page 1 sapphire fab condition room temp 21~25 ℃ ; △≦ ±1 ℃ /h humidity have to below: 80%...
TRANSCRIPT
Page 1
Sapphire
Fab condition Room temp 21~25 ℃ ; △≦ ±1 /h℃ Humidity have to below: 80%
Cooling system confirmed the first lay-out 12 tools assy main piping stainless ; sub-piping stainless Inlet 26~30 ;outlet 32~36 ; T℃ ℃ △ =~ 6 (max=40 )℃ ℃ Flow rate = 10m3/h; 3.5 bar
Power system confirmed the first lay-out 12 tools assy for local power cabinet 3 tools for one group and AVR is need Power cable tray is need
Layout status stilling on going To split management and engineering office Labby and show room lay-out Fab entrance room lay-out Fab window glass is need 3 rooms for CEO/GM/VP
Facility FDMS facility design management system final confirming
Air condition Broken repair one tool; PM one tool and total max capacity is 300T
Page 2
Sapphire
1. 原則上以能控制恆溫恆濕且無持續微塵污染源即可。2. 潔淨室溫度設計<製程冷卻水。至少 1℃ 以上為避免冷凝水損害機台。3. 溫度設計實例 : 濕度需低於 80% ,△≦ ±1%/h 。
4. 單一機台供電 :3P4W380V(+3-1%)60Hz 需建置穩壓系統; R_Gnd 4≦ Ω 獨立接地 。5. 規劃 12 台設置容量, 8/E 兩台, 9/E 三台,含二次側。6. 單一機台用電 :280/280/20A; max=90kw; avg=75kw 。 ( 需三台一組已達相位平衡 )7. 每台機台約有 15kw 的能量散失 ( 變壓器 ) ,需要考量潔淨室空調或加裝 exhaust 排風。8. 製程冷卻水單一流量 10 m3/h(167LPM) inlet:26~29 ( ±1/h; T=6 ) ℃ △≦ △ ℃9. Gas system: Ar purity: 99.99% centre supply( 鋼瓶供氣 ) 。10.exhaust system: 一般排。
潔淨室條件 vs 機台主要需求
Grower (outlet water <40℃)water flow/h
inlet water
outlet eater
room temp
10m3 21 27 20℃5m3 21 33 20℃3.5m3 21 39 20℃10m3 26 32 25℃5m3 26 38 25℃
Page 3
Sapphireby pass line
Design Concept of Cooling Water System
Tank 2
10 tones
Chiller- 20cm tilt- 5cm distance between
growers- Valve close 2.6 bar- Valve open 1.5 bar- One production line have 12
tools
Tank 1
20 tones
EMO CT in
PumpNeed UPS
10m^3/hour
Heat Exchanger
Pump
at least 50cm lower than pipe
At least 4m higher than growers
△ ≦±1 /h; ℃T=6△ ℃
- Pipes and Tanks must be made of stainless steel or plastic that capable to withstand 4~6 bars and temperature up to 100 centigrade.
- Cooling water have to higher than room temp 1℃- ΔT≤+-1 /h℃- Add filter is need- Max temp below 40 ℃
S12.6bar35 ℃
S22.6bar30 ℃
S41.2bar33 ℃
S31.3bar28 ℃
by pass line
Manual valve control pressure
4 bar
To city Water exhaust
1. HH/LL sensor2. Leak sensor3. Over flow design
Funnel10 line
冰機冷卻水
製程冷卻水
1. HH/LL sensor2. Leak sensor3. Over flow design
Funnel10 line
CT refill
DI refill
EMO CT out
Page 4
Sapphire
1. 15s mean to next 15s mean vibration 1 mv≦2. Max vibration in 15s < 4 mv3. Gnd < 4 Ω4. 8~10 V must stable and control limit < 1mv5. Water out have to less then 40 else water vapper ℃6. 12 set Grower power : 12*90=1080 kw7. Chiller = Take out thermal energy = 1080*1.25=1350 kw8. A group for 3 tools9. 3P4W400~420Vac(min376V)
Design Concept of Power System
Heater
thyristor
380V ACSpec: 415~376V
380V ACSpec: 0~380V
376V ACSpec: 0~376V
12V ACSpec: 0~12V
10V ACSpec: 0~10V
Growercontroller
3P; 4w 380V
穩壓器
Grower 1
Grower 2
Grower 3
R_Gnd 4≦ Ω; 機台需獨立接地
Page 5
Sapphire
1. Inside grower max power 75kw2. Outside grower 15kw lost by WATT power meter3. Cooling water by manual measurement by weight is 9.9 m3/h4. Total power= 75kwX3600s=270x10E6 (J)5. Total bring out thermal energy by cooling water is C x weight x T=4200x6x9900=249x10E6 (J)△6. 12 set tool =249x10E6x12set=2988x10E6(J)= 717.12x10E6 (cal)(1J=0.24cal)7. Total water cooling by grower= 237.14USRT(1USRT=3024kcal)8. Total air condition cooling by grower= 15kwx3600x12=648x10E6(J) = 155.52x10E3 k.cal=51.48USRT 9. Suitable condition by
Conclusion:
Grower (outlet water <40℃)water flow/h
inlet water
outlet eater
room temp
10m3 21 27 20℃5m3 21 33 20℃3.5m3 21 39 20℃10m3 26 32 25℃5m3 26 38 25℃
Grower (outlet water <40℃)water flow/h
inlet water
outlet eater
room temp
10m3 21 27 20℃5m3 21 33 20℃3.5m3 21 39 20℃10m3 26 32 25℃5m3 26 38 25℃