panelview plus specifications -...

28
Technical Data PanelView Plus Specifications Catalog Numbers 2711P, 2711PC PanelView Plus Family PanelView Plus HMI terminals are used for applications with a need to monitor, control, and display information graphically, allowing operators to quickly understand the status of their application. All PanelView Plus applications are programmed with FactoryTalk View Studio for Machine Edition (ME) software and have FactoryTalk View ME Station runtime installed on each terminal. This family provides a broad range of rugged terminals offering these features: Premier integration with the Integrated Architecture platform Scalable 4- to 15-inch displays with touch screen, keypad, or both for input Common development software Real-time monitoring of a terminal's displays via a web browser Use this document along with the Visualization Solutions Selection Guide, publication VIEW-SG001 , to make decisions on the visualization solutions best suited for your system requirements. Topic Page Environmental Specifications 2 Certifications 3 PanelView Plus 6 Terminals 4 PanelView Plus 400 and 600 Terminals 11 PanelView Plus Compact Terminals 15 External Power Supply 18 HMI Software 20 Communication Cables 23 Migration Hardware 27 Additional Resources 28 www.klinkmann.com 6 / 2011

Upload: doanphuc

Post on 21-May-2018

227 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

Technical Data

PanelView Plus SpecificationsCatalog Numbers 2711P, 2711PC

PanelView Plus Family PanelView Plus HMI terminals are used for applications with a need to monitor, control, and display information graphically, allowing operators to quickly understand the status of their application. All PanelView Plus applications are programmed with FactoryTalk View Studio for Machine Edition (ME) software and have FactoryTalk View ME Station runtime installed on each terminal.

This family provides a broad range of rugged terminals offering these features:• Premier integration with the Integrated Architecture platform• Scalable 4- to 15-inch displays with touch screen, keypad, or both for input• Common development software• Real-time monitoring of a terminal's displays via a web browser

Use this document along with the Visualization Solutions Selection Guide, publication VIEW-SG001, to make decisions on the visualization solutions best suited for your system requirements.

Topic Page

Environmental Specifications 2

Certifications 3

PanelView Plus 6 Terminals 4

PanelView Plus 400 and 600 Terminals 11

PanelView Plus Compact Terminals 15

External Power Supply 18

HMI Software 20

Communication Cables 23

Migration Hardware 27

Additional Resources 28

www.klinkmann.com6 / 2011

Page 2: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

2 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Environmental Specifications

The environmental certifications apply to all PanelView Plus terminals:• PanelView Plus 6 terminals including logic, communication modules,

and 700, 1000, 1250, 1500 display modules• PanelView Plus 400 and 600 terminals• PanelView Plus Compact 400, 600, and 1000 terminals

Table 1 - Environmental Specifications - PanelView Plus Terminals

Attribute 2711P, 2711PC

Temperature, operating 0…55 °C (32…131 °F)

Temperature, storage -25…70 °C (-13…158 °F)

Heat dissipation400, 600700, 1000, 1250, 1500

85 BTU/hr240 BTU /hr

Relative humidity 5...95% noncondensing

Vibration 0.012 in. peak-peak 10…57 Hz2 g at 57…500 Hz

Altitude, operating 2000 m (6561 ft)

Shock, operating 15 g at 11 ms

Shock, nonoperating 30 g at 11 ms

Enclosure ratings NEMA Type 12, 13, 4X (indoor use only), IEC IP54, IP65

Airborne contaminants For PVP/PVP-CE conformal-coated PCBA level products:ANSI/ISA S71.04 - 1985 Severity Level G3EN60654-4: 1998 Class 3

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 3: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 3www.klinkmann.com6 / 2011

Certifications The certifications apply to all PanelView Plus terminals:• PanelView Plus 6 terminals including logic, communication modules,

and 700, 1000, 1250, 1500 display modules• PanelView Plus 400 and 600 terminals• PanelView Plus Compact 400, 600, and 1000 terminals

Table 2 - Certifications - PanelView Plus Terminals

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

2711P, 2711PC

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E10314.

UL Listed Industrial Control Equipment for use in:• Class I, Div 2, Groups A, B, C, D• Class I, Zone 2, Group IIC (2)

• Class II, Div 2 Groups F, G• Class III Hazardous Locations

(2) Applies only to the 1250 high-bright display module.

CE (EMC) European Union 2004/108/EC EMC Directive, compliant with:• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions

CE (LVD) European Union 2006/95/EC Low Voltage Directive, compliant with:• EN 61131-2; Programmable Controllers

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Marine(3)

(3) The 700 and 1000 display modules are marked as marine-certified.

Products identified with the suffix M in the catalog number are certified to the requirements of one or more marine societies. For additional marine-certified components, refer to the Product Certification link below this table.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 4: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

4 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

PanelView Plus 6 Terminals The PanelView Plus 6 terminals use modular components allowing for flexible configuration, installation, and upgrades. Factory-assembled terminals, with a display module (700, 1000, 1250, 1500) and logic module, are available as a single catalog number or as separate components for field installation. Optional communication modules can be ordered for additional network communication.

The field-replaceable 6.5, 10.4, 12.1, and 15.1-in. flat-panel color displays come with keypad, touch screen, or keypad/touch-screen input. Other display options are available to meet more stringent environmental conditions:

• High-bright display module for outdoor applications• Conformal-coated displays• Marine-certified displays• Displays with built-in antiglare overlays

The high-performance logic module runs the Windows CE 6.0 operating system allowing you to run HMI applications with the ability to also access the desktop. For users with more complex application requirements, the platform and logic module can be ordered with optional, extended features and file viewers.

For a complete listing of catalog number selections, refer to the Visualization Solutions Selection Guide, publication VIEW-SG001.

Table 3 - Logic Module Features

Features Description

High memory capacity 512 MB nonvolatile flash and 512 MB RAM

Power input AC or DC

Network interface For optional DH+, DH-485, or ControlNet communication module

Communication ports Ethernet, RS-232 serial

USB ports • 2 USB host ports for connecting a USB mouse, keyboard, printer, and USB flash drives that are hot swappable

• 1 USB device port for connecting a host personal computer

Secure Digital (SD) card slot Hot-swappable card slot supports 1784-CDx SD cards for transferring files, upgrading firmware, or logging data

Operating system All terminals run the Windows CE 6.0 operating system (OS) providing OS functionality needed for most users needs:• FTP server• VNC client/server• PDF reader• Active X controls• Third-party device support

Additional functionality is available by ordering terminals with optional, extended features:• Internet Explorer web browser• Remote desktop connection• Media player• Microsoft file viewers for PowerPoint, Excel, and Word• WordPad text editor• PDF reader

FactoryTalk View software • FactoryTalk View Machine Edition software, version 6.0 or later, is preloaded and activated on each terminal

• Single license support for FactoryTalk ViewPoint software, version 1.2 or later, gives remote users access to a terminal’s displays via standard web browser

• HMI applications are developed with FactoryTalk View Studio for Machine Edition software, which is purchased separately

Reset and Default Switches Provide easy access to diagnostic and repair operations.

OptionalExtended Features

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 5: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 5www.klinkmann.com6 / 2011

Technical Specifications - PanelView Plus 6 Terminals

Table 4 - Technical Specifications - PanelView Plus 6 Terminals

Attribute 700 Color(1)

2711P-K7C4Dx, 2711P-T7C4Dx, 2711P-B7C4Dx, 2711P-K7C4Ax, 2711P-T7C4Ax, 2711P-B7C4Ax

1000 Color(1)

2711P-K10C4Dx, 2711P-T10C4Dx, 2711P-B10C4Dx, 2711P-K10C4Ax, 2711P-T10C4Ax, 2711P-B10C4Ax

1250 Color(1)

2711P-K12C4Dx, 2711P-T12C4Dx, 2711P-B12C4Dx, 2711P-K12C4Ax, 2711P-T12C4Ax, 2711P-B12C4Ax

1500 Color(1)

2711P-K15C4Dx, 2711P-T15C4Dx, 2711P-B15C4Dx, 2711P-K15C4Ax, 2711P-T15C4Ax, 2711P-B15C4Ax

Operator input Keypad, Touch, or Key/Touch Keypad, Touch, or Key/Touch Keypad, Touch, or Key/Touch Keypad, Touch, or Key/Touch

Display type Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT

Display size 6.5 in. 10.4 in. 12.1 in. 15 in.

Display area (WxH) 132 x 99 mm (5.2 x 3.9 in.) 211 x 158 mm (8.3 x 6.2 in.) 246 x 184 mm (9.7 x 7.2 in.) 304 x 228 mm (12.0 x 9.0 in.)

Resolution 640 x 480, 18-bit color graphics 800 x 600, 18-bit color graphics 1024 x 768, 18-bit color graphics

Luminance 300 cd/m2 Nits 300 cd/m2 Nits(2)

Backlight 50,000 h life, min., field replaceableBacklight for 1250 high-bright display module is not replaceable

Touch screen 8-wire analog resistiveActuation: 1 million presses; operating force: 10…110 g

Keypad description Stainless-steel membraneNumeric, navigation, and function keysActuation: 1 million presses; operating force: 340 g

Keypad function keys 22 function keys F1…F10 and K1…K12

32 function keys F1…F16 and K1…K16

40 function keys F1…F20 and K1…K20

40 function keys F1…F20 and K1…K20

Real-time clock Battery-backed clock timestamps critical data, ±2 minutes per monthBattery life: 4 year min. @ 25 °C (77 °F)Field-replaceable: cat. no. 2711P-RY2032

Memory 512 MB nonvolatile flash and 512 MB RAM

External storage Secure Digital (SD) card, cat. no.1784-SDx, supported by hot-swappable SD card slotUSB flash drives supported by high-speed, hot-swappable, 2.0 USB host ports

Operating system Windows CE 6.0 operating system with or without extended features/file viewers

Software FactoryTalk View Machine Edition, version 6.0 or laterFactoryTalk ViewPoint, version 1.2 or later

Communication ports Ethernet (10/100 Mbps, Auto-MDI/MDI-X), RS-232, (2) USB host, (1) USB device Network interface for optional DH+/DH-485, or ControlNet (scheduled or unscheduled) communication module

Input voltage, DC 18…32V DC (24V DC nom)

Power consumption, DC 70 W max (2.9 A at 24V DC)

External power supply Cat. no. 2711P-RSACDIN, Class 2 or Safety Extra-Low Voltage (SELV) power supply for 700 to 1500 DC powered terminals; 85…264V AC, 120VA max

Input voltage, AC 85…264V AC, 47…63 Hz

Power consumption, AC 160VA max

Weight, approx.(3) Keypad: 1.8 kg (4.1 lb)Touch: 1.7 kg (3.7 lb)

Keypad: 2.8 kg (6.2 lb)Touch: 2.5 kg (5.6 lb)

Keypad: 3.4 kg (7.5 lb)Touch: 3.2 kg (7.0 lb)

Keypad: 4.5 kg (9.9 lb)Touch: 4.2 kg (9.2 lb)

Dimensions (HxWxD), approx. (3) Keypad: 193 x 290 x 55 mm7.58 x 11.40 x 2.18 in.

Touch: 179 x 246 x 55 mm7.04 x 9.68 x 2.18 in.

Keypad: 248 x 399 x 55 mm9.77 x 15.72 x 2.18 in.

Touch: 248 x 329 x 55 mm 9.77 x 12.97 x 2.18 in.

Keypad: 282 x 416 x 55 mm 11.12 x 16.36 x 2.18 in.Touch: 282 x 363 x 55 mm 11.12 x 14.30 x 2.18 in.

Keypad: 330 x 469 x 65 mm 12.97 x 18.46 x 2.55 in.Touch: 330 x 416 x 65 mm 12.97 x 16.37 x 2.55 in.

Cutout dimensions (HxWxD) Keypad: 167 x 264 mm6.57 x 10.39 in.

Touch: 154 x 220 mm6.08 x 8.67 in.

Keypad: 224 x 375 mm8.8 x 14.75 in.

Touch: 224 x 305 mm8.8 x 12.0 in.

Keypad: 257 x 390 mm10.11 x 15.35 in.

Touch: 257 x 338 mm10.11 x 13.29 in.

Keypad: 305 x 419 mm12.0 x 16.5 in.

Touch: 305 x 391 mm12.0 x 15.4 in.

(1) Replace x in catalog number with an 8 or 9. For catalog numbers ending in 9, the Windows CE operating system includes extended features and file viewers; catalog numbers ending in 8 do not support these features.

(2) The 1250 high-bright display module, cat. no. 2711P-RDT12H, for outdoor operations, has a luminance of 1000 cd/m2 Nits. The backlight is not replaceable.(3) Weights and dimensions do not include communication module. Add 95 g (0.21 lb) to the weight for a communication module.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 6: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

6 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Terminal Dimensions - PanelView Plus 6 Terminals

The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals. The 1000 keypad and touch terminal is shown for reference. Other models look similar.

b a

1000 Keypad

b a

1000 Touch

Table 5 - PanelView Plus 6 Terminal Dimensions

Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height

700 Keypad or Keypad/Touch 290 mm11.40 in.

193 mm7.58 in.

55 mm2.18 in.

83 mm3.27 in.

264 mm10.39 in.

167 mm6.59 in.

700 Touch 246 mm9.68 in.

179 mm7.04 in.

55 mm2.18 in.

83 mm3.27 in.

220 mm8.67 in.

154 mm6.08 in.

1000 Keypad or Keypad/Touch 399 mm15.72 in.

248 mm9.77 in.

55 mm2.18 in.

83 mm3.27 in.

375 mm14.75 in.

224 mm8.8 in.

1000 Touch 329 mm12.97 in.

248 mm9.77 in.

55 mm2.18 in.

83 mm3.27 in.

305 mm12.00 in.

224 mm8.8 in.

1250 Keypad or Keypad/Touch 416 mm16.36 in.

282 mm11.12 in.

55 mm2.18 in.

83 mm3.27 in.

390 mm15.35 in.

257 mm10.11 in.

1250 Touch 363 mm14.30 in.

282 mm11.12 in.

55 mm2.18 in.

83 mm3.27 in.

338 mm13.29 in.

257 mm10.11 in.

1250 High-bright Touch 363 mm14.30 in.

282 mm11.12 in.

74 mm2.9 in.

101 mm3.99 in.

338 mm13.29 in.

257 mm10.11 in.

1500 Keypad or Keypad/Touch 469 mm18.46 in.

330 mm12.97 in.

65 mm2.55 in.

93 mm3.65 in.

419 mm16.50 in.

305 mm12.00 in.

1500 Touch 416 mm16.37 in.

330 mm12.97 in.

65 mm2.55 in.

93 mm3.65 in.

391 mm15.40 in.

305 mm12.00 in.

(1) Dimension is from display to logic module.(2) Dimension is from display to communication module.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 7: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 7www.klinkmann.com6 / 2011

Accessories - PanelView Plus 6 Terminals

Tables 6…18 lists accessories for the PanelView Plus 6 platform.

Table 6 - Display Modules

Cat. No. Input Type Display Marine Certified

ConformalCoated

Built-inAntiglare Overlay

700 Model

2711P-RDK7C Keypad 7-in. color

2711P-RDK7CK Keypad •

2711P-RDT7C Touch

2711P-RDT7CK Touch •

2711P-RDT7CM Touch •

2711P-RDB7C Keypad/Touch

2711P-RDB7CK Keypad/Touch •

2711P-RDB7CM Keypad/Touch •

1000 Model

2711P-RDK10C Keypad 10-4 in. color

2711P-RDT10C Touch

2711P-RDT10CM Touch •

2711P-RDB10C Keypad/Touch

2711P-RDB10CM Keypad/Touch •

1250 Model

2711P-RDK12C Keypad 12.1-in. color

2711P-RDK12CK Keypad •

2711P-RDT12C Touch

2711P-RDT12CK Touch •

2711P-RDT12AG Touch •

2711P-RDT12H(1)

(1) This catalog number is a high-bright display module, indicated by the H at end of cat. no., that is designed for outdoor applications. The high-bright display module can only be used with DC-powered logic modules.

Touch

2711P-RDB12C Keypad/Touch

2711P-RDB12CK Keypad/Touch •

1500 Model

2711P-RDK15C Keypad 15-in. color

2711P-RDT15C Touch

2711P-RDT15AG Touch •

2711P-RDB15C Keypad/Touch

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 8: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

8 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Table 7 - Logic Modules

Cat. No. Power Input

Nonvolatile Flash/ RAM Memory Communication Conformal

Coated Included Software

Without Extended Features

2711P-RP8A AC 512 MB/512 MB • Ethernet• RS-232• Network interface for

communication module

• Windows CE 6.0 operating system without extended features/file viewers

• FactoryTalk View Machine Edition runtime, version 6.0 or later

• FactoryTalk ViewPoint, version 1.2 or later

2711P-RP8D DC 512 MB/512 MB

2711P-RP8DK DC 512 MB/512 MB •

With Extended Features

2711P-RP9A AC 512 MB/512 MB • Ethernet• RS-232• Network interface

communication module

• Windows CE 6.0 operating system with extended features/file viewers

• FactoryTalk View Machine Edition runtime, version 6.0 or later

• FactoryTalk ViewPoint, version 1.2 or later

2711P-RP9D DC 512 MB/512 MB

2711P-RP9DK DC 512 MB/512 MB •

Table 8 - Communication Modules

Cat. No.Communication Conformal

CoatedMarine CertifiedDH+ DH-485 ControlNet (1)

(1) Scheduled and unscheduled communication.

2711P-RN6 • •

2711P-RN6K • • •

2711P-RN15S • •

2711P-RN15SK • •

Table 9 - Secure Digital (SD) Cards

Cat. No. Description

1784-SD1 1 GB Secure Digital (SD) card

1784-SD2 2 GB Secure Digital (SD) card

2711C-RCSD USB to SD adapter for secure Digital card (SD)

Table 10 - Function Key Legend Inserts

Cat. No.PanelView Plus 6 Terminal Model(1)

(1) Applies to keypad and keypad/touch-screen terminals.

Includes

2711P-RFK7 700 keypad

Blank legend inserts and software

2711P-RFK10 1000 keypad

2711P-RFK12 1250 keypad

22711P-RFK15 1500 keypad

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 9: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 9www.klinkmann.com6 / 2011

Table 11 - Antiglare Overlays

Cat. No.(1)

(1) Three overlays are shipped with each catalog number.

PanelView Plus 6 Terminal Model

Operator Input

Keypad Touch Key/Touch

2711P-RGK7700

• •

2711P-RGT7 •

2711P-RGK101000

• •

2711P-RGT10 •

2711P-RGK121250

• •

2711P-RGT12 •

2711P-RGK151500

• •

2711P-RGT15 •

Table 12 - Solar Visor

Cat. No. Description

2711P-RVT12 Solar visor for 1250 high-bright display module, cat. no. 2711P-RDT12H

Table 13 - Mounting Hardware

Cat. No. Description Quantity

2711P-RTMC Mounting clips 8

Table 14 - Battery Replacement

Cat. No. Description Quantity

2711P-RY2032 Replacement battery 1

Table 15 - Power Supply and Power Terminal Blocks

Cat. No. Description Quantity

2711P-RSACDIN DIN-rail power supply, AC-to-DC, 85…265V AC, 47…63 Hz 1

2711P-RTBAC3 AC power terminal block 10

2711P-RTBDC2 2-pin DC power terminal block 10

Table 16 - Programming Cable

Cat. No. Description Length

2711C-CBL-UU02 USB host to USB device programming cable 2 m (6.5 ft)

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 10: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

10 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Table 17 - Backlight Replacements

Cat. No. PanelView Plus 6 Display Module Size Series Number of

Backlights

2711P-RL7C 700 A and B 1

2711P-RL7C2 C and D 1

2711P-RL10C 1000 A 1

2711P-RL10C2 B and C 1

2711P-RL12C 1250 A and B 2

2711P-RL12C2 C 1

2711P-RL15C 1500 B 2

Table 18 - Bezel Replacements

Cat. No. PanelView Plus 6 Terminal Model

Operator Input

Keypad Touch Key/Touch

2711P-RBK7

700

2711P-RBT7 •

2711P-RBB7 •

2711P-RBK10

1000

2711P-RBT10 •

2711P-RBB10 •

2711P-RBK12

1250

2711P-RBT12 •

2711P-RBT12H(1)

(1) Applies to the cat. no. 2711P-RDT12H 1250 high-bright display module.

2711P-RBB12 •

2711P-RBK15

1500

2711P-RBT15 •

2711P-RBB15 •

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 11: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 11www.klinkmann.com6 / 2011

PanelView Plus 400 and 600 Terminals

The PanelView Plus 400 and 600 terminals combine a 3.5 or 5.5-in. display, logic module, memory, and power (AC or DC) in the base unit. The terminals offer a range of display and input options:

• PanelView Plus 400 grayscale graphic displays with keypad input• PanelView Plus 400 color graphic displays with keypad or combination

keypad/touch-screen input• PanelView Plus 600 color or grayscale graphic displays with keypad, touch

screen, or combination keypad/touch-screen input

Two base units are available.

Other features include the following:• Unique mounting mechanism requiring a single die-cut and no special

tools for installation• Replaceable bezel ID labels for terminal or system identification• Function key legend kit and software for customizing the function key

legends of PanelView Plus 600 keypad terminals• Same panel cutouts as the PanelView Standard 550 terminals

Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation. Applications are created using FactoryTalk View Studio for Machine Edition software.

For a complete listing of catalog number selections, refer to the Visualization Solutions Selection Guide, publication VIEW-SG001.

Table 19 - Base-configured Terminals

Base Unit Contains

RS-232 unit This base unit contains the following:• RS-232 communication port• USB port connects to mouse, keyboard, printer, bar code

scanner and other devices.• CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication, the RS-232 port of this unit supports DF1, DH-485, and other multivendor PLC protocols.

Ethernet and RS-232 unit This base unit contains the following:• Ethernet port• RS-232 communication port• USB port connects to mouse, keyboard, printer, bar code

scanner and other devices.• CompactFlash slot for file transfers and data logging.• Network interface for optional communication modules

including DH-485, DH+, ControlNet, and isolated RS-232For distributed and complex applications requiring PLC communication, this unit can provide simultaneous communication with multiple networks.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 12: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

12 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Technical Specifications - PanelView Plus 400 and 600 Terminals

Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals

Attribute 400 Grayscale

2711P-K4M400 Color

2711P-K4C, -B4C600 Grayscale

2711P-K6M, -T6M, -B6M600 Color

2711P-K6C, -T6C, -B6C

Operator input Keypad Keypad or Keypad/Touch Keypad, Touch, or Key/Touch Keypad, Touch, or Key/Touch

Display type Grayscale passive-matrix FSTN

Color active-matrix TFT Grayscale passive-matrix FSTN

Color active-matrix TFT

Display size 3.8 in. 3.5 in. 5.5 in.

Display area (WxH) 78 x 59 mm (3.07 x 2.32 in.) 71 x 53 mm (2.8 x 2.1 in.) 111 x 84 mm (4.37 x 3.30 in.)

Resolution 320 x 240, 32-level gray 320 x 24018-bit color graphics

320 x 240, 32-level gray 320 x 24018-bit color graphics

Luminance 120 cd/m2 Nits 200 cd/m2 Nits 300 cd/m2 Nits 300 cd/m2 Nits

Backlight LED CCFL 50,000 h life, min.; not replaceable

Touch screen — Analog resistiveActuation: 1 million pressesOperating force: 10…110 g

Analog resistiveActuation: 1 million pressesOperating force: 10…110 g

Keypad description Poly-domed membraneNumeric, navigation, and function keysActuation: 1 million presses; operating force: 340 g

Stainless-steel membraneNumeric, navigation, and function keysActuation: 1 million presses; operating force: 340 g

Keypad function keys 8 function keys (F1…F8) 10 function keys (F1…F10)

Real-time clock Battery-backed clock timestamps critical data, ±2 minutes per month

Battery Not replaceable - Battery life: 5 year min. @ 25 °C (77 °F)

Memory 64 MB nonvolatile flash/64 MB RAM for bitmaps or recording data (not expandable); 20 MB for application storage

External storage 256 MB (cat. no. 2711P-RC3) or 512 MB (cat. no. 2711P-RC4) CompactFlash card

Software FactoryTalk View Studio for Machine Edition or Enterprise Series

Communication ports RS-232 and 1 USB or Ethernet, RS-232, and 1 USB plus optional DH-485, DH+, ControlNet(1), or Isolated RS-232 communication module

Input voltage, DC 18…30V DC (24V DC nom)

Power consumption, DC 25 W max (1.0 A at 24V DC)

External power supply Cat. no. 2711P-RSACDIN, Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals; 85…264V AC, 120VA max

Input voltage, AC 85…264V AC, 47…63 Hz

Power consumption, AC 60VA max

Weight, approx. Keypad: 562 g (1.24 lb)Touch: —

Keypad: 562 g (1.24 lb)Touch: —

Keypad: 930 g (2.05 lb)Touch: 789 g (1.74 lb)

Dimensions (HxWxD), approx. Keypad: 152 x 185 x 90 mm6.0 x 7.28 x 3.54 in.

Touch: —

Keypad: 152 x 185 x 90 mm6.0 x 7.28 x 3.54 in.

Touch: 152 x 185 x 90 mm6.0 x 7.28 x 3.54 in.

Keypad: 167 x 266 x 98 mm6.58 x 10.47 x 3.86 in.

Touch: 152 x 185 x 98 mm6.0 x 7.28 x 3.86 in.

Cutout dimensions (HxWxD) Keypad: 123 x 156 mm4.86 x 6.15 in.

Touch: —

Keypad: 123 x 156 mm4.86 x 6.15 in.

Touch: 123 x 156 mm4.86 x 6.15 in.

Keypad: 142 x 241 mm5.61 x 9.50 in.

Touch: 123 x 156 mm4.86 x 6.15 in.

(1) ControlNet network requires FactoryTalk View Machine Edition software, version 4.0 or later.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 13: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 13www.klinkmann.com6 / 2011

Terminal Dimensions - PanelView Plus 400 and 600 Terminals

The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals. The 600 touch, and keypad and touch terminal are shown for reference.

+

ba

600 Keypad Shown

ab

600 Touch Shown

Table 21 - PanelView Plus 400 and 600 Terminal Dimensions

Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height

400 Keypad 185 mm7.28 in.

152 mm6.00 in.

60 mm2.35 in.

90 mm3.54 in.

156 mm6.15 in.

123 mm4.86 in.

600 Keypad and Touch 266 mm10.57 in.

167 mm6.58 in.

68 mm2.68 in.

98 mm3.86 in.

241 mm9.50 in.

142 mm5.61 in.

600 Touch 185 mm7.28 in.

152 mm6.00 in.

68 mm2.68 in.

98 mm3.86 in.

156 mm6.15 in.

123 mm4.86 in.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 14: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

14 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Accessories - PanelView Plus 400 and 600 Terminals

Tables 22…27 lists accessories for the PanelView Plus 400 and 600 terminals.

Table 22 - Communication Modules

Cat. No.Communication

DH+ DH-485 ControlNet(1)

(1) Scheduled and unscheduled communication.

RS-232 Isolated

2711P-RN3 •

2711P-RN8 •

2711P-RN15C •

2711P-RN22C •

Table 23 - Antiglare Overlays

Cat. No.(1)

(1) Three overlays are shipped with each catalog number.

Terminal ModelInput Type

Keypad Touch Key/Touch

2711P-RGK4 400 Grayscale •

2711P-RGB4 400 Color • •

2711P-RGK6600 Grayscale or Color

• •

2711P-RGT6 •

Table 24 - CompactFlash Cards

Cat. No. Description

2711P-RC3 256 MB blank CompactFlash card

2711P-RC4 512 MB blank CompactFlash card

2711P-RCH CompactFlash to PCMCIA adapter

Table 25 - Power Terminal Blocks

Cat. No. Description Quantity

2711P-RVAC AC power terminal block 10

2711-TBDC DC power terminal block 10

Table 26 - Mounting Hardware

Cat. No. Description Quantity

2711P-RTFC Mounting levers 8

Table 27 - Function Key Legend Inserts

Cat. No. Terminal Model Includes

2711P-RFK6 600 keypad and keypad/touch Blank legend inserts and software

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 15: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 15www.klinkmann.com6 / 2011

PanelView Plus Compact Terminals

The PanelView Plus Compact 400, 600, and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application. These terminals are a subset of the PanelView Plus family with selective hardware and software functionality. They are the preferred HMI solution for many of the CompactLogix controllers.

These are the major features of the PanelView Plus Compact terminals:• Preferred HMI for CompactLogix controllers• RS-232 serial port, Ethernet port, USB port (two on 1000 model), DC

power input, and CompactFlash Type 1 slot• Serial and Ethernet communication only• Connection to a single controller by using either RSLinx Enterprise

software, version 5.20 or later, or KEPServer software• 25 displays and 200 alarm messages supported in the FactoryTalk View

Compact Machine Edition application and runtime software• Fixed hardware configurations without the addition or replacement of

modular components

For a complete listing of catalog number selections, refer to the Visualization Solutions Selection Guide, publication VIEW-SG001.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 16: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

16 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Technical Specifications - PanelView Plus Compact Terminals

Table 28 - Technical Specifications - PanelView Plus Compact Terminals

Attribute 400 Grayscale

2711PC-K4M20D400 Color

2711PC-B4C20D600 Grayscale

2711PC-T6M20D600 Color

2711PC-T6C20D1000 Color

2711PC-T10C4D1

Operator input Keypad Keypad/Touch Touch Touch Touch

Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT

Display size 3.8 in. 3.5 in. 5.5 in. 10.4 in.

Display area (WxH) 78 x 59 mm (3.07 x 2.32 in.) 71 x 53 mm (2.8 x 2.1 in.) 111 x 84 mm (4.37 x 3.30 in.) 211 x 158 mm (8.3 x 6.2 in.)

Resolution 320 x 240, 32-level gray 320 x 240, 18-bit color 320 x 240, 32-level gray 320 x 240, 18-bit color 640 x 480, 18-bit color

Luminance 120 cd/m2 Nits 200 cd/m2 Nits 300 cd/m2 Nits 300 cd/m2 Nits

Backlight LED CCFL 50,000 h life, min.Not replaceable

CCFL 50,000 h life, min., field replaceable

Touch screen — Analog resistive; actuation 1 million presses; operating force 10…110 g

Keypad description Poly-domed membraneNumeric, navigation, and function keysActuation: 1 million presses; operating force: 340 g

Stainless-steel membraneNumeric, navigation, and function keysActuation: 1 million presses; operating force: 340 g

Keypad function keys 8 function keys (F1…F8) — — —

Real-time clock Battery-backed clock timestamps critical data, ±2 minutes per month

Battery 5 year min. @ 25 °C (77 °F);Not replaceable

4 year min. @ 25 °C (77 °F)Replacement: 2711P-RY2032

Memory 64 MB nonvolatile flash/64 MB RAM, non-expandable20 MB for application storage

64 MB nonvolatile flash/64 MB RAM, non-expandable;25 MB for application storage

External storage 256 MB (cat. no. 2711P-RC3) or 512 MB (cat. no. 2711P-RC4) CompactFlash card

Software FactoryTalk View Studio for Machine Edition, version 5.1

Communication ports RS-232, Ethernet, 1 USB; no communication interface RS-232, Ethernet, 2 USB; no communication interface

Input voltage, DC 18…30V DC (24V DC nom) 18…32V DC (24V DC nom)

Power consumption, DC 25 W max (1.0 A at 24V DC) 70 W max (2.9 A at 24V DC)

External power supply Cat. no. 2711P-RSACDIN, Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals; 85…264V AC, 120VA max

Weight, approx. 562 g (1.24 lb) 562 g (1.24 lb) 789 g (1.74 lb) 2.6 kg (5.7 lb)

Dimensions (HxWxD), approx.

152 x 185 x 90 mm6.0 x 7.28 x 3.54 in.

152 x 185 x 90 mm6.0 x 7.28 x 3.54 in.

152 x 185 x 98 mm6.0 x 7.28 x 3.86 in.

248 x 329 x 55 mm9.77 x 12.97 x 2.18 in.

Cutout dimensions (HxWxD)

123 x 156 mm4.86 x 6.15 in.

123 x 156 mm4.86 x 6.15 in.

123 x 156 mm4.86 x 6.15 in.

224 x 305 mm8.8 x 12.0 in.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 17: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 17www.klinkmann.com6 / 2011

Accessories - PanelView Plus Compact Terminals

Tables 29…34 lists accessories for the PanelView Plus Compact terminals.

Table 29 - Antiglare Overlays

Cat. No.(1)

(1) Three overlays are shipped with each catalog number.

Terminal ModelOperator Input

Keypad Touch Key/Touch

2711P-RGK4 400 grayscale •

2711P-RGB4 400 color • •

2711P-RGT6 600 color grayscale •

2711P-RGT10 1000 color •

Table 30 - CompactFlash Cards

Cat. No. Description

2711P-RC3 256 MB blank CompactFlash card

2711P-RC4 512 MB blank CompactFlash card

2711P-RCH CompactFlash to PCMCIA Adapter

Table 31 - Backlight Replacement

Cat. No. Description

2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays

Table 32 - Bezel Replacements

Cat. No. Description

2711P-RBT10 Replacement bezel for the 1000 touch terminal

Table 33 - Mounting Hardware

Cat. No. Terminal Model Description Quantity

2711P-RTFC 400 and 600 Mounting levers 8

2711P-RTMC 1000 Mounting clips 8

Table 34 - Power Terminal Blocks

Cat. No. Terminal Model Description Quantity

2711-TBDC 400 and 600 DC power terminal block 10

2711P-RTBDC2 700 to 1500 series E or later

2-pin DC power terminal block 10

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 18: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

18 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

External Power Supply This SELV or PELV, 24V DC power supply can be used to power any of the

PanelView Plus terminals with a DC power input. This power supply provides

protection so that under normal and single fault conditions, the voltage

between conductors and earth ground does not exceed a safe value.

Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply

Attribute 2711P-RSACDIN

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold)IEC 60068-2-2 (Test Bd, Operating Dry Heat)IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…55 °C (32…131 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb, Unpackaged, Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5...95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

5 g at 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

ESD immunityIEC 61000-4-2

4 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 30…1000 MHz

EFT/B immunityIEC 61000-4-4

±2 kV at 5 kHz on power ports

Surge transient immunityIEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on AC power ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1kHz sine wave 80% AM from 150 kHz…80 MHz

Enclosure type rating None (open-style)

Power conductorsWire Size

Category

12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 °C (167 °F) or greater1.2 mm ((3/64 in.) insulation max1 (1)

(1) Use this conductor capacity information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 36 - Certifications - 2711P-RSACDIN Power Supply

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

2711P-RSACDIN

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E10314.UL Listed for Class, Division 2 Groups A, B, C, and D for US and Canada.

