in depth (from 86 mm to 68 mm)Applicable to rated current of 250 ADecrease in breaking capacity at 690 V AC

NV-C

NV63-CW NV63-CV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

NV125-CW NV125-CV No changes in dimensions and performance

NV250-CW NV250-CV Same dimensionIncrease in breaking capacity

− 3 −

Page 5: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Series Previous W & WS Series New WS-V Series Differences in dimensions and performance between previous and new models

NV-S

NV32-SW NV32-SV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

NV63-SW NV63-SV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

NV125-SW NV125-SV Same dimensionIncrease in breaking capacity

NV250-SW NV250-SV Same dimensionIncrease in breaking capacity

NV250-SEW NV250-SEVSame dimensionApplicable to rated current of 250 AIncrease in breaking capacity

NV-H

NV63-HW NV63-HV

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

NV125-HW NV125-HVSame dimensionApplicable to rated current of 125 AIncrease in breaking capacity

NV250-HW NV250-HVSame dimensionApplicable to rated current of 250 AIncrease in breaking capacity

NV250-HEW NV250-HEVSame dimensionApplicable to rated current of 250 AIncrease in breaking capacity

MB

MB50-CW NF63-CV (Note)

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

MB30-SW NF32-SV (Note)

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

MB50-SW NF63-SV (Note)

Same dimensionChange of tripping method (from hydraulicmagnetic to thermal magnetic)Changes in operating characteristicsIncrease in breaking capacity

MB100-SW NF125-SV (Note) Same dimensionIncrease in breaking capacity

MB225-SW NF250-SV (Note) Same dimensions and characteristicsIncrease in breaking capacity

Note: The circuit breakers for motor protection have the same basic model names as NF/NV.

● New models

Model name Remarks

NF125-LGV, NF160-LGV, NF250-LGV Thermally adjustable models having breaking capacity of 50 kA at 440 V AC are newly introduced.

NV125-SEV, NV125-HEV Electronic breakers

− 4 −

Page 6: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

3. Replacement of Previous Models with New Models(1) Circuit breaker body (front connection, with 3 poles)

NF32-SWNF63-CW/SW/HWMB30-SWMB50-CW/SW

PreviousW & WSSeries

NewWS-VSeries

Drillingdimension

Front platecutout plan

NF32-SVNF63-CV/SV/HV

NF125-CW/SW/HWMB100-SW

NF125-CV/SV/HV

PreviousW & WSSeries

NewWS-VSeries

Drillingdimension

NV32-SWNV63-CW/SW/HW

NV32-SVNV63-CV/SV/HV

NV125-CW/SW/HW

NV125-CV/SV/HV

NV250-CW/SW/HWNV250-SEW/HEW

NV250-CV/SV/HVNV250-SEV/HEV

Front platecutout plan

No change

No change

No change No change No change No change

No change No change

No change No change No change

No change No change No change

No change No change

M4×0.7 screw or φ5 hole

Breaker

111

25

Breaker

70

52

R1

M4×0.7 screw or φ5 hole

Breaker

111

30

Breaker

52

86

R1

111

30

Breaker

M4×0.7 screw or φ5 hole

R1

86

52

Breaker

25

111

M4×0.7 screw or φ5 hole Breaker

70

52

R1

Breaker

NF160-SW/HWNF250-CW/SW/HWMB225-SW

NF250-CV/SV/HV

52

100

Breaker

R1

35

126

Breaker

M4×0.7 screw or φ5 hole

NF125-SGW/HGWNF160-SGW/HGWNF250-SGW/HGW

NF125-SGV/LGV/HGVNF125-SEV/HEVNF160-SGV/LGV/HGVNF250-SGV/LGV/HGVNF250-SEV/HEV

52

100

Breaker

R1

35

126

Breaker

M4×0.7 screw or φ5 hole

NF125-RGW/UGWNF250-RGW/UGW

NF125-RGVNF250-RGV

NF125-UGVNF250-UGV

52

100

Breaker

R1

35

126

Breaker

M4×0.7 screw or φ5 hole

52

100

11.5

Breaker

R1

201

35

Breaker

M4×0.7 screw or φ5 hole

35

126

Breaker

M4×0.7 screw or φ5 hole

52

100

Breaker

R1

change

change

− 5 −

Page 7: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

(2) Circuit breaker and operating handle (front connection, 3P)

NF32-SWNF63-CW/SW/HWMB30-SWMB50-CW/SW

PreviousW & WSSeries

NewWS-VSeries

Previous modelsNew modelsPrevious modelsNew modelsPrevious modelsNew models

Dril

ling

dim

ensi

ons

for

mou

ntin

g of

circ

uit b

reak

erF

ront

pla

te c

utou

t dim

ensi

ons

NF32-SVNF63-CV/SV/HV

NV32-SWNV63-CW/SW/HW

NV125-CW/SW/HW

NV32-SVNV63-CV/SV/HV

NF125-CW/SW/HWMB100-SW

NF125-CV/SV/HV NV125-CV/SV/HV

105 mm

102 mm

Circ

uit b

reak

er b

ody

F ty

pe

F ty

peS

type

V ty

pe

S ty

peV

type

F ty

peS

type

V ty

pe

Dis

tanc

e be

twee

n ci

rcui

t bre

aker

bo

ttom

and

fron

t pl

ate

F-05S2, F-05S, F-05SEF-05SV2, F-05SV, F-05SVE

S-05SWS-05SV

V-05S, V-05SEV-05SV, V-05SVE

S-1SWS-05SV

V-1S, V-1SEV-1SV, V-1SVE

F-05S, F-05SEF-05SV, F-05SVE

F-1S2, F-1S, F-1SEF-1SV2, F-1SV, F-1SVE

F-1S, F-1SEF-1SV, F-1SVE

No change

No change

No change

No change

No change

No change

No change

No change

No change

No change125 mm (stationary type)

No change125 mm (stationary type)

− 6 −

Page 8: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

PreviousW & WSSeries

NewWS-VSeries

Previous modelsNew modelsPrevious modelsNew modelsPrevious modelsNew models

Dril

ling

dim

ensi

ons

for

mou

ntin

g of

circ

uit b

reak

erF

ront

pla

te c

utou

t dim

ensi

ons

Circ

uit b

reak

er b

ody

F ty

pe

F ty

peS

type

V ty

pe

S ty

peV

type

F ty

peS

type

V ty

pe

Dis

tanc

e be

twee

n ci

rcui

t bre

aker

bo

ttom

and

fron

t pl

ate

NF160-SW/HWNF250-CW/SW/HWNF250-SEW/HEWMB225-SW

NF250-CV/SV/HVNF250-SEV/HEV

NV250-CW/SW/HWNV250-SEW/HEW

NV250-CV/SV/HVNV250-SEV/HEV

NF125-SGW/HGWNF160-SGW/HGWNF250-SGW/HGW

NF125-SGV/LGV/HGVNF125-SEV/HEVNF160-SGV/LGV/HGVNF250-SGV/LGV/HGVNF250-SEV/HEV

NF125-RGW/UGWNF250-RGW/UGW

NF125-RGVNF250-RGV

NF125-UGVNF250-UGV

No change

No change

No change

No change

No change

No change

No change

No change

No change

125 mm (stationary type)

F-2S, F-2SEF-2SV, F-2SVE

S-2SWS-2SV

V-2S, V-2SEV-2SV, V-2SVE

F-2UG, F-2UGE

V-2UG, V-2UGE

F-2SG, F-2SGEF-2SV, F-2SVE

S-2GSWS-2SV

V-2SG, V-2SGEV-2SV, V-2SVE

F-2SV, F-2SVE

S-2SV

V-2SV, V-2SVE

F-2UV, F-2UVE

V-2UV, V-2UVE

New models110 mm

Previous models128 mm

New models107 mm

Previous models125 mm

No change

No change

No change

No change No changeNo changeNo change

Previous models143 mm

(stationary type)

New models125 mm

(stationary type)

New models110 mm

Previous models128 mm

New models107 mm

Previous models125 mm

Previous models143 mm

(stationary type)

New models125 mm

(stationary type)

New models110 mm

Previous models128 mm

New models107 mm

Previous models125 mm

Previous models143 mm

(stationary type)

New models125 mm

(stationary type)

Center of circuit breaker handle Center of circuit

breaker handle

Center of circuit breaker

Center of operating handle M4×0.7 screw

or φ5 holeM4×0.7 screw or φ5 hole

Previous model New model

Center of circuit breaker and operating handle

Differing in hole position

Center of operating handle

Center of operating handle

M4×0.7 screw or φ5 hole

M4×0.7 screw or φ5 hole

M4×0.7 screw or φ5 hole

M4×0.7 screw or φ5 hole

Previous model New model

Previous model New model

Center of circuit breaker and operating handle

Center of circuit breaker and operating handle

Breaker

Breaker

Differing in hole position

Differing in hole position

Center of circuit breaker handle

Center of circuit breaker handle

Center of circuit breaker and circuit breaker handle

Center of circuit breaker and circuit breaker handle

Center of circuit breaker

Center of circuit breaker

− 7 −

Page 9: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Products

Models CompatibilityAccessories

Applicable models (New models)New breakers with previous accessories

Previous breakers with

new accessoriesPrevious models New models

Cassette-type

accessories (Note)

AL-05SW* AX-05SW* ALAX-05SW*

AL-05SV* AX-05SV* ALAX-05SV*

NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

AL-1SW AX-1SW ALAX-1SW NF/NV125-CV/SV/HV ✕ ✕

AL-2SW* AX-2SW* ALAX-2SW* NF/NV250-CV/SV/HV ✕ ✕

AL-2GSW* AX-2GSW* ALAX-2GSW*

NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

SHTMMMM-05SWR

SHTMMMM-05SVR

NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

SHTMMMM-1SWR NF/NV125-CV/SV/HV ✕ ✕

SHTMMMM-2SWR NF/NV250-CV/SV/HV ✕ ✕

SHTMMMM-2GSWR NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

UVTNMMMM-05SW*

UVTNMMMM-05SV*UVTSMMMM-05SV*

NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

UVTNMMMM-1SW* NF/NV125-CV/SV/HV ✕ ✕

UVTNMMMM-2SW* NF/NV250-CV/SV/HV ✕ ✕

UVTSMMMM-2GSW* NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

Rear stud(B-ST)

ST-05SW2, 3, 4 ST-05SV2, 3, 4 NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

ST-1SW2, 3, 4 ST-1SV2, 3, 4 NF/NV125-CV/SV/HV(3, 4P) ✕ ✕

ST-1HW2 ST-1HV2 NF125-HV(2P) ✕ ✕

ST-2SW2, 3, 4ST-2SV2, 3, 4

NF/NV250-CV/SV/HV ✕ ✕

ST-2GSW2, 3, 4 NF125-SGV/LGV/HGV/SEV/HEV,NF250-SGV/LGV/HGV/SEV/HEV, etc. ✕ ✕

Plug-in terminal

(PM)

PM-05SW2, 3, 4 PMDN-05SV2, 3, 4 NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

PM-NV05SW2 PMDN-NV05SV2 NV63-CV/SV(2P) ✕ ✕

PM-1SW2, 3, 4 PMDN-1SV2, 3, 4 NF/NV125-CV/SV/HV ✕ ✕

PM-1HW2 PMDN-1HV2 NF125-HV(2P) ✕ ✕

PM-2SW2, 3, 4PMDN-2SV2, 3, 4

NF/NV250-CV/SV/HV ✕ ✕

PM-2GSWIP2, 3, 4 NF125-SGV/LGV/HGV/SEV/HEV,NF250-SGV/LGV/HGV/SEV/HEV, etc. ✕ ✕

PM-2GUW2, 3PMDN-2SV2, 3 NF125-RGV, NF250-RGV ✕ ✕

PMDN-2UV2, 3 NF125-UGV, NF250-UGV ✕ ✕

Conductor(FB)

FB-05SW FB-05SV NF/NV32-SV, NF/NV63-CV/SV/HV (50A or less) K K

FB-1SW FB-1SV NF/NV125-CV/SV/HV K K

FB-2SW FB-2SV NF/NV250-CV/SV/HV K K

Barrier

BAF-05SW BAF-05SV NF/NV32-SV, NF/NV63-CV/SV/HV, NF/NV125-CV/SV/HV, etc. K K

BAF-2SW BAF-2SV NF/NV250-CV/SV/HV, etc. K ✕

BAG-05SW3 BAG-05SV3 NF/NV32-SV, NF/NV63-CV/SV/HV K K

BAG-1SW3 BAG-1SV3 NF/NV125-CV/SV/HV K K

BAG-2SW3BAG-2SV3

NF/NV250-CV/SV/HV, etc. K K

BAG-2GSW3 NF125-SGV/LGV/HGV/RGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/SEV/HEV, etc. ✕ ✕

4. Compatibility of Optional Accessories

Note: In *, a symbol indicating the mounting pole is shown. In M, the voltage is shown.

− 8 − − 9 −

Page 10: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Products

Models CompatibilityAccessories

Applicable models (New models)New breakers with previous accessories

Previous breakers with

new accessoriesPrevious models New models

Operating handle

F-05S2 F-05SV2 NF32-SV(2P), NF63-CV/SV/HV(2P) ✕ ✕

F-05S F-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

F-1S2 F-1SV2 NF125-CV/SV(2P) ✕ ✕

F-1S F-1SV NF/NV125-CV/SV/HV ✕ ✕

F-2SF-2SV

NF/NV250-CV/SV/HV ✕ ✕

F-2SG NF125-SGV/LGV/HGV/RGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/SEV/HEV, etc. ✕ ✕

F-2UG F-2UV NF125-UGV, NF250-UGV ✕ ✕

F-RCS (release protection) F-RCS (release protection) F type operating handle is applicable to all models. K K

S-05SW S-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

S-1SW S-1SV NF/NV125-CV/SV/HV ✕ ✕

S-2SWS-2SV

NF/NV250-CV/SV/HV ✕ ✕

S-2GSW NF125-SGV/LGV/HGV/RGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/SEV/HEV, etc. ✕ ✕

V-05S2 V-05SV2 NF32-SV(2P), NF63-CV/SV/HV(2P) ✕ ✕

V-05S V-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

V-1S2 V-1SV2 NF125-CV/SV(2P) ✕ ✕

V-1S V-1SV NF/NV125-CV/SV/HV ✕ ✕

V-2SV-2SV

NF/NV250-CV/SV/HV ✕ ✕

V-2SG NF125-SGV/LGV/HGV/RGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/SEV/HEV, etc. ✕ ✕

V-2UG V-2UV NF125-UGV, NF250-UGV ✕ ✕

V-AD3S (adjusting unit) V-AD3S (adjusting unit) V type operating handle is applicable to all models. K K

ClampTG-S05SW TG-S05SV NF/NV32-SV, NF/NV63-CV/SV/HV, etc. K K

TG-S2SW TG-S2SV NF/NV250-CV/SV/HV, etc. K K

TC-S

TCS-05SW2W, 3W, 4W TCS-05SV2, 3, 4 NF/NV32-SV, NF/NV63-CV/SV/HV K K

TCS-1SW2W, 3W, 4W TCS-1SV2, 3, 4 NF/NV125-CV/SV/HV K K

TCS-2SW3W, 4WTCS-2SV3, 4

NF/NV250-CV/SV/HV K K

TCS-2GSW3W, 4W NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

TC-L

TCL-05SW2W, 3W, 4W TCL-05SV2, 3, 4 NF/NV32-SV, NF/NV63-CV/SV/HV K K

TCL-1SW2W, 3W, 4W TCL-1SV2, 3, 4 NF/NV125-CV/SV/HV K K

TCL-2SW3W, 4W TCL-2SV3, 4

TCL-2SV3L

NF/NV250-CV/SV/HV K K

TCL-2GSW3W, 4W NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

TTC

TTC-05SW2, 3 TTC-05SV2, 3 NF/NV32-SV, NF/NV63-CV/SV/HV K K

TTC-1SW2, 3 TTC-1SV2, 3 NF/NV125-CV/SV/HV K K

TTC-2SW3TTC-2SV3

NF/NV250-CV/SV/HV K K

TTC-2GSW3 NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

BTC

BTC-05SW2W, 3W BTC-05SV2, 3 NF/NV32-SV, NF/NV63-CV/SV/HV K K

BTC-1SW2W, 3W BTC-1SV2, 3 NF/NV125-CV/SV/HV K K

BTC-2SW3WBTC-2SV3

NF/NV250-CV/SV/HV K K

BTC-2GSW3W NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

PTC

PTC-05SW2W, 3W PTC-05SV2, 3 NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

PTC-1SW2W, 3W PTC-1SV2, 3 NF/NV125-CV/SV/HV ✕ ✕

PTC-2SW3WPTC-2SV3

NF/NV250-CV/SV/HV ✕ ✕

PTC-2GSW3W NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

− 9 −

Page 11: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Note: In *, a symbol indicating the mounting pole is shown. In M, the voltage is shown.

