pd measurement

Upload: pemanr1914

Post on 13-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/24/2019 Pd measurement

    1/6

    MEASUREMENT OF PARTIAL DISCHARGES IN AN INDUSTRIAL HV TEST LABORATORY

    R. MALEWSKI* W. MOKASKI J. WIERZBICKI

    Instytut Elektrotechniki Bydgoszcz Cable Works Tradeways

    Poland

    Keywords: HV cable test - Partial discharge Induced disturbanceElectromagnetic shield - Shielded HV laboratory

    Shielding efficiency - Conducted disturbance RF filter - Deep grounding Higher harmonics

    Introduction

    An acceptance test of HV cables, transformers and other

    HV apparatus is carried out in industrial HV

    laboratories. Some of these laboratories are designed to

    perform Partial Discharge (PD) measurements, and they

    have to be equipped with an electromagnetic shield that

    is sometimes referred to as Faraday cage. An ideal

    shield forms a continuous metal enclosure that covers

    the walls, ceiling and floor of the test hall. Faraday has

    discovered that an external electromagnetic field

    impinging on such shield induces a current that flows in

    the walls, ceiling or floor. This current prevents the

    external field from penetration inside the enclosure.Radio stations broadcasting in AM mode emit the

    disturbing electromagnetic field. Besides, transient

    electromagnetic field can be generated by the ignition

    system of internal combustion engines, by sparking

    between an electric locomotive pantograph and tractionwire, by an arc welding, and by many other sources.

    In practice, the electromagnetic shield cannot be

    continuous and completely enclosed, since it is

    composed of metal panels connected to each other at the

    edge, and of doors and windows. It is imperative to

    ensure a low-impedance contact between the panels, andbetween the door and its frame.

    The minute current induced in the shield by e.g. a

    broadcasting station can be diverted by greasy contacts

    between the door and its frame, or by a layer of oxide

    on the metal panels bonded together by bolts. An

    electromagnetic field enters the HV test hall through

    such discontinuity, or opening in the shield, and

    induces disturbances in the PD measuring circuit that

    acts as a large-size antenna. Such disturbances mask the

    minute PD signals and impair diagnostic of the

    examined HV insulation.

    The shield efficiency is defined as a ratio of the electric

    (or magnetic) field component outside and inside theshielded area. The higher the efficiency, the lower is

    background disturbance level. Naturally, the cost of HV

    test hall depends largely on the electromagnetic shield

    efficiency.

    An acceptable PD level is specified for each kind ofapparatus, and ranges from a few hundreds of

    picocoulombs (pC) for power transformers, down to a

    single pC for cross-linked polyethylene (XLPE) cables.

    In the case of HV power transformers the background

    disturbance should not exceed a few tens of pC,

    however, to test XLPE HV cables, the backgrounddisturbance should be reduced to approximately one pC.

    _______________________________________________________________________________________________*Prof. Dr-Ing. Ryszard Malewski, owicka 53 m 12, 02 535 Warszawa, Poland, E-mail: [email protected]

    21, rue d'Artois, F-75008 Parishttp://www.cigre.org

    Session 2002 CIGR33-303

  • 7/24/2019 Pd measurement

    2/6

    A well-designed electromagnetic shield can effectively

    reduce disturbance inducedin the PD measuring circuit.

    However, disturbances are also conductedby the supply

    and control cables, or by the laboratory grounding. The

    power and control cables carry mainly power-frequency

    currents, whereas the conducted disturbances containhigh-frequency spectral components. Radio-frequency

    (RF) filters inserted in series with the supply wires

    prevent these high-frequency currents form entering the

    shielded enclosure.

    Besides, in an industrial environment stray currents

    circulate in the upper soil layers, between different

    grounding points of supply transformers, large motors

    and other loads installed in different factory buildings.

    A large metal enclosure of the shielded HV test hall

    offers a low-impedance path for these stray currents. An

    on-and-off switching of such current induces a transient

    disturbance in the PD measuring circuit. To prevent the

    stray current from flowing in the electromagnetic shieldit has to be isolated from the local ground and from

    structural elements connected to such ground. A special

    grounding rod is driven deep into the soil, and insulated

    from the upper soil layers. The electromagnetic shield

    has to be connected to such deep-driven grounding rod,and insulated from all locally grounded structures.

