1 GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA - 390 007 TENDER SPECIFICATION FOR Supply, Erection, Testing and Commissioning of various equipments & materials for new 220 / 66 KV system excluding all civil works at existing 400 KV Asoj Sub-station. PART - III PRICE BID TENDER NO: GETCO/CE(P)/EE(R&M)/DRM1/Tender EPC/2012/Asoj

Upload: others

Post on 19-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

1

GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED

SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA - 390 007

TENDER SPECIFICATION FOR

Supply, Erection, Testing and Commissioning of various equipments & materials for new 220 /

66 KV system excluding all civil works at existing 400 KV Asoj Sub-station.

PART - III PRICE BID

TENDER NO:

GETCO/CE(P)/EE(R&M)/DRM1/Tender EPC/2012/Asoj

Page 2: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

2

TENDER SPECIFICATION NO. : GETCO/CE(P)/EE(R&M)/DRM1/Tender EPC/2012/Asoj

Sub: Supply, Erection, Testing and Commissioning of various equipments & materials for new 220 / 66 KV system excluding all civil works at existing 400 KV Asoj Sub-station.

In connection with above subject, I / we confirm the following:

(A) I / We, the undersigned, have read and examined the Tender Specification No.

GETCO/CE(P)/EE(R&M)/DRM1/Tender EPC/2012/Asoj, Supply, Erection, Testing and

commissioning of various equipments & materials for new 220 / 66 KV system excluding

all civil works at existing 400 KV Asoj Sub-station including tender specification Part - I

special condition of contract in detail.

(B) Price components in the bid are subject to FIRM PRICE BASIS in line with Tender

Specification and stand valid till completion of the contract, if awarded.

(C) I/We declare that our bid is strictly in line with Tender Specifications and there is no

deviation. Further, I / we also agree that additional conditions / deviations, if any found in

bid, the offer shall be out rightly rejected without assigning any reason thereof.

Name of Agency: ____________________________ Signature : ____________________________

Name : ____________________________

Designation : ____________________________

Bidder's Seal :

Date : __________

Page 3: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

3

SUMMARY

Name of work : Supply, Erection, Testing and Commissioning of various equipments & materials for new 220 / 66 KV system excluding all civil works at existing 400 KV Asoj Sub-station.

Sr. No. Description

Estimated Cost in Rs.

Supply Part Erection Part Total

1 Electrical Erection Part

2 Protection part

3 SCADA part

4 Total (1 + 2 + 3)

(Figure in words : ____________________________________________)

Name of Agency: ____________________________ Signature : ____________________________

Name : ____________________________

Designation : ____________________________

Bidder's Seal :

Date : __________

Page 4: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

4

Tender No. : GETCO/CE(P)/EE(R&M)/DRM1/Tender EPC/2012/AsojName of Work: Supply, Erection, Testing and Commissioning of various equipments & materialsfor new 220 / 66 KV system excluding all civil works at existing 400 KV Asoj Sub-stationSCHEDULE B(1) Supply of Materials & Equipments for 400kV Asoj S/S - (220/66kv System) All Rates in Rs.

Sr.No. Particulars of Item Unit Suppl

y Qty.

UnitRate ExWorks

Freight Insu.UnitFORPrice

ED@

__%Rate

GST@

__%Rate

VAT@__%Rate

UnitEndcost

TotalFORcost

TotalEndcost

A Supply and Erection of 220kV Equipments as per respectivetechnical specifications and relevant special conditions .

1 Surge Arrester 198kV, 10kA, Cl-3 with str and clamp connectorsas per Technical spec No. 6

2 BPI 8kN with str and clamp connectors as per Technical spec No. 483 HBPI 8kN with str and clamp connectors as per Technical spec No. 6

4HDB Isolator without ES 1600A, 40kA 3s ( As indicated in SCC ofrespective tender) with str and clamp connectors as perTechnical spec

Set. 2

5Tandem DB Isolator 1600A, 40kA 3s ( As indicated in SCC ofrespective tender) with str and clamp connectors as perTechnical spec

Set. 6

6CT conventional 1200-600-300/1, 4C- 40kA 3s( As indicated inSCC of respective tender) with str and clamp connectors as perTechnical spec

No. 6

7 CB 2000A 40kA 3s ( As indicated in SCC of respective tender)with str and clamp connectors as per Technical spec Set. 2

B

Supply and Erection of 220kV Switchyard materials as perrespective technical specifications and relevant specialconditions suitable for Two Main & One Transfer Busscheme with Quad ACSR Moose conductor and relevantFlyover Bus with Twin ACSR Moose conductor.

1 Gantry structures GI as per BOM, Steel & A/B part MT 32.92 Gantry structures GI as per BOM, Bolt nut part MT 1.5

3

Stringing of bus with Quad Moose ACSR conductor for all thethree phases with required insulators, hardwares & accessories,spacers provided at every 3.0 mtr. interval etc. complete as perrelevant standards and approved drawings with Jumpers forcontinuous Bus Arrangement (It includes cost ofconductor,insulators, hardwares & accessories, spacers etc.allitems required for satisfactory functioning. Any variation inquantities shall be absorbed by contractor).

Page 5: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

5

a Main Bus with 36Mtr span including bus jumpers No. ofSpan 4

4

Stringing of bus with Twin Moose ACSR conductor for all thethree phases with required insulators, hardwares & accessories,spacers provided at every 3.0 mtr. interval etc. complete as perrelevant standards and approved drawings with Jumpers forcontinuous Bus Arrangement (It includes cost ofconductor,insulators, hardwares & accessories, spacers etc.allitems required for satisfactory functioning. Any variation inquantities shall be absorbed by contractor).

a Transfrer Bus with 36Mtr span including bus jumpers No. ofSpan 2

5

Stringing of Earth Wire with 7/3.15 GS wire with requiredhardwares & accessories etc. complete as per standards andapproved drawings for span of 72.7 meters.(It includes cost ofEarthwire,hardwares & accessories, etc. all items required forsatisfactory functioning. Any variation in quantities shall beabsorbed by contractor).

Span 2

6

Droppers (including required suspension string with hardware &accessories if any) & Jumpers (including Equipment toEquipment) with Twin Moose ACSR conductor as per standardsand approved drawings with provision of required spacers(Suitable for 350mm spacing) at every 3.0 mtr. interval .(Itincludes cost of conductor,insulators, hardwares & accessories,Fire Wedge connectors, spacers etc.all items required forsatisfactory functioning. Any variation in quantities shall beabsorbed by contractor)

a 220/66KV Transformer Bay No. ofbay 2

CSupply and Erection of 66kV Equipments as per respectivetechnical specifications and relevant special conditionssuitable.

1 Power Transformer 66/11kV 5MVA with oil andaccessories,connector suitable for Single Moose ACSR No. 1

2 Surge Arrester 60kV, 10KA, Class 3 with structure and clampconnectors suitable for Single Moose ACSR No. 27

3 PT 66kV/v3-/110V/v3-2C with structure and clamp connectorssuitable for Single Moose ACSR No. 6

4 BPI 4kN with structure and clamp connectors suitable for SingleMoose ACSR No. 56

5 BPI 4kN with structure and clamp connectors suitable for TwinZebra ACSR No. 22

Page 6: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

6

6 HBPI 4kN with structure and clamp connectors suitable for TwinZebra No. 6

7 HDB Isolator with one ES 630A 25 kA 3s with structure andclamp connectors suitable for Single Moose ACSR Set. 6

8 HDB Isolator without ES 630A 25 kA 3s with structure andclamp connectors suitable for Single Moose ACSR Set. 15

9HDB Isolator without ES 630A 25 kA 3s with structure andclamp connectors suitable for Single Moose ACSR (3nos./set) &Twin Zebra ACSR (3nos./set)

Set. 2

10 HDB Isolator without ES 1250A 25 kA 3s with structure andclamp connectors suitable for Twin Zebra ACSR Set. 6

11 CT 600-300/1 3C, 31.5kA 3S with structure and clampconnectors suitable for Single Moose ACSR No. 18

12 CT 1200-600/1 3C 31.5kA 3S with structure and clampconnectors suitable for Twin Zebra ACSR No. 9

13 CT 100-50/1 3C 31.5kA 3S with structure and clamp connectorssuitable for Single Moose ACSR No. 3

14CB 1600A 25 kA 3S ( As indicated in SCC of respective tender)with structure and clamp connectors suitable for Single MooseACSR

Set. 7

15CB 1600A 25 kA 3S ( As indicated in SCC of respective tender)with structure and clamp connectors suitable for Twin ZebraACSR

Set. 3

D

Supply and Erection of 66kV Switch Yard Material as perrespective technical specifications and relevant specialconditions suitable for Two Main Bus with Twin ACSR Zebraconductor scheme & relevant Flyover Bus with Twin ACSRZebra conductor.

1 Gantry structures GI as per BOM , Steel & A/B part MT 49.982 Gantry structures GI as per BOM , Bolt nut part MT 2.73

3

Stringing of bus for all the three phases with Twin Zebra ACSRconductor, insulators hardwares, spacers(suitable for 350mmspacing) at interval of 4.0 mtr complete as per relevantstandards and approved drawings.(The scope includes the costof conductor, insulators, hardwares, accessories, spacers etc.allitems required for satisfactory operation. Any variation inquantities shall be absorbed by erection contractor).

a Main Bus with 36.00 Mtr. Span including bus jumpers Span 2b Main Bus with 30.900 Mtr. Span including bus jumpers Span 4

c Line flyover bus with 23.8 Mtr. Span No. ofbay 8

d 66/11KV Trf. flyover bus with 23.8 Mtr. Span No. ofbay 1

Page 7: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

7

e Transformer flyover bus with 32.2 Mtr. Span No. ofbay 2

f Transformer flyover bus with 18.1 Mtr. Span No. ofbay 2

4

Stringing of Earth Wire with 7/3.15 GS wire with requiredhardwares & accessories etc. complete as per standards andapproved drawings for the shown span. (It includes cost ofEarthwire,hardwares & accessories etc. all items for satisfactoryfunctioning. Any variation in quantities should be absorbed byerection contractor)

a Main Bus with 30.900 Mtr. Span Span 2b Other Requiements with

9.00 Mtr. Span Span 312.00 Mtr. Span Span 114.00 Mtr. Span Span 215.00 Mtr. Span Span 118.60 Mtr. Span Span 119.80 Mtr. Span Span 123.20 Mtr. Span Span 125.70 Mtr. Span Span 1

c Line flyover bus with 23.8 Mtr. Span No. ofbay 5

d Transformer flyover bus with 32.2 Mtr. Span No. ofbay 4

e Transformer flyover bus with 18.1 Mtr. Span No. ofbay 4

5

Droppers (including required suspension string with hardware &accessories if any) & Jumpers with Single Moose ACSRconductor as per standards and approved drawings. (It includescost of conductor,insulators, Fire wedge connectors,hardwares& accessories etc. all items required for satisfactory functioning.Any variation in quantities shall be absorbed by erectioncontractor).

a 220/66KV Transformer Bay - LA No. ofbay 2

b 66KV PT Bay No. ofbay 2

c 66KV Line Bay No. ofbay 6

d 66/11KV, 5MVA Transformer Bay - LA No. ofbay 1

Page 8: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

8

6

Droppers and Jumpering (equipment to equipment) with TwinZebra ACSR conductor as per standards and approveddrawings with provision of spacers suitable for 350mm spacingat 4.0 mtr interval. (The scope includes the cost ofconductor,accessories ,spacers, fire wedge connectors etc.allitems required for satisfactory operation.)

a 220/66KV Transformer Bay (66KV side) No. ofbay 2

b 66KV Bus Coupler Bay No. ofbay 1

FSupply and Erection of General purpose equipments andmaterials as per respective technical specifications andrelevant special conditions.

1

Suitable arrangement of 11KV connection from 5MVA 66/11kVtransformer to distribution tr (11/0.415kV) with required 22kVCT, its junction box, support structure insulated conductor andDP structure with DO fuse, 22kV BPIs arrangement forproteciton of dist transformer and mounting arrangement of Distbox suitable to dist transformer.

Package LS

5 Distribution Transformer 11kV/415V,500 kVA with suitable Dist.Box and its fixing -mounting arragement. Set 1

6 Providing major spares as per Ann A attached herewith Set 1

10 Providing of Insulating Mat as per IS15652:2006(Size2000x1000x2mm) in control room No. 15

G

Supply and installation of materials for Illumination systemin all respect as per respective specifications and specialconditions ( Sucessful bidder has to submit the completedesign and BOQ for approval)

1

Providing and fixing of flood light luminaries as per design for220kV switch yard area with Philips/CGL/Bajaj/GE/Oshrammake HPSV 150/250/400W lamp with energy efficient typechoke (HF) with control gear box & ancillaries and suitable formounting on structure at appropriate height ( as per design) asper specifications TS illuminations cl. no 2.10.4.8 withnecessary GI fabrication & GI bolt nuts to fix control gear box atthe structure with complete internal and external wiring to J. box,Dist panel/section feeder pillar etc with supply of required 3 c x2.5 mm2 copper armoured cable (as per spec ) .The scopeincludes supply and erection of all the materials required forsatisfactory functioning of above work.

Package LS

Page 9: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

9

2

Providing and fixing of flood light luminaries as per design for66kV switch yard area with Philips/CGL/Bajaj/GE/Oshrammake HPSV 150/250W lamp with energy efficient type choke(HF) with control gear box & ancillaries and suitable formounting on structure at appropriate height ( as per design) asper specifications TS illuminations cl. no 2.10.4.8 withnecessary GI fabrication & GI bolt nuts to fix control gear box atthe structure with complete internal and external wiring to J. box,Dist panel/section feeder pillar etc with supply of required 3 c x2.5 mm2 copper armoured cable (as per spec ) .The scopeincludes supply and erection of all the materials required forsatisfactory functioning of above work.

Package LS

Providing and fixing of street light luminaries for reamaing area(like road, peripheral area etc.) of switch yard complete as perdesign with Philips/CGL/Bajaj/GE/Oshram make and energyefficient type 70 W (or suitable wattage )lamp with control gearbox & ancillaries suitable for mounting on 7.0 mtr swaged polesas per spec.TS illuminations cl. no 2.10.4.8 (EEO2) atappropriate height with necessary GI fabrication & GI bolt nuts tofix control gear box with complete internal and external wiringto J. box ,dist panel/section feeder pillar, fixing terminal etc withsupply of required 3 c x 2.5 mm2 copper armoured cable (as perspec). This also includes the supply and erection of 7.0 mtrswaged pole and foundation work as per spec. and panting withtwo coats of primer and two priming of zinc chromate as well asearthing with main mesh. The scope includes supply anderection of all the materials required for satisfactory functioningof above work.

Package LS

3

Supply and Erection of main lighting Panel ACP-2 as perSpecifications Set comprises minimum 4 nos.of such panels qtymay be more if required as per design.Scope also includes theproviding and erection of 25x6 GI strip for earthing with mainmesh

Set 1

4

Supply and Erection of main lighting Panel ACP-4 as perSpecifications Set comprises minimum 2 nos.of such panels qtymay be more if required as per design.Scope also includes theproviding and erection of 25x6 GI strip for earthing with mainmesh

Set 1

5

Supply and Erection of main Yard light Dist. Board as perdesigned capacity ratings.Scope also includes the providing anderection of Cable(Size as per design Requirement) 50x6 GI stripfor earthing with main mesh

Nos 1

Page 10: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

10

6

Providing earthing to all tubularpole, main yard light DB, sectionDistribution panels/boxes, Junction boxes etc. as per standardswith coil type earthing using 16SWG copper wire in seperatelyprepared earth pit of 1.5Mtr. Depth by using salt/coke(Charcoal)16KGs each & remainng filling with BC Soil and requiredclamping with earth wire.

Package LS

7Providing of concreting in 1:2:4 mix including muffing for erectionof pole & Dist boxes panels including excavation of HR/SR asper approved drawing.

Package LS

8Providing & fixing of ' B ' Class ISI marked GI pipe of 25 mminner diameter for cable looping, road crossing with necessaryelbow / band to J. Box etc.

Package LS

9

Providing and fixing of GI clamp (25mm wide GI strip with 6 mmGI nut bolts) on structure at approx. 1/2 Mtr. Interval forclamping of cable . Clamp should be fix in such a way thatcable can be easily mount inside it & sustain standing onstructure. This also includes required other materials,accessories required for complete functioning of Illuminationsystem of whole project (switch yard and all buildings,structures) those are not covered in this schedule forIllumination. Please refer the drawing "General Schematic forIllumination" in the TS Illumination.

Package LS

Note: The qunatities of the ACP's mentioned in the schedule of requirementare based on std. requirement, which shall be finalised during detailengineering. The bidder has to assess the qty. of ACP's at the time ofquoting the bid. The qty of ACP's finalised during detail engineering isbinding to the bidder & no any extra payment shall be made. In all the casethe decision of GETCO will be final.

H

Supply and installation of materials for Earthing system inall respect as per respective specifications and specialconditions ( Sucessful bidder has to submit the completedesign and BOQ for approval)

1

Supply and Installation of earthing strips/round bars as shownbelow including digging of 600 mm depth and 450 mm widetrench fixing on structure as per std equipment earthingphylosophy incuding fixing arrangement with two boltarrangement, jointing, welding etc. complete.a) 75 x 10 mm GI strip. RMt. 2688b) 50 x 6 mm GI strip. RMt. 7124c) 40 mm dia steel rod RMt. 3571d) 40mm dia 3mtr long steel rod Nos. 83e) 7/3.15 Earth wire for earthing of Towers with peak RMt. 552

2 Providing and installing Check pit as per drawing and instructionof Engineer In charge with provision of earth chamber. Nos. 4

Page 11: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

11

3

Installation of treated pipe electrode providing 100 mm innerdiameter CI pipe of 13 mm thickness and 3000 mm length asper GETCO drg No P011. Work includes fabrication and fixing ofGI strips for earthing connection

Nos. 37

4 Providing BB masonary inspection chamber (man hole) incl.lighttype CI cover as per GETCO drawing no P011 Nos. 37

Note: Extra earth should be removed away from the site s/s premises orrefilling earthing pits if required. All required materials for this job such asCI pipe, CI cover with frame, salt, cement, sand, charcoal/bentonite, gravel,bricks etc. to be supplied by the contractor.

ISupply and Erection of Ladder Type Cable Trays andAccesories as per respective Technical Specifications andrelevant special conditions.Width of tray450mm Rmtr. 546350mm Rmtr. 546Length: Standard length of tray is 2500mm, Height is 75mm, Thickness is 2mm(min.)Note: Cross, Tees, Elbows, Coupler plates, Bends, Reducer etc. required forcomplete installation of Ladder Type Tray are included in the Scope.NOTE:Supply & Erection of 220/66KV Transformer is not in the scope of awardee, butawardee will erect the itmes other than the scope of transformer manufacturerand witness during the erection and testing of the same and provide all the resultin as built drawings/documents.Total For S/S Equipments & Materials

PROTECTION BOQ (for SCADA & CRP Package) of 400KV ASOJ S/S for 220/ 66 KV System All Rates in Rs

Sr.No. Particulars of Item Unit Suppl

y Qty.

UnitRate ExWorks

Freight Insu.UnitFORPrice

ED@

__%Rate

GST@

__%Rate

VAT@__%Rate

UnitEndcost

TotalFORcost

TotalEndcost

A

Supply, Erection, Testing and Commissioning of Protectionequipments and materials as per respective technicalspecifications and relevant special conditions and suitablefor Two Main and Transfer Bus system on 220kV side.

1 Control & Protection panels for 220KV Bays ( Control Voltage -110V DC ) as per tech specifications with following break up1) Control & Protection panel for line Set 02) Control & Protection panel for Transformer without Differential Set 03) Control & Protection panel for Transformer with Differential(220/66KV) Set 2

4) Control & Protection panel for TBC Set 0

Page 12: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

12

5) Control & Protection panel for BC Set 0Numerical Bus Bar Protection Bay Units - Areva make Micom P743 (to be erected in Control & Protection Panel) Nos. 2

2 GPS based Time Syncronising Unit (IEC 61850 compatible) Set 0

B

Supply, Erection, Testing and Commissioning of Protectionequipments and materials as per respective technicalspecifications and relevant special conditions and suitablefor Two Main Bus system on 66kV side

1 Control & Protection Panel for 66kV bays ( Control Voltage -110V DC ) as per tech specifications with following break up.1) Control & Protection Panel for two lines Set 32) Control & Protection Panel for Two Transformer (WithoutDiffererential Relay) Set 1

3) Control & Protection Panel for Bus Coupler & StationTransformer (66/11KV Transformer) Set 1

C

Supply and Erection of General purpose equipments andmaterials as per respective technical specifications andrelevant special conditions and suitable for Two Main andTransfer Bus scheme on 220kV side, and Two Main Bussystem on 66kV side.

1 DCDB-110 V with 20 Feeder No. 42 LTPB - (SCADA compatible) No. 2

DSupply and installation of materials/item for Power Cableand control Cable wiring including preparation of wiringschedule.

1

Supply and Laying of 1.1 kV PVC armoured copper/Aluminumcontrol/LT power cable in trench including binding/clamping ofcable with PVC locable wire tie as per requirement includingsupply and fixing of identification tags on both ends and atdistance of every 100mtr.(Note :- Aluminium cables of size 185 mm2 & above shall beXLPE type)1) 2c x 2.5 mm2, armoured copper control cable Mtr. 18002) 2c x 4 mm2 , armoured copper control cable Mtr. 2003) 4cx2.5 mm2, armoured copper control cable Mtr. 15004) 4c x 4 mm2 , armoured copper control cable Mtr. 61005) 7c x 2.5 mm2, armoured copper control cable Mtr. 5506) 12c x 2.5 mm2, armoured copper control cable Mtr. 20007) 12c x 4 mm2, armoured copper control cable Mtr. 28008) 19c x 2.5 mm2 , armoured copper control cable Mtr. 42009) 27c x 2.5 mm2 , armoured copper control cable Mtr. 450

Page 13: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

13

10A) 1 x 50 mm2 , armoured copper cable Mtr. 445010B) 4C x 10 mm2 , armoured copper control cable Mtr. 011) 4 x 10 mm2 , Al. armoured LT cable Mtr. 10012) 3.5 x 25 mm2 , Al. armoured LT cable Mtr. 160013) 3.5 x 50 mm2 , Al. armoured LT cable Mtr. 50014) 3.5 x 120 mm2 , Al. armoured LT cable Mtr. 015) 1C x 150 mm2 , Al. armoured LT cable Mtr. 405016) 1C x 240 mm2 , Al. armoured LT cable Mtr. 017) 1C x 300 mm2 , Al. armoured LT cable Mtr. 018) 3.5 x 300 mm2 , Al. armoured LT cable Mtr. 0

2

Termination of the control cable at panel / MK box/equipmentincluding PVC binding dressing/shaping drilling of holes inpanels for glands nuts for following size. The work also includesLooping in panel and MK box with using crimping type of lugs ofsuitable size with ferruling with proper size of copper cable wire.The loops should be bunched with using button tape and propershaping etc.1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size No. 3502) cables above 7 core No. 400

3

Laying of 1.1kv PVC/XLPE armored Al. LT power cable inground by digging trench of suitable width and 450 mm depthwith providing and fixing of brick and sand layer covering thecable in any type of soil and Laying of 1.1kv PVC armoredcopper control cable in heavy duty PVC pipe of suitable sizeburied in ground by digging trench of suitable width and 450mm depth in any type of soil including supply,fixing of Pipe &identification tags at distance of every 100 Mtrs for following size1) Control Cables upto 7 core Mtr. 4002) Control Cables above 7 core and all LT cables Mtr. 1300

4

Providing and fixing of 50mm dia 'B' class GI pipes withnecessary size of band and couplings for control cableprotection of CT, PT/CVT etc. equipments including fixing withstructures as per instruction of Engineer-in-charge.1) 220 kV Switch Yard Mtr. 1502) 66 kV switch yard Mtr. 150

4a

Providing and fixing of 100mm dia 'B' class GI pipes withnecessary size of band and couplings for control cableprotection of CB, Isolator etc.equipments including fixing withstructures as per instruction of Engineer-in-charge.1) 220 kV Switch Yard Mtr. 1252) 66 kV switch yard Mtr. 125

Page 14: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

14

5 Providing and fixing bay MK as per tech spec No. 2

6 Providing and fixing Yard LT ACDB as per tech spec -with 20OG feeders No. 1

7 Providing and fixing Yard LT ACDB as per tech spec -with 12OG feeders No. 1

8

Providing and fixing of all weather proof, cold rolled sheet steeljunction box for CVT & PT, CT terminations with 30 Nos. ofdisconnecting type, 'Elmex' make CATDM 4 or equivalent typeconnectors and required no of fuses, links etc.as per instructionof Engineer-in-charge.CT JB Nos. 10PT JB Nos. 2CVT JB Nos. 0Total For Protection Materials

SCADA BOQ (for SCADA & CRP Package) of 400 KV Asoj Sub Station for 220/ 66 KV System All Rates in Rs.

Sr.No. Particulars of Item Unit Suppl

y Qty

UnitRate ExWorks

Freight Insu.UnitFORPrice

ED@

__%Rate

GST@

__%Rate

VAT@__%Rate

UnitEndcost

TotalFORcost

TotalEndcost

A

Supply, Erection, Testing and Commissioning of SCADAequipments and materials as per respective technicalspecifications and relevant special conditions and suitablefor Two Main and Transfer Bus system on 220kV side andTwo Main Bus on 66KV side

1 Bay Control Unit / RTU for Substation Auxiliaries # Nos 12 Bay Control Unit for PLCC ** Nos 03 HMI Server computer with required softwares $ Nos 04 DR workstation PC $ No. 05 Gateway for remote control with software $ No 06 Gateway for RTU Data with software $ No 07 SCADA software (For Local end only) $ No 0

8 Ethernet Fiber Switches* Nos 3

9 Line Interface unit - 2 Cable entry, 12 ports Nos 5

10 Line Interface unit - 8 Cable entry, 32 ports(To be provided in220 kV Bus Bar Panel in Control Room. Nos 1

11 OPGW Terminal equipments (FOTE) with required hardwareand software for remote connectivity Set 0

12 Armoured Fibre Optic approach cable with HDPE duct forconnecting OPGW to FOTE MTR. 0

13 Laser Jet colour Printer Nos 1

Page 15: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

15

14 Laser Jet Printer Nos 115 3KVA UPS with battery (12V, 26AH X 30 Nos, SMF Battery)$ Nos 016 3KVA UPS without battery $ Nos 017 Modem for RTU Data Nos 018 Armoured Fibre Optic Cable with HDPE duct MTR. 125019 Yard Kiosk for 220KV Switchyard20 Internal Dimensions - 5000 (L) X 3500 (W) X 3300 (H) mm Nos 221 Yard Kiosk for 66KV Switchyard22 Internal Dimensions - 6000 (L) X 3500 (W) X 3300 (H) mm Nos 123 Panel for mounting SCADA equipments Nos 024 Panel for mounting Station Auxiliaries BCU/RTU Nos 0

25Integration of bays (under scope of this tender) with ExistingSCADA System.[ Make & Type of SCADA shall be given duringdetailed engineering.]

Job 0

Spares for SCADA and Protection1 Bay Control Unit Nos 12 Line Interface Unit - 8 Cable entry, 32 ports Nos 13 Ethernet fiber switch Nos 14 Busbar Protection Peripheral Unit Nos 1

Total For SCADA MaterialsNote:1) Any material/equipment accessories which are not listed in BOQ or in scope ofsupply but

required to complete the job shall be included and shown in technical bid.2)*Ethernet switches shall have as many spare ports as utilized ports.3) ** PLCC BCU shall have sufficient I/Os as per given list.4) # BCU for station Auxiliary shall have sufficient I/Os as per listor otherwise suitable RTU shall be provided.

5) $ SCADA system to be provided by PGCIL. 400 kv Extension will be used for this Project (220/66Extension) also.

6) $ EFS in Control Room shall be a part of PGCIL SCADASystem.

Page 16: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

16

Tender No. : GETCO/CE(P)/EE(R&M)/DRM1/Tender EPC/2012/AsojName of Work: Supply, Erection, Testing and Commissioning of various equipments & materials for new 220 / 66 KV systemexcluding all civil works at existing 400 KV Asoj Sub-stationSCHEDULE - B(2) - Erection of Materials & Equipments for 400kV Asoj S/S (220/66kv System)

All Rates in Rs.

Sr.No. Particulars of Item Unit Erection

Qty.

Unit Ratefor

Erection

SreviceTax@

____%

Unit Rateof Erectionwith S. Tax

TotalAmount

of Erectionwith S. Tax

A Supply and Erection of 220kV Equipments as per respective technicalspecifications and relevant special conditions .

1 Surge Arrester 198kV, 10kA, Cl-3 with str and clamp connectors as per Technical spec No. 62 BPI 8kN with str and clamp connectors as per Technical spec No. 483 HBPI 8kN with str and clamp connectors as per Technical spec No. 6

4 HDB Isolator without ES 1600A, 40kA 3s / 63 kA 1s ( As indicated in SCC of respectivetender) with str and clamp connectors as per Technical spec Set. 2

5 Tandem DB Isolator 1600A, 40kA 3s / 63 kA 1s ( As indicated in SCC of respectivetender) with str and clamp connectors as per Technical spec Set. 6

6 CT conventional 1200-600-300/1, 4C- 40kA 3s / 63 kA 1s ( As indicated in SCC ofrespective tender) with str and clamp connectors as per Technical spec No. 6

7 CB 2000A 40kA 3s / 63 kA 1s ( As indicated in SCC of respective tender) with str andclamp connectors as per Technical spec Set. 2

B

Supply and Erection of 220kV Switchyard materials as per respective technicalspecifications and relevant special conditions suitable for Two Main & OneTransfer Bus scheme with Quad ACSR Moose conductor and relevant FlyoverBus with Twin ACSR Moose conductor.

1 Gantry structures GI as per BOM, Steel & A/B part MT 34.42 Gantry structures GI as per BOM, Bolt nut part MT

3

Stringing of bus with Quad Moose ACSR conductor for all the three phases withrequired insulators, hardwares & accessories, spacers provided at every 3.0 mtr.interval etc. complete as per relevant standards and approved drawings with Jumpersfor continuous Bus Arrangement (It includes cost of conductor,insulators, hardwares &accessories, spacers etc.all items required for satisfactory functioning. Any variation inquantities shall be absorbed by contractor).

a Main Bus with 36Mtr span including bus jumpers No. of span 4

Page 17: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

17

4

Stringing of bus with Twin Moose ACSR conductor for all the three phases withrequired insulators, hardwares & accessories, spacers provided at every 3.0 mtr.interval etc. complete as per relevant standards and approved drawings with Jumpersfor continuous Bus Arrangement (It includes cost of conductor,insulators, hardwares &accessories, spacers etc.all items required for satisfactory functioning. Any variation inquantities shall be absorbed by contractor).

a Transfrer Bus with 36Mtr span including bus jumpers No. of Span 2

5

Stringing of Earth Wire with 7/3.15 GS wire with required hardwares & accessories etc.complete as per standards and approved drawings for span of 72.7 meters.(It includescost of Earthwire,hardwares & accessories, etc. all items required for satisfactoryfunctioning. Any variation in quantities shall be absorbed by contractor).

Span 2

6

Droppers (including required suspension string with hardware & accessories if any) &Jumpers (including Equipment to Equipment) with Twin Moose ACSR conductor asper standards and approved drawings with provision of required spacers( Suitable for350mm spacing) at every 3.0 mtr. interval .(It includes cost of conductor,insulators,hardwares & accessories, Fire Wedge connectors, spacers etc.all items required forsatisfactory functioning. Any variation in quantities shall be absorbed by contractor)

a 220/66KV Transformer Bay No. of bay 2

C Supply and Erection of 66kV Equipments as per respective technicalspecifications and relevant special conditions suitable.

