Correlating Committee Note No. 4-NFPA 101-2016 [ Global Input ] Submitter Information Verification Submitter Full Name: SAF-AAC Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 08 07:40:31 EST 2016 Committee Statement Committee Statement: The Correlating Committee notes, in response to the Affirmative with Comment ballot of Tierney, that the numerous paragraphs that he referenced have been revised to use the term “delayed egress electrically locking systems” but not to use his suggested term of “delayed egress electrical locking systems.” Further, the Correlating Committee directs the TC on Means of Egress (MEA) to consider the Affirmative with Comment ballot of Tierney so as to change the term “delayed egress electrically locking systems” to “delayed egress electrical locking systems” throughout the code. This action will be considered as a public comment. First Revision No. 5041-NFPA 101-2015 [Global Input] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 46 1/29/2016 4:05 PM Page 1 of 46

Upload: others

Post on 27-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 4-NFPA 101-2016 [ Global Input ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 07:40:31 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Affirmative with Comment ballot of Tierney, that the numerousparagraphs that he referenced have been revised to use the term “delayed egress electrically locking systems” but not to usehis suggested term of “delayed egress electrical locking systems.”

Further, the Correlating Committee directs the TC on Means of Egress (MEA) to consider the Affirmative with Comment ballotof Tierney so as to change the term “delayed egress electrically locking systems” to “delayed egress electrical lockingsystems” throughout the code.

This action will be considered as a public comment.

First Revision No. 5041-NFPA 101-2015 [Global Input]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 46 1/29/2016 4:05 PM

Page 1 of 46

Page 2: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 1-NFPA 101-2016 [ Section No. 3.3.56 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 07:22:45 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Means of Egress (MEA) to consider the Affirmative with Comment ballots ofPappas and Tierney to revise the definition by combining the two sentences to read as follows:

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.(SAF-MEA)

This action will be considered as a public comment.

FR-5009-NFPA 101-2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 46 1/29/2016 4:05 PM

Page 2 of 46

Page 3: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 46-NFPA 101-2016 [ Section No. 3.3.196.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 08:19:42 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Affirmative with Comment ballot of Gencarelli, the change beingmade by the FR is to the annex text, not to the definition of ambulatory health care occupancy.

FR-3501-NFPA 101-2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 46 1/29/2016 4:05 PM

Page 3 of 46

Page 4: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 2-NFPA 101-2016 [ Section No. 4.2.3 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 07:27:45 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on fundamentals (FUN) to revise the reference embedded within 4.2.3 from“4.1.4” to “4.1.3”.

This action will be considered as a public comment.

FR-3023-NFPA 101-2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 46 1/29/2016 4:05 PM

Page 4 of 46

Page 5: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 45-NFPA 101-2016 [ New Section after 7.2.1.5.3 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:51:19 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the occupancy committees (AXM, BCF, DET, END, RES, MER, IND, HEA) to reviewthe additional door locking allowances that are being proposed in FCR-6.

This action will be considered as a public comment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 46 1/29/2016 4:05 PM

Page 5 of 46

Page 6: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 44-NFPA 101-2016 [ New Section after 7.2.1.5.10.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:49:39 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Committee Statement, that two FCRs have been developed toaddress the request of the committee statement.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 46 1/29/2016 4:05 PM

Page 6 of 46

Page 7: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 7-NFPA 101-2016 [ Section No. 7.2.1.6.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 07:57:52 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Means of Egress (MEA) to consider the Affirmative with Comment ballot ofTierney to revise the term “delayed egress electrically locking systems” to “delayed egress electrical locking systems” andmake consistent use of the term.

This action will be considered as a public comment.

First Revision No. 5029-NFPA 101-2015 [Section No. 7.2.1.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 46 1/29/2016 4:05 PM

Page 7 of 46

Page 8: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:00:13 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Negative ballot of Frable, that the TC on Means of Egress (MEA) wasprovided with copies of all applicable BHMA standards via a November 3, 2015 e-mail and posting to the NFPA 101 documentinformation page, immediately following the November 2 opening of the committee balloting process.

First Revision No. 5030-NFPA 101-2015 [Section No. 7.2.1.9.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 46 1/29/2016 4:05 PM

Page 8 of 46

Page 9: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 9-NFPA 101-2016 [ Section No. 7.2.3.9 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:02:43 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Means of Egress (MEA) to correct the metric value in 7.2.3.9.4(2) from “(5mm)” to “(51 mm)”.

This action will be considered as a public comment.

First Revision No. 5032-NFPA 101-2015 [Section No. 7.2.3.9]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 46 1/29/2016 4:05 PM

Page 9 of 46

Page 10: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 10-NFPA 101-2016 [ New Section after 8.2.2.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:03:55 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to revise terminology in 8.2.2.5(4) from “fire-resistive rating” to “fire resistance rating”.

This action will be considered as a public comment.

First Revision No. 2501-NFPA 101-2015 [New Section after 8.2.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 46 1/29/2016 4:05 PM

Page 10 of 46

Page 11: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 47-NFPA 101-2016 [ Sections 8.3.3, 8.3.4, 8.3.5, 8.3.6 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 08:21:09 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to do the following:

1. Change the text within 8.3.3.2.2 from “the fire protection rating for opening protectives…” to “the fire rating for openingprotectives…” for correlation with the title of Table 8.3.3.2.2 (First Draft report numbering) as the table addresses both fireprotection ratings and fire resistance ratings.

2. Consider the Negative ballot of Klein relative to the inconsistency being created in Table 8.3.3.2.2 by requiring a smokepartition with 1-hr fire resistance rating to have 1-hr fire protection-rated opening protectives but continuing to allow a smokebarrier with 1-hr fire resistance rating to have 1/3-hr fire protection-rated opening protectives.

3. Consider the Negative ballot of Koffel relative to applicability of annex text (see, for example, A.8.3.3.3.4, A.8.3.3.5.3 andA.8.3.3.6.6) as not all opening protectives in a fire barrier are tested to limit smoke spread. Split annex text as appropriate sothat it is tied to the applicable code requirement.

4. Revise 8.3.3.3.5, relative to fire doors not exceeding size requirements of NFPA 80, to delete the words “except as modifiedby Chapter 7” unless it can be documented that Chapter 7 permits larger fire doors.

5. Revise 8.8 Inspection and Testing of Door Assemblies so the embedded reference is changed from “8.3.3.10” to “8.3.3.3.1”.

6. Within Table 8.3.3.2.2, the section on “fire barriers” within the table should be relocated to the beginning of the table or theend of the table to clarify that it addresses fire barriers as otherwise not addressed within the table. The term “other firebarriers” is suggested.

These actions will be considered as a public comment.

First Revision No. 6502-NFPA 101-2015 [Sections 8.3.3, 8.3.4, 8.3.5, 8.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 46 1/29/2016 4:05 PM

Page 11 of 46

Page 12: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 48-NFPA 101-2016 [ Section No. 8.3.6 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 12:45:01 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to consider exempting existing fire barriers fromthis new requirement. The provision of 8.3.5.1.2 (First Draft Report numbering) exempts approved existing materials andmethods of construction used to protect existing joints, but the AHJ might not approve an existing installation which is notcompliant with the new requirement of 8.3.5.3. Where is the substantiation to justify retroactive application of this newrequirement? This Correlating Committee recommendation is made, in part, in response to the Negative ballot of Humblerelative to 1/2-hour fire resistance-rated barriers. The Code utilizes 1/2-hour barriers for existing installations. This CN is relatedto FR 6503.

This action will be considered as a public comment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 46 1/29/2016 4:05 PM

Page 12 of 46

Page 13: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 11-NFPA 101-2016 [ New Section after 8.4.3.5 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:09:22 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to consider the Affirmative with Comment ballotof Koffel and the Abstention ballot of McHugh to revise the text to capture what the smoke detector installation is toaccomplish, similar to that which is currently done for door operation in 7.2.1.9.2(4).

This action will be considered as a public comment.

First Revision No. 2503-NFPA 101-2015 [New Section after 8.4.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 46 1/29/2016 4:05 PM

Page 13 of 46

Page 14: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 12-NFPA 101-2016 [ Sections 8.5.6.2, 8.5.6.3, 8.5.6.4, 8.5.6.5 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:12:17 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to do the following:

1. Revise the requirement of 8.5.6.5 so that it has applicability if the smoke barrier is also constructed as a fire barrier – forsample language, see 8.5.5.2.2.

2. Consider the Negative ballot of Hugo relative to clarifying the applicability – is it for membrane penetrations? Is it forthrough-penetrations?

3. Consider the Negative ballot of Shino relative to providing substantiation for the requirement for 0.30 inches water column,given that the provisions 7.2.3 for smokeproof enclosures require 0.05 inches water column in sprinklered buildings and 0.10inches water column in nonsprinklered buildings.

4. Revise the text of 8.5.6.6 as needed based on the following words not working together correctly: “fill with a listed system ofa material capable or restricting the transfer of smoke”. Was the text meant to read: “fill with a listed system or a materialcapable of restricting the transfer of smoke”?

These actions will be considered as a public comment.

First Revision No. 2505-NFPA 101-2015 [Sections 8.5.6.2, 8.5.6.3, 8.5.6.4, 8.5.6.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 46 1/29/2016 4:05 PM

Page 14 of 46

Page 15: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 13-NFPA 101-2016 [ Sections 8.5.7.1, 8.5.7.2, 8.5.7.3, 8.5.7.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:13:40 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to do the following:

1. Revise the requirement of 8.5.7.2 so that it has applicability if the smoke barrier is also constructed as a fire barrier – forsample language, see 8.5.5.2.2.

2. Consider the Negative ballot of Shino relative to providing substantiation for the requirement for 0.30 inches water column,given that the provisions 7.2.3 for smokeproof enclosures require 0.05 inches water column in sprinklered buildings and 0.10inches water column in nonsprinklered buildings.

These actions will be considered as a public comment.

First Revision No. 2506-NFPA 101-2015 [Sections 8.5.7.1, 8.5.7.2, 8.5.7.3, 8.5.7.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 46 1/29/2016 4:05 PM

Page 15 of 46

Page 16: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 14-NFPA 101-2016 [ Section No. 8.6.11.3 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:16:05 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fire Protection Features (FIR) to consider the Negative ballots of Devlin,Gerdes, Klein, Richardson, Shino and Stashak relative to providing technical substantiation for why a draft stop additionallyneeds fire resisting capability like that provided by Type X gypsum wall board.

This action will be considered as a public comment.

First Revision No. 2511-NFPA 101-2015 [Section No. 8.6.11.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 46 1/29/2016 4:05 PM

Page 16 of 46

Page 17: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 15-NFPA 101-2016 [ Section No. 9.6.3.7 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:24:54 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Building Service and Fire Protection Equipment (BSF) to consider the Negativeballot of Larrimer so as to make clear that existing audible devices need not meet the requirements of the current edition ofNFPA 72. The committee should retain the existing performance-based language (rather than deleting it as proposed in theFR) for applicability to existing appliance installations.

This action will be considered as a public comment.

First Revision No. 1003-NFPA 101-2015 [Section No. 9.6.3.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 46 1/29/2016 4:05 PM

Page 17 of 46

Page 18: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 16-NFPA 101-2016 [ New Section after 9.13 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:26:18 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Fundamentals (FUN) and the occupancy committees (AXM, END, HEA, BCF,RES, DET, MER, IND) to review the proposed change and determine if further changes are needed in the Code. TheCorrelating Committee will revisit the scope of the TC on Building Service and Fire Protection Equipment (BSF) after theypropose any desired changes.

This action will be considered as a public comment.

First Revision No. 1006-NFPA 101-2015 [New Section after 9.13]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 46 1/29/2016 4:05 PM

Page 18 of 46

Page 19: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 17-NFPA 101-2016 [ Section No. 10.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:44:06 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Interior Finish and contents (FUR) to do the following:

1. Consider the Affirmative with Comment ballot of Hirschler as the test method for factory-produced laminated products wasincorrectly shown as ASTM E2404 when it should have been ASTM E2579, Standard Practice for Specimen Preparation andMounting of Wood Products to Assess Surface Burning Characteristics.

2. Add ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface BurningCharacteristics to the Chapter 2 ASTM referenced standards in 2.3.6.

3. Add correlative references to avoid conflicts. For example, the provision of 10.2.1.1 would provide better guidance if thefollowing was added: “…unless otherwise provided in 10.2.4.1 and 10.2.4.1.2”. Similarly, the text of 10.2.4.1 and 10.2.4.1.2would be more accurate if wording was added to the effect: “…and the provision of 10.2.1.1 shall not apply.”

4. Revise 10.2.3.2(3) to replace the word “defined” with “described” to read: “Flashover, as described in NFPA 286, shall notoccur.” This will make 10.2.3.2 relative to NFPA 286, consistent with 10.2.4.4.2 relative to NFPA 265. NFPA 286 Chapter 3does not define flashover; its 9.1 Procedure describes flashover as having occurred when any two of five possible criteria aremet.

5. Provide a boldface heading to 10.3.3 relative to Rate of Heat Release Testing of Upholstered Furniture and Mattresses asdone for cigarette ignition testing of upholstered furniture and mattresses in 10.3.2. Renumber 10.3.3. to become 10.3.3.1;renumber the 10.3.4s to become the 10.3.3.2s; renumber subsequent paragraphs as needed.

These actions will be considered as a public comment.

First Revision No. 4505-NFPA 101-2015 [Section No. 10.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 46 1/29/2016 4:05 PM

Page 19 of 46

Page 20: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 18-NFPA 101-2016 [ Section No. 11.3.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:45:31 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Industrial and Storage Occupancies (IND) to do the following:

1. Consider the Affirmative with Comment ballot of Allison to add the word “such” to 11.3.4.2(1) so as to read: “Uses thatsupport tower operations, such as electrical…”

2. Revise 11.3.4.4.1(3)(b) from “Means of egress” to the former term “Common areas” or something else that is definitiveas “means of egress” includes ALL spaces where an occupant can be present.

3. Revise 11.3.4.4.2 to insert the word “diagonal” to read “…maximum overall diagonal dimension…”

4. Revise second sentence of 11.3.4.8.1 to change “is permitted’ to “shall be permitted” to read: “The emergency commandcenter shall be permitted to be located…”

These actions will be considered as a public comment.

First Revision No. 4012-NFPA 101-2015 [Section No. 11.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 46 1/29/2016 4:05 PM

Page 20 of 46

Page 21: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 20-NFPA 101-2016 [ New Section after 12.3.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 08:52:22 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Assembly Occupancies (AXM) to consider the Negative ballot of Humble relativeto dining spaces open to cooking areas; whether fireplaces are fuel-burning appliances; permanently installed versus portableequipment; use of the term “centrally-located” without respect to the size of the space; and whether some provisions havebeen duplicated.

This action will be considered as a public comment.

First Revision No. 10-NFPA 101-2015 [New Section after 12.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 46 1/29/2016 4:05 PM

Page 21 of 46

Page 22: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 43-NFPA 101-2016 [ Section No. 14.2.2.2.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:42:48 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Committee Statement, that two FCRs have been developed toaddress the request of the committee statement. This CN is related to PI 193.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 46 1/29/2016 4:05 PM

Page 22 of 46

Page 23: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 21-NFPA 101-2016 [ New Section after 14.2.2.2.3 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:01:42 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Educational and Day-Care Occupancies (END) to consider the Affirmative withComment ballot of Dubrowski and the Negative ballot of Roeper to add a charging statement as the provisions are notpresented in context; include the term “without special knowledge”; and reference the mounting height of the operable parts ofthe releasing mechanism rather than the location of the release itself.

This action will be considered as a public comment.

The Correlating Committee notes, in response to the Committee Statement, that two FCRs have been developed to addressthe request of the committee statement.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 46 1/29/2016 4:05 PM

Page 23 of 46

Page 24: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 23-NFPA 101-2016 [ Section No. 14.3.4.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:12:07 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Educational and Day-Care Occupancies (END) to consider the Negativeballot of Mertens relative to detector installation locations and coverage areas.

This action will be considered as a public comment.

First Revision No. 2030-NFPA 101-2015 [Section No. 14.3.4.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 46 1/29/2016 4:05 PM

Page 24 of 46

Page 25: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 24-NFPA 101-2016 [ Section No. 14.3.4.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:14:36 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Building Service and Fire Protection Equipment (BSF) to consider the Affirmativewith Comment ballot of Stashak and the Negative ballot of Shirey so as to revise Section 9.12 CO Detection and WarningEquipment to provide guidance to the various occupancy technical committees on installation and listing standards for COdetection devices in other than residential living units.

This action will be considered as a public comment.

First Revision No. 2030-NFPA 101-2015 [Section No. 14.3.4.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 46 1/29/2016 4:05 PM

Page 25 of 46

Page 26: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 22-NFPA 101-2016 [ New Section after 15.2.2.2.3 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:10:56 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Educational and Day-Care Occupancies (END) to consider the Affirmative withComment ballot of Dubrowski and the Negative ballot of Roeper to add a charging statement as the provisions are notpresented in context; include the term “without special knowledge”; and reference the mounting height of the operable parts ofthe releasing mechanism rather than the location of the release itself.

This action will be considered as a public comment.

First Revision No. 2002-NFPA 101-2015 [New Section after 15.2.2.2.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 46 1/29/2016 4:05 PM

Page 26 of 46

Page 27: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 25-NFPA 101-2016 [ New Section after 17.2.11.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:16:53 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Educational and Day-Care Occupancies (END) to consider the Affirmative withComment ballot of Dubrowski and the Negative ballot of Longhitano noting that the text of 17.2.11.3 is wrong in that it presentsthe reason for the change rather than the intended code requirement. Make 17.2.11.3 read the same as 16.2.11.3 fromFR-2008.

This action will be considered as a public comment.

First Revision No. 2009-NFPA 101-2015 [New Section after 17.2.11.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 46 1/29/2016 4:05 PM

Page 27 of 46

Page 28: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 26-NFPA 101-2016 [ Sections 18.2.3.4, 18.2.3.5 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:19:09 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Health Care Occupancies (HEA) to consider the Affirmative with Commentballot of Rickard so as to correct the reference embedded within 18.2.3.4(9)(f) to refer to 18.2.3.4(9)(e).

This action will be considered as a public comment.

First Revision No. 3519-NFPA 101-2015 [Sections 18.2.3.4, 18.2.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 46 1/29/2016 4:05 PM

Page 28 of 46

Page 29: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 27-NFPA 101-2016 [ Section No. 18.3.6.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:21:55 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Health Care Occupancies (HEA) to consider the Affirmative with Commentballot of Rickard so as to correct, in the last sentence of A.18.3.6.1(1), the spelling of the word “louver”.

This action will be considered as a public comment.

First Revision No. 3558-NFPA 101-2015 [Section No. 18.3.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 46 1/29/2016 4:05 PM

Page 29 of 46

Page 30: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 28-NFPA 101-2016 [ Section No. 18.3.6.2.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:27:40 EST 2016

Committee Statement

Committee Statement: The Correlating Committee directs the TC on Fire Protection Features to consider similar annex text for 8.4.2.

This action will be considered as a public comment.