    It has been reported that PD measured with purely

    sinusoidal voltage waveform are lower than the

    respective measurements taken on the same object with

    a distorted-waveform voltage. However, an industrial

    plant often uses large motors with a thyristor speed-controlled drive. Such drive generates higher harmonics

    of current and voltage in the supply system. A distortedsupply voltage affects the test voltage waveform, and

    increases the PD level measured on the examined test

    object. To reduce the test-voltage waveform distortion,

    the HV laboratory should be supplied by a separatepower transformer.

    To test of big EHV power transformers a very large

    laboratory is required. The huge test hall has to be

    protected by an electromagnetic shield that is required

    to enable broad-band PD measurement. Such shield has

    been designed for the world largest HV laboratories of

    IREQ in Montreal [1] and EdeF in Renardieres. An

    important practical experience was gathered since their

    commissioning. Comments on this experience and somefindings on the shield performance may be of use for

    designers of new installations, and will be presented in

    this paper.

    Testing HV power cables imposes the most stringent

    requirements on the background disturbance level.

    Design of a large laboratory that can perform

    contractual and development test of XLPE cables rated

    up to 400 kV represents a challenge to engineers

    specialized in HV technique and in electromagnetic

    compatibility. Such laboratory was recently

    commissioned at Bydgoszcz Cable Works [2], and

    represents the state of the art facility for quality control

    of EHV power cables. This installation may serve as an

    example how to protect the PD measuring circuitagainst both induced and conducted disturbances.

    P D measurement during acceptance-test of power

    transformers.

    International Standards require PD measurement during

    the induced voltage test for transformers rated at 220 kVand higher. However, many utilities specify PDacceptance levels also for windings rated at 110 kV.

    Usually, the acceptance level is indicated at 500 pC, but

    recently lower values (300 pC and even 200 pC) are

    often required [3]. Some specifications delimit an

    acceptable variation of the measured PD level during

    the last 30 minutes of one-hour test duration, and suchvariation shall not exceed e.g. 30 pC. An unstable and

    high level of PDs may indicate a high content of

    moisture in cellulose, particles in oil and other

    technological flaws that disqualify the transformer.

    A reliable measurement of PDs at 100 pC level can be

    performed if the background noise is restricted to 10 pCrange. The test circuit of 400 kV or 220 kV transformer

    acts as a large size antenna and collects the signals

    induced by stray electromagnetic field. In an unshielded

    test hall such disturbance may exceed by orders of

    magnitude the PDs measured in the transformerinsulation. The small, sought PD impulses are then

    completely masked. To suppress the disturbance to an

    acceptable level the test circuit has to be installed in an

    efficient electromagnetic shield.

    Design of the electromagnetic shieldDesign features of the electromagnetic shield are

    presented on an example of very large (8267m, 52m

    clearance to the ceiling) HV test hall equipped with anelectromagnetic shield. The shielding efficiency of the

    electric and magnetic field component was measured at

    690 kHz and is presented in form of equal attenuation

    lines shown in Fig. 1 [4]. Experience of transformer test

    laboratories indicates that the attenuation of themagnetic field component by 60 dB is in general

    sufficient to reduce the PD background disturbance to

    the required 10 pC level [5].

    Fig.1 (after [4]). Attenuation of the electric (E) and

    magnetic (H) field component inside a large

    shielded HV test hall. A leakage of the disturbance

    field in vicinity of the large entrance door, as well

    as near the windows can be identified on this graph.

    A penetration of the external disturbance field into thetest hall is mainly caused by a poor contact between the

  • 7/24/2019 Pd measurement

    3/6

    3

    doors and doorframe. This is due to a thin layer of

    grease or dirt on the contact surface. The current that

    circulates in the electromagnetic shield walls can be

    effectively prevented from flowing across the door by

    such a thin layer of dirt. An impedance of the dirt layer

    is high enough to stop the current, since the voltage

    difference at the contacts is of the order of somemicrovolts only. Such doors behave then as a large

    opening in the shield, and the external field can

    penetrate into the test hall.

    The shield has been construed from 44 m steel panelsconnected by welding at spots spaced by approximately

    0.3 m. The steel panels covered the four walls and

    ceiling, and the whole shield was welded at spots spaced

    by the same distance to the copper mesh that covers thewhole laboratory floor. A conceptual drawing of the

    current flow in the electromagnetic shield is shown in

    Fig. 2, assuming a vertically directed magnetic field (H)

    vector.

    Fig. 2. The drawing shows an exaggerated effect of the

    disturbance field penetration between the spotconnections of the adjacent metal panels. An

    external electromagnetic field induces a current that

    flows in the shield walls, and prevents the applied

    field from penetration into the shielded area. Any

    disturbance or attenuation of the induced currentflow affects the shielding efficiency and allows the

    field to leak-in.

    The disturbance field can penetrate into the shielded

    area due to the non-continuous, spot connection of the

    adjacent panels. However, such the penetration depth

    may reach the distance equal to the spacing between the

    welded points, if the wavelength of applied

    electromagnetic field is comparable to this spacing. Inreality, the PD measurements in power transformers are

    performed in the frequency range up to 1 MHz, and the

    shielding efficiency beyond this frequency is of nopractical concern.

    It has been observed in one of the test laboratories that a

    high efficiency electromagnetic shield has deteriorated

    after years of service. The shield was made of

    overlapping copper panels simply nailed together along

    the edge to ensure a good contact between adjacentpanels. The shield worked fine as long the copper

    surface was free from oxidation. However, under the

    action of atmospheric humidity a layer of oxide has

    developed and the contact resistance increased to theextent to impair circulation of induced current. At this

    moment, the electromagnetic shield became transparent

    to the external electromagnetic field, and thebackground noise level increased by orders of

    magnitude. Although trivial, this example confirms the

    necessity of welded or soldered contacts between the

    panels that form an electromagnetic shield.

    Some manufacturers use a moving-bridge (crane) totransport their transformers from the production hall tothe HV test area. The moving-bridge rails and supply

    wires enter into the shielded test hall and reduce its

    shielding efficiency. More modern plants use air

    cushions to move the transformers, and then the

    shielded test hall can be effectively closed.

    Due consideration should be given to the cost of anelectromagnetic shield of a HV test hall large that is

    enough to accommodate 400 kV power transformer

    with the necessary clearance to the ceiling and walls.

    Some smaller manufacturers cannot afford such

    investment, and try to perform the induced voltage test

    during night hours, when most of the disturbancesources are not active. However, the presence and

    intensity of disturbances are random and unpredictable.

    A large manufacturer is bound to deliver transformers

    according to a tight schedule and cannot afford the

    suitable time testing.

    PD measurement during acceptance test of cross-

    linked polyethylene(XLPE)power cablesHV cross-linked polyethylene power cables are the most

    difficult test objects for PD measurements, due to a very

    low level of acceptable PDs. Usually the test

    specification allows one, two or at most five pC. Thebackground disturbance shall be less than 1 pC, despite

    a large physical size of test circuit. For instance, the 400kV rated cable pothead assembled on a supporting

    structure may be as high as 10 m. Even modest

    electromagnetic disturbance field will induce a strong

    signal in such antenna. An electromagnetic shield of theHV test hall shall have a high efficiency, exceeding 100

    dB in the frequency range extending to the PD

    measuring instrument upper frequency limit, (usually

    250 kHz). It is rather difficult, if not impossible, to

    reach so high attenuation in an electromagnetic shield

    improvised from metal panels welded at spots [6].

    At Bydgoszcz Cable Works two professional, shielded

    rooms have been installed, with specially designed

    seams and joints [7]. Each Faraday cage has the floorsize 2516 m and 13 m clearance to the ceiling. These

    are primarily used for PD measurements on XLPE

    cables up to 400 kV rated voltage. Besides, lightning

    and switching impulse, HVDC and power frequency

    voltage withstand tests are carried out in these two

    shielded laboratories.

    This shielded enclosure complies with the International

    [8] and American National [9] standard requirements.

    The attenuation characteristic compares favorably to the

    US military and National Security Agency specification

    for shielding efficiency [10].