1 Power Transformer 66/11kV 5MVA with oil and accessories,connector suitable forSingle Moose ACSR No. 1

2 Surge Arrester 60kV, 10KA, Class 3 with structure and clamp connectors suitable forSingle Moose ACSR No. 27

3 PT 66kV/v3-/110V/v3-2C with structure and clamp connectors suitable for Single MooseACSR No. 6

4 BPI 4kN with structure and clamp connectors suitable for Single Moose ACSR No. 565 BPI 4kN with structure and clamp connectors suitable for Twin Zebra ACSR No. 226 HBPI 4kN with structure and clamp connectors suitable for Twin Zebra No. 6

7 HDB Isolator with one ES 630A 31.5 kA 3s with structure and clamp connectorssuitable for Single Moose ACSR Set. 6

8 HDB Isolator without ES 630A 31.5 kA 3s with structure and clamp connectors suitablefor Single Moose ACSR Set. 15

9 HDB Isolator without ES 630A 31.5 kA 3s with structure and clamp connectors suitablefor Single Moose ACSR (3nos./set) & Twin Zebra ACSR (3nos./set) Set. 2

10 HDB Isolator without ES 1250A 31.5 kA 3s with structure and clamp connectorssuitable for Twin Zebra ACSR Set. 6

11 CT 600-300/1 3C, 31.5kA 3S with structure and clamp connectors suitable for SingleMoose ACSR No. 18

Page 18: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

18

12 CT 1200-600/1 3C 31.5kA 3S with structure and clamp connectors suitable for TwinZebra ACSR No. 9

13 CT 100-50/1 3C 31.5kA 3S with structure and clamp connectors suitable for SingleMoose ACSR No. 3

14 CB 1600A 31.5 kA 3S ( As indicated in SCC of respective tender) with structure andclamp connectors suitable for Single Moose ACSR Set. 7

15 CB 1600A 31.5 kA 3S ( As indicated in SCC of respective tender) with structure andclamp connectors suitable for Twin Zebra ACSR Set. 3

D

Supply and Erection of 66kV Switch Yard Material as per respective technicalspecifications and relevant special conditions suitable for Two Main Bus withTwin ACSR Zebra conductor scheme & relevant Flyover Bus with Twin ACSRZebra conductor.

1 Gantry structures GI as per BOM , Steel & A/B part MT 52.712 Gantry structures GI as per BOM , Bolt nut part MT

3

Stringing of bus for all the three phases with Twin Zebra ACSR conductor, insulatorshardwares, spacers(suitable for 350mm spacing) at interval of 4.0 mtr complete as perrelevant standards and approved drawings.(The scope includes the cost of conductor,insulators, hardwares, accessories, spacers etc.all items required for satisfactoryoperation. Any variation in quantities shall be absorbed by erection contractor).

a Main Bus with 36.00 Mtr. Span including bus jumpers Span 2b Main Bus with 30.900 Mtr. Span including bus jumpers Span 4c Line flyover bus with 23.8 Mtr. Span No. of bay 8d 66/11KV Trf. flyover bus with 23.8 Mtr. Span No. of bay 1e Transformer flyover bus with 32.2 Mtr. Span No. of bay 2f Transformer flyover bus with 18.1 Mtr. Span No. of bay 2

4

Stringing of Earth Wire with 7/3.15 GS wire with required hardwares & accessories etc.complete as per standards and approved drawings for the shown span. (It includes costof Earthwire,hardwares & accessories etc. all items for satisfactory functioning. Anyvariation in quantities should be absorbed by erection contractor)

a Main Bus with 30.900 Mtr. Span Span 2b Other Requiements with

9.00 Mtr. Span Span 312.00 Mtr. Span Span 114.00 Mtr. Span Span 215.00 Mtr. Span Span 118.60 Mtr. Span Span 119.80 Mtr. Span Span 123.20 Mtr. Span Span 125.70 Mtr. Span Span 1

c Line flyover bus with 23.8 Mtr. Span No. of bay 5d Transformer flyover bus with 32.2 Mtr. Span No. of bay 4

Page 19: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

19

e Transformer flyover bus with 18.1 Mtr. Span No. of bay 4

5

Droppers (including required suspension string with hardware & accessories if any) &Jumpers with Single Moose ACSR conductor as per standards and approveddrawings. (It includes cost of conductor,insulators, Fire wedge connectors,hardwares &accessories etc. all items required for satisfactory functioning. Any variation in quantitiesshall be absorbed by erection contractor).

a 220/66KV Transformer Bay - LA No. of bay 2b 66KV PT Bay No. of bay 2c 66KV Line Bay No. of bay 6d 66/11KV, 5MVA Transformer Bay - LA No. of bay 1

6

Droppers and Jumpering (equipment to equipment) with Twin Zebra ACSR conductoras per standards and approved drawings with provision of spacers suitable for 350mmspacing at 4.0 mtr interval. (The scope includes the cost of conductor,accessories,spacers, fire wedge connectors etc.all items required for satisfactory operation.)

a 220/66KV Transformer Bay (66KV side) No. of bay 2b 66KV Bus Coupler Bay No. of bay 1

F Supply and Erection of General purpose equipments and materials as perrespective technical specifications and relevant special conditions.

1

Suitable arrangement of 11KV connection from 5MVA 66/11kV transformer todistribution tr (11/0.415kV) with required 22kV CT, its junction box, support structureinsulated conductor and DP structure with DO fuse, 22kV BPIs arrangement forproteciton of dist transformer and mounting arrangement of Dist box suitable to disttransformer.

Package LS

5 Distribution Transformer 11kV/415V,500 kVA with suitable Dist. Box and its fixing -mounting arragement. Set 1

6 Providing major spares as per Ann A attached herewith Set 010 Providing of Insulating Mat as per IS 15652:2006(Size2000x1000x2mm) in control room No. 0

GSupply and installation of materials for Illumination system in all respect as perrespective specifications and special conditions ( Sucessful bidder has to submitthe complete design and BOQ for approval)

1

Providing and fixing of flood light luminaries as per design for 220kV switch yard areawith Philips/CGL/Bajaj/GE/Oshram make HPSV 150/250/400W lamp with energyefficient type choke (HF) with control gear box & ancillaries and suitable for mountingon structure at appropriate height ( as per design) as per specifications TS illuminationscl. no 2.10.4.8 with necessary GI fabrication & GI bolt nuts to fix control gear box at thestructure with complete internal and external wiring to J. box ,Dist panel/section feederpillar etc with supply of required 3 c x 2.5 mm2 copper armoured cable (as per spec ).The scope includes supply and erection of all materials required for satisfactoryfunctioning of above work.

Package LS

Page 20: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

20

2

Providing and fixing of flood light luminaries as per design for 66kV switch yard areawith Philips/CGL/Bajaj/GE/Oshram make HPSV 150/250W lamp with energy efficienttype choke (HF) with control gear box & ancillaries and suitable for mounting onstructure at appropriate height ( as per design) as per specifications TS illuminations cl.no 2.10.4.8 with necessary GI fabrication & GI bolt nuts to fix control gear box at thestructure with complete internal and external wiring to J. box ,Dist panel/section feederpillar etc with supply of required 3 c x 2.5 mm2 copper armoured cable (as per spec ).The scope includes supply &erection of materials required for satisfactory functioning ofabove work.

Package LS

Providing and fixing of street light luminaries for reamaing area (like road, peripheralarea etc.) of switch yard complete as per design with Philips/CGL/Bajaj/GE/Oshrammake and energy efficient type 70 W (or suitable wattage )lamp with control gear box &ancillaries suitable for mounting on 7.0 mtr swaged poles as per spec.TS illuminationscl. no 2.10.4.8 (EEO2) at appropriate height with necessary GI fabrication & GI boltnuts to fix control gear box with complete internal and external wiring to J. box ,distpanel/section feeder pillar, fixing terminal etc with supply of required 3 c x 2.5 mm2copper armoured cable (as per spec). This also includes the supply and erection of 7.0mtr swaged pole and foundation work as per spec. and panting with two coats of primerand two priming of zinc chromate as well as earthing with main mesh. The scopeincludes supply and erection of all the materials required for satisfactory functioning ofabove work.

Package LS

3Supply and Erection of main lighting Panel ACP-2 as per Specifications Set comprisesminimum 4 nos.of such panels qty may be more if required as per design.Scope alsoincludes the providing and erection of 25x6 GI strip for earthing with main mesh

Set 1

4Supply and Erection of main lighting Panel ACP-4 as per Specifications Set comprisesminimum 2 nos.of such panels qty may be more if required as per design.Scope alsoincludes the providing and erection of 25x6 GI strip for earthing with main mesh

Set 1

5Supply and Erection of main Yard light Dist. Board as per designed capacityratings.Scope also includes the providing and erection of Cable(Size as per designRequirement) 50x6 GI strip for earthing with main mesh

Nos 1

6

Providing earthing to all tubularpole, main yard light DB, section Distributionpanels/boxes, Junction boxes etc. as per standards with coil type earthing using16SWG copper wire in seperately prepared earth pit of 1.5Mtr. Depth by usingsalt/coke(Charcoal) 16KGs each & remainng filling with BC Soil and required clampingwith earth wire.