Products

Models CompatibilityAccessories

Applicable models (New models)New breakers with previous accessories

Previous breakers with

new accessoriesPrevious models New models

Lock cover

LC-05SW LC-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

LC-1SW LC-1SV NF/NV125-CV/SV/HV ✕ ✕

LC-2SWLC-2SV

NF/NV250-CV/SV/HV ✕ ✕

LC-2GSW NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

Handle lock

HLF-05SW, HLN-05SW HLF-05SV, HLN-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

HLF-1SW, HLN-1SW HLF-1SV, HLN-1SV NF/NV125-CV/SV/HV ✕ ✕

HLF-2SW, HLN-2SWHLF-2SV, HLN-2SV

NF/NV250-CV/SV/HV ✕ ✕

HLF-2GSW, HLN-2GSW NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

HLS-05SW, HLS-05SW2P HLS-05SV, HLS-05SV2P NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

HLS-1SW, HLS-1SW2P HLS-1SV, HLS-1SV2P NF/NV125-CV/SV/HV ✕ ✕

HLS-2SWHLS-2SV

NF/NV250-CV/SV/HV ✕ ✕

HLS-2GSW NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc. ✕ ✕

SBOX

NFS-05SW2P NFS-05SV2P NF32-SV(2P), NF63-CV/SV/HV(2P), etc. K K

NFS-05SW NFS-05SV NF/NV32-SV, NF/NV63-CV/SV/HV K K

NFS-1SW2P NFS-1SV2P NF125-CV/SV K K

NFS-1SW NFS-1SV NF/NV125-CV/SV/HV K K

NFS-2SW NFS-2SV NF/NV250-CV/SV, etc. K K

IBOX

NFI-05SW NFI-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

NFI-1SW NFI-1SV NF/NV125-CV/SV/HV ✕ ✕

NFI-2SW NFI-2SV NF/NV250-CV/SV/HV, etc. ✕ ✕

WBOX

NFW-05SW NFW-05SV NF/NV32-SV, NF/NV63-CV/SV/HV ✕ ✕

NFW-1SW NFW-1SV NF/NV125-CV/SV ✕ ✕

NFW-1HW NFW-1HV NF/NV125-HV ✕ ✕

NFW-2SW NFW-2SV NF/NV250-CV/SV/HV, etc. ✕ ✕

Electric operation

unit(Note)

MDSMMMM-NF1SWE MDSMMMM-NF1SVE NF125-CV/SV/HV ✕ ✕

MDSMMMM-NV1SWE MDSMMMM-NV1SVE NV125-CV/SV/HV ✕ ✕

MDSMMMM-NF2SWE MDSMMMM-NF2SVE NF250-CV/SV/HV ✕ ✕

MDSMMMM-NF2GSWE MDSMMMM-NF2SVE NF125-SGV/LGV/HGV/RGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/SEV/HEV, etc. ✕ ✕

MDSMMMM-NV2SWE MDSMMMM-NV2SVE NV250-CV/SV/HV ✕ ✕

Mechanical interlock

MI-05SW3 MI-05SV3

NF/NV32-SV, NF/NV63-CV/SV/HV, NF/NV125-CV/SV/HV, NF/NV250-CV/SV/HV, NF125-SGV/LGV/HGV/RGV/UGV/SEV/HEV,NF250-SGV/LGV/HGV/RGV/UGV/SEV/HEV, etc.

K K

IEC 35 mm rail mounting

adapter

DIN-05SW DIN-05SV NF/NV32-SV, NF/NV63-CV/SV/HV, etc. ✕ ✕

DIN-1SW2 – No new models ✕ –

DIN-1SW3 – No new models ✕ –

Card holder CH-P NO.5 CH-P NO.5 NF/NV250-SV or lower K K

− 10 −

Page 12: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Previous W & WS Series New WS-V Series

Models Reference page Models Reference page

NF32-SW, NF63-CW, NF63-SW, NF63-HW 13 NF32-SV, NF63-CV, NF63-SV, NF63-HV 14

NV32-SW, NV63-CW, NV63-SW, NV63-HW 15 NV32-SV, NV63-CV, NV63-SV, NV63-HV 16

NF125-CW, NF125-SW, NF125-HW 17 NF125-CV, NF125-SV, NF125-HV 18

NV125-CW, NV125-SW, NV125-HW 19 NV125-CV, NV125-SV, NV125-HV 20

NF250-CW, NF250-SW, NF250-HW, MB225-SW 21 NF250-CV, NF250-SV, NF250-HV 22

NV250-CW, NV250-SW, NV250-HW 23 NV250-CV, NV250-SV, NV250-HV 24

NV250-SEW, NV250-HEW 25 NV250-SEV, NV250-HEV 26

NF125-SGW, NF125-HGW, NF160-SGW, NF160-HGW, NF250-SGW, NF250-HGW

27

NF125-SGV, NF125-LGV, NF125-HGV, NF125-SEV, NF125-HEV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV

28

NF125-RGW, NF250-RGW 29 NF125-RGV, NF250-RGV 30

NF125-UGW, NF250-UGW 31 NF125-UGV, NF250-UGV 32

MB30-SW, MB50-CW, MB50-SW 13 NF32-SV, NF63-CV, NF63-SV (Note) 14

MB100-SW 17 NF125-SV (Note) 18

5. Outline Dimensions of Previous and New Models

Note: The circuit breakers for motor protection have the same basic model names as NF.

− 11 −

Page 13: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Wire size applicable to direct connection of wireφ1.6 22 mm2

CL

CL

LC

LC

22

Neutral pole

Insulating barrier(removable)

Mounting hole

Tripbutton

25

50 50

75

25

75

10050

130

111

12.5 max.

6

φ5.5(φ6.5 for 60 A and 63 A)

LC

CL

CLCLBreaker

Drilling plan

M4 × 0.7 screw or φ5 hole

2525

111

5084

24

45

φ8.5

61

68

724

90

M5 × 0.8 screw(M6 screw for 60 A and 63 A)

φ4.5

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

LC

CL LC LC

φ14

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

111

25

25

75

25

5025

27 min.

8

72

68

42

111

8

50

Mounting plate t = 3.2 max.

Insulating tube

M6 screw

M4 × 0.7 screw for breaker mounting

LC

LC

Front-panel cutout

1.0 mm clearance on each side of the handle frame

CL

CL

50

2-pole

3-pole

CLLC

22.5

70

52

4-pole

Breaker

CL LC LC

Center of circuit breaker body

Drilling plan

Breaker (plug-in terminal block)

M5 × 0.8 screw or φ6 hole

54

5454

80

57 82

25

107

50

Conductor drilling drawing

4-pole3-pole

5080

7525

105

111

55

25

16.5 max.

7

φ6.5

LC11

Plug-in terminal block

Mounting plate

Details of terminal

M6 screw

M5 × 0.8 screwMounting with terminal block mounting nut or mounting directly with screw

3

180

83.5

85

30

21

89

5.5 15.5

10

R1

2-pole 3-pole 4-pole

2-pole 3-pole 4-pole

2-pole 3-pole 4-pole

2-pole 3-pole 4-pole2-pole

Molded-case circuit breakers

Previous W & WS SeriesNF32-SW, NF63-CW, NF63-SW, NF63-HW,MB30-SW, MB50-CW, MB50-SW

Front connection

Rear connection

Plug-in

− 12 −

Page 14: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

42 (44 for 60 A and 63 A)

21

3089

11

7

16.5 max.

57 82

25 50

107

5480

54

5483.5

85

170

116

80

50

25

55

105

75

25

5.5

φ6.5

8

Mounting plate t = 3.2 max.

Insulating tube

50

22.5φ14

70

52

R1

111

25

25

75

25

5025

50

4268

72

8

27 min.

27 min.

112

112

Mounting hole

22

25

50

50

75

25

75

100

5013

0

Insulating barrier (removable)

Neutral pole

Trip button

8

φ8.5 45

5084

24

61

68

724

90

12.5 max.

φ4.5

φ5.5(φ8.5 for 60 A and 63 A)

(16 max. for 60 A and 63 A)

(31 min. for 60 A and 63 A)

(29 min. for 60 A and 63 A)

(46 for 60 A and 63 A)

M5 × 0.8 screw (M8 screw for 60 A and 63 A)

(Conductor thickness t = 5 max.)

Conductor drilling for direct connection

2525

111

BreakerM4 × 0.7 screw or φ5 hole

Breaker

M4 × 0.7 screw or φ5 hole

M6 screwM4 × 0.7 screw for breaker mounting

Drilling plan Front-panel cutout

1.0 mm clearance on each side of the handle frame

2-pole

3-pole

4-pole

Breaker

Breaker (plug-in terminal block)

M5 × 0.8 screw or φ6 hole

4-pole3-pole

Plug-in terminal block

Mounting plate

M6 screw

M5 × 0.8 screw for mounting terminal block

Wire size applicable to direct connection of wireφ1.6 22mm2

(For M5 × 0.8 screw)

Drilling plan

Drilling plan

Details of terminal Conductor drilling drawing

Molded-case circuit breakers

New WS-V SeriesNF32-SV, NF63-CV, NF63-SV, NF63-HV

Front connection

Rear connection

Plug-in

2-pole 3-pole 4-pole

2-pole 3-pole 4-pole

2-pole2-pole

3-pole 4-pole

2-pole 3-pole 4-pole

112

− 13 −

Page 15: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

25

6

12.5 max.

90

4 72

68

61

φ8.5

φ4.5

45

24

84

75

50

22

111

130

111

50

Mounting hole

Insulating barrier (removable)

Sensitivity current switching unit

Earth-leakage indicating button

Test button

Trip button

M5 × 0.8 screw (M6 screw for 60 A and 63 A)

φ5.5(φ6.5 for 60 A and 63 A)

Wire size applicable to direct connection of wireφ1.6 22 mm2

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

LC

LC

LC

LC

27 min.

8

72

68

42

111

8

50

50

25

111

Mounting plate t = 3.2 max.

Insulating tube

M6 screw

M4 × 0.7 screw for breaker mounting

φ14

M4 × 0.7 screw or φ5 hole

Breaker

Drilling plan

LC

LC

LC

LC

52

70

Breaker

Front-panel cutout

1.0 mm clearance on each side of the handle frame

R1

LC

LC

10

15.5

5.5

89

21

30

85

83.5 18

0

3

7

16.5 max.

111

80

50

25

82

8054

54

54

11

Plug-in terminal block

Mounting plate

M5 × 0.8 screwMounting with terminal block mounting nut or mounting directly with screw

M6 screw

φ6.5

Conductor drilling drawing

M5 × 0.8 screw or φ6 hole

Breaker (plug-in terminal block)

Center of circuit breaker body

Drilling plan

LC

LC

50

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

Details of terminal

Earth-leakage circuit breakers

Previous W & WS SeriesNV32-SW, NV63-CW, NV63-SW, NV63-HW

Front connection

Rear connection

Plug-in

− 14 −

Page 16: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

112

8

72

68 42

50

50

25

R1

52

70φ14

φ4.5

25

90

4 72

68

61

24

8475

50

22

50

φ6.5

111

130

112

50

8

5.5

50

80

116

170

85

54

5480

54

25

82

7

11

89 30

21

8

45

φ8.5 12.5 max.

(16 max. for 60 A and 63 A)

Mounting hole

Insulating barrier (removable)

Sensitivity current switching unit

Earth-leakage indicating button

Test button

Tripbutton

M5 × 0.8 screw (M8 screw for 60 A and 63 A)

φ5.5 (φ8.5 for 60 A and 63 A)

Breaker

M4 × 0.7 screw or φ5 hole

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

27 min.

Mounting plate t = 3.2 max. Insulating tube

M6 screw

M4 × 0.7 screw for breaker mounting

M4 × 0.7 screw or φ5 hole

Breaker

Drilling plan

Drilling plan

Breaker

1.0 mm clearance on each side of the handle frame

Front-panel cutout

16.5 max.

Plug-in terminal block

Mounting plate

M6 screw

Conductor drilling drawing

M5 × 0.8 screw or φ6 hole

Breaker (plug-in terminal block)

Drilling plan

83.5

M5 × 0.8 screw for mounting terminal block

Details of terminal

Earth-leakage circuit breakers

New WS-V SeriesNV32-SV, NV63-CV, NV63-SV, NV63-HV

Front connection

Rear connection

Plug-in

Wire size applicable to direct connection of wireφ1.6 22 mm2

(For M5 × 0.8 screw)

111

112

− 15 −

Page 17: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

CL

LC

LC

CL

50Neutral pole

30

90

120

112

130

60

30

90

60

22

Tripbutton

Insulating barrier(removable)

Mounting hole

CLLCLC

LC

30

110-

111

(Not

e 1)

30

Breaker

Drilling plan

M4 × 0.7 screw or φ5 hole

24

84 50

68

61

45

724

90

φ8.5

8

M8 screw

19 max. (comb-like conductor: 16.5 max.)

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

φ8.5

φ4.5

CL

102

15

72

68

8.5

2.5

15

54.5

104.5

15

2.5

16

112

Mounting plate t = 3.2 max. Stud rotatable by 90°

Insulating tube

Connecting allowance

M8 bolt

90

8

60

5

Insulating tube

M4 × 0.7 screw for breaker mounting

LCCL

CL

LC

3011

0-11

1 (N

ote

1)

90

3011

230

60

30

M4 × 0.7 screw or φ5 hole

Breaker

Drilling plan

φ18

LC

LCLC

LC

28

57 86

52

Breaker

R1 R1

CL

8912.5

Plug-in terminal block

Mounting plate

98 190

11

21

30

5.5 20

Details of terminal

M8 screw

M5 × 0.8 screwMounting with terminal block mounting nut or mounting directly with screw

Drilling plan

CL

LC CL CL

Breaker (plug-in terminal block)

54 9456

56

127

6030

9767

M5 × 0.8 screw or φ6 hole

30

95

60

125

90

30

65

16.5 max.

12

φ8.5

Conductor drilling drawing

134

2-pole

3-pole 4-pole

Front-panel cutout

1.0 mm clearance on each side of the handle frame

Molded-case circuit breakers

Previous W & WS SeriesNF125-CW, NF125-SW, NF125-HW,MB100-SW

Front connection

Rear connection

Plug-in

Note (1) Applicable to both mounting sizes 110 and 111Remarks: 1. 2-pole model of NF125-HW are 3-pole model with the central pole removed.

2. Only 2- and 3-pole models are available for the model of NF125- CW and only 3-pole models are available for the model of MB100-SW.

2-pole 3-pole 4-pole

2-pole

3-pole 4-pole

2-pole

2-pole

3-pole 4-pole

3-pole 4-pole

2-pole

3-pole

4-pole

2-pole 3-pole

4-pole

Solderless terminalfor wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 16 −

Page 18: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Drilling plan

111

111

8

φ8.5

φ8.5

φ18

φ4.5

R1R1

30

50

90

30

90

120

28

90

3011

2

30

112

130

102

52

15

72

68

8.5

2.5

15

54.5

104.5

15

2.5

16

112

60

5

30 57 86

52

60

30

60

30

90

60

22

24

84 50

68

61

45

724

90

8

30

5.5

83.5

85

170

12

3089

21

11

54 8056

56

67 97 127

60

95

30

65

116

30

90

125

Mounting hole

Insulating barrier(removable)

Tripbutton

Neutral pole

M8 screw

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

Drilling plan

M4 × 0.7 screw or φ5 hole

19 max. (comb-like conductor: 16.5 max.)

Breaker

BreakerBreaker

Front-panel cutout

M4 × 0.7 screw or φ5 hole

Drilling plan

M4 × 0.7 screw for breaker mounting

Insulating tube

Mounting plate t = 3.2 max.

Insulating tube

Stud rotatable by 90°

Connecting allowance

M8 bolt

Breaker (plug-in terminal block)

M5 × 0.8 screwor φ6 hole

φ8.5

Conductor drillingdrawing

20 max.

Details of terminal

Plug-in terminal block

Mounting plate

M5 × 0.8 screwMounting with terminal block mounting nut or mounting directly with screw

M8 screw

1.0 mm clearance on each side of the handle frame

2-pole

2-pole

3-pole

3-pole

4-pole

4-pole

2-pole

3-pole

4-pole2-pole 3-pole

4-pole

Molded-case circuit breakers

New WS-V SeriesNF125-CV, NF125-SV, NF125-HV

Front connection

Rear connection

Plug-in

2-pole 3-pole 4-pole

2-pole 3-pole 4-pole

2-pole 3-pole 4-pole

Remarks: 1. 2-pole model of NF125-SV are 3-pole models with the central pole removed. 2. Only 2- and 3-pole models are available for the model of NF125-CV.

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 17 −

Page 19: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

CLLC

LC

3030

Breaker

Drilling plan

M4 × 0.7 screw or φ5 hole

CL

LC

LC

Tripbutton

Tripbutton

Operating time changing unit (time delay type)

Sensitivity current switching unit

Test button

Earth-leakage indicating button

120

90

30 Neutral pole

Earth-leakage indicating button

Test button

Sensitivity current switching unit

Operating time changing unit

130

112

50

90

60

22

Insulating barrier(removable)

Mountinghole

24

84 50

68

61

45

724

90

φ8.5

M8 screw

19 max. (comb-like conductor: 16.5 max.)

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

φ8.5

φ4.5

8CL

102

52

Connecting allowance 15

72

68

8.5

2.5

15

54.5

104.5

15

2.5

16

112

Mounting plate t = 3.2 max.

Stud rotatable by 90°

Insulating tube

M8 bolt

90

60

5

8

Insulating tube

M4 × 0.7 screw for breaker mounting

LCCL

CL

110-

111(

Not

e 1)

30

30

90

112

60

30

M4 × 0.7 screw or φ5 hole

Breaker

Drilling plan

φ18

LC

LC

LC

28

Breaker

52

86

R1

12.5

5.5 20

Details of terminal

16.5 max.

12

φ8.5

Conductor drillingdrawing

CL

89

Plug-in terminal block

Mounting plate

98 190

11

21

30M8 screw

M5 × 0.8 screwMounting with terminal block mounting nut or mounting directly with screw

LC

Drilling plan

CL CL

Breaker (plug-in terminal block)

54 9456

56

127

6030

97

M5 × 0.8 screw or φ6 hole

30

125

90

95

60

134

Note (1) Applicable to both mounting sizes 110 and 111Remark: NV125-CW is available in 3-pole only.

110-

111

(Not

e 1)

Front-panel cutout

1.0 mm clearance on each side of the handle frame

Earth-leakage circuit breakers

Previous W & WS SeriesNV125-CW, NV125-SW, NV125-HW

Front connection

Rear connection

Plug-in

3-pole

4-pole

3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole

3-pole

4-pole

4-pole

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 18 −

Page 20: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

111

111

8

19 max.

(comb-like conductor: 16.5 max.)

50

112

130

φ18

R1

30

50

90

30

90

120

28

90

30

112

30

112

130

102

52

72

68

8.5

2.5

15

54.5

104.5

15

2.5

16

112

60

5

86

52

60

30

90

60

22

24

84 50

68

61

45

724

90

8

30

5.5

83.5

85

170

12

3089

21

11

54 8054

54

97 127φ8.5

60

95

116

30

90

125

Connecting allowance 15

Drilling plan

Breaker (plug-in terminal block)

M5 × 0.8 screw or φ6 hole

20 max.

Conductor drilling drawingDetails of terminal

Plug-in terminal block

Mounting plate

M8 screw

M5 × 0.8 screwMounting with terminal blockmounting nut or mounting directly with screw

Breaker

Drilling plan

M4 × 0.7 screw or φ5 hole

3-pole

Tripbutton

Operating time changing unit (time delay type)

4-pole

Neutral pole

Earth-leakage indicating button

Test button

Sensitivity current switching unit

Insulating barrier (removable)

Mounting hole

φ8.5

M8 screw

Conductor drilling for direct connection

(Conductor thickness t = 5 max.)

φ8.5

φ4.5

Breaker

Insulating tube

M4 × 0.7 screw for breaker mounting

M4 × 0.7 screw or φ5 hole

Breaker

Drilling plan

Mounting plate t = 3.2 max. Stud rotatable by 90°

Insulating tube

M8 bolt

Front-panel cutout

1.0 mm clearance on each side of the handle frame

Remark: NV125-CV is available in 3-pole only.

Earth-leakage circuit breakers

New WS-V SeriesNV125-CV, NV125-SV, NV125-HV

Front connection

Rear connection

Plug-in

3-pole

4-pole

3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 19 −

Page 21: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Molded-case circuit breakers

Previous W & WS SeriesNF250-CW, NF250-SW, NF250-HW,MB225-SW

Front connection

Rear connection

Plug-in

105

102

50

61

68

45

724

92

24

70

22

23 max.

10

35

φ4.5

φ8.5

35

126

140

105

35

100

100

165

144

Neutral pole

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

Mounting hole

Insulating barrier(removable)

Tripbutton

M8 bolt with hexagon hole

φ8.5

CL

CLLC

CL CL

CL

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

15

15

22

20

144

70

35

φ24

68

72

71

106

8

6

105

70

35

105

35

126

144

Drilling plan

M4 × 0.7 screw or φ5 hole

Breaker

M4 × 0.7 screw for breaker mounting

Insulating tubeφ9M8 bolt

Connecting allowance

Insulating tube

Stud rotatable by 90°Mounting plate t = 3.2 max.

CL CL

LCLC

32.5

52

100

Breaker

LCCL

CL R1

86

200

18

32

144

34.5

28

20

70

105

153

6

14

70

107

70

15

22

φ7

58.5

58.5

8054

142

105

Studs can be installed in this direction only.

Insulating barrier

M6 screw for mounting terminal block

Mounting plate Plug-in terminal block

Connecting allowance

φ9M8 bolt

Drilling plan

Breaker (plug-in terminal block)

CL CL

CLCL

LC

3-pole 4-pole

3-pole 4-pole

Front-panel cutout

1.0 mm clearance on each side of the handle frame

Remarks: 1. 2-pole models are 3-pole models with the central pole removed. 2. Only 2- and 3-pole models are available for the model of NF250-CW and only 3-pole models are available for the model of MB225-SW.

3-pole

4-pole

3-pole 4-pole

3-pole4-pole

3-pole 4-pole

3-pole

4-pole

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 20 −

Page 22: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

105

102

50

61

68

45

724

92

24

70

22

25 max.