CE European Union 89/336/EEC EMC Directive, compliant with:• EN 61000-6-2; Industrial Immunity• EN 61326, Meas./Control/Lab., Industrial Requirements• EN 61000-6-4; Industrial EmissionsEuropean Union 73235/EEC Low Voltage Directive, compliant with:• EN 61131-2; Programmable Controllers

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS 2064, Industrial Emissions

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 19: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 19www.klinkmann.com6 / 2011

Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply

Attribute 2711P-RSACDIN

Input Specifications

Supply voltage, nom 120V AC, 47…63 Hz, 1.7 A max230V AC, 47…63 Hz, 1.1 A max

Voltage range 85…265V AC

Inrush current 40 A typical, 1 AC cycle at Vin 265V AC, 55 °C (131 °F)

Interruption Output voltage will stay within specification when input drops out for 1/2 cycle at 47 Hz, 85V AC with max load

Output Specifications

Output voltage, nom +24V DC SELV

Voltage range 20.4…27.6V DC, includes noise and 5% AC ripple

Inrush current 40 A typical, 1 AC cycle at Vin 265V AC, 55 °C (131 °F)

Minimum load 50 mA

Overvoltage protection Output internally limited to 35V DC. Cycle power to re-energize.

Overcurrent protection Current limit 3.2 A min (107% min)

Leakage current 0.5 mA rms max at rated input and output

Isolation voltage 2830V DC for 1 second

Table 38 - Dimensions - 2711P-RSACDIN Power Supply

Attribute 2711P-RSACDIN

Mounting Horizontal on a DIN railWall or panel mount with cat. no. 1794-NM1 panel mounting kit

Terminal screw torque 0.5…0.6 N•m (5…7 lb•in)

Dimensions (HxWxD), approx. 87 x 68 x 69 mm (3.4 x 2.7 x 2.7 in.)

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 20: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

20 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station.

Machine Edition Station runs projects developed with FactoryTalk View Studio. Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals.

You can import PanelView Standard/PanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard. The Import Wizard steps you through a few options such as scaling to a new screen resolution size, and then converts objects, text, tags, and communication configurations to ones that are available in Machine Edition.

FactoryTalk ViewPoint software, an add-on to FactoryTalk View Studio software, allows plant managers, production supervisors, system integrators, and other key stakeholders to view real-time plant floor operations remotely from a web browser. FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser. The remote user can also view displays that are not the active display of the terminal.

Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal. No additional software is required.

For a complete list of available HMI software, visit http://www.rockwellautomation.com/rockwellsoftware.

Table 39 - HMI Software for PanelView Plus Terminals

Cat. No, Description

9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications.

9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 21: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 21www.klinkmann.com6 / 2011

Software ComparisonTECHNOLOGY: Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32

Operating systems (32-bit) • Windows XP• Windows Server 2003• Windows Vista Business• Windows Server 2008

• Windows XP• Windows 7 Professional• Windows CE• Windows Vista Home Basic/Vista Business• Windows Server 2003/2008

• Windows XP/2000/NT/9x/• Windows Server 2003

Embedded platforms ✔

Windows domain security ✔ ✔ ✔

OPC/ActiveX ✔ ✔ ✔

FactoryTalk enabled ✔ ✔ ✔

Server-side VBA ✔

Client-side VBA ✔

ARCHITECTURE: Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32

Primary application Supervisory level: single-station or multiple-server, multiple-client

Machine level: single-station Supervisory level; single station or single server, multiple client

Tag-based HMI ✔ ✔ • Windows XP/2000/NT/9x/• Windows Server 2003

Direct referencing ✔ ✔

Network (Distributed) Local

Max number of servers/clients 10/50 1/20

FactoryTalk ViewPoint ✔ ✔ ✔ (1) ✔

RSView32 web server ✔

Thin clients (terminal services) ✔ ✔

Multi-user development ✔

Remote configuration at runtime ✔

Redundancy - data server ✔

Redundancy - HMI server ✔ Active display

(1) Supported only on PanelView Plus terminals.

FEATURES: Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32

Animation - visibility, color, fill, horizontal and vertical position, width, height, rotation, horizontal and vertical slider, and more

And touch And touch And touch

Alarms • Tag-based and device-based • Digital and analog• Definable alarm severities• Alarm log

• State-based (from controller)• Alarm log

• Tag-based• Digital and analog• Definable alarm severities• Alarm log

Data logging • 20 data log models per project• Each with up to 10,000 tags• Log to ODBC or proprietary database

• 1 data log model per project• With up to 100 tags• 300K records max• Export to dbf

• 20 plus data log models per project• Each with up to 10,000 tags• Log to ODBC or proprietary database

Trending TrendX 4.0 TrendX 4.0 subset TrendX 3.1 and native

Security • Security assigned to tags, graphic displays, macros, commands, OLE objects

• Local or Windows security

• Display-based• Local or Windows security

• Security assigned to tags, graphic displays, macros, commands, OLE objects

• Local or Windows security

Other features • Test run macros• Derived tags • Event detector

• Test run macros• Derived tags

• Test run macros• Derived tags • Event detector

Pricing model • Display-based pricing • Multiple levels

• Included with PanelView Plus or display-based pricing

• Multiple levels for FactoryTalk View ME Station

• Tag-based pricing• Multiple levels

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 22: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

22 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Software Selection

FactoryTalk View Studio for Machine Edition software is configuration

software for developing and testing machine level HMI applications. It

includes RSLinx Enterprise and KEPServer Enterprise.

FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional, XP/Vista Home Basic/Vista Business/Windows Server 2003/2008 operating system including the industrial computers. FactoryTalk View ME Station is included with all PanelView Plus terminals.

FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio

software, allowing casual users to view real-time plant floor operations

remotely from a web browser. FactoryTalk ViewPoint server and a single client

access license is included with the purchase of a PanelView Plus terminal. No

other catalog numbers are required to use FactoryTalk ViewPoint software

with PanelView Plus terminals.

Table 40 - FactoryTalk View Machine Edition (ME) Software

Cat. No.(1)

(1) Order localized versions of the software by replacing EN in the catalog number with DE for German, FR for French, JP for Japanese, or ZH for Chinese.

Description

9701-VWSTMENE FactoryTalk View Studio Machine Edition

Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime

Cat. No.(1)

(1) Order localized versions of the software by replacing EN in the catalog number with DE for German, FR for French, JP for Japanese, or ZH for Chinese.

Description

9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays

9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays

9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays

9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable, 9-pin D Shell to 8-pin Mini DIN

Table 42 - FactoryTalk ViewPoint Software

Cat. No.(1)

(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications.

Description

9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)

9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)

9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)

9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)

9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)

9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 23: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 23www.klinkmann.com6 / 2011

Communication Cables The table provides a general list of cables used by the PanelView Plus terminals. All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal.

PanelView Plus Runtime CablesTables 44…47 list required runtime cables for PanelView Plus 400/600 and PanelView Plus 6 (700, 1000, 1250, 1500) terminals.

Table 43 - Cables

Cat. No. Description Length

2711C-CBL-UU02(1)

(1) This cable is used only by PanelView Plus 6 terminals.

USB host to USB device programming cable 2 m (6.5 ft)

2711-NC13 RS-232 operating/program cable, 9-pin D-shell to 9-pin D-shell 5 m (16.4 ft)

2711-NC14 RS-232 operating/program cable, 9-pin D-shell to 9-pin D-shell 10 m (32.7 ft)

2711-NC17 Remote RS-232 cable assembly, 9-pin D-shell to 9-pin D-shell 3 m (10 ft)

2711-NC21 RS-232 operating cable, 9-pin D-shell to 8-pin mini DIN 5 m (16.4 ft)

2711-NC22 RS-232 operating cable, 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)

1761-CBL-AS03DH-485 network cable, 6-pin Phoenix to RJ45

3 m (10 ft)

1761-CBL-AS09 9 m (30 ft)

2711P-CBL-EX04 Ethernet CAT5 crossover cable 4.3 m (14 ft)

Table 44 - Runtime Communication Cables: PanelView Plus Terminals to SLC Controllers

Protocol PanelView Plus Comm Port400, 600, 700, 1000, 1250, 1500

SLC 500, 5/01, 5/02CH1 RJ45 (DH-485)

SLC 5/03, 5/04, 5/05CH0 (9-pin RS-232)

(DF1 or DH-485)

SLC 5/03CH1 (RJ45)

(DH-485)SLC 5/04

CH1 (DH+)SLC 5/05

CH1 (ENET)

DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)

— 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

— — —

DH-485

RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)

Use AIC+ module(1761-NET-AIC)

to connect to port 1 or 2

2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

Use AIC+ Module(1761-NET-AIC)

to connect to port 1 or 2— —

DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)

1747-C10 (2 m/6 ft) 1747-C11 (0.3 m/1 ft)1747-C20 (6 m/20 ft)

Use AIC+ module(1761-NET-AIC)

to connect to port 3

1747-C10 (2 m/6 ft) 1747-C11 (0.3 m/1 ft)1747-C20 (6 m/20 ft)

— —

DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6, -RN6K

1761-CBL-AS03 (3 m/10 ft)

1761-CBL-AS09 (9 m/30 ft)

Use AIC+ module(1761-NET-AIC)

to connect to Port 3

1761-CBL-AS03 (3 m/10 ft)

1761-CBL-AS09 (9 m/30 ft)

— —

ControlNet

ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S, -RN15SK

— — — — —

EtherNet/IP EtherNet/IP portPanelView Plus 400 to 1500

— Use 1761-NET-ENI modulewith Ethernet cable

— —1585J-M type cable or

2711P-CBL-EX04 (4 m/14 ft) (2)

DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6, -RN6K

— ——

shieldedtwinaxial

cable (1770-CD)

(1) For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).(2) EtherNet/IP direct connection from the terminal to an SLC 5/05 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 24: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

24 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Table 45 - Runtime Communication Cables: PanelView Plus Terminals to PLC-5 and MicroLogix Controllers

Protocol PanelView Plus Comm Port400, 600, 700, 1000, 1250, 1500

PLC-5, PLC-5C, PLC-5ECH0 (25-pin RS-232)

(DF1)

MicroLogix 1400, 1500LRPCH1/CH2 (9-pin RS-232)

(DF1 or DH-485)

MicroLogix 1000, 1100, 1200, 1400, 1500LSP

CH0 (8-pin Mini DIN)(DF1 or DH-485)

MicroLogix 1100, 1400 Ethernet

DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)

2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

(9-to-25 pin adapter required)

2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

2711-NC21 (5 m/16 ft)2711-NC22 (15 m/49 ft) (3)

DH-485

RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)

— 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

2711-NC21 (5 m/16 ft)2711-NC22 (15 m/49 ft)

DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)

PanelView Plus 700 to 1500Requires 2711P-RN6, -RN6K

— —Use AIC+ module(1761-NET-AIC)

to connect to Port 3—

ControlNet

ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S, -RN15SK

To PLC-5C with ControlNet cable

— — —

EtherNet/IPEtherNet/IP portPanelView Plus 400 to 1500

To PLC-5E with1585J-M type cable or

2711P- CBL-EX04 (4 m/14 ft) (2)

Use 1761-NET-ENI modulewith Ethernet cable

1585J-M type cable or 2711P- CBL-EX04 (4 m/14 ft) (2)

DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6, -RN6K

shielded twinaxial cable(1770-CD)

— — —

(1) For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable.(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply.

Table 46 - Runtime Communication Cables: PanelView Plus Terminals to Logix Controllers

Protocol PanelView Plus Comm Port400, 600, 700, 1000, 1250, 1500

ControlLogixCH0 (9-pin RS-232)

(DF1)

CompactLogixCH0 (9-pin RS-232)

(DF1 or DH-485)

DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)

2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)2706-NC13 (3 m/10 ft)

DH-485

RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)

— 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)2706-NC13 (3 m/10 ft)

DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)

PanelView Plus 700 to 1500 requires 2711P-RN6, -RN6K—

Use AIC+ module(1761-NET-AIC)

to connect to port 3

ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S, -RN15SK

Use 1756-CNB module with ControlNet cable1769-L35CR, 1769-L32C, 1768-CNB, or 1768-CNBR

with ControlNet cable

EtherNet/IPEtherNet/IP portPanelView Plus 400 to 1500

Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or

2711P- CBL-EX04 (4 m/14 ft)(2)

To 1769-L35E, 1769-L23E, 1769-L32E, or 1768-ENBT module with 1585J-M type cable

or 2711P- CBL-EX04 (4 m/14 ft)(2)

DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6, -RN6K

Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) —

(1) For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).(2) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 25: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 25www.klinkmann.com6 / 2011

PanelView Plus Compact Runtime Cables

Tables 48…51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations.

Table 47 - Runtime Communication Cables: PanelView Plus Terminals to Interface Modules

Protocol PanelView Plus Comm Port400, 600, 700, 1000, 1250, 1500 1747-AIC

1761-NET-AIC 1771-NET-ENI

Port 1 (9-pin) Port 2(8-pin Mini DIN)

Port 3(DH-485)

Port 2(8-pin Mini DIN)

DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)

— 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

2711-NC21 (5 m/16 ft)2711-NC22 (15 m/49 ft)

Null modem required—

1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)

2711-CBL-PM10 (10 m)

DH-485

RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)

— 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

2711-NC21 (5 m/16 ft)2711-NC22 (15 m/49 ft)

Null modem required—

DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)

1747-C10 (2 m/6ft) 1747-C11 (0.3 m/1 ft)1747-C20 (6 m/20 ft)

— — 1761-CBL-AS03 (3 m/10 ft)1761-CBL-AS09 (9 m/30 ft)

to single AIC+

DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6, -RN6K

Direct connection to single AIC with

Belden 9842 cable(2)— —

Direct connection to single AIC+ with

Belden 9842 cable(2)—

(1) For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution.

Table 48 - Runtime Communication Cables: PanelView Plus Compact Terminals to SLC Controllers

Protocol PanelView Plus Compact400, 600, 1000 Comm Port

SLC-500, 5/01, 5/02CH1 RJ45 (DH-485)

SLC-5/03, 5/04, 5/05CH0 (9-pin RS-232)

(DF1 or DH-485)

SLC 5/03CH1 (RJ45)

(DH-485)SLC 5/04

CH1 (DH+)SLC 5/05

CH1 (ENET)

DF1 RS-232 (DF1) Comm port (9-pin) — 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft) —

— —

DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)

to connect to port 1 or 2

2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

Use AIC+ module(1761-NET-AIC)

to connect to port 1 or 2— —

EtherNet/IP EtherNet/IP Comm port — Use 1761-NET-ENI modulewith Ethernet cable — — 2711P- CBL-EX04 Ethernet

crossover cable (1)

(1) An EtherNet/IP direction connection between a PanelView Plus Compact terminal and an SLC 5/05 requires hub or crossover cable listed.

Table 49 - Runtime Communication Cables: PanelView Plus Compact Terminals to MicroLogix Controllers

Protocol PanelView Plus Compact400, 600, 1000 Comm Port

MicroLogix 1500LRPCH1 (9-pin RS-232)

(DF1 or DH-485)

MicroLogix 1000, 1200, 1500LSPCH0 (8-pin Mini DIN)

(DF1 or DH-485)MicroLogix 1100, 1400

Ethernet Port

DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft) (1) —

DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft) (1) —

EtherNet/IP EtherNet/IP Comm portUse 1761-NET-ENI module

with Ethernet cable1585J-M type cable or

2711P-CBL-EX04 cable (4 m/14 ft)(2)

(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply.(2) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 26: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

26 PanelView Plus Specificationswww.klinkmann.com

6 / 2011

Table 50 - Runtime Communication Cables: PanelView Plus Compact to Logix Controllers

Protocol PanelView Plus Compact400, 600, 1000 Comm Port

ControlLogixCH0 (9-pin RS-232)

(DF1)

CompactLogixCH0 (9-pin RS-232)

(DF1 or DH-485)

DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

DH-485 RS-232 (DH-485) Comm port (9-pin) — 2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

EtherNet/IP EtherNet/IP Comm portUse 1756-EN2T or 1756-ENBT module

with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m/14 ft)(1)

To 1769-L35E, L23E, L32E with1585J-M type cable or

2711P-CBL-EX04 cable (4 m/14 ft)(1)

(1) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.

Table 51 - Runtime Communication Cables: PanelView Plus Compact to Network Modules

Protocol PanelView Plus Compact400, 600, 1000 Comm Port

1761-NET-AIC

Port 1 (9-pin) Port 28-pin Mini DIN

Port 3(DH-485)

DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

2711-NC21 (5 m/16 ft)2711-NC22 (15 m/49 ft)

DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m/16 ft)2711-NC14 (10 m/32 ft)

2711-NC21 (5 m/16 ft)2711-NC22 (15 m/49 ft) —

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 27: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

PanelView Plus Specifications 27www.klinkmann.com6 / 2011

Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals. When migrating to a new platform, consider both the display size and the unit size. PanelView Plus terminals uses the same panel cutouts as existing PanelView products, yet offer a larger display. For instance, a PanelView Plus 6, 1250 terminal with a 12.1-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 10.4-inch display. When choosing a terminal with the same display size, adapter plates are used to adapt the cutout of the new terminal.

Table 52 - PanelView Plus Replacement Terminals

PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required

Adapter Plate Cat. No.

PanelView Standard 300 or 300 Micro None available(1) — —

PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypad/touchPanelView Plus or PanelView Plus Compact 600 touch No —

PanelView 550 keypadPanelView 550 keypad/touch

PanelView Plus 600 keypad or keypad/touch No —

PanelView Plus PanelView Plus Compact 400 keypad or keypad/touchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4

PanelView 600 keypadPanelView 600 keypad/touch

PanelView Plus 600 keypad or keypad/touch Yes 2711P-RAK6

PanelView Plus 6, 700 keypad or keypad/touch No —

PanelView 900 keypadPanelView Plus 6, 700 keypad or keypad/touch Yes 2711P-RAK7

PanelView Plus 6, 1000 keypad or keypad/touch No —

PanelView 900 touchPanelView Plus 6, 700 touch Yes 2711P-RAT7

PanelView Plus 6 or PanelView Plus Compact 1000 touch No —

PanelView 1000 keypadPanelView Plus 6, 1000 keypad or keypad/touch Yes 2711P-RAK10

PanelView Plus 6, 1250 keypad or keypad/touch No —

PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10

PanelView Plus 6, 1250 touch No —

PanelView 1400 keypadPanelView Plus 6, 1250 keypad or keypad/touch Yes 2711P-RAK12S

PanelView Plus 6, 1500 keypad or keypad/touch No —

PanelView1400e keypadPanelView Plus 6, 1500 keypad or keypad/touch(2) Yes 2711P-RAK15

None available — —

PanelView 1400 touch PanelView Plus 6, 1250 touch Yes 2711P-RAT12S

PanelView Plus 6, 1500 touch No —

PanelView 1400e touchPanelView Plus 6,1500 touch(2) Yes 2711P-RAT15

None available — —

PanelView 1200, 1200e/1400e Keypad PanelView Plus 6,1250 keypad(2) Yes RAK12E

None available — —

PanelView 1200, 1200e Touch PanelView Plus 6,1250 touch(3) Yes RAT12E

None available — —

PanelView 1200/1200E touch PanelView Plus 6,1250 touch(3) Yes 2711P-RAT12E2

None available — —

(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout.(2) Adapter plate required for stud-mounted terminals.(3) Requires modification of panel cutout.

Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010

Page 28: PanelView Plus Specifications - Klinkmannmedia.klinkmann.fi/...Interface_PanelView_Plus_Specifications_Tech...Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010 2 PanelView

28 PanelView Plus Specifications

611.pdf

Rigatel. +klink

.ua

Additional Resources These documents contain additional information concerning related Rockwell Automation products.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

Resource Description

Visualization Solutions Selection Guide, publication VIEW-SG001

Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation.

PanelView 6 Terminals User Manual, publication 2711P-UM006

Provides information on how to install, configure, operate, and troubleshoot the PanelView Plus 6 (700 to 1500) terminals.

PanelView Plus 6 Terminals Installation Instructions, publication 2711P-IN029

Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel.

PanelView Plus Compact Terminals User Manual, publication 2711PC-UM001

Provides information on how to install, configure, operate, and troubleshoot the PanelView Plus Compact terminals.

PanelView Plus Terminals User Manual, publication 2711P-UM001

Provides information on how to install, configure, operate, and troubleshoot the PanelView Plus 400 and 600 terminals.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com

Provides declarations of conformity, certificates, and other certification details.

Publication 2711P-TD005A-EN-P - November 2010 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Rockwell_Operator_Interface_PanelView_Plus_Specifications_Tech_Data_en_0

Samaratel. +7 846 273 95 [email protected]

Yekaterinburgtel. +7 343 376 [email protected]

St. Petersburgtel. +7 812 327 [email protected]

Moscowtel. +7 495 641 [email protected]

Helsinkitel. +358 9 540 [email protected]

Vilnius МinskTallinn

Кievtel. +38 044 495 33 [email protected]

www.klinkmann.com

tel. +370 5 215 [email protected]

371 6738 [email protected]

tel. +375 17 200 [email protected]

tel. +372 668 [email protected]