Package LS

7 Providing of concreting in 1:2:4 mix including muffing for erection of pole & Dist boxespanels including excavation of HR/SR as per approved drawing. Package LS

8 Providing & fixing of ' B ' Class ISI marked GI pipe of 25 mm inner diameter for cablelooping, road crossing with necessary elbow / band to J. Box etc. Package LS

Page 21: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

21

9

Providing and fixing of GI clamp (25mm wide GI strip with 6 mm GI nut bolts) onstructure at approx. 1/2 Mtr. Interval for clamping of cable . Clamp should be fix insuch a way that cable can be easily mount inside it & sustain standing on structure.This also includes required other materials ,accessories required for completefunctioning of Illumination system of whole project (switch yard and all buildings,structures) those are not covered in this schedule for Illumination. Please refer thedrawing "General Schematic for Illumination" in the TS Illumination.

Package LS

Note: The qunatities of the ACP's mentioned in the schedule of requirement are based on std.requirement, which shall be finalised during detail engineering. The bidder has to assess the qty. ofACP's at the time of quoting the bid. The qty of ACP's finalised during detail engineering is binding to thebidder & no any extra payment shall be made. In all the case the decision of GETCO will be final.

H Supply and installation of materials for Earthing system in all respect as per respective specificationsand special conditions ( Sucessful bidder has to submit the complete design and BOQ for approval)

1

Supply and Installation of earthing strips/round bars as shown below including diggingof 600 mm depth and 450 mm wide trench fixing on structure as per std equipmentearthing phylosophy incuding fixing arrangement with two bolt arrangement, jointing,welding etc. complete.a) 75 x 10 mm GI strip. RMt. 2688b) 50 x 6 mm GI strip. RMt. 7124c) 40 mm dia steel rod RMt. 3571d) 40mm dia 3mtr long steel rod Nos. 83e) 7/3.15 Earth wire for earthing of Towers with peak RMt. 552

2 Providing and installing Check pit as per drawing and instruction of Engineer In chargewith provision of earth chamber. Nos. 4

3Installation of treated pipe electrode providing 100 mm inner diameter CI pipe of 13 mmthickness and 3000 mm length as per GETCO drg No P011. Work includes fabricationand fixing of GI strips for earthing connection

Nos. 37

4 Providing BB masonary inspection chamber (man hole) incl.light type CI cover as perGETCO drawing no P011 Nos. 37

Note: Extra earth should be removed away from the site s/s premises or refilling earthing pits if required.All required materials for this job such as CI pipe, CI cover with frame, salt, cement, sand,charcoal/bentonite, gravel, bricks etc. to be supplied by the contractor.

I Supply and Erection of Ladder Type Cable Trays and Accesories as perrespective Technical Specifications and relevant special conditions.

Width of tray450mm Rmtr. 546350mm Rmtr. 546Length: Standard length of tray is 2500mm, Height is 75mm, Thickness is 2mm (min.)

Page 22: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

22

Note: Cross, Tees, Elbows, Coupler plates, Bends, Reducer etc. required for complete installation ofLadder Type Tray are included in the Scope.NOTE:Supply & Erection of 220/66KV Transformer is not in the scope of awardee, but awardee will erect the itmes otherthan the scope of transformer manufacturer and witness during the erection and testing of the same and provideall the result in as built drawings/documents.

Total For S/S Equipments & Materials ErectionPROTECTION BOQ (for SCADA & CRP Package) of 400KV ASOJ S/S for 220/ 66 KV System All Rates in Rs.

Sr.No. Particulars of Item Unit Erection

Qty.

Unit Ratefor

Erection

SreviceTax@

____%

Unit Rateof Erectionwith S. Tax

TotalAmount

of Erectionwith S. Tax

ASupply, Erection, Testing and Commissioning of Protection equipments andmaterials as per respective technical specifications and relevant specialconditions and suitable for Two Main and Transfer Bus system on 220kV side.

1 Control & Protection panels for 220KV Bays ( Control Voltage - 110V DC ) as per techspecifications with following break up1) Control & Protection panel for line Set 02) Control & Protection panel for Transformer without Differential Set 03) Control & Protection panel for Transformer with Differential (220/66KV) Set 24) Control & Protection panel for TBC Set 05) Control & Protection panel for BC Set 0Numerical Bus Bar Protection Bay Units - Areva make Micom P 743 (to be erected inControl & Protection Panel) Nos. 2

2 GPS based Time Syncronising Unit (IEC 61850 compatible) Set 0

BSupply, Erection, Testing and Commissioning of Protection equipments andmaterials as per respective technical specifications and relevant specialconditions and suitable for Two Main Bus system on 66kV side

1 Control & Protection Panel for 66kV bays ( Control Voltage - 110V DC ) as per techspecifications with following break up.1) Control & Protection Panel for two lines Set 32) Control & Protection Panel for Two Transformer (Without Differerential Relay) Set 13) Control & Protection Panel for Bus Coupler & Station Transformer (66/11KVTransformer) Set 1

CSupply and Erection of General purpose equipments and materials as perrespective technical specifications and relevant special conditions and suitablefor Two Main and Transfer Bus scheme on 220kV side, and Two Main Bus systemon 66kV side.

1 DCDB-110 V with 20 Feeder No. 42 LTPB - (SCADA compatible) No. 2

Page 23: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

23

D Supply and installation of materials/item for Power Cable and control Cable wiringincluding preparation of wiring schedule.

1

Supply and Laying of 1.1 kV PVC armoured copper/Aluminum control/LT power cable intrench including binding/clamping of cable with PVC locable wire tie as per requirementincluding supply and fixing of identification tags on both ends and at distance of every100mtr. (Note :- Aluminium cables of size 185 mm2 & above shall be XLPE type)

1) 2c x 2.5 mm2, armoured copper control cable Mtr. 18002) 2c x 4 mm2 , armoured copper control cable Mtr. 2003) 4cx2.5 mm2, armoured copper control cable Mtr. 15004) 4c x 4 mm2 , armoured copper control cable Mtr. 61005) 7c x 2.5 mm2, armoured copper control cable Mtr. 5506) 12c x 2.5 mm2, armoured copper control cable Mtr. 20007) 12c x 4 mm2, armoured copper control cable Mtr. 28008) 19c x 2.5 mm2 , armoured copper control cable Mtr. 42009) 27c x 2.5 mm2 , armoured copper control cable Mtr. 45010A) 1 x 50 mm2 , armoured copper cable Mtr. 445010B) 4C x 10 mm2 , armoured copper control cable Mtr. 011) 4 x 10 mm2 , Al. armoured LT cable Mtr. 10012) 3.5 x 25 mm2 , Al. armoured LT cable Mtr. 160013) 3.5 x 50 mm2 , Al. armoured LT cable Mtr. 50014) 3.5 x 120 mm2 , Al. armoured LT cable Mtr. 015) 1C x 150 mm2 , Al. armoured LT cable Mtr. 405016) 1C x 240 mm2 , Al. armoured LT cable Mtr. 017) 1C x 300 mm2 , Al. armoured LT cable Mtr. 018) 3.5 x 300 mm2 , Al. armoured LT cable Mtr. 0

2

Termination of the control cable at panel / MK box/equipment including PVC bindingdressing/shaping drilling of holes in panels for glands nuts for following size. The workalso includes Looping in panel and MK box with using crimping type of lugs of suitablesize with ferruling with proper size of copper cable wire. The loops should be bunchedwith using button tape and proper shaping etc.1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size No. 3502) cables above 7 core No. 400

3

Laying of 1.1kv PVC/XLPE armored Al. LT power cable in ground by digging trench ofsuitable width and 450 mm depth with providing and fixing of brick and sand layercovering the cable in any type of soil and Laying of 1.1kv PVC armored copper controlcable in heavy duty PVC pipe of suitable size buried in ground by digging trench ofsuitable width and 450 mm depth in any type of soil including supply and fixing of Pipeand identification tags at distance of every 100 Mtrs for following size

Page 24: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

24

1) Control Cables upto 7 core Mtr. 4002) Control Cables above 7 core and all LT cables Mtr. 1300

4

Providing and fixing of 50mm dia 'B' class GI pipes with necessary size of band andcouplings for control cable protection of CT, PT/CVT etc. equipments including fixingwith structures as per instruction of Engineer-in-charge.1) 220 kV Switch Yard Mtr. 1503) 66 kV switch yard Mtr. 150

4a

Providing and fixing of 100mm dia 'B' class GI pipes with necessary size of band andcouplings for control cable protection of CB, Isolator etc.equipments including fixingwith structures as per instruction of Engineer-in-charge.1) 220 kV Switch Yard Mtr. 1253) 66 kV switch yard Mtr. 125

5 Providing and fixing bay MK as per tech spec No. 26 Providing and fixing Yard LT ACDB as per tech spec -with 20 OG feeders No. 17 Providing and fixing Yard LT ACDB as per tech spec -with 12 OG feeders No. 1

8

Providing and fixing of all weather proof, cold rolled sheet steel junction box for CVT &PT, CT terminations with 30 Nos. of disconnecting type, 'Elmex' make CATDM 4 orequivalent type connectors and required no of fuses, links etc.as per instruction ofEngineer-in-charge.CT JB Nos. 10PT JB Nos. 2CVT JB Nos. 0Total For Protection Equipments & Materials Erection

SCADA BOQ (for SCADA & CRP Package) of 400 KV Asoj Sub Station for 220/ 66 KV System All Rates in Rs.

