paper_45 stator winding fault
TRANSCRIPT
-
8/20/2019 Paper_45 Stator Winding Fault
1/8
Effects of Turn to Turn Stator Winding Faults in
Synchronous Generators - A Numerical Study
Meinolf Klocke, Jens RosendahlUniversity of Dortmund
Chair of Electrical Drives and Mechatronics1
Emil-Figge-Str. 70, D-44221 Dortmund, Germany
Abstract — The effects of stator winding faults on the
behaviour of a synchronous generator are of interest for
predicting the severity of the occurring damage. The paper
in hand describes the numerical transient field and net-
work calculation for the sudden occurrence of stator wind-
ing turn to turn short circuits within coil groups and be-
tween different phases. For a 2-pole 775 MVA generator
six different locations of short circuits varying in the num-
ber of shorted turns and the position of the bypassed turns
in the winding are investigated. Transient currents in the
short-circuited windings as well as in the remaining stator
coils are calculated, taking saturation into account. Addi-
tionally, the unbalanced magnetic pull is determined and
output as a function of time. The results of the calculations
clarify the severity of such faults even if the machine is
disconnected from the grid and de-energized within a very
short period after the occurrence of the short-circuit.
Index Terms— Electrical machine, stator winding fault,
numerical field computation, coupled problems.
I. I NTRODUCTION
Stator winding faults are of great importance in large
synchronous generators as they not only damage the
stator winding of the machine severely, but can also
destroy the whole stator core. Common reasons for these
faults are material fatigue of the insulation conditioned
by mechanical stress in the end winding zone as well as
thermal influences and moisture [1, 2 and 3].
The transient numerical field and network calcula-
tion appears to be an adequate and advantageous tool for
the quantitative prediction of effects of stator winding
faults since experimental studies are much too costly or
completely unfeasible. In opposition to a merely net-
work based analysis the transient variation of mutual
and self inductances caused by changes in the level of
iron saturation is implicitly taken into account since the
discretised model can be considered a representation of
the whole magnetic circuit.
The output quantities can be used for further evalua-
tions, e.g. the reconstruction of disturbances having
finally destroyed a generator. Forces having been ex-
erted on the end-winding zone of a destroyed generator
for instance can be calculated from the resulting coil
currents.
1 The Chair of Electrical Drives and Mechatronics, University ofDortmund, Germany, is held by Prof. Dr.-Ing. Dr.-Ing. S. Kulig.
This allows identifying the stator winding fault as
the primary cause of end-winding zone deformation of
the wrecked generator. In this study a finite difference
scheme coupled with an arbitrary circuit containing
windings and lumped elements is applied to a 2pole-775
MVA generator.
II. NUMERICAL TIME-STEPPING FIELD COMPUTATION
COUPLED TO STATOR NETWORK A NALYSIS
In a strongly coupled numerical time-stepping com-
putation for field and circuit quantities the governing
equations are solved simultaneously for each time-step.
The time-stepping results from replacing the time de-
rivatives by quotients of differences. In the program
used here this time discretisation is carried out accord-
ing to the θ-method as described in [4]. The spatialdiscretisation method for the magnetic field applied in
the program is a finite difference scheme. Since thesemethods are not novel, only a basic sketch of the result-
ing system of equations (1) for a given time-step is de-
scribed in the following [3, 4, 5, 6 and 7].
Like in the finite element method a reluctance matrix
(α) results from the spatial discretisation process, whichinterrelates the unknown nodal values of the magnetic
vector potential on the discretised machine cross-section
to each other. It should be noted that such a nodal ap-
proach on a 2D cross-section can be considered equiva-
lent to a 3D edge approach applied to a cross-sectional
one-element-layer model. The inherent constraints are
given by edges in the front and back plane with a value
of zero whereas the unknown values occur for edges in
perpendicular direction.
In massive conductive regions like the rotor core and
the damper bars eddy currents have to be taken into
account. They are assumed to close ideally, i.e. without
additional voltage drop in the machine end region. Their
current densities do not occur explicitly. Since they are
only determined by the time derivative of the vector
potential and the material conductivity, their expressions
can immediately be inserted in the equations for the
vector potentials. Discretisation and rearrangement leads
to a diagonal matrix of nodal conductance coefficients
( F γ) with time step width h and the θ -method weightingfactor (1− θ) in the denominator.
