parameter 500 mw
TRANSCRIPT
-
7/27/2019 Parameter 500 Mw
1/3Sheet 1 of 3
CONTRACT DATA SHEET
CONTRACT NO. 0663
Contract Date:
April, 2008
PURCHASER CSEB
PLANT NAME
KORBA WEST TPP EXTN -
STAGE III 1 x 500 MW,
CONS. ENGG
--- Utility
PROPOSED FUEL Sub Bituminous CoalAsh Fusion
Temp
HHV
Kcal/kg
Grindability
(HGI)
FC% 24.0 VM% 21.0 M% 14.0 Ash% 41.0 S% 0.28 1400oC 3300 55
FUEL BURNING EQUIPMENT
TYPE
MainBurners
Tilting Tangential
StabilisationBurn
ers
Low NOx
MILLS
Type: XRP 1003
MAKE & NOS. BHEL, 40 BHEL, 20 Make & Nos.: BHEL, 10
CONTROL Air Damper Air Damper Capacity: 65.0 t/h @ DC
CAPACITY 55 x 106 kcal/hr. 18.51 x 106 kcal/hr.Motor kW : 525Speed (RPM) : 1000
DISPOSITION Corners Corners System: Cold PA
FURNACE Type: Balanced Draft Furnace with Fusion Welded Water Walls
WIDTH 19177 mm DEPTH 16115 mmVolume m : 17599 (as per specification)
Fuel Heat Input: 1234.2x106 kcal/hr @ BMCR DC
BOILER Controlled Circulation with Rifled Tubing, (CC+),
Radiant Reheat, Dry Bottom, Top Supported
Pressure
Drum Design:
209 kg/cm2 (g)
DESIGNATION:
+
CC
51235
51301
16115
19177
Super heater outlet:
178.0 kg/cm2 (g) - BMCR
SUPER HEATERStage: 1
Type: LTSH Horizontal and Pendant
H.S
.Aream
2 8661
Total H.S. m2
11561
Stage: 2
Type: SH Division Panellette (Tube Projected)1415
Stage: 3
Type: SH Finish Platen (Tube Projected)1485
ATTEMPERATOR Type: SprayNo. of Stages:
Single Stage
Medium of Spray:
Feed Water
REHEATERType: Stage-I: Pendant Platen,
Stage-II: Pendant Spaced
Total: H.S. m
8620
Control: Burner Tilt
and Excess Air
-
7/27/2019 Parameter 500 Mw
2/3
Sheet 2 of 3
CONTRACT DATA SHEET
CONTRACT NO. 0663
Contract Date:
April, 2008
ECONOMISER Type: Plain Tube Total H. S. m : 15200 No. of Blocks: 3
AIR HEATER
Type: Bisector
Primary: 27.5 VI 2000
Secondary: 30.0 VI 2000
Total:
H.S. m2
Primary:40070
Secondary:62740
Motor
kW
Primary:11.0
Secondary:18.5
Nos.:Primary: 2 Nos.
Secondary: 2 Nos.Make: BHEL
BOILER AUXILIARIES
FANS Type Make NosFlow
m3/s
Pressure
mmwc
Temp
oC
DriveSpeed
rpm
Motor
kWControl
FDFAN
AXIALAP1-26/16
BHEL 2 277 410 50 Motor 980 1430BladePitch
Control
PAFAN
AXIALAP2-20/12
BHEL 2 193 1195 50 Motor 1480 2800BladePitch
Control
IDFAN
RADIAL NDZV47
SIDORBHEL 2 609 490 150 Motor 580 4000
InletDamperControl+ VFD
SOOT BLOWERS TYPE Make No.s Medium
FURNACE Wall Blowers BHEL 88 Steam
SH PANELSH PLATENLTSHREHEATERECONOMISER
Long RetractableSoot Blowers
BHEL 40 Steam
DUST COLLECTOR Make Nos.DustConcentrationat inlet
Flue Gas FlowCombinedEfficiency %
FAA-9x45M-
2x92150-2BHEL 4 74.0 g/Nm3 617.1 Nm3/Sec
(One field out of
service)
99.932
PIPE LINES MAIN STEAM HOT REHEAT COLD REHEAT FEED WATER
SIZE mm x mm 406.4 x 38 711.0 x 25 660 x 22 508 x 64
No. OFF 2 2 2 1
MATERIAL SA 335 P91 SA 335 P91 SA 106 GR.C SA 106 GR.C
-
7/27/2019 Parameter 500 Mw
3/3
Sheet 3 of 3
CONTRACT DATA SHEET
CONTRACT NO. 0663
Contract Date:
April, 2008
BOILER MOUNTINGS
Location Type Make No. Set Pr. Kg/cm2(g)Size in / out
(mm)
Safety
Valves
Drum
1750 WB
1740 WB
BHEL
4
2
209.0, 211.1
213.2, 213.2
215.3, 215.376.2/152.4
SH
Outlet
SV
ERV
1740 WD
1538 VX-10W BHEL
2
5
188.5, 188.5
185.5, 185.5,186.6,
186.6, 186.6
76.2/152.4
63.5/101.6
RH
Inlet 1786 WB BHEL 4 52.4, 52.4, 54.0, 54.0 152.4/254
Outlet
1786 WE
1525 VX BHEL
4
4
48.4, 48.4, 49.9, 49.9
47.4, 47.4, 47.9, 47.9
152.4/203.2
152.4/203.2
WaterLevel
IndicatorDrum
DWLG
EWLI
Yarway
BHEL
2
4
-
-
21 VISIBILITY
BHELVISION
MAIN PARAMETERS
FUEL DESIGN COAL
UNIT100%BMCR
100%TMCR
50% TMCR
GENERATOR MW - 500 250
FLOWSuperheat t/h 1590.0 1457.9 755.4
Reheat t/h 1358.0 1302.1 656.8
STEAM
Total Heat Output of System (Q Duty) Mkcal/h 1046.6 969.7 538.6
Pressure at Super Heater Outlet kg/cm2(g) 178.0 176.6 171.1
Temperature at SH Outlet oC 540 540 540
Pressure at Reheater Inlet kg/cm2(g) 45.02 43.19 21.45
Temperature at Reheater Inlet oC 337.5 337.1 310.7
Pressure at Reheater Outlet kg/cm2(g) 42.37 40.65 20.17
Temperature at Reheater Outlet oC 568 568 568
Feed Water Temperature (ECO Inlet) oC 254.5 253.4 219.4
Ambient Air Temperature oC 27 27 27
Combustion Air Temperature (Secondary) oC 311 305 262
Fuel Quantity t/h 374 347 193
Air Quantity (Total Combustion Air) t/h 2024 1855 1033
FLUE
GAS
Temp. of Gas at Boiler Exit (Corrected) oC 126 125 114
Temp. of Recirculation Gas oC - - -
Quantity of Recirculation Gas t/h - - -
Efficiency Based on HHV (BSEN 12953-15:2003) % 84.84 84.85 84.74