Sr.No. Particulars of Item Unit Erection

Qty

Unit Ratefor

Erection

SreviceTax@

____%

Unit Rateof Erectionwith S. Tax

TotalAmount

of Erectionwith S. Tax

A

Supply, Erection, Testing and Commissioning of SCADA equipments andmaterials as per respective technical specifications and relevant specialconditions and suitable for Two Main and Transfer Bus system on 220kV sideand Two Main Bus on 66KV side

1 Bay Control Unit / RTU for Substation Auxiliaries # Nos 12 Bay Control Unit for PLCC ** Nos 03 HMI Server computer with required softwares $ Nos 04 DR workstation PC $ No. 05 Gateway for remote control with software $ No 06 Gateway for RTU Data with software $ No 07 SCADA software (For Local end only) $ No 08 Ethernet Fiber Switches* Nos 39 Line Interface unit - 2 Cable entry, 12 ports Nos 5

Page 25: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

25

10 Line Interface unit - 8 Cable entry, 32 ports(To be provided in 220 kV Bus Bar Panel inControl Room. Nos 1

11 OPGW Terminal equipments (FOTE) with required hardware and software for remoteconnectivity Set 0

12 Armoured Fibre Optic approach cable with HDPE duct for connecting OPGW to FOTE MTR. 013 Laser Jet colour Printer Nos 114 Laser Jet Printer Nos 115 3KVA UPS with battery (12V, 26AH X 30 Nos, SMF Battery)$ Nos 016 3KVA UPS without battery $ Nos 017 Modem for RTU Data Nos 018 Armoured Fibre Optic Cable with HDPE duct MTR. 125019 Yard Kiosk for 220KV Switchyard20 Internal Dimensions - 5000 (L) X 3500 (W) X 3300 (H) mm Nos 221 Yard Kiosk for 66KV Switchyard22 Internal Dimensions - 6000 (L) X 3500 (W) X 3300 (H) mm Nos 123 Panel for mounting SCADA equipments Nos 024 Panel for mounting Station Auxiliaries BCU/RTU Nos 0

25 Integration of bays (under scope of this tender) with Existing SCADA System.[ Make &Type of SCADA shall be given during detailed engineering.] Job 1

Spares for SCADA and Protection1 Bay Control Unit Nos 02 Line Interface Unit - 8 Cable entry, 32 ports Nos 03 Ethernet fiber switch Nos 04 Busbar Protection Peripheral Unit Nos 0

Total For SCADA Equipments & Materials ErectionNote:1) Any material/equipment accessories which are not listed in BOQ or in scope of supply but

required to complete the job shall be included and shown in technical bid.2)*Ethernet switches shall have as many spare ports as utilized ports.3) ** PLCC BCU shall have sufficient I/Os as per given list.4) # BCU for station Auxiliary shall have sufficient I/Os as per list or otherwise suitableRTU shall be provided.5) $ SCADA system to be provided by PGCIL. 400 kv Extension will be used for this Project (220/66 Extension) also.6) $ EFS in Control Room shall be a part of PGCIL SCADA System.

Page 26: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

26

BREAK UP OF SWITCHYARD BOQ FOR 400KV ASOJ SUB-STATION(220/66KV SYSTEM) All Rates in Rs.Sr.No Particulars of Item Unit Erection

QtyErection

RateErection

AmtSupply

QtySupply

RateSupplyAmount

B

Supply and Erection of 220kV Switchyard materials as perrespective technical specifications and relevant special conditionssuitable for Two Main & One Transfer Bus scheme with QuadACSR Moose conductor and relevant Flyover Bus with Twin ACSRMoose conductor.

3

Stringing of bus with Quad Moose ACSR conductor for all the threephases with required insulators, hardwares & accessories, spacersprovided at every 3.0 mtr. interval etc. complete as per relevantstandards and approved drawings with Jumpers for continuous BusArrangement (It includes cost of conductor,insulators, hardwares &accessories, spacers etc. all items required for satisfactory functioning.Any variation in quantities shall be absorbed by contractor)-Qty. perspan of 3phase

3a Main Bus with 36Mtr span including bus jumpers No. ofSpan 4 4

ACSR Moose Conductor per Span Rmtr. 491 491Insulators-120KN AF Per Span No. 192 192Double Tension H/W & Acc with Turn Buckle.-Quad Moose ACSR PerSpan No. 3 3

Double Tension H/W & Acc without Turn Buckle.-Quad Moose ACSRPer Span No. 3 3

Spacers suitable for Quad Moose ACSR (350mm Spacing) in Main BusPer Span No. 39 39

4

Stringing of bus with Twin Moose ACSR conductor for all the threephases with required insulators, hardwares & accessories, spacersprovided at every 3.0 mtr. interval etc. complete as per relevantstandards and approved drawings with Jumpers for continuous BusArrangement (It includes cost of conductor,insulators, hardwares &accessories, spacers etc. all items required for satisfactory functioning.Any variation in quantities shall be absorbed by contractor)-Qty. perspan of 3phase

4a Transfer Bus with 36Mtr span including bus jumpers No. ofSpan 2 2

ACSR Moose Conductor per Span Rmtr. 245 245Insulators-120KN AF Per Span No. 192 192

Page 27: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

27

Double Tension H/W & Acc with Turn Buckle.-Twin Moose ACSR PerSpan No. 3 3

Double Tension H/W & Acc without Turn Buckle.-Twin Moose ACSRPer Span No. 3 3

Spacers suitable for Twin Moose ACSR (350mm Spacing) Per Span No. 39 39

5

Stringing of Earth Wire with 7/3.15 GS wire with required hardwares& accessories etc. complete as per standards and approved drawingsfor span of 72.7 meters.(It includes cost of Earthwire,hardwares &accessories etc. all items required for satisfactory functioning. Anyvariation in quantities shall be absorbed by contractor)

Span 2 2

Earthwire per Span Rmtr. 72.7 72.7Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 2

6

Droppers (including required suspension string with hardware &accessories if any) & Jumpers (including Equipment to Equipment)with Twin Moose ACSR conductor as per standards and approveddrawings with provision of required spacers (Suitable for 350mmspacing) at every 3.0 mtr. interval (It includes cost ofconductor,insulators, hardwares & accessories, Fire Wedgeconnectors, spacers etc.all items required for satisfactory functioning.Any variation in quantities shall be absorbed by contractor)-Qty. per bayof 3phase

a 220/66KV Transformer Bay (220KV Side) No. ofbay 2 2

ACSR Moose Conductor per Bay Rmtr. 562 562Insulators-120KN AF Per Bay No. 0 0Single Suspension H/W & Acc.-Twin Moose ACSR Per Bay No. 0 0Spacers suitable for Twin Moose ACSR (350mm Spacing) Per Bay No. 69 69Fire Wedge Connectors suitable for Moose ACSR to Moose ACSR Perbay No. 18 18

DSupply and Erection of 66kV Switch Yard Material as perrespective technical specifications and relevant special conditionssuitable for Single Bus with Twin Zebra ACSR Conductor

3

Stringing of bus for all the three phases with Twin Zebra ACSRconductor, insulators hardwares, spacers(suitable for 350mm spacing)at interval of 4.0 mtr complete as per relevant standards and approveddrawings.The scope includes the cost of conductor, insulators,hardwares, accessories, spacers etc.all items required for satisfactoryoperation. Any variation in quantities shall be absorbed by erectioncontractor)-Qty. per span/bay of 3phase