    The shield walls are made of a double-layer aluminum

    sheath, with plywood panels sandwiched in between toprovide a structural rigidity. Specially designed

  • 7/24/2019 Pd measurement

    4/6

    moldings fastened by a row of bolts join edges of

    adjacent panels. Particular attention is paid to the

    entrance doors that are large enough (54 m) to allow

    for transportation of large and heavy HV cable drums.

    An electromagnetic gasket sometimes referred to as

    fingers is installed along the edge of the door frame,

    and a knife edge of the doors is squeezed into thesefingers when the door is closed. The fingers are made

    of a hard beryllium-copper alloy and soldered to the

    doorframe. Each time the door is open and closed the

    sharp and elastic fingers scratch the door edge,

    remove the dirt layer and refresh the galvanic contact

    between the shield and the doors.

    Forced-air ventilation ducts of the shielded enclosure

    are equipped with honeycomb type electromagnetic

    barrier, and interference-free lighting fixtures do not

    contribute to the background disturbance level.

    Amplitude characteristic of the electromagnetic shield

    installed in Bydgoszcz Cable Works, is shown in Fig. 3.

    Fig. 3. Attenuation of the magnetic field component bythe electromagnetic shield manufactured by

    Universal Shielding Corporation Company and

    installed in the HV test hall of Bydgoszcz Cable

    Works. Superimposed are characteristics specified

    by the US Air Force and the National Security

    Agency (NSA 65-6).

    German Standard (VDE) specifies 2 pC as the highest

    allowed PD level measured during the test of HV

    cables, and Polish Standard [11] imposes 5 pC limit at

    the test voltage U=2*Uo. These requirements are

    routinely fulfilled during the tests of XLPE cables

    manufactured by Bydgoszcz Cable Works.

    High Voltage test equipment

    The state of the art shielded enclosure requires equally

    refined HV test equipment that provides the PD-free test

    voltage. A resonant-circuit test set-up, tuned to power

    frequency by reactors with a moving magnetic core was

    chosen [12], to avoid intense interference produced by

    semiconductor controlled, frequency-regulated resonant

    test set-ups. Two regulated reactors rated at 350 kV, 30

    A can be stacked up and tuned to resonance with the

    examined cable section. The test voltage is supplied by

    a 500 kVA regulator and an exciting transformer with

    500 kV rated highest-voltage output.

    The measuring instrumentation is composed from thecomputer assisted TE-571 PD detector, HV divider and

    coupling capacitor, as well as auxiliary instruments, all

    from the same leading manufacturer of HV test

    equipment. A computerized test procedure can be

    implemented owing to the integrated system of test

    voltage control and measurement, as well as PD

    recording. A fault location procedure is incorporated in

    the PD measuring system, and a damaged insulation ofthe examined cable section can be located within a few

    meter uncertainty.

    Filtering out the conducted disturbances

    A well-designed and installed shield suppresses the

    disturbances induced by external electromagnetic field

    to a negligible level. High quality HV test equipment

    provides PD-free test voltage. At this stage thedominant disturbance is conducted by the supply and

    control, as well as by the grounding system.

    The requirement of a very low disturbance level brings

    to the test hall designer attention another mechanism of

    disturbance penetration into the test circuit. Namely,

    disturbances conducted by the supply, control andmeasuring cables. Special filters are installed in all

    circuits entering the shielded HV test hall, to attenuate

    the conducted disturbing signals. The filter complexity

    and cost depends on the required attenuation

    characteristic and on the power frequency current that

    has to pass through the filter.

    A typical filter is composed of series connected reactors

    and parallel capacitors. A circuit diagram and amplitude

    characteristic of such filter is shown in Fig. 4.

    Fig. 4. Circuit diagram of a typical RF filter employed

    to supply the HV test transformer. An effect of core

    saturation on the filter attenuation characteristic is

    shown on the right sketch. An attenuation of the

    differential and common mode disturbance is

    presented conceptually on the lower sketch.

    The air core reactors attenuate the differential mode

    disturbance, and magnetic core reactors, with bi-filar

    winding reduce the common mode disturbance. Thelatter is conducted by the phase-conductors and returnsvia the ground. In principle, the load current i50Hzshall

  • 7/24/2019 Pd measurement

    5/6

    5

    not saturate the reactor core, since the bi-filar winding

    compensates the magnetic flux induced by the go and

    return current. However, the residual flux may saturate

    the core, if the reactor rated current is exceeded. A

    saturated core reduces the reactor inductance and shifts

    the attenuation characteristic toward a higher frequency.

    Besides, the saturated reactor core contributes to thetest-voltage waveform distortion.

    Distortion of the test voltage waveform by harmonics

    One of practical problems to be solved by an industrial

    test laboratory is to maintain a spectrally pure waveform

    of the test voltage.

    Usually the HV laboratory is located next to production

    area, supplied from the same substation, and sometimes

    even from the same transformer. A thyristor controlled

    drive of large machines, and other non-linear loads,

    distort the current, and in consequence the supply

    voltage waveform.

    This distortion is transferred to the test voltage andcorrupts PD measurements. For instance, the PD

    intensity in a gas bubble trapped in solid insulation

    increases with the test voltage steepness. An increasing

    content of higher harmonics results in a steeper voltage

    slope, and in consequence in a higher PD intensity. This

    problem has been investigated [13], and a typicalexample of such distortion is shown in Fig. 5.

    Fig. 5. (After [13]). An effect of the test voltage

    distortion on the PD charge distribution Q=f1()

    and frequency of occurrence N=f2(). On the left

    side the Total Harmonic Distortion is negligible

    (THD=0.7%). On the right side a high content of

    fifth harmonics results in THD=10%.

    To eliminate this problem at the source, Bydgoszcz

    Cable Works has installed a separate power transformer

    to supply the HV laboratory.

    Faraday cage grounding

    The electromagnetic shield is connected to a group of 5grounding rods driven to the depth of 20 m, and

    insulated from the topsoil layers to the depth of 6 m.

    The grounding rods are star-connected and bonded to

    the shielded enclosure in one point. This joint allows for

    periodic checks of the grounding resistance (that does

    not exceed 1 even during the dry season,) and also for

    checking the insulation between the shielded enclosure

    and locally grounded objects.The upper soil layers conduct ground currents, and in

    particular the higher harmonics of the power frequency

    current. Such harmonics are generated by thyristor

    controlled loads, such as electric motors, or rectifiers

    [14].

    Fig. 6. Supply circuit of thyristor controlled drives, and

    the higher harmonics current flow path. The

    harmonics and transient disturbance current flow

    through the upper soil layers, as well as in structuralmembers of steel buildings.

    It should be noted that the third and ninth harmonic

    current flow by the three phase conductors in the same

    phase. In consequence, these harmonic currents flow inthree-phase conductor in such a way, as if they were one

    common conductor, i.e. homopolarly, as it is

    schematically shown in Fig. 6.

    This current returns to the supply source (power

    transformer in substation) by the zero wire, and also

    through the grounding system that is parallel to zero

    conductor. At higher frequency the zero conductor

    impedance is in general higher than that of the ground

    return. For instance, the reactive impedance Xoof 300 m

    section of zero wire attains Xo=2350[Hz]1[H/m]

    300[m] 0.3 at the third harmonics, and at the ninth

    it approaches 1.

    Grounding system in general has lower impedance, andthe higher harmonics, as well as transient common

    mode disturbance currents tend to flow through the

    upper soil layer. Such transients are generated by arc

    welding, sparking at the breaker or disconnect contacts,sparking of the electric traction locomotive and similar

    events.

    Any metal object buried in the ground offers even lower

    impedance path and attracts the ground currents. For

    instance, a steel structure of the HV hall attracts the

    higher harmonic currents, as well as any metal cableshield, or a pipe buried in the ground, as it is sketched in

    Fig. 7.

    Random occurring disturbances sometimes recorded bythe PD measuring instrument come to the test set-up

  • 7/24/2019 Pd measurement

    6/6

    through the harmful coupling between the

    electromagnetic shield and the factory grounding

    system. Another path leads through the RF filters, if

    they are saturated by an excessive load-current.

    Fig. 7. Paths of the ground return current flow in the

    upper layers of soil. To prevent this current fromflowing in the Faraday cage it has to be insulated

    from local groundings, and connected to a deep

    driven grounding rod.

