Page 1: Ovation Ppt

PRESENTATION ON

OVATION

Page 2: Ovation Ppt

FEATURES OF OVATION:

AMS Intelligent Device Manager Ovation Plant Web Alerts Ovation Operator Workstation Intuitive Programming Tools Ovation Network Ovation Process Historian Ovation Security Features Connectivity

Page 3: Ovation Ppt

OVATION COMPONENTS:

Network Controllers Input / Output Modules Relational Database Enterprise Integration Workstations Historians Report Servers

Page 4: Ovation Ppt

NETWORK FEATURES: Real time data transmission without loss ,

even during plant upsets Fast 100Mbps Communication Interchangeable Fiber-optic and copper

media with UTP, Multi-mode Fiber, and single-mode fiber for network architecture

Page 5: Ovation Ppt

TYPES OF NETWORKS

Network Speed Drops Points

W1 2 MB 254 16,383

W2 2 MB 254 32,000

W3 100 MB 254 2,00,000

Page 6: Ovation Ppt

CONTROLLER FEATURES:

Provides Ultimate Flexibility through open Computing Standards

Executes Simple or complex modulating and sequential control strategies

Performs data acquisition functions and interfaces to ovation network and I/O Subsystem

Broadcast Value and status of each point in a drop at appropriate frequency

Page 7: Ovation Ppt

I /O MODULE FEATURES: Provides low power consumption and heat dissipation. Feature standard DIN rail mounting for fast and easy

installation. I/O Module Consists of:

Electronic modulePersonality moduleTerminal Block

• Electronic Modules: Converts field signals into data and sends in to the

controller• Personality Module:

Characterizes the category of type of I/O and offers the number of protection features.

• In an I/O Module both personality and Electronic module should be same

Page 8: Ovation Ppt

Module NumberingLeft Branch - Top to bottomRight Branch- Bottom to top

• Relay I/O Module Should be mixed with standard I/O Modules

• Controller is connected to the remote nodes through Media Attachment Unit(MAU) and Remote node Controller.

• MAU-Converts electrical signal in to Optical Signals.

• Remote Node Controller(RNC) interfaces controller and Remote Modules.

• MAU and RNC are connected via Fiber Optic Cable.• 1 MAU can connect 4 RNC.

Page 9: Ovation Ppt

Features UTP STP Coaxial MultiMode Fiber

Single mode Fiber

Cost Low Low Moderate High High +

Installation Simple Simple Simple Differential Differential

Capacity 100Mbps

155Mbps

500Mbps 2Gbps 50Gbps

Distance 100meter

100meter

1Km 4km 30km

EMI N/R Poor Fair Excellent Excellent

Page 10: Ovation Ppt

CONTROLLER OCR-400:

A Set of Controllers

Primary Controller

Partner Controller(Redundant) It is called as Compact Controller. Capability to originate 16,000 points. It uses Intel Pentium processor. Speed for the processor is 400MHz. Capable of simultaneously executing as many as five process control

tasks at loop speed ranging from 10 milliseconds to 30 seconds Each control task is comprised of I/O process point input scan, the

control scheme execution followed by output scan

1. One scan task -1S task 2.Second scan task -100mS task

3.Three, Four ,Five - User Selectable

Page 11: Ovation Ppt

Control Scheme:Building control Sheets with an extensive set of

algorithms.Controller can provide execution of 6000

Control Sheets.• Controller Redundancy:

Ovation Network InterfaceFunctional Processor, Memory and Network ControllerProcessor Power SupplyI/O InterfaceInput power FeedI/O Power SupplyAuxiliary power SupplyRemote I/O Communication Media

Page 12: Ovation Ppt

Controller Specification:ITEM CAPABILITY

Bus Structure PCI Standard

Originated Points 16,000

Process Control Task Up to 5 with different execution rate, two defined

and three user definable

Control Task Execution Rate Every 10ms to 30sec in 10ms increments

Processor Intel

Memory 128MB Flash &128MB RAM

NIC Ports 4*10/100 MB Ethernet

Power 24V DC 40W

Page 13: Ovation Ppt

CONTROLLER I/O CAPABILITIES:ITEM CAPABILITY

Local Ovation I/O 2 Set of up to 8 independent branches of

8 modules per branch for a total of 128

modules

Direct wired local I/O Maximums

Analog =1024 or Digital or

SOE=2048

Remote Ovation I/O Up to 8 nodes of 64 modules

Maximum number of remote nodes

8 nodes per ovation controller

Maximum number of I/O Modules per remote

node

64(8 branches with 8 modules for each

branch)

Maximum number of I/O Modules per controller

512(8 nodes,8 branches for each node,8 modules

for each branch)

Maximum number of I/O Modules per controller

1024

Page 14: Ovation Ppt

TYPES OF I/O MODULES:

8 Channels Analog input 8 channel HART Analog input 8 channel Thermocouple input 8 channel RTD input 4 channel Analog output 16 channel Digital input 16 channel control input 16 channel Digital output 2 channel Pulse Accumulator/Counter 16 channel Sequence of Events

Page 15: Ovation Ppt

I/O MODULES ADDRESSING D.N.B.S

D-Device number 1-Local Ovation 2-Local Ovation 3-Local Q-Line 4-Can be

Remote Ovation Remote Q-Line Local Q-Line• 5-9 – Third Party Devices

N-Node number(used for remote 1-8)B-Branch numberS-Slot number

Page 16: Ovation Ppt

ANALOG I/O MODULES:

Individually Isolated Low Power Requirements Analog I/O Modules include:

13-bit Analog Input 14-bit Analog Input RTD Input Analog Output

• Locally powered and Field powered transmitters can be connected in a same module

Page 17: Ovation Ppt

13-bit Analog Input: Individually isolated inputs 8 channels per module Individual A/D Converter Per channel 13 bit resolution , including sign 10 updates per second under normal conditions

14-bit Analog Input:

8 channels per module Consists of 2 groups of personality and electronic modules

providing current signal of 4-20 mA and voltage signal of +/- 1V

20 updates per second under normal conditions

Page 18: Ovation Ppt

DIGITAL I/O MODULES: 16 channels per module Single ended or differential inputs Handling AC or DC inputs ranging from 24V to 125VSequence of Events: 16 channels per module Supports digital, single ended or differential inputs Ranges include

24 VAC/VDC Single ended/Differential ended48 VAC/VDC Single ended/Differential ended125 VAC/VDC Single ended/Differential ended

1/8 m sec event time tag resolution with in a controller

Page 19: Ovation Ppt

OCR400 PROCESSOR AND I/O INTERFACE MODULES

NETWORK INTERFACE PORTS:N1- Other Additional Interfaces(eg : Allen Bradlely)N2- Single Attached Network InterfacesN3- Dual Attached Network InterfacesN4- Dedicated Control Synchronization

I/O INTERFACE MODULES:R3- Supports 4 nodes of remote or 4 nodes of remote Q-LineR4- Supports 4 nodes of remote or 4 nodes of remote Q-LineQ5- Supports 4 create(1 node) local Q-line

Page 20: Ovation Ppt

SPECIAL MODULES: Link Controller Modules

Programming Port Pulse Accumulator

Counting of pulses Valve Positioner

Linear Variable Differential Transformer

Speed Detector

Page 21: Ovation Ppt

HISTORIAN ARCHITECTURE Modular Design:

Historian functions separated in to independent software subsystem.

Each subsystem performs unique function like scanning , collecting, storing , retrieving or displaying historical data.

• Client /server Architecture: Server portion runs on historian. Server collects the data from ovation network, send the data to archive storage and responds to retrieval requests.

Client application program runs on operator or engineer work station. It provides the functions to display ,print or save the data collected by server.

Page 22: Ovation Ppt

HISTORICAL SCANNING AND COLLECTING:

Scans or collects six type of historical dataReal time point values and statusesLaboratory dataHigh speed dataAlarm messagesOperator action messagesSequence of events messagesReport files

Page 23: Ovation Ppt

POINT HISTORY: Main History:

Continually collects process point data Scan up to 20,000 data points Multiple scan frequency defined by the user on 1sec

increments Collection based on dead band Selection and change in

point status

Long term storage Memory:• Collects and store process point data and retrieves data based on

user request• Scans 600 user definable points and stores the value in online

storage value• Collection based on dead band Selection and change in point status•Dedicated storage allows information to remain online for long time

Page 24: Ovation Ppt

EVENT HISTORY:

Events such as plant trips or equipment startup can be saved.

Once event is activated 500 user defined points are collected at 100 ms rate and scheduled for archive.

Scans and collects 1hr worth of data. OWS or EWS can generate trends or

reviews of the values collected in the event history.

Page 25: Ovation Ppt

POINT GROUP HISTORY:

It is similar to the event history capable to define up to 5 historical groups of 20 points each.

Scan and collect information on points with in the predefined sets at a 100ms rate for an hour.

Collection of group data associated with common control functions

Event History Point group

Scan Rate 100ms 100ms

Points Scanned 500 points Up to 5 group of 20 each

Collection rate 100ms 100ms

Page 26: Ovation Ppt

LABORATORY DATA

Unique data collection method for handling point data , i.e. not acquired in real time.

Up to 1000 individual points collected via manual entry or by communication with external device

Stored in to historical archive for use in trends , reports and other retrieval functions

Page 27: Ovation Ppt

MESSAGE HISTORY

Alarm History Receives and stores alarm sent by alarm logging drop Allows an operator or engineer to display , print or

save to a file the list of alarms collected Capability to filter the alarm list based on factors such

as Point name Time period or Originating period.

Page 28: Ovation Ppt

OPERATOR EVENT HISTORY Records operator actions received from OWS

or ovation controller Data Retrieval up on client application

request Filtering is done through time period

originating drop or event typeFile History Saves and archive operator shift diary output

and report generator output as data files in the historian.

File history client interface used to retrieve these data from historian by OWS or EWS

Page 29: Ovation Ppt

SEQUENCE OF EVENT HISTORY

Collects SOE data from controller ,sorts in to a list and searches the “first-out” events.

Interface allows the operator to view the SOE report and filter it based on tag name , controller or “first-out” point

Appropriate SOE I/O modules are equipped to perform function.

Page 30: Ovation Ppt

HISTORICAL DATA STORAGE AND RETRIEVAL Historical data scanned and collected is stored for

future retrievals Historian utilizes 3 storage areas

Primary storage Secondary Storage Long term Storage

• Primary Storage• Stores most recently collected data• Includes information from main event point long term histories.

• Information from primary storage transferred to secondary storage at user selectable time.

• It allows Primary storage to clear and available for collection of the next time period data

Page 31: Ovation Ppt

SECONDARY STORAGE

Maintains a period of historical files on hard disk.

Automatic copy of all data placed in secondary storage to long-term storage provides redundancy

Storage limits are determined by capacity of hard drive(s) and size of files.

Page 32: Ovation Ppt

LONG TERM STORAGE

Optical disk storage is available to store up to 5.2 gigabytes

Disk size varies from 80GB to 400GB

Storage Summary

Type Minimum Size

Primary Hard Drive 2GB

Secondary Hard Drive 4GB+

Long term Optical Disk DriveDrive Jukeboxes

5.2GB/disk80-330GB

Page 33: Ovation Ppt

ARCHIVE MANAGER

3 functions Moves Historical files Manages retrieval functions Manages redundancy and recovery functions

Moving Historical filesResponsible for moving historical files from one storage place to another Files are automatically moved from primary to secondary and from secondary to long term storageDeletes oldest secondary files when permanently placed in long term storage

Page 34: Ovation Ppt

MANAGING DATA RETRIEVALS Automatically locates stored historical data

for retrievals It can find information stored in the hard

drive when user enters the requested time. Automatic retrieval of information within

an optical jukebox is a unique functionRedundancy and Recovery Consist of two separate identical sets of

computer hardware Concurrent redundancy scheme in primary

and partner historians

Page 35: Ovation Ppt

RETRIEVAL HISTORICAL DATA Historical Trends

Utilize information collected in the data histories Up to 8 user definable points can be trended.Time period can be determined by the userTime periods can be defined in 3 ways

Start and End times End time with specified intervals Start time with specified intervals

• Point Review•Tabular method of displaying historical information

• Point group Review•Allows operator to display , print or save to a file the historical data collected from the point group history.

Page 36: Ovation Ppt

ALARM REVIEW• Allows operator to display , print or save to a file the

historical data collected from the alarm history.

Operator Event History List of events filters the list of operator events by

time period originating drops or events

SOE Review Allows the operator to view SOE report generated

by SOE history.

SQL Queries Historical data may be recalled in response to standard SQL data queries