Page 28: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

28

a Main Bus with 36.0 Mtr. Span including bus jumpers Span 2 2ACSR Zebra Conductor per Span Rmtr. 276 276Insulators-90KN AF Per Span No. 72 72Double Tension H/W & Acc. With Turn Buckle suitable for Twin ZebraACSR cond. & 90KN Insulator disc Per Span No. 3 3

Double Tension H/W & Acc. Without Turn Buckle suitable for TwinZebra ACSR cond. & 90KN Insulator disc Per Span No. 3 3

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Span No. 30 30b Main Bus with 30.900 Mtr. Span including bus jumpers Span 4 4

ACSR Zebra Conductor per Span Rmtr. 205 205Insulators-90KN AF Per Span No. 72 72Double Tension H/W & Acc. With Turn Buckle suitable for Twin ZebraACSR cond. & 90KN Insulator disc Per Span No. 3 3

Double Tension H/W & Acc. Without Turn Buckle suitable for TwinZebra ACSR cond. & 90KN Insulator disc Per Span No. 3 3

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Span No. 21 21c Line flyover bus with 23.8 Mtr. Span Span 8 8

ACSR Zebra Conductor per Span Rmtr. 121 121Insulators-90KN AF Per Span No. 72 72Double Tension H/W & Acc. With Turn Buckle suitable for Twin ZebraACSR cond. & 90KN Insulator disc Per Span No. 3 3

Double Tension H/W & Acc. Without Turn Buckle suitable for TwinZebra ACSR cond. & 90KN Insulator disc Per Span No. 3 3

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Span No. 15 15d 66/11KV Trf. flyover bus with 23.8 Mtr. Span Span 1 1

ACSR Zebra Conductor per Span Rmtr. 121 121Insulators-90KN AF Per Span No. 72 72Double Tension H/W & Acc. With Turn Buckle suitable for Twin ZebraACSR cond. & 90KN Insulator disc Per Span No. 3 3

Double Tension H/W & Acc. Without Turn Buckle suitable for TwinZebra ACSR cond. & 90KN Insulator disc Per Span No. 3 3

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Span No. 15 15

e 220/66KV Transformer flyover bus with 32.2 Mtr. Span (66KV side) No. ofbay 2 2

ACSR Zebra Conductor per Span Rmtr. 173 173Insulators-90KN AF Per Span No. 72 72Double Tension H/W & Acc. With Turn Buckle suitable for Twin ZebraACSR cond. & 90KN Insulator disc Per Span No. 3 3

Double Tension H/W & Acc. Without Turn Buckle suitable for TwinZebra ACSR cond. & 90KN Insulator disc Per Span No. 3 3

Page 29: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

29

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Span No. 21 21

f 220/66KV Transformer flyover bus with 18.1 Mtr. Span (66KV side) No. ofbay 2 2

ACSR Zebra Conductor per Span Rmtr. 86 86Insulators-90KN AF Per Span No. 72 72Double Tension H/W & Acc. With Turn Buckle suitable for Twin ZebraACSR cond. & 90KN Insulator disc Per Span No. 3 3

Double Tension H/W & Acc. Without Turn Buckle suitable for TwinZebra ACSR cond. & 90KN Insulator disc Per Span No. 3 3

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Span No. 15 15

4

Stringing of Earth Wire with 7/3.15 GS wire with required hardwares &accessories (including spike reqd, if any) etc. complete as perstandards and approved drawings for the shown span. (It includes costof Earthwire, hardwares & accessories etc. all items for satisfactoryfunctioning. Any variation in quantities should be absorbed by erectioncontractor)

a Main Bus with 30.900 Mtr. Span Span 2 2Earthwire per Span Rmtr. 30.9 30.9Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 2

b Other Requiements with9.00 Mtr. Span Span 3 3

Earthwire per Span Rmtr. 9 9Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 212.00 Mtr. Span Span 1 1

Earthwire per Span Rmtr. 12 12Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 214.0 Mtr. Span Span 2 2Earthwire per Span Rmtr. 14 14Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 215.0 Mtr. Span Span 1 1Earthwire per Span Rmtr. 15 15Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 218.6 Mtr. Span Span 1 1Earthwire per Span Rmtr. 18.6 18.6Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 219.8 Mtr. Span Span 1 1Earthwire per Span Rmtr. 19.8 19.8Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 223.20 Mtr. Span Span 1 1Earthwire per Span Rmtr. 23.2 23.2

Page 30: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

30

Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 225.70 Mtr. Span Span 1 1Earthwire per Span Rmtr. 25.7 25.7Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 2

c Line bay with 23.8 Mtr. Span No. ofbay 5 5

Earthwire per Span Rmtr. 23.8 23.8Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 2

d 220/66KV Transformer flyover bus with 32.2 Mtr. Span (66KV side) No. ofbay 4 4

Earthwire Per Span Rmtr. 32.2 32.2Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 2

e 220/66KV Transformer flyover bus with 18.1 Mtr. Span (66KV side) No. ofbay 4 4

Earthwire Per Span Rmtr. 18.1 18.1Earthwire Access.- Suitable for 7/3.15 GS per span No. 2 2

5

Droppers (including required suspension string with hardware &accessories if any) & Jumpers with Single Moose ACSR conductor asper standards and approved drawings. (It includes cost of conductor,insulators, hard ware’s & accessories etc. all items required forsatisfactory functioning. Any variation in quantities shall be absorbed byerection contractor).-Qty. per bay of 3phase

a 220/66KV Transformer Bay (66KV Side) - LA No. ofbay 2 2

ACSR Moose Conductor per Bay Rmtr. 27 27Fire Wedge Connectors suitable for Zebra ACSR to Moose ACSR Perbay No. 6 6

Fire Wedge Connectors suitable for Moose ACSR to Moose ACSR Perbay No. 3 3

b 66KV PT Bay No. ofbay 2 2

ACSR Moose Conductor per Bay Rmtr. 11.5 11.5

c 66KV Line Bay No. ofbay 6 6

ACSR Moose Conductor per Bay Rmtr. 181 181Insulators-90KN AF Per Bay No. 30 30Single Suspension H/W & Acc. Suitable for Single Moose ACSR &90KN Insulator disc- Per Bay No. 6 6

Fire Wedge Connectors suitable for Zebra ACSR to Moose ACSR Perbay No. 24 24

Page 31: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

31

Fire Wedge Connectors suitable for Moose ACSR to Moose ACSR Perbay No. 18 18

Fire Wedge Connectors suitable for Panther/Dog ACSR to MooseACSR Per bay No. 3 3

d 66/11KV Transformer Bay No. ofbay 1 1

ACSR Moose Conductor per Bay Rmtr. 170 170Insulators-90KN AF Per Bay No. 15 15Single Suspension H/W & Acc. Suitable for Single Moose ACSR &90KN Insulator disc- Per Bay No. 3 3

Fire Wedge Connectors suitable for Zebra ACSR to Moose ACSR Perbay No. 24 24

Fire Wedge Connectors suitable for Moose ACSR to Moose ACSR Perbay No. 15 15

6

Droppers (including required suspension string with hardware &accessories if any) and Jumpering (equipment to equipment) with TwinZebra ACSR conductor as per standards and approved drawings withprovision of spacers suitable for 350mm spacing at 4.0 mtr interval. Thescope includes the cost of accessories ,spacers, fire wedge connectorsetc.all items required for satisfactory operation. Any variation inquantities shall be absorbed by erection contractor -Qty. per bay of3phase

a 220/66KV Transformer Bay (66KV Side) No. ofbay 2 2

ACSR Zebra Conductor per Bay Rmtr. 350 350Insulators-90KN AF Per Bay No. 30 30Single Suspension H/W & Acc.suitable for Twin Zebra ACSR Cond.And 90KN Insulator disc- Per Bay No. 6 6

Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Bay No. 33 33Fire Wedge Connectors suitable for Zebra ACSR to Zebra ACSR Perbay No. 42 42

b 66KV Bus Coupler Bay No. ofbay 1 1

ACSR Zebra Conductor per Bay Rmtr. 160 160Spacers suitable for Twin Zebra ACSR (350mm Spacing) Per Bay No. 18 18Fire Wedge Connectors suitable for Zebra ACSR to Zebra ACSR Perbay No. 24 24

Page 32: PART - III PRICE BID Office/000001/nps/Part... · End cost Total FOR cost Total End cost A ... Stringing of bus with Twin Moose ACSR conductor for all the three phases with required

32