1
-
8/20/2019 Paper_45 Stator Winding Fault
2/8
The field excitations caused by stator and rotor
winding currents (iw) and (if ) are included by the matri-ces of turn density coefficients ( F N,1)
T for the stator and
( F N,2)T for the rotor. The same matrices in transposed
form occur for the flux linkage calculation in the branch
voltage equations of stator and rotor windings. The
matrices ( Bw) and ( Bf ) contain the loop incidences ofstator and rotor winding branches in the overall net-
work. ( Dw) and ( Df ) are diagonal matrices for the wind-ing currents in the voltage equations. Their coefficients
are calculated from resistances and leakage inductances
directly associated with the windings. In the present case
the coefficients of ( Dw) are zero since the armaturewinding resistances and leakage inductances are mod-
elled as external network elements (see Fig. 1b).
Network branch currents and voltages are embraced
in the vector ( x b). The coefficients in matrix ( M b) on theone hand result from the dynamic current-voltage be-
haviour of the branches. On the other hand loop inci-
dences for voltages and node incidences for currents are
explicitly included there, too. The matrices (C w) and (C f ) provide these nodal incidences for the stator and rotor
winding currents (iw) and (if ) as they are not included in( x b).
( ) ( )
( ) ( ) ( ) ( )
( ) ( ) ( ) ( )
( ) ( ) ( ) ( ) ( )
( ) ( ) ( ) ( ) ( )
( )
( )
( )
( )
( )
( )
( )
( ) ⎟⎟⎟
⎟⎟⎟⎟⎟⎟⎟
⎠
⎞
⎜⎜⎜
⎜⎜⎜⎜⎜⎜⎜
⎝
⎛
=
⎟⎟⎟
⎟⎟⎟⎟⎟⎟⎟
⎠
⎞
⎜⎜⎜
⎜⎜⎜⎜⎜⎜⎜
⎝
⎛
⋅
⎟⎟⎟
⎟⎟⎟⎟⎟⎟⎟
⎠
⎞
⎜⎜⎜
⎜⎜⎜⎜⎜⎜⎜
⎝
⎛
−
−
−+
f
w
b
A
f
w
b
f f
Fe
2, N
ww
Fe
1, N
f w b
T
2, N
T
1, N
01
01
0
01
r
r
r
r
i
i
x
A
D Bl
h F
D Bl
h F
C C M
F F h
F
θ
θ
θ α
γ
(1)
The right hand side of (1) is calculated from initial
values or the results of the previous time step. It is em-
phasised that all network equations are explicitly taken
into account without the use of reductive methods like
node potential or loop current formulations. This ap-
proach for network analysis is known as the “sparse
tableau approach” as referred to in [9].
The number of network equations appears to be neg-
ligible in the presence of thousands of field equations.Moreover, ill-conditioned systems, which would result
from practically cutting or short-circuiting branches by
extreme values of their resistances in reductive methods,
can be avoided by the sparse tableau approach.
The solution of the linear system of equations is car-
ried out directly, where a total pivot search is applied
during the elimination of the lower network matrices.
The nonlinear magnetic characteristic of stator and rotor
core material makes the reluctance matrix (α ) become
field dependent. This requires a few iterations per time
step, where the permeability is adapted by under-
relaxation.
In the program used here the stator was formerly re-
lated to fixed topologies and winding arrangements, i.e.
star and delta connection of an m-phase winding with allcoil groups of a phase connected in series or in parallel.
In contrast the stator coil groups are treated like inde-
pendent branch elements in (1). This concept was al-
ready introduced in [8] for the rotor circuitry. It has
been adapted for the stator without the need of changes
of the program source code. A virtual polyphase wind-ing is prescribed for the machine stator with a non regu-
lar winding scheme explicitly forced to be read in.
By neither specifying the star or delta connection of
phases – an option previously implemented for consider-
ing grounded neutral points – the distinction between an
external supply network and the stator winding ar-
rangement vanishes. The former output line to ground
voltages of the network may be reinterpreted as inde-
pendent winding branch voltages by a proper choice of
loop equations. This procedure allows modelling an
arbitrary stator network topology.
III. APPLICATION TO A SYNCHRONOUS GENERATOR
A stator circuitry including three possible locations
for turn to turn short circuits within a given coil group
and three positions for short circuits between neighbour-
ing phases is set up according to Fig. 1a -c.
U
V
W
45678910
32
1234567
15161718192021
32142414039
17161514131211
32333435363738
42414039383736
293031333435
31302928272625
141312111098
18192021
28272625
upper
layer
lower layer
upper
layer
lower
layer
ps_II ps_III
ps_I
ws_I
ws_II
ws_III
positive
coil group
negative
coil group
slot numbers
Fig. 1a. Connectivity of the investigated windings.
The two parallel coil groups of each winding phase
are split into two partial windings, which in Fig. 1b are
denoted w1 – w7 and w10 – w4 for phase U, w2 – w8 andw11 – w5 for phase V as well as w3 – w9 and w6 – w12 for phase W. The RL-elements in series to the partial wind-ings represent the ohmic resistance of a partial winding
and its contribution to the end zone leakage inductance.
Both are assumed to be turn number proportional to the
total values of one coil group.
2
-
8/20/2019 Paper_45 Stator Winding Fault
3/8
Fig. 1b. Network arrangement of stator windings with partial winding
coil groups w1…12 coupled directly to the field problem.
The resistive-inductive branches RL1…3 stand for theimpedance of the grid and the leakage inductance of the
machine transformer. The relative short circuit voltage is
set to 11 %. A capacitive-ohmic neutral to ground con-
nection of the winding star node with practically negli-gible admittance is inserted in order to allow for a sym-
metric arrangement of network loop equations.
TABLE 1: CHARACTERISTICS A ND ABBREVIATIONS
case phases coil group affected turns
ws_I U positive 2nd from terminal U
ws_II V positive 5th, 6th from terminal V
ws_III W negative 3rd, 4th, 5th (central turns)
ps_I U / V neg. / neg. 1st / 1st, 2nd from neutral
ps_II V / W neg. / pos.1st, 2nd from neutral
/ 1st-3rd from terminal W
ps_III W / U pos. / neg.1st-3rd from terminal W
/ 1st from neutral
Furthermore, the voltage between the winding neu-
tral point and ground becomes an accessible output
quantity as the branch voltage of the related network
element. The partial windings w1, w2 and w3 with one,two and three turns can be shunted by a resistive branch
in parallel in order to simulate a turn to turn winding
fault within one coil group. The separating nodes be-tween the partial windings w10 – w4 and w11 – w5 as wellas w6 – w12 can be interconnected by correspondingresistive branches allowing for the simulation of wind-
ing faults between neighbouring phases. All cases are
listed in Table 1. The undisturbed operation is modelled
by interconnecting resistances of 1012
Ω.
Fig. 1d. Finite-difference polar grid of the machine cross-section Slot
numbering clockwise beginning with the first slot above the horizontal
line on the left side
Partial winding no.:+12 –5 –5 –11 … …–11 +7+1+7 … … …+7 –9 –9 –9 –3 …… –3 +8 … .. +8 +2+2 +8 -4–10 … … … .. -10+6 +6+6+12 ...
Fig. 1c. Winding scheme with locations of short circuits within single coil groups ( ) and between different phases (). Shorted turns are marked by “×” for the shorts in a single coil group, and by “↑” for the shorts between different phases.
ws_I ws_IIws_III ps_I ps_III ps_II
3
-
8/20/2019 Paper_45 Stator Winding Fault
4/8
At the instant of the short circuit (t sc = 3.5 s), thisvalue is reduced to 5 mΩ for the winding fault underconsideration. The prescription of the complete topology
of the stator circuitry including all possible short-circuit
branch elements artificially enlarges the network and
leads to additional computational cost. For a given fault
under investigation many obsolete network elementsappear and twelve stator voltage equations instead of
six, seven or eight have to be solved permanently. How-
ever, as an advantage only one time consuming calcula-
tion has to be carried out for reaching steady state opera-
tion of the machine.
The locations of the winding faults under considera-
tion are shown in Fig. 1c. Coil conductors on slot
ground are depicted thick on the left and upper layer
thin on the right. Short circuits at the marked crossing
points in the end winding zone result in different num-
bers of shorted turns and positions within the affected
coil groups. The cases also differ in the phases these coil
groups belong to as briefly characterised in Table 1. In
Fig. 1c the turns of these coil groups are also marked.
The cross-section of the machine is discretised by a grid
with about 19,000 nodes as shown in Fig. 1d, which also
shows the positions of coil cross-sections of w1, w2 andw3, the partial windings to be shunted. Fig. 1d addition-ally contains the rotor reference frame axes d and q.
This coordinate system is used as a frame of reference
for the magnetic pull on the rotor later on. The simula-
tions start with short-circuiting the connection under
investigation. A period of time later (0.2 s) the machine
is disconnected from the power grid as a result of pro-
tection equipment interaction and de-excitation is initi-ated by immediately reducing the exciter voltage to
zero.
IV. R ESULTS
A. Currents
In all investigated cases high short circuit currents
occur as listed in Table 2.
Fig. 2. Current in short-circuit resistance for three-turn winding faultin phase W (case ws_III) from FD calculation.
In general their characteristics qualitatively are quite
similar to the one depicted in Fig. 2 showing one ex-
treme case ws_III. The time-course is characterised by a
quickly vanishing asymmetric part at the very begin-
ning, the intensity of which strongly depends on the
phase condition at the instant of time before the fault
occurs.The effective value of the uninterrupted short-circuit
current I sc, eff is reached within about 0.15 s. It is notmuch reduced after de-excitation and disconnection of
the machine from the power grid. I sc, eff, disc is at mostonly about 20 % less than I sc, eff , as shown in Table 2.Even 1.8 s after disconnection there is still a high level
of short-circuit current up to about a half of the value at
the instant of disconnection and start of de-excitation.
TABLE 2: CHARACTERISTICSHORT-CIRCUIT CURRENT VALUESFor comparison: rated value per coil group I eff, group = 8.6 kA.
|isc, peak | I sc, eff I sc, eff, disc I sc, eff, 1.8 sCase kA kA kA kA
ws_I 215.2 107.8 107.9 59.96
ws_II 207.9 118.7 105.5 51.14
ws_III 307.4 128.2 104.8 45.48
ps_I 139.4 96.6 87.8 41.25
ps_II 250.1 113.5 79.72 29.89
ps_III 259.2 103.5 79.56 34.87
The process of de-excitation is shown in Fig. 3.
Right after the short-circuit the contribution of the
shorted windings to the overall fundamental MMF is
reduced to zero. This loss of MMF is partly compen-
sated by the field winding hence its current is raised.
The excitation if is superposed by a grid frequencyalternating current which is induced by the asymmetric
field distribution of the armature winding. After discon-
nection it drops off sharply until it reaches a more flat
course later on. The transient characteristic of whole
process is rather double exponential than single expo-
nential, due to the inductive interaction between the
massive iron and the damper bars on the one hand and
the field winding on the other hand
Fig 3. Excitation Current for case ws_III with de-excitation starting at3.7 s.
4
-
8/20/2019 Paper_45 Stator Winding Fault
5/8
Fig. 4a. Line currents in case ws_I (Phase U) from FD calculation
Fig. 4b. Line currents in case ws_II (Phase V) from FD calculation
Fig. 4c. Line currents in case ws_III (Phase W)
In contrary to the fast reduction of if , the short circuitcurrent isc is decaying slowly. The degressive course ofinduction due to nonlinearity and iron saturation pre-
vents a fast drop down of isc. In addition the massiveiron and the damper winding are taking over the amper-
age of the exciter due to induction; this also is a reason
for the rather single exponential decay of current ampli-
tude in Fig. 2.
The line currents at the terminals iline in the Figures 4and 5 show a strong asymmetric behaviour, which fi-
nally triggers protection equipment for all investigated
cases.
Fig. 5a. Line currents in case ps_I (between Phase U and V)
Fig. 5b. Line currents in case ps_II (between Phase V and W)
Fig. 5c. Line currents in case ps_III (between Phase W and U)
Obviously the transient behaviour after the occur-
rence of the short circuit is stronger the more windings
are shorted, as shown in Fig. 4c for case ws_III with
three shorted windings. The maximum effective value
occurs in the phase following the one with the shorted
turns, whereas the line current in the phase before is
decreased in cases ws_II and ws_III.
Winding faults between different phases are of much
higher effect regarding the terminal currents, as shown
in Fig. 5 a-c. The current peaks are much higher and a
stronger asymmetry occurs.
5
-
8/20/2019 Paper_45 Stator Winding Fault
6/8
Fig. 6a. Winding currents in phase U (case ps_III)
Fig. 6b. Winding currents in phase V (case ps_III)
Fig. 6c. Winding currents in phase W (case ps_III)
Strong circulating currents in the parallel coil groupsof the affected as well as the undisturbed phases arise
during the fault and after disconnecting the machine
from the grid. The currents in the winding partitions for
case ps_II are displayed in Fig. 6 a-c, where the wind-
ings w12 and w4 form a shorted loop through the neutral
point. Hence strong currents can be observed in the two
windings (see Fig. 6a and c).
After disconnection (t=3.7s) still serious circulatingcurrents are induced in those windings, which are only
little lower than before and decreasing slowly.
On the other hand, the undamaged coil groups in
phase V (Fig. 6b) carry much lower currents, as ex- pected. However, it is not the rule that undamaged coil
groups are little affected by short-circuits, by reason of
inductive coupling between all windings of the machine,
e.g. in Fig. 6c. The first peak of the current in the undis-
turbed coil group w3 and w9 is about 4 times of its rated
value. After disconnection it is even rising to about 3
times the rated value.
All those currents do not disappear before total de-excitation of the machine.
B. Unbalanced magnetic pull
Another phenomenon, which was already discussed
in context with the rotor short-circuits [8], is the unbal-
anced magnetic pull generated by the asymmetric field.
The forces in the rotor d-, q- coordinates follow a char-
acteristic similar to the time-function of the short-circuit
currents since they are strongly related to each other.
Hence the resulting force magnitude is displayed in
Table 2 for 4 characteristic values (in similar manner as
for the currents in Table 2).As expected the highest peak occurs instantly after
the short circuit. The magnitude is decreasing exponen-
tially during the transient phase of 0.2-0.3 s. In the case
of ps_II a very high peak value acts on the rotor, which
is equivalent to a weight of 736000 kg.
TABLE 3: FORCE MAGNITUDES OF U NBALANCED MAGNETIC PULL
peak F
max F
discmax,
F
s1.8max, F
Case MN MN MN MN
ws_I 1.076 0.741 0.750 0.257
ws_II 2.206 1.718 1.604 0.388ws_III 1.267 0.582 0.502 0.0847
ps_I 1.980 1.894 1.850 0.496
ps_II 7.361 4.157 3.541 0.525
ps_III 6.364 3.275 2.753 0.558
The transients level of to a steady state value | F
| max
until the machine is disconnected from the power grid.
Thereafter the force magnitudes decay like the short-
circuit currents. Case ws_I shows the lowest values in
Table 3, but is still more critical than rotor winding
splay the time after
disconnection during de-excitation.
shorts.
Figures 7 and 8 display the trajectories of the magneticforce exerted on the rotor in the d-, q- reference frame.
Since all cases generate a similar pattern, only the least
and most critical cases are included here, namely ws_I
on the left side and ps_II on the right. The upper trajec-
tories are shown during 0.2 s after the instant of the
short circuit and the lower ones di
6
-
8/20/2019 Paper_45 Stator Winding Fault
7/8
Fig. 7a. Trajectory of force vector on rotor in rotor reference frame for
a period of 0.2 s after winding fault in phase U (case ws_I).
Fig. 7b. Trajectory of force vector on rotor in rotor reference frame
after disconnection (case ws_I).
The orbit of the force vector follows an epicyclical
curve getting smaller during the transient process and
stabilizing after a few turns of the rotor. During the
steady state process the force vector can be separated
into of a fundamental frequency and a triple frequency
part of the same magnitude. In stator related coordinates
this corresponds with the sum of a constant and a double
frequency part, whereas the rotation is oriented in theopposite direction. The shorted windings create a con-
stant pressure on the rotor as well as an alternating part
every time a pole passes the axis of the coils.
In the Figures 7 and 8 a continuous change of the
angle between the long axis of the epicycle and the d-
axis of the rotor after disconnection can be observed.
This result in a slow variation of the direction of the
magnetic pull related to the stators reference frame.
Fig. 8a. Trajectory of force vector on rotor in rotor reference frame for
a period of 0.2 s after the fault between V and W (case ps_II).
Fig. 8b. Trajectory of force vector on rotor in rotor reference frame
after disconnection (case ps_II).
C. Field map
The field map in Fig. 9 on the cross-section of the
investigated machine at an instant of time with maxi-
mum rotor forces at 3.693 s (case ps_II) shows obvious
irregularities. It illustrates the influence of the asymmet-
ric field distribution on the unbalanced magnetic pull on
the rotor. The shorted coils are marked with the refer-ence direction of the short-circuited loop.
Obviously the current in this loop strongly disturbs
the field. Knowing that normal components contribute
tensile stress to the fictitious Maxwell stress tensor,
whereas the tangential components result in compres-
sive stress, the extreme high forces may be explained.
7
-
8/20/2019 Paper_45 Stator Winding Fault
8/8
The tangential field lines are pushing mainly on the
left side of the rotor, whereas much more normal flux is
pulling on the right than on the left. A flux density of 1
Tesla creates a tensile stress of about 400 kN per square
meter. With diameter of 1 m and a length of 7 m of the
rotor, the calculated values in Table 3 appear plausibly.
A more distinct asymmetry leads to stronger forces.
Fig. 9. Field map 3.693 s after occurrence of sudden short circuit in
phase W (case ps_II).
V. CONCLUSION
Six different stator winding faults differing in the
number of shorted turns and affected phases have beeninvestigated by means of a combined transient network-
field computation. In all cases a strong impact on the
machine arises while the machine is still connected to
the power-grid. But even immediately disconnecting the
machine from the grid cannot be considered an effective
measure for reducing the occurring damage unless a
quick de-excitation is provided. The turn currents re-
main at a high level of about six to nine times their rated
values in the short circuit loop and also winding parts
not included in the short circuit path are exposed to
inadmissibly high currents, if the excitation remains at
its previous level.
As for the rotor, attention has been paid to the unbal-anced magnetic pull which besides the damper currents
and eddy current losses not dealt with here appears to be
a quantity with problematic values. Further investiga-
tions concerning the mechanical consequences of such
strong impacts on the mechanical properties of bearings
and the shaft train seem to be indicated. However, prac-
tical observations of bearing damages or permanent
bending deformation of rotor shafts caused by stator
winding faults are not known to the authors.
R EFERENCES
[1] T. S. Kulig, Die innere Unsymmetrie vonSynchronmaschinen, PhD thesis AGH, Krakau1974.
[2] T. S. Kulig, Über die Beeinflussung der Ströme und
des Elektromagnetischen Drehmoments vonTurbogeneratoren durch Windungs- und
Phasenschlüsse, PhD thesis, Hannover 1979.[3] M. Daneshnejad, Erfassung von Windungs-
schlüssen in der Erregerwicklung einesTurbogenerators, PhD thesis, University ofDortmund, Institute of Electrical Machines, Drives
and Power Electronics, 2001.
[4] M. Klocke, Zur Berechnung dynamischer Vorgängebei von einem Drehstromsteller gespeisten
Antrieben mit Asynchronmaschinen und mehreren gekoppelten Massen mittels Finite-Differenzen- Zeitschrittrechnung , PhD thesis, University ofDortmund, Institute of Electrical Machines, Drivesand Power Electronics, 1999.
[5] R. Gottkehaskamp, Nichtlineare Berechnung von Asynchronmaschinen mit massiveisenem Rotor und zusätzlichem Dämpferkäfig im transienten Zustandmittels Finiter Differenzen und Zeitschrittrechnung ,PhD thesis, University of Dortmund, Institute of
Theoretical Electrical Engineering and Electrical
Machines, 1992.
[6] A. Krawczyk, J. A. Tegopoulos, Numerical Model-ling of Eddy Currents, Oxford: Clarendon Press,1993.
[7] T. S. Kulig “Anwendung der numerischen
Feldberechnung zur Modellierung elektrischer
Drehstrom-Maschinen mit inneren Fehlern” Bulletin
SEV/VSE(1990)7.
[8] M. Klocke, M. Daneschnejad: “New Aspects of
Winding Faults in the Rotor of a Large
Synchronous Generator”, Record of the 2001 IEEE
International Symposium on Diagnostics for
Electrical Machines, Power Electronics and Drives
(SDEMPED 2001), p. 161-166. Grado, Italy,
September 1-3, 2001.
[9] W. Mathis: Theorie nichtlinearer Netzwerke,Springer-Verlag, Berlin, Heidelberg, New York,
1987.
8