    Conclusions

    Partial discharges measured in a HV laboratory

    designed to test power transformers and XLPE cables

    have a distinctly different intensity. In consequence, the

    background disturbance level acceptable in these

    laboratories is also quite different. The most severe

    requirements are specified for XLPE power cables, andthe cable test laboratory has to be equipped with a high

    efficiency electromagnetic shield. An electromagnetic shield of a large HV test hall

    represents a large investment for the factory, and has to

    be carefully designed to attain the required, lowdisturbance level. In the case of a power transformer

    factory the shield can be made of steel panels welded

    together in regularly spaced spots. However, a XLPE

    cable factory had to acquire a professionally made

    shield, with carefully designed seams and joints.

    In addition to the disturbance signals inducedby an

    external electromagnetic field, disturbances may be

    conducted by supply, control and measuring cables that

    enter the shielded enclosure. An effective system of

    filters has been installed, and every wire that penetratesthe shield passes through such filter.

    Thyristor controlled drives and other non-linearloads generate higher harmonics of the current drawn

    from the local supply circuit. These result in a distortion

    of the supply voltage, and in consequence of the test

    voltage waveform. PDs measured in HV insulation

    depend on the voltage steepness, and a distorted test

    voltage waveform results in an exaggerated PD

    intensity. To reduce the harmonic distortion, a separate

    power transformer was installed to supply the HV test

    laboratory directly from the substation.

    Higher harmonics and transient disturbance

    currents are conducted through the factory groundingsystem. A large part of such currents circulates in the

    topsoil layers. To suppress such disturbance, the

    electromagnetic shield has been insulated from the

    factory grounding system and connected to a group of

    deep driven rods insulated from the topsoil. A specialized supplier has delivered a complete setof PD-free regulated transformer and reactors, as well as

    a modern computer-assisted recording instrumentation.

    These are pre-requisites to achieve the sought, very low-

    level background disturbances.

    References

    1. G., Karady, N., Hylten-Cavallius, Electromagnetic

    Shielding of HV Laboratory, (IEEE Trans. Vol.

    PAS-90, No. 3, May/June 1971, p. 1400).

    2. H., Wesolowski, A., Rynkowski, New HV

    Laboratory of Bydgoszcz Cable Plant, (V

    Conference Power and communication cablelines, Zakopane, March 1990, p. 265).

    3. G., Vaillancourt, R., Malewski, D., Train,

    "Comparison of Three Techniques of PartialDischarge Measurements in Power Transformers",

    (IEEE Transactions, Vol. PAS-104, No. 4, 1985,

    pp. 900-909).4. F., Rizk, Y., Gervais, H., Lhrmann, Performance

    of Electromagnetic Shields in HV Laboratory,

    (IEEE Trans. Vol. PAS-94, No. 6, 1975).

    5. B., Don Russel, W.C., Kothenheimer, R.,

    Malewski, Substation Electromagnetic

    Interference. Part 2: Susceptibility Testing and EMI

    Simulation in High Voltage Laboratories,(IEEETransactions, Vol. Vol.PAS-103, No. 7, p. 1871-

    1878)

    6. J., Miedziski, Electromagnetic Screeing Theory

    and Practice, (The British Electrical and Allied

    Industries Research Association, Report #M/T135,1959, Leatherhead, UK).

    7. Shielded Enclosures, (catalogue of Universal

    Shielding Corporation, US, 1996).

    8. International Electrotechnical Commission, (Publ.

    1000-4, -3; Publ, 461/462D).9. American National Standards Association, (Std.

    C63.4).

    10. Department of Defense, US (Military StandardMIL-258,).

    11. Polish Standard Committee, (National Standard

    PN-E-90410: 1994)12. AC Voltage Test System Model RSZ, (Haefely

    catalogue #E152.50, Basel, 1994).

    13. M., Florkowski, Distortion of Partial Discharge

    Images caused by High Voltage Harmonics, (10th

    International Symposium on HV Engineering,

    Montreal, 25-29 August, 1997, tom 4, p. 95.)14. R., Redl, P., Tenti, Daan J., van Wyk, Power

    Electronics Polluting Effects, (IEEE Spectrum,

    May 1997, p. 33).