9

35

φ4.5

φ8.5

35

126

140

105

35

100

100

165

144

Neutral pole

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

Mounting hole

Insulating barrier(removable)

Tripbutton

M8 bolt with hexagon hole

φ8.5

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

15

15

22 20

144

70

35

φ24

68

72

71

106

8

6

105

70

105

35

126

144

Drilling plan

M4 × 0.7 screw or φ5 hole

Breaker

M4 × 0.7 screw for breaker mounting

Insulating tubeφ9M8 bolt

Connecting allowance

Insulating tube

Stud rotatable by 90°Mounting plate t = 3.2 max.

32.5

52

100

Breaker

1.0 mm clearance on each side of the handle frame

Front-panel cutout

R1

89

112

190

165

21

30

31

144

34.5

28 20

3-pole 70

4-pole 105

3-pole 105

4-pole 140

1516

11

70

107

70

15

24

56.5

56.5

8054

142

105

Studs can be installed in this direction only.

Insulating barrier

Mounting plate

Plug-in terminal block

Connecting allowance

φ9M8 bolt

Drilling plan

Breaker (plug-in terminal block)

4-pole 145

3-pole 110

35

M5 × 0.8 screw or φ6 hole

M5 screw for mounting terminal block

or

C1

C1

10

25 max.

φ8.5

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

Molded-case circuit breakers

New WS-V SeriesNF250-CV, NF250-SV, NF250-HV

Front connection

Rear connection

Plug-in

3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole

4-pole

3-pole 4-pole

Remarks: 1. 2-pole models are 3-pole models with the central pole removed. 2. Only 2- and 3-pole models are available for the model of NF250-CV.

− 21 −

Page 23: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Earth-leakage circuit breakers

Previous W & WS SeriesNV250-CW, NV250-SW, NV250-HW

Front connection

Rear connection

Plug-in

Drilling plan

M4 × 0.7 screw or φ5 hole

Breaker

126

3535

LC

LC

LC

Test button

Operating time changing unit (time delay type)

Sensitivity current switching unit

Earth-leakage indicating button

Test button

105

70

Insulating barrier(removable)

Mountinghole

Tripbutton

Operating time changing unit (time delay type)

Sensitivity current switching unit

Earth-leakage indicating button

Neutral pole

144

165

100

100

35

105

140

LC

CL

LC

22

φ8.5

M8 bolt with hexagon hole

φ8.5

φ4.5

10

24

92

4 72

45

68

61

50102

23 max.

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

144

126

35

105

35φ2435

70

CL CL

LCLC

Mounting plate t = 3.2 max.

Stud rotatable by 90°

Insulating tube

φ9M8 bolt

Insulating tube

M4 × 0.7 screw for breaker mounting

70

105

6

8

106

71

72

68

144

20

Connecting allowance 22

15

15

1.0 mm clearance on each side of the handle frame

Breaker

100

52

32.5

LC

LCCL

R1

φ9M8 bolt

Insulating barrier

Studs can be installed in this direction only.

15

70

153

70

105

20

LC Breaker (plug-in terminal block)

Drilling plan

105

142

54 8058

.558

.5

φ7107

70

CLLC

LC

Plug-in terminal blockMounting plate

M6 screw for mounting terminal block

14

6

2834

.514

4

32

18

200

86

LC

4-pole3-pole

Front-panel cutout

22 C

onne

ctin

g al

low

ance

Remark: NV250-CW are available in 3-pole only.

3-pole

4-pole3-pole

4-pole

3-pole 4-pole

3-pole4-pole

3-pole 4-pole

3-pole 4-pole

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 22 −

Page 24: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

100

144

165

15

105

102

50

61

68

45

724

92

24

70

22

9

φ8.5

15

20

144

70

35

35

φ24

φ4.5

68

72

71

106

φ8.5

35

126

140

105

35

100

100

165

144

8

6

105

70

35

105

35

126

144

32.5

R1

52

100

8056

.556

.5

107 142

34.5

2814

4

6

21

89

112

190 11165

30

31

20

151

70

24 C

onne

ctin

g al

low

ance

15

54

70 105

25 max.

Breaker

Breaker

Drilling plan

M4 × 0.7 screw or φ5 hole

Insulating tube

M4 × 0.7 screw for breaker mounting

Test button

Insulating barrier (removable)Mounting hole

Tripbutton

Operating time changing unit (time delay type)

Sensitivity current switching unitEarth-leakage indicating button

Neutral pole

M8 bolt with hexagon hole

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

Mounting plate t = 3.2 max.

Stud rotatable by 90°

Insulating tube

φ9M8 bolt

Connecting allowance 22

M4 × 0.7 screw or φ5 hole

M5 × 0.8 screw or φ6 hole

Drilling plan Front-panel cutout

1.0 mm clearance on each side of the handle frame

Breaker

Plug-in terminal blockMounting plate

φ9M8 bolt

Insulating barrier Studs can be installed in this direction only.

4-pole 145

4-pole 105

3-pole 110

3-pole 70

4-pole 140

3-pole 105Drilling plan

M5 screw for mounting terminal block

Remark: NV250-CV are available in 3-pole only.

Earth-leakage circuit breakers

New WS-V SeriesNV250-CV, NV250-SV, NV250-HV

Front connection

Rear connection

Plug-in

3-pole

4-pole

3-pole 4-pole

3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

or

C1

C1

10

25 max.

φ8.5

− 23 −

Page 25: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

NV250-SEW, NV250-HEW

Front connection

Rear connection

Plug-in

Insulating barrier

22 C

onne

ctin

g al

low

ance

15

153

20

70

105

70

φ9M8 bolt

Studs can be installed in this direction only.

Breaker (plug-in terminal block)

Drilling plan

Plug-in terminal blockMounting plate

105

142

54 8058

.558

.5

φ7

107

70

14

6

2834

.514

4

32

18

200

86

(Note) To change the settings, open the upper cover.

Current indicating LED OVER PAL 70%

Overcurrent test connector

(Conductor thickness t = 7 max.)

φ8.5

M8 bolt with hexagon hole

Tripbutton

Mounting hole

Drilling plan

Breaker

Neutral pole

144

165

100

100

35

105

140

126

35φ8.5

φ4.5

35

10

23 max.

22

70

24

92

4 72

45

68

61

50

102

(Upp

er co

ver)

105

Earth-leakage test button

Tripping characteristic switching unit

Sensitivity current switching unit

Earth-leakage indicating button

Operating time changing unit (time delay type)

Insulating barrier (removable)

M4 × 0.7 screw or φ5 hole

Conductor drilling for direct connection

Breaker3-pole

4-pole

100

52

32.5

R1

Insulating tube

22 Connecting allowance

φ9M8 bolt Insulating tube

M4 × 0.7 screw for breaker mounting

Breaker

Drilling plan

144

126

35

105

35

70

105

6

8

106

71

72

68

φ24

35

70

144

20

15

15 M4 × 0.7 screw or φ5 hole

Stud rotatable by 90°Mounting plate t = 3.2 max.

3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole

4-pole

1.0 mm clearance on each side of the

handle frame

Front-panel cutout

M6 screw for mounting terminal block

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

Earth-leakage circuit breakers

Previous W & WS Series

− 24 −

Page 26: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

NV250-SEV, NV250-HEV

Front connection

Rear connection

Plug-in

165

165

100

144

144

100

Tripping characteristic switching unit

Test button

Sensitivity current switching unit

Earth-leakage indicating button

25 max.

M8 bolt with hexagon hole

105

102

50

61

68

45

724

92

24

70

22

9

φ8.5

35

Mounting hole

(Conductor thickness t = 7 max.)

Breaker

φ4.5

φ8.5

35

126

140

105

35

100

Neutral pole

Tripbutton

Operating time changing unit (time delay type)

Insulating barrier (removable)

Conductor drilling for direct connection Drilling plan

M4 × 0.7 screw or φ5 hole

Breaker

32.5

52

100

R1

Stud rotatable by 90°

15

15

20 144

70

35

Mounting plate t = 3.2 max.

Insulating tube

22 Connecting allowance

φ9M8 bolt

M4 × 0.7 screw for breaker mounting

φ24

68

72

71

106

Insulating tube

8

6

105

70

35

105

35

126

144

Breaker

Drilling plan

M4 × 0.7 screw or φ5 hole

Front-panel cutout4-pole 140

4-pole 105

8056

.556

.5

107 142

34.5

2814

4

6

21

89

112

190

11165

30

31

20

3-pole 70

151

70

24 C

onne

ctin

g al

low

ance

15

3-pole 105

54

70

Plug-in terminal block

Mounting plate

105

Insulating barrier

M5 × 0.8 screw or φ6 hole

φ9M8 bolt

Studs can be installed in this direction only.

4-pole 145

3-pole 110

M5 screw for mounting terminal block

3-pole

4-pole 3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

1.0 mm clearance on each side of the

handle frame

Front-panel cutout

Earth-leakage circuit breakers

New WS-V Series

or

C1

C1

10

25 max.

φ8.5

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 25 −

Page 27: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

NF125-SGW, NF125-HGW, NF160-SGW, NF160-HGW, NF250-SGW, NF250-HGW

Remark: 1. 2-pole models are 3-pole models with the central pole removed.

Mounting plate

4530Stud can berotated 90°

5454

9466

4-pole

3-pole

110

104810

3

M8 bolt(Hex-soket)12 96

4

4854

.514

4

120

15

200

4-pole3-poleφ9M8 bolt

105

142

Drilling plan

Con

nect

ion

al

low

ance

Insulating barrier(removable)

M6 screw for mounting terminal block

Breaker (Terminal block)

φ7

Plug-in terminal block

107

70

70

20

86

3-pole

4-pole

100

52

32.5

Breaker

Front-panel cutout

R1

35

90

86

Breaker

4-pole3-pole

144

126

35

105

35

70

105

6

8

3-pole

4-pole

Insulatingtube

M4 × 0.7tapsor φ5

Drilling plan

106

71

φ24

M4 × 0.7 screw for breaker mounting

φ9M8 bolt

Connectionallowance

Insulating tube

Stud can berotated 90°

Mounting plate t = 3.2 max.

70

144

20

22

15

15

Hex-socket set screwWire connection

Solderless terminalfor wire size2.5 185 mm2

10

6.1

2235

24 max.

110

90

86

79

63

112

4-pole3-pole

Neutralpole

4-pole3-pole

144

165

5050

35

105

140

126

35φ8.5

φ4.5

M4 × 0.7 tapsor φ5

Drilling plan

BreakerM8 bolt(Hex-soket)

(Bus t max. = 7)

Bus drilling fordirect connection

Tripbutton

Mounting hole

Insulating barrier(removable)

φ8.5

10

22

70

24

450

105

Front connection

Rear connection

Plug-in

Molded-case circuit breakers

Previous W & WS Series

1.0 mm clearance on each side of the handle frame

− 26 −

Page 28: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

NF125-SGV, NF125-LGV, NF125-HGV, NF125-SEV, NF125-HEV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV

105

102

50

61

68

45

724

92

24

70

2225 max.

9

35

φ4.5

φ8.5

35

126

140

105

35

100

100

165

144

Neutral pole

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

Mounting hole

Insulating barrier(removable)

Tripbutton

M8 bolt with hexagon hole

φ8.5

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

15

15

22 20

144

70

35

φ24

68

72

71

106

8

6

105

70

105

35

126

144

Drilling plan

M4 × 0.7 screw or φ5 hole

Breaker

M4 × 0.7 screw for breaker mounting

Insulating tubeφ9M8 bolt

Connecting allowance

Insulating tube

Stud rotatable by 90°Mounting plate t = 3.2 max.

32.5

52

100

Breaker

1.0 mm clearance on each side of the handle frame

Front-panel cutout

R1

89

112

190

165

21

30

31

144

34.5

28 20

3-pole 70

4-pole 105

3-pole 105

4-pole 140

1516

11

70

107

70

15

24

56.5

56.5

8054

142

105

Studs can be installed in this direction only.

Insulating barrier

Mounting plate

Plug-in terminal block

Connecting allowance

φ9M8 bolt

Drilling plan

Breaker (plug-in terminal block)

4-pole 145

3-pole 110

35

M5 × 0.8 screw or φ6 hole

M5 screw for mounting terminal block

Front connection

Rear connection

Plug-in

3-pole

4-pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

3-pole

4-pole

3-pole 4-pole

Molded-case circuit breakers

New WS-V Series

or

C1

C1

10

25 max.

φ8.5

Remark: 2-pole models are 3-pole models with the central pole removed.

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 27 −

Page 29: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

NF125-RGW, NF250-RGW

Front connection

Rear connection

Plug-in

φ7

Drilling plan

Mounting plate

φ9M8 bolt

275

34.5

219

28

6

32

18

14

104

1570

20

70

153

70

58.5

58.5

155

129

107

100

32.5

52

4-pole

3-pole

R1

Breaker

1.0 mm clearance on each side of the handle frame

Front-panel cutout

11.5

105

35

35

70

35

4-pole

3-pole

8

105

70

6

20

15

15

90 106

7186

4-pole3-pole

Insulatingtube

M4 × 0.7tapsor φ5

Drilling plan

φ24

M4 × 0.7 screw for breaker mounting

φ9M8 bolt

Connectionallowance

Insulating tube

Stud can berotated 90°

Mounting plate t = 3.2 max.

201

219

219

108

73

22

Breaker

24

(Bus t max. = 7)

24 max.

10

M8 bolt(Hex-soket)

M4 × 0.7 tapsor φ5

3535

110

4 90

86

79

φ8.5

63

22

φ4.5

50112

4-pole

5050

35

105

140

22

70

105 4-pole3-pole

Neutralpole

3-poleDrilling plan

Breaker

Tripbutton

Mounting hole

Insulating barrier(removable)

201

240

219

φ8.5

6.1

Solderless terminalfor wire size2.5 185 mm2

10

Bus drilling fordirect connection

Wire connection

Hex-socket set screw

26.5

7516

5

Remark: 2-pole models are 3-pole models with the central pole removed.

Molded-case circuit breakers

Previous W & WS Series

Plug-in terminal block

M6 screw for mounting terminal block

Breaker (Terminal block)

Insulatingbarrier

Stud attachable in thisderection only

22

Connecting allowance

− 28 −

Page 30: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Molded-case circuit breakers

New WS-V SeriesNF125-RGV, NF250-RGV

15

15

22 20

144

70

35

φ24

68

72

71

106

8

6

70

Drilling plan

M4 × 0.7 screw or φ5 hole

Breaker

M4 × 0.7 screw for breaker mounting

Insulating tubeφ9M8 bolt

Connecting allowance

Insulating tube

Stud rotatable by 90°Mounting plate t = 3.2 max.

32.5

52

100

Breaker

1.0 mm clearance on each side of the handle frame

Front-panel cutout

R1

Front connection

Rear connection

Plug-in

3-pole

3-pole

70

107

Drilling plan

Breaker (plug-in terminal block)

3-pole

105

70

22

Mounting hole

Insulating barrier(removable)

Tripbutton

3-pole

3-pole

35

Breaker

M4 × 0.7 screw or φ5 hole

Drilling plan

3-pole

102

50

61

68

45

724

92

24

25 max.

9

φ4.5

φ8.5

M8 bolt with hexagon hole

φ8.5

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

or

C1

C1

10

25 max.

φ8.5

89

112

190

165

21

30

31

144

34.5

28

6

11

Mounting plate

Plug-in terminal block

M5 screw for mounting terminal block

20

3-pole 70

3-pole 105

151

70

15

24

Studs can be installed in this direction only.

Insulating barrier

Connecting allowance

φ9M8 bolt

3-pole 110

Remark: 2-pole models are 3-pole models with the central pole removed.

Solderless terminal for wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 29 −

Page 31: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

NF125-UGW, NF250-UGW

Front connection

Rear connection

Plug-in

φ7

Drilling plan

Mounting plate

φ9M8 bolt

275

34.5

219

28

6

32

18

14

104

1570

20

70

153

70

58.5

58.5

155

129

107

100

32.5

52

4-pole

3-pole

R1

Breaker

1.0 mm clearance on each side of the handle frame

Front-panel cutout

11.5

105

35

35

70

35

4-pole

3-pole

8

105

70

6

20

15

15

90 106

7186

4-pole3-pole

Insulatingtube

M4 × 0.7tapsor φ5

Drilling plan

φ24

M4 × 0.7 screw for breaker mounting

φ9M8 bolt

Connectionallowance

Insulating tube

Stud can berotated 90°

Mounting plate t = 3.2 max.

201

219

219

108

73

22

Breaker

24

(Bus t max. = 7)

24 max.

10

M8 bolt(Hex-soket)

M4 × 0.7 tapsor φ5

3535

110

4 90

86

79

φ8.5

63

22

φ4.5

50112

4-pole

5050

35

105

140

22

70

105 4-pole3-pole

Neutralpole

3-poleDrilling plan

Breaker

Tripbutton

Mounting hole

Insulating barrier(removable)

201

240

219

φ8.5

6.1

Solderless terminalfor wire size2.5 185 mm2

10

Bus drilling fordirect connection

Wire connection

Hex-socket set screw

26.5

7516

5

Remark: 2-pole models are 3-pole models with the central pole removed.

Molded-case circuit breakers

Previous W & WS Series

Plug-in terminal block

M6 screw for mounting terminal block

Breaker (Terminal block)

Insulatingbarrier

Stud attachable in thisderection only

22

Connecting allowance

− 30 −

Page 32: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

106

71

72

68

8

6

105

70

2022

15

15

219

φ24 35

105

35

70

32.5

52

10035

219

201

11.5

35

201

35

92

4 72

68

61

45

φ4.55010

2

24

100

100

240

219

140

105

35

105

70

22

7516

5

10

φ8.5

φ8.5

28

7516

5

73

108

Breaker

Drilling plan

M4 × 0.7 screw or φ5 hole

23 max.

Insulating barrier(removable)

Mounting hole

Trip button

Conductor drilling for direct connection

(Conductor thickness t = 7 max.)

M4 × 0.7 screw or φ5 hole

Drilling plan

Breaker

3-pole

M4 × 0.7 screw for breaker mountingInsulating tube

φ9M8 bolt

Connecting allowance

Insulating tube Stud rotatable by 90°

Mounting plate t = 3.2 max. Breaker

3-pole

4-pole

1.0 mm clearance on each side of the handle frame

Front-panel cutout

R1

Breaker (plug-in terminal block)

Mounting platePlug-in terminal block

Studs can be installed in this direction only.

Insulating barrier

Con

nect

ing

allo

wan

ce

155

56.5

56.5

107

34.5

2821

9

6

21

89

11

30

31

20

70

151

70

24

15

110

105

129

70φ9M8 bolt M5 screw or φ6 hole

265

Drilling plan

Molded-case circuit breakers

New WS-V SeriesNF125-UGV, NF250-UGV

Front connection

Rear connection

Plug-in

Neutral pole

3-pole 4-pole

3-pole 4-pole

3-pole 4-pole

M8 bolt with hexagon hole

4-pole

M5 screw for mounting terminal block

Remark: 2-pole models are 3-pole models with the central pole removed.

Solderless terminalfor wire size125~175A 14~95mm2

200~250A 70~125mm2

Wire connection

− 31 −

Page 33: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

MEMO

Page 34: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance
Page 35: Comparison of Previous and New Models - Mitsubishi …. Comparison of Previous and New Models Series Previous W & WS Series New WS-V Series Differences in dimensions and performance

Revised publication, effective Sep. 2010.Specifications subject to change without notice.

This pamphlet is made from recycled paper.

Safety Tips : Be sure to read the instruction manual fully before using this product.

Country / Region Company Address Telephone

Australia

China

Mitsubishi Electric Australia Pty. Ltd.

Mitsubishi Electric Automation (CHINA) Ltd.

348 Victoria Road, Rydalmere, N.S.W. 2116, Australia +61-2-9684-7777

+86-21-2322-303017/F., ChuangXing Financial Center, No.288 West Nanjing Road, Shanghai, 200003

China Mitsubishi Electric Automation (HongKong) Ltd. +852-2887-881010/F., Manulife Tower, 169 Electric Road, North Point, Hong Kong

Colombia Proelectrico Representaciones S.A. Carrera 53 No 29C-73 - Medellin, Colombia +57-4-235-30-38

Egypt Cairo Electrical Group9, Rostoum St. Garden City P.O. Box 165-11516 Maglis El-Shaab, Cairo - Egypt

+20-2-27961337

Europe Mitsubishi Electric Europe B.V. Gothaer Strasse 8, D-40880 Ratingen, Germany +49-(0)2102-486-0

Indonesia

Korea

Laos

Mitsubishi Electric Automation Korea Co., Ltd

Societe Lao Import Co., Ltd.

P.O.Box 5045 Kawasan Industri Pergudangan, Jakarta, Indonesia

1480-6, Gayang-Dong, Gangseo-Gu, Seoul, Korea

43-47 Lane Xang Road P.O. BOX 2789 VT Vientiane Laos

+62-(0)21-6610651-9

+82-2-3660-9572

+856-21-215043

P. T. Sahabat Indonesia

Lebanon Comptoir d'Electricite Generale-LibanCebaco Center - Block A Autostrade Dora, P.O. Box 11-2597 Beirut - Lebanon

+961-1-240445

Myanmer

Nepal

Peace Myanmar Electric Co.,Ltd.

Watt&Volt House

NO137/139 Botataung Pagoda Road, Botataung Town Ship 11161, Yangon, Myanmar

KHA 2-65, Volt House Dillibazar Post Box:2108,Kathmandu, Nepal

Malaysia Mittric Sdn Bhd5 Jalan Pemberita U1/49, Temasya Industrial Park, Glenmarie 40150 Shah Alam, Selangor, Malaysia

+603-5569-3748

+95-(0)1-202589

+977-1-4411330

Comptoir d'Electricite Generale-International-S.A.L.

Cebaco Center - Block A Autostrade Dora P.O. Box 11-1314 Beirut - Lebanon

+961-1-240430Other Middle East

Arab Countries & Cyprus

Pakistan

Philippines

Prince Electric Co.

Edison Electric Integrated, Inc.

1&16 Brandreth Road, Lahore-54000, Pakistan

24th Fl. Galleria Corporate Center, Edsa Cr. Ortigas Ave., Quezon City Metro Manila, Philippines

+92-(0)42-7654342

+63-(0)2-634-8691

Saudi Arabia Center of Electrical GoodsAl-Shuwayer St. Side way of Salahuddin Al-Ayoubi St. P.O. Box 15955 Riyadh 11454 - Saudi Arabia

+966-1-4770149

South Africa CBI-electric: low voltage Private Bag 2016, Isando, 1600, South Africa +27-(0)11-9282000

Taiwan

Thailand

Setsuyo Enterprise Co., Ltd

United Trading & Import Co., Ltd.

6th Fl., No.105, Wu Kung 3rd, Wu-Ku Hsiang, Taipei, Taiwan, R.O.C.

77/12 Bamrungmuang Road, Klong Mahanak, Pomprab Bangkok Thailand

+886-(0)2-2298-8889

+66-223-4220-3

Uruguay Fierro Vignoli S.A. Avda. Uruguay 1274, Montevideo, Uruguay +598-2-902-0808

Venezuela Adesco S.A.Calle 7 La Urbina Edificio Los Robles Locales C y D Planta Baja, Caracas - Venezuela

+58-212-241-9952

Chile Rhona S.A. Agua Santa 4211 P.O. Box 30-D Vina del Mar, Chile +56-32-2-320-600

Vietnam CTY TNHH-TM SA GIANG10th Floor, Room1006-1007,225 Tran Hung Dao St., Co Giang Ward, Dist.1, Ho Chi Minh City. Viet Nam

+84-8-838-6727/28/29

Singapore Mitsubishi Electric Asia Pte. Ltd.307, Alexandra Road, #05-01/02Mitsubishi Electric Building, Singapore 159943

+65-6473-2308

Y-0702 1009 printed in Japan(MDOC)

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN