Washington State Patrol Fire Protection Bureau Phone: (360)596-3900 Business Name Address City, State, Zip Brookdale College Place 550 E WHITMAN DR , College Place, WA 99324 Provider Number Approval Status Facility Type 2322 Approved Residential Care On 05/01/2018 the Office of the State Fire Marshal conducted an inspection at your facility. All violations noted during previous related inspection(s) have been corrected. Owner or Owner's Representative UlL/^j^ ^ Signature I" 13 W^^ |'^3/K^ ^ZtA]\l-C ^V^ Print Name and Title {Y Deputy State Fire Marshal Doug DeGrafT 143302 E Law Lane KennewickWA 98007 (509) 531-3384 77 •?? ^l -Signature Right of appeal. Any person may appeal any decision made by the Fire Protection Bureau in accordance with WAC 212-12.

Upload: others

Post on 31-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Owner or Owner's Representative UlL/^j^€¦ · I" 13 W^^ |'^3/K^ ^ZtA]\l-C ^V^ Print Name and Title {Y Deputy State Fire Marshal Doug DeGrafT 143302 E Law Lane KennewickWA 98007

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Brookdale College Place

550 E WHITMAN DR ,

College Place, WA 99324

Provider Number

Approval Status

Facility Type

2322

Approved

Residential Care

On 05/01/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

All violations noted during previous related inspection(s) have been corrected.

Owner or Owner's Representative

UlL/^j^ ^Signature

I" 13 W^^ |'^3/K^ ^ZtA]\l-C ^V^Print Name and Title

{Y

Deputy State Fire Marshal Doug DeGrafT143302 E Law LaneKennewickWA 98007(509) 531-3384

77 •?? ^l-Signature

Right of appeal. Any person may appeal any decision made by the Fire Protection Bureau in accordance with WAC 212-12.

Page 2: Owner or Owner's Representative UlL/^j^€¦ · I" 13 W^^ |'^3/K^ ^ZtA]\l-C ^V^ Print Name and Title {Y Deputy State Fire Marshal Doug DeGrafT 143302 E Law Lane KennewickWA 98007

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Brookdale College Place

550 E WHITMAN DR ,

College Place, WA 99324

Provider Number

Approval Status

Facility Type

2322

Disapproved

Residential Care

On 03/06/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

1 Admin New Requirements

For your information:

703.2 Opening protectives. Opening protective shall bemaintained in an operative condition in accordance with NFPA80.

NFPA80 Chapter 19 Installation, Testing, and Maintenance ofFire Dampers.19.4 Periodic Inspection and Testing.19.4.1 Each damper shall be tested and inspected 1 year afterinstallation.19.4.1.1 The test and inspection frequency shall then be every4 years, except in hospitals, where the frequency shall be every6 years.

EFFECTIVE JULY 1,2018.907.10 National Institute for Certification in EngineeringTechnologies.907.10.1 Scope. This section shall apply to new and existingfire alarms systems.907.10.2 Design review. All construction documents shall bereviewed by a NICET III in fire alarms or a licensed professionalengineer (PE) in Washington prior to being submitted forpermitting. The reviewing professional shall submit a stamped,signed, and dated letter; or a verification method approved bythe local authority having jurisdiction indicating the system hasbeen reviewed and meets or exceeds the design requirementof the Washington and the local jurisdiction (effective July 1 ,2018).907.10.3 Testing/maintenance: All inspection, testingmaintenance and programing not defined as "electrical trade"by chapter 19.28 RCW shall be completed by a NICET It in firealarms (effective July 1, 2018).

2 Multi-Plug Adapters - Power Supply.

Relocatable power taps shall be directly connected to apermanently installed receptacle.

(IFC 605.4.2)

Two power strips were discovered daisy-chained in the 2ndfloor Activities Room.

1of2 Initials of Authorized Facility Representative:

Page 3: Owner or Owner's Representative UlL/^j^€¦ · I" 13 W^^ |'^3/K^ ^ZtA]\l-C ^V^ Print Name and Title {Y Deputy State Fire Marshal Doug DeGrafT 143302 E Law Lane KennewickWA 98007

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Brookdale College Place

550 E WHITMAN DR ,

College Place, WA 99324

Provider Number

Approval Status

Facility Type

2322

Disapproved

Residential Care

On 03/06/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

3 Opening protectives.

Opening protectives shall be maintained in an operativecondition in accordance with NFPA 80. Where allowed by thefire code official, the application of field-apptied labelsassociated with the maintenance of opening protectives shallfollow the requirements of the approved third-party certificationorganization accredited for listing the opening protective. Firedoors and smoke barrier doors shall not be blocked orobstructed, or otherwise made inoperable. Fusible links shall bereplaced promptly whenever fused or damaged. Fire doorassemblies shall not be modified.

IFC 703.2

The facility is unable to provide documentation for currenttesting and maintenance of the fire dampers (in the HVACsystem).

NFPA80 Chapter 19 Installation, Testing, and Maintenance ofFire Dampers.19.4 Periodic Inspection and Testing.19.4.1 Each damper shall be tested and inspected 1 year afterinstallation.19.4.1.1 The test and inspection frequency shall then be every4 years, except in hospitals, where the frequency shall beevery 6 years.

4 Inspection, testing and maintenance.

Fire detection, alarm, and extinguishing systems, mechanicalsmoke exhaust systems, and smoke and heat vents shall bemaintained in an operative condition at all times, and shall bereplaced or repaired where defective. Nonrequired fireprotection systems and equipment shall be inspected, testedand maintained or removed.

(IF^901.6 2012,2015)

1. The facility has no documentation of current backflowtesting for the fire sprinkler system.2. The current annual report for the trip test of the dry systemreveals that the accelerator failed to trip on testing. Facilityunable to provide documentation of correction for thisdeficiency.

Next inspection scheduled on or after: 04/05/2018

Right of appeal. Any person may appeal any decision made by the Fire Protection Bureau in accordance with WAC 212-12.

Owner or Authorised representativeT°rAU'3IrL^C^

Signature^" .^i ^

PrirSt Narhe and Titleq^h^Q^^i'^y_y ^

Deputy State Fire Marshal Doug DeGraff143302 E Law LaneKennewickWA 98007(509)531-3384

-r7 -^7 -/S^ffature^ '^•j?^

2 of 2 Initials of Authorized Facility Representative: