p12x_envcc55 hard-soft ware
TRANSCRIPT
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
1/12
Technical Guide P12x/EN VC/C55
MiCOM P120/P121/P122/P123
HARDWARE/SOFTWARE VERSION
P120 P121 P122 P123
HISTORY AND COMPATIBILITY
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
2/12
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
3/12
Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 1/10
P120 - Serial number Hardware Correlation
Serial Number Hardware installed
From 2299001 to 4799797 HARDWARE VERSION 2
From 4799798 to 1001999 HARDWARE VERSION 3
From 1101001 HARDWARE VERSION 4
Relay Type P120
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V1.F 11/06/99 Resolution of KITZ201problem
Modification of the outputrelay latching
HARD V 2
HARD V 3HARD V 4
V3.B 19/11/99 Suppression of password inorder to acknowledge thealarms
Auto acknowledgement ofthe instantaneous
Modbus time out of 200 ms
Display of the letter P in the
menu N and N-1 whenpassword is active
!V2.0
V3.C 22/08/00 VDEW improvements !V2.0
HARD V 3
HARD V 4
V4.A 15/03/01 Integration of DNP3protocol
Management of alternativelogic input
Latching of the auxiliaryoutput relay by relay and
not by functionThe digital input can workwith AC signals (100 to 250
V AC)
!V2.0 HARD V 4
V4.D 27/08/02 Courier improvment :adding of the cell 0010 (CBcontrol)
IEC103 : correction of thechecksum calculation forshort message.
!V2.0 HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
4/12
P12x/EN VC/C55 Technical GuideHardware/Software Version
Page 2/10 MiCOM P120/P121/P122/P123
P121 - Serial number Hardware Correlation
Serial Number Hardware installed
From 2599001 to 4799797 HARDWARE VERSION 2
From 4799798 to 0801999 HARDWARE VERSION 3
From 0901001 HARDWARE VERSION 4
Relay Type P121
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V2.J 30/08/99 MODBUS improvement :
Correction of alencountered problem(answer to asynchronisation telegram,creation of a 2 secondstime out )
HARD V 2
HARD V 3HARD V 4
V3.B 19/11/99 Suppression of password inorder to acknowledge thealarms
Auto acknowledgement ofthe instantaneous
Modbus time out of 200 ms
Display of the letter P in themenu N and N-1 whenpassword is active
!V2.0 HARD V 3
HARD V 4
V3.C 25/01/00 Evolution of Modbus writing16 bits
!V2.0
V3.E 16/03/00 Czech and Hungarianversion delivery
!V2.0
V3.G 22/08/00 VDEW improvements !V2.0
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
5/12
Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 3/10
Relay Type P121
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V4.E 31/01/01 Latch of the output relaysLatch of the auxiliary relays,relay by relay and not byfunction (like previously upto V3 version). On the otherhand the latch of the TRIPoutput relay remains byfunction.
If the auxiliary relays arelatched, no alarm isdisplayed. For anaknowledgment of the latchthe user has to go in theOP-PARAMETERS/Relaystatus Menu and push onthe clear push button.
DNP3 level 2 and 3
Addition of the tripping andclosing order for IEC103
The digital input can work
with AC signals (100 to 250V AC)
!V2.0
V5.D 31/01/01 Improvement of the englishlabels.
!V2.0
HARD V 4
V5.F 08/08/02 Courier improvment :adding of the cell 0010 (CBcontrol)
IEC103 : correction of thechecksum calculation forshort message.
!V2.0 HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
6/12
P12x/EN VC/C55 Technical GuideHardware/Software Version
Page 4/10 MiCOM P120/P121/P122/P123
P122 - Serial number Hardware Correlation
Serial Number Hardware installed
From 2599001 to 4799797 HARDWARE VERSION 2
From 4799798 to 0801999 HARDWARE VERSION 3
From 0901001 HARDWARE VERSION 4
Relay Type P122
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V2.J 30/08/99 MODBUS improvement :
Correction of alencountered problem(answer to asynchronisation telegram,creation of a 2 secondstime out )
HARD V 2
HARD V 3HARD V 4
V3.B 29/11/99 Suppression of password inorder to acknowledge thealarms
Auto acknowledgement ofthe instantaneous
Modbus time out of 200 ms
Display of the letter P in themenu N and N-1 whenpassword is active
!V2.0
V3.C 06/01/00 Label correction !V2.0
V3.D 06/04/00 Evolution of Modbus writing16 bits
!V2.0
V3.E 16/03/00 Czech and Hungarianversion delivery
!V2.0
V3.G 22/08/00 VDEW improvements !V2.0
HARD V 3
HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
7/12
Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 5/10
Relay Type P122
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V4.E 31/01/01 Latch of the output relaysLatch of the auxiliary relays,relay by relay and not byfunction (like previously upto V3 version). On the otherhand the latch of the TRIPoutput relay remains byfunction.If the auxiliary relays arelatched,an alarm will be displayed.
If the user acknowledgesthis alarm, the auxiliaryrelays will be delatched.DNP3 level 2 and 3
Addition of the tripping andclosing order for IEC103Phase rotation (ABC or
ACB)Third threshold algorithmfor improvment of thebehaviour on saturatedcurrent transformersTimer for the undercurrentfeature (0 to 150 sec)Tripping curves (rectifiercurve + LABORELLECcurves)Selection of the Settinggroup by level or by edge.CB fail detection (possibilityto inhibit the startingsignals)Instanteneous record
Rolling demandPeak value demandInstantaneous alarmsettable : self or not selfresetMatrix for the autorecloserThe digital input can workwith AC signals signals (24
V to 250 V AC)Necessity to set in HMIConfiguration menu, the
type of voltage used, eitherACor DC
!V2.0 HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
8/12
P12x/EN VC/C55 Technical GuideHardware/Software Version
Page 6/10 MiCOM P120/P121/P122/P123
Relay Type P122
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V5.A 27/09/01 Maintenance mode formanual command of theoutput relays
Reset of leds by logic inputor control command orfront panel or on new faultappearance
Addition of negativesequence protection feature(ANSI code 46) with twothresholds
Addition of the CBsupervision feature.
!V2.0
V5.C 04/10/01 VDEW improvements
(Updating of theinformation SCN into the
ASDU END OF GENERALINTERROGATION)
!V2.0
V5.D 30/01/02 Addition of orderCOM1/COM2/COM3/CO
M4 assignalble on theauxiliary relays.
Addition of the logic inputsAUX3 and AUX 4 do notgenrating alarm message.
Improvement of englishlabel
!V2.0
HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
9/12
Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 7/10
Relay Type P122
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V5.F 08/08/02 EA approval option : logicalinput filtering on 24samples instead of 12either 15 ms at 50 Hz)
Improvment of theRecording of rollingdemand in ram saved. Theprevious version could leadto an untimely ram savederror message due to themanagement of this
recording
Courier improvment :adding of the cell 0010 (CBcontrol) protected bypassword
Correction of theconfiguration of taux3 andtaux4 for MODBUS
IEC103 : correction of thechecksum calculation for
short message. Correctionof the I0 channel data intothe disturbance record
!V2.0 HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
10/12
P12x/EN VC/C55 Technical GuideHardware/Software Version
Page 8/10 MiCOM P120/P121/P122/P123
P123 - Serial number Hardware Correlation
Serial Number Hardware installed
From 2599001 to 4799797 HARDWARE VERSION 2
From 4799798 to 0801999 HARDWARE VERSION 3
From 0901001 HARDWARE VERSION 4
Relay Type P123
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V2.J 30/08/99 MODBUS improvement :
Correction of al
encountered problem(answer to asynchronisation telegram,creation of a 2 secondstime out )
HARD V 2
HARD V 3
HARD V 4
V3.B 29/11/99 Suppression of password inorder to acknowledge thealarms
Auto acknowledgement ofthe instantaneous
Modbus time out of 200 msDisplay of the letter P in themenu N and N-1 whenpassword is active
!V2.0
V3.C 06/01/00 Label correction !V2.0
V3.D 06/04/00 Evolution of Modbus writing16 bits
!V2.0
V3.E 13/04/00 Czech and Hungarianversion delivery
!V2.0
V3.G 22/08/00 VDEW improvements !V2.0
HARD V 3
HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
11/12
Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 9/10
Relay Type P123
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V4.E 31/01/01 Latch of the output relaysLatch of the auxiliary relays,relay by relay and not byfunction (like previously upto V3 version). On the otherhand the latch of the TRIPoutput relay remains byfunction. If the auxiliaryrelays are latched, an alarmwill be displayed. If the useracknowledges this alarm,
the auxiliary relays will bedelatched.DNP3 level 2 and 3
Addition of the tripping andclosing order for IEC103Phase rotation (ABC or
ACB)Third threshold algorithmfor improvement of thebehaviour on saturatedcurrent transformersTimer for the undercurrentfeature (0 to 150 sec)Tripping curves (rectifiercurve + LABORELLECcurves)Selection of the Settinggroup by level or by edge.CB fail detection (possibilityto inhibit the startingsignals)Instantaneous recordRolling demand
Peak value demandInstantaneous alarmsettable : self or not selfresetMatrix for the auto-recloser
Addition of a secondthreshold with definite timefor the I2 featureThe digital input can workwith AC signals (24 V to250 V AC)
Necessity to set in HMIConfiguration menu, thetype of voltage used, eitherACor DC .
!V2.0 HARD V 4
-
8/13/2019 p12x_envcc55 Hard-Soft Ware
12/12
P12x/EN VC/C55 Technical GuideHardware/Software Version
Page 10/10 MiCOM P120/P121/P122/P123
Relay Type P123
SoftwareVersion
Date ofIssue
Full Description of ChangesS1Compatibility
BackwardCompatibility withprevious hardware
V5.A 27/09/01 Maintenance mode formanual command of theoutput relays
Reset of leds by logic inputor control command orfront panel or on new faultappearance
!V2.0
V5.C 04/10/01 VDEW improvements
(Updating of theinformation SCN into the
END OF GENERALINTERROGATION ASDU)
!V2.0
V5.D 30/01/02 Addition of orderCOM1/COM2/COM3/COM4 assignalble on theauxiliary relays.
Addition of the logic inputsAUX3 and AUX 4 do notgenerating alarm message.
Improvement of english
label
!V2.0
HARD V4
V5.F 08/08/02 EA approval option : logicalinput filtering on 24samples instead of 12either 15 ms at 50 Hz)Improvment of theRecording of rollingdemand in ram saved. Theprevious version could leadto an untimely ram savederror message due to themanagement of thisrecordingCourier improvment :adding of the cell 0010 (CBcontrol) protected bypasswordCorrection of theconfiguration of taux3 andtaux4 for MODBUSIEC103 : correction of thechecksum calculation for
short message. Correctionof the I0 channel data intothe disturbance record
!V2.0 HARD V4