overvoltage protection - powerwiki ii - 11- overvoltage... · overvoltage protection of overhead...
TRANSCRIPT
Power Engineering II
Overvoltage Protection
Overvoltage Protection 2
Power Engineering II
Overvoltage Protection of Overhead Lines
• Usage of ground wires -> likelihood of ground wire striking is higher than the likelihood of phase conductors striking -> just prevention of the worst case, overvoltage can be still induced to the phase conductors
• Arrangement of ground wires on line is based on the theory of protecting zones
Z
Lα
hZhL
S
S
βS
Zone A Zone BZone A Zone C
Zone A – Lightning is likely hits the ground conductorZone B – Lightnint is likely hits the phase conductorProtecting angle α – determine the position of ground conductor above phase conductor
Protecting distance S – is given by empirical formula 𝑆 = 10𝐼2
3 [m; kA]
Overvoltage Protection 3
Power Engineering II
Overvoltage protection
• Fundamental classification– Spark (rod)-gaps
• Air spark-gaps with preset spark distance, connected between phase conductor and ground, permanent arc burning occures during the action-> failure state -> protection relays have to switch off the electric circuit
– Gapped surge arresters• Gap and nonlinear resistor (SiC material) in series, current is
limited to few amps after the overvoltage
– Metal oxide surge arresters• Gapless surge arresters, cylindrical blocks of nonlinear
resistors in parallel, Metal-oxide resistors (90% zinc oxide and 10% of various additives (Bi, Sb, Co, Mn)
Overvoltage Protection 4
Power Engineering II
Gapped surge arresters
• V-A characteristic and important parameters
Uzn
Ur
Umn
0 In i
u
In Peak value of rated discharge current
Umn vrcholová hodnota jmenovitého napětí
Uzn rated residual voltageUr rázové zapalovací napětí
Overvoltage Protection 5
Elektroenergetika 1
Gapped arresters (Valve type arresters)
• Construction • Both main gaps are ignited when the overvoltage occures at the terminals of arrester. At the same time, the current flows through the coil and nonlinear limiting resistor
• The current increase causes voltage across the coil , which iniciate ignition of auxiliary gap and bridging of coil
• The impadance of arrester is then given only as voltage drop across the nonlinear limiting resistor
• After the overvoltage decrease the impedance of coil decrease as well -> extinguishing of auxiliary gap and conection of coil into the circuit
• The magnetic field created by coil pushes the arc of main gaps to quenching chambers
Main gaps
Main gaps
Auxiliary gapCoil
Stabilizing resistor
Stabilizing resistor
Main gaps
Nonlinear resistor
Overvoltage Protection 6
Power Engineering II
Gapped Arresters
• Main parameters of gapped arresters– Rated ignition voltage at lightning impulse (1,2/50 µs)
• The lowest peak value of impulse which will causes the action of surge arrestor
– Residual voltage• Voltage drop caused by current impulse 8/20 µs
– Rated discharge current of arrester• The peak value of impulse 8/20 µs (1,5 kA, 2,5 kA, 5 kA, 10 kA, 20 kA,
40 kA)
– Rated voltage of gapped arrester• Highest RMS value of power frequency voltage across the arrester
terminals at which the arrester is closed
– AC ignition voltage of surge arrestor• RMS value of AC voltage at which the arrester opens
Overvoltage Protection 7
Power Engineering II
MO Surge Arresters
• Construction
Compression spring
Pressure relief diaphragm
Venting outlet Sealing ring
Cement joint
Metallic spacer
MO resistor
Supporting rod
Holding plate
Porcelain housing
Aluminum flange
Source: Volker Hinrichsen, Metal-Oxide Surge Arresters in High-Volgate Power Systems
Metal-Oxide (MO) resistors (ABB Switzerland Ltd.)
MO structure with grains and the boundaries between them (ABB Switzerland Ltd.)
Overvoltage Protection 8
Power Engineering II
MO Surge Arresters
• V-A characteristic
10-4 10-2 1 102 104
Peak value of continuous operating voltage: 2 𝑈𝑐 = 2 268 𝑘𝑉 = 379 𝑘𝑉
Peak value of phase-to-earth voltage: 2𝑈𝑠/ 3 = 2 242 𝑘𝑉 = 343 𝑘𝑉
Leakage current ≈ 100 µA Nominal discharge current In= 10 kA
Peak value of rated voltage: 2 𝑈𝑟 = 2 336 𝑘𝑉 = 475 𝑘𝑉
10-kA residual voltage = lightning impulse protection level = 806 kV
Peak value of current (A)
Peak
val
ue
of
volt
age
(kV
)
Overvoltage Protection 9
Power Engineering II
MO Surge Arresters• Main parameters of MO Surge Arresters
– Continuous operating voltage Uc• Maximum rms value of power-frequency voltage, which the arrester can be operated
at, without any type of restrictions. Uc is equal or more than maximal operating voltage in the place where the surge arrester is mounted
– Rated voltage Ur• Maximum rms value of power-frequency voltage under the temporary overvoltage
conditions. It is usually given as amplitude of equivalent overvoltage Ueq with a time period 10 s:
𝑈𝑒𝑞 = 𝑈𝑡𝑇𝑡
10
𝑚,
where Ut is the amplitude of temporary overvoltage, Tt is the overvoltage time duration and m is a constant that depens on surge arrester construction (roughly 0,02)• Usually, the ralatio between Uc and Ur is:
𝑈𝑐
𝑈𝑟=0,8
– Nominal discharge current In• The peak value of lightning current impulse. It is used for surge arrestor classification
when the current impulse 4/10 µs (which the surge arrester must withstand) is assigned to each nominal lightning current impulse 8/20 µs, e.g. : (10 000 A - 100 kA), (5 000 A- 65 kA)
Overvoltage Protection 10
Power Engineering II
Traveling wave processes• A surge arrester is always placed as close as possible to protected
object to eliminated an influence of reflected voltage waves• The surge arrester protects objects which are inside of so called
protective zone (distance) before and behind of surge arrester – Surge arrester placed in point P has an ignition and
residual voltage Ur
– After the steep voltage wave reaches the interface in point P one part of the wave is reflected and the second part is penetrated through the interface
– The penetrated wave is limited to Ur and the reflected wave has a shape of original wave but with opposite polarity
– The superposition of reflected and original wave causes that the voltage before surge arrestor is lower than would be from comming original wave
– Considering an insulation level of equipment Uithen the protective distance d can be found for given wave steepness S, i.e. the distance in which no voltage higher than Ui will occures
Overvoltage Protection 11
Power Engineering II
Protective distance of surge arrester• The protective diastance of a surge arrester can be determined from the
similarity of ABC and A´B´C triangles• If z is the distance, which a voltage wave traveled by velocity v in time, in
which the wave reaches Ur after comming to point P, then 𝑧 =𝑈𝑟
𝑆𝑣 and
from the similarity of triangles:𝑈𝑖
2𝑑 + 𝑧=𝑈𝑟𝑧
• The protective distance can be derived as:
𝑑 =𝑈𝑖 − 𝑈𝑟2𝑆
𝑣
z
Overvoltage Protection 12
Power Engineering II
Protection of electrical systems within structures against lightning
• Lightning protection systems classification– External lightning protection system
• Lightning conductor including connection to internal terminal for equipotential bonding needs
– Internal lightning protection system• Set of measures inside of building to prevent uncontrolled
iniciations of flashovers and breakdowns (including connected electric appliances)
• Equipotential bonding– Is a part of internal lightning protection, which
incorporates direct connection of all conductive parts together and connection of live conductors through surge arresters
Overvoltage Protection 13
Power Engineering II
External lightning protection system
• Capture device– Meshed cage– Lightning rods (simple or with triggering system)
• Earth down-conductor– Electrical connection of capture device with earthing system
• Earthing system– low voltage drop when the lightning current flows to ground
Meshed cage lightning conductor Air-Termination Lightning Protection System
Overvoltage Protection 14
Power Engineering II
Internal lightning protection system
• Set of measures to the reduction of electromagnetic impulses effects caused by lighning current inside a protected object:– Equipotential bounding– Usage of surge arresters– Electromagnetic shielding
• It is impossible to reach the effective protection by only one measure -> cascaded or selective protection
• Surge arresters are divided into four classes from A to D Class Way of usage
For overhead line instalation
Lightning current surge arresters for the main potential balancing, zone interface ZBO 0A and ZBO 1
Surge arresters, overvoltage protection in fixed electrical wiring
Surge arresters, overvoltage protection in fixed or flexible electrical wiring
Overvoltage Protection 15
Power Engineering II
Internal lightning protection system
• Selection of surge arrester class is done with respect to lightning protection zones and residual voltage
• Lightning protection zones conception– ZBO 0A – external unprotected area– ZBO 0B – protected by captured devices, direct lightning stroke is impossible– ZBO 1, ZBO 2, ZBO 3 – internal areas
• Surge arrester types– Gas filled spark gaps
• Function depends on steepness of voltage impulse, time response approx. 100 ns
– Varistors• Bipolar elements with voltage dependency (SiC, ZnO), minimal consequent current, time
response approx. 20 ns
– Voltage supressors • Special types of Zener’s diod, TRANSZORB, ZAP, TRANSIL
Overvoltage Protection 16
Power Engineering II
Internal lightning protection system
• Cascading (coordination) of lightning protections from the main distribution power panel
Overvoltage category(IEC 664)Withstand impulse voltage
Class of surge arrester