First Revision No. 3534-NFPA 101-2015 [Section No. 18.3.6.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 46 1/29/2016 4:05 PM

Page 30 of 46

Page 31: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 29-NFPA 101-2016 [ Section No. 22.2.11 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:29:26 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Detention and Correctional Occupancies (DET) to consider the Affirmativewith Comment ballot of Gaw so as to correct the reference in 22.2.11.1.9.2 from “23.2.11.9.1(1)” to “22.2.11.1.9.1(1)”.

This action will be considered as a public comment.

First Revision No. 1508-NFPA 101-2015 [Section No. 22.2.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 46 1/29/2016 4:05 PM

Page 31 of 46

Page 32: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 30-NFPA 101-2016 [ Section No. 23.2.11 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:31:32 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Detention and Correctional Occupancies (DET) to renumber 23.2.11.1.11 and23.2.11.1.12 to become 23.2.11.2 and 23.2.11.3 for consistency with the numbering in Chapter 22.

This action will be considered as a public comment.

First Revision No. 1509-NFPA 101-2015 [Section No. 23.2.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 46 1/29/2016 4:05 PM

Page 32 of 46

Page 33: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 31-NFPA 101-2016 [ Section No. 24.3.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:39:10 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Residential Occupancies (RES) to consider the Negative ballots of Klein,Longhitano, Mayl and Weaver relative to enforceability of hazardous materials protection requirements for 1- and 2-familydwellings. Also, the committee should readdress the provisions of 24.3.2 with regards to items like flammable liquids, gasesand common hazardous materials found within one-and-two family dwellings.

This action will be considered as a public comment.

First Revision No. 6015-NFPA 101-2015 [Section No. 24.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 46 1/29/2016 4:05 PM

Page 33 of 46

Page 34: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 32-NFPA 101-2016 [ Section No. 24.3.5.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:42:11 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Residential Occupancies (RES) to consider the Affirmative with Commentballots of Asp and Klein to reword code text so as to correctly capture the allowable scope of NFPA 13R.

This action will be considered as a public comment.

First Revision No. 6003-NFPA 101-2015 [Section No. 24.3.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 46 1/29/2016 4:05 PM

Page 34 of 46

Page 35: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 33-NFPA 101-2016 [ New Section after 32.1.8 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:44:09 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Board and Care Facilities (BCF) to consider the Negative ballot of Larrimernoting that small board and care facilities do not have means of egress; they have means of escape.

This action will be considered as a public comment.

First Revision No. 515-NFPA 101-2015 [New Section after 32.1.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 46 1/29/2016 4:05 PM

Page 35 of 46

Page 36: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 35-NFPA 101-2016 [ Section No. 32.2.3.4.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:47:08 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Board and Care Facilities (BCF) to consider the Negative ballot of Larrimernoting that 32.3.3.4.2(2) requires the sprinklers to provide protection throughout the building yet where NFPA 13D or NFPA13R systems are used the sprinklers are not provided “throughout”. The provision of 32.2.3.4.2(2) could be reworded to read:

(2) Automatic sprinkler system that complies with 9.6.2.1(3) and the provisions of 32.2.3.5.

This action will be considered as a public comment.

First Revision No. 502-NFPA 101-2015 [Section No. 32.2.3.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 46 1/29/2016 4:05 PM

Page 36 of 46

Page 37: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 37-NFPA 101-2016 [ Section No. 32.3.3.6.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 10:33:07 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Board and Care Facilities (BCF) to consider the Affirmative with Comment ballotof Bonisch relative to the need to clarify the location or separation condition for the lounge. If the lounge is open to the corridor,the wall that separates the lounge from the sleeping room cannot be exempted from protection as it serves as a continuation ofthe corridor wall envelope.

This action will be considered as a public comment.

First Revision No. 509-NFPA 101-2015 [Section No. 32.3.3.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 46 1/29/2016 4:05 PM

Page 37 of 46

Page 38: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 38-NFPA 101-2016 [ Section No. 32.3.3.8.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 10:34:07 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Board and Care Facilities (BCF) to consider the Affirmative with Commentballot of Bonisch relative lack of test standard for cooktop temperature. Follow the UL 858 STP work and reference theappropriate test standard for cooktop temperature measurement.

This action will be considered as a public comment.

First Revision No. 510-NFPA 101-2015 [Section No. 32.3.3.8.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 46 1/29/2016 4:05 PM

Page 38 of 46

Page 39: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 34-NFPA 101-2016 [ New Section after 33.1.8 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:46:05 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Board and Care Facilities (BCF) to consider the Negative ballot of Larrimernoting that small board and care facilities do not have means of egress; they have means of escape.

This action will be considered as a public comment.

First Revision No. 516-NFPA 101-2015 [New Section after 33.1.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 46 1/29/2016 4:05 PM

Page 39 of 46

Page 40: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 36-NFPA 101-2016 [ New Section after 33.2.3.4.1.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 09:48:41 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Board and Care Facilities (BCF) to consider the Negative ballot of Larrimernoting that 33.3.3.4.2(2) requires the sprinklers to provide protection throughout the building yet where NFPA 13D or NFPA13R systems are used the sprinklers are not provided “throughout”. The provision of 33.2.3.4.2(2) could be reworded to read:

(2) Automatic sprinkler system that complies with 9.6.2.1(3) and the provisions of 33.2.3.5.

This action will be considered as a public comment.

First Revision No. 504-NFPA 101-2015 [New Section after 33.2.3.4.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 46 1/29/2016 4:05 PM

Page 40 of 46

Page 41: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 40-NFPA 101-2016 [ Section No. 38.2.2.2.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:14:33 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Committee Statement, that language has been prepared for Chapter 7that can be considered at the Second Draft meeting. See FCR-5 and FCR-6. This CN is related to PI 408.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 46 1/29/2016 4:05 PM

Page 41 of 46

Page 42: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 39-NFPA 101-2016 [ Section No. 38.2.2.2.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:13:33 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Committee Statement, that language has been prepared for Chapter 7that can be considered at the Second Draft meeting. See FCR-5 and FCR-6. This CN is related to CI 5537.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 46 1/29/2016 4:05 PM

Page 42 of 46

Page 43: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 41-NFPA 101-2016 [ Section No. 39.2.2.2.1 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:18:14 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Committee Statement, that language has been prepared for Chapter 7that can be considered at the Second Draft meeting. See FCR-5 and FCR-6. This CN is related to PI 409.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 46 1/29/2016 4:05 PM

Page 43 of 46

Page 44: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 42-NFPA 101-2016 [ Section No. 39.2.2.2.2 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 08 11:24:35 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee notes, in response to the Committee Statement, that language has been prepared for Chapter 7that can be considered at the Second Draft meeting. See FCR-5 and FCR-6. This CN is related to CI 5338.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 46 1/29/2016 4:05 PM

Page 44 of 46

Page 45: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 49-NFPA 101-2016 [ Section No. A.36.4.4.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 12:46:32 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Mercantile and Business Occupancies (MER) to consider the Affirmative withComment ballot of Gauvin relative to revising the text of A.36.4.4.4 from “where pedestrian way…” to “where a pedestrianway…”. This CN is related to FR 5542.

This action will be considered as a public comment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 46 1/29/2016 4:05 PM

Page 45 of 46

Page 46: Page 1 of 46 - National Fire Protection Association€¦ · Page 7 of 46. Correlating Committee Note No. 8-NFPA 101-2016 [ Section No. 7.2.1.9.1 [Excluding any Sub-Sections] ] Submitter

Correlating Committee Note No. 50-NFPA 101-2016 [ Section No. A.37.4.4.4 ]

Submitter Information Verification

Submitter Full Name: SAF-AAC

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 12:47:34 EST 2016

Committee Statement

CommitteeStatement:

The Correlating Committee directs the TC on Mercantile and Business Occupancies (MER) to consider the Affirmative withComment ballot of Gauvin relative to revising the text of A.37.4.4.4 from “where pedestrian way…” to “where a pedestrianway…”. This CN is related to FR 5543.

This action will be considered